1869 SEA OATS DR SOLR23-0008 - ELECTRICAL PLANSKARL KLEIN RESIDENCE PROJECT #: P-0088870 1869 SEA OATS DRIVE ATLANTIC BEACH, FL, 32233 METER #: 20194409SHEET NUMBERSHEET TITLELOCATIONDRAWN BY:DATE:REVISIONSREVDATEDESCRIPTIONLUMIO HX INC 1550 W DIGITAL DRLEHI, UT 840431 (888) 586-4649LIC #: EC13011870A.A.10/12/23GENERAL NOTES:· THESE CONSTRUCTION DOCUMENTS HAVE BEEN BASED ON FIELD INSPECTIONS AND OTHER INFORMATION AVAILABLE AT THE TIME. ACTUAL FIELD CONDITIONS MAYREQUIRE MODIFICATIONS IN CONSTRUCTION DETAILS.· CONTRACTOR HAS THE FULL RESPONSIBILITY TO CHECK AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS. ANY DISCREPANCIES SHALL BE REPORTED TO THEENGINEER BEFORE PROCEEDING WITH THE WORK. ANY WORK STARTED BEFORE CONSULTATION AND ACCEPTANCE BY THE ENGINEER SHALL BE THE SOLERESPONSIBILITY OF THE CONTRACTOR AND SHALL BE SUBJECT TO CORRECTION BY THEM WITHOUT ADDITIONAL COMPENSATION.· THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE PROPER INSTALLATION AND COMPLETION OF THE WORK WITH APPROVED MATERIALS.· THE EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTION SHALL BE INSTALLED ONLY BY QUALIFIED PEOPLE. A QUALIFIED PERSON IS ONE WHO HASSKILLS AND KNOWLEDGE RELATED TO THE CONSTRUCTION AND OPERATION OF THE ELECTRICAL EQUIPMENT AND INSTALLATIONS AND HAS RECEIVED SAFETY TRAININGTO RECOGNIZE AND AVOID THE HAZARDS INVOLVED. (NEC 690.4(C), NEC 2017).· NEW CONDUIT ROUTING SHOWN IS ESSENTIALLY SCHEMATIC. CONTRACTOR SHALL LAY OUT RUNS TO SUIT FIELD CONDITIONS AND THE COORDINATIONREQUIREMENTS OF OTHER TRADES.· ARRAY WIRING SHOULD NOT BE READILY ACCESSIBLE EXCEPT TO QUALIFIED PERSONNEL.· THE AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH.· ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION· ALL SOLAR EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER INSTRUCTIONSINSTALL A ROOF MOUNTED SOLAR PHOTOVOLTAIC SYSTEM AT THE KARL KLEIN RESIDENCE.TITLESHEETVICINITY MAPNTS001Governing CodesElectrical Code2017 NECFire Code2018 NFPA / 2020 FFPCBuilding Code2020 FBCResidential Code2018 IRCKARL KLEIN RESIDENCE1869 SEA OATS DRIVEATLANTIC BEACH, FL 32233PROJECT DESCRIPTIONSYSTEM SPECIFICATIONSAHJ:UTILITY COMPANY:SYSTEM SIZE:SOLAR MODULES MAKE:MODEL:QUANTITY: MICROINVERTERS MAKE:MODEL:QUANTITY: CITY OF ATLANTIC BEACHJEA6.000kW DC4.350kW ACHANWHA Q CELLSQ.PEAK DUO BLK ML-G10+/T 400 15ENPHASEIQ8PLUS-72-2-US15SHEET INDEXTS001TITLE SHEETE001ROOF PLANE0023-LINE DIAGRAME003LABELSS001 ATTACHMENT PLANMSDDATA SHEETSTHIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY OMAR TIRADO ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEAL, AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES2023.11.07 12:13:50 -05'00' AB36" FIRE SETBACK36" FIRE SETBACK36" FIRE SETBACK 36" FIRE SETBACK ROOF 1FRONT OF RESIDENCE BACK OF RESIDENCE EXISTING SYSTEM36" FIRESETBACKMACD(E) UTILITY METER(N)COMBINER BOX(N)AC DISCONNECTCB(E) MAIN SERVICE PANEL MSP A AAAAABBBBBBBJBNKARL KLEIN RESIDENCE PROJECT #: P-0088870 1869 SEA OATS DRIVE ATLANTIC BEACH, FL, 32233 METER #: 20194409SHEET NUMBERSHEET TITLELOCATIONDRAWN BY:DATE:REVISIONSREVDATEDESCRIPTIONLUMIO HX INC 1550 W DIGITAL DRLEHI, UT 840431 (888) 586-4649LIC #: EC13011870A.A.10/12/23ROOF PLANE001- UTILITY METERLEGENDM- EXISTING- NEW(E)(N)- MODULE STRING IDX- MAIN SERVICE PANELMSP- SUBPANELSUB- JUNCTION BOXJB- STRING CENTER TAPSCT- APPROX. CONDUIT/ATTIC RUN- LOAD CENTERLC- AC DISCONNECTACD- ENERGY STORAGEBAT- INTERCONNECTION DEVICEICD- COMBINER BOXCB- BACK UP LOADS PANELBUL- FIRE CODE SETBACKSSITE PLANSCALE: 1/8" = 1'-0"THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY OMAR TIRADO ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEAL, AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES IDINITIAL CONDUCTORLOCATIONFINAL CONDUCTORLOCATIONMIN. CONDUCTOR SIZE(AWG)MIN. DIA CONDUITSIZE (IN.)# OF PARALLELCIRCUITSCURRENT-CARRYINGCONDUCTORSIN CONDUITOCPD(A)MIN. EGC SIZE(AWG)TEMP. CORR.FACTORCONDUIT FILLFACTORCONT. CURRENT(A)MAX. CURRENT(A)BASE AMP.(A)DERATEDAMP.(A)TERM. AMP.RATING(A)LENGTH (FT)VOLTAGE DROP(%)1STRING AJUNCTION BOX 12Q CABLEN/A12N/A 6BARE COPPER0.76 55°C N/A8.4710.593022.8N/A28.000.392STRING BJUNCTION BOX 12Q CABLEN/A12N/A 6BARE COPPER0.76 55°C N/A9.6812.103022.8N/A38.000.613JUNCTION BOXCOMBINER BOX10THWN-2 COPPER0.75 LTNM2420 10THWN-2 COPPER0.7655°C0.89.6812.104024.33567.000.674 COMBINER BOXAC DISCONNECT10THWN-2 COPPER0.75 LTNM13N/A10THWN-2 COPPER0.9634°C118.1522.694038.4355.000.095AC DISCONNECTMSP10 THWN-2 COPPER0.75 LTNM1330 10 THWN-2 COPPER 0.96 34°C118.1522.694038.43525.000.45LIST OF EQUIPMENTEQUIPMENTQTYDESCRIPTIONSOLAR PV MODULE15HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+/T 400MICROINVERTER15ENPHASE IQ8PLUS-72-2-USJUNCTION BOX1JUNCTION BOX, NEMA 3R, UL LISTEDCOMBINER BOX1ENPHASE IQ COMBINER 4/4C W/ IQ ENVOY (X-IQ-AM1-240-4)AC DISCONNECT160A NON-FUSED AC DISCONNECT, 240V, NEMA 3R, UL LISTED(7) ENPHASE IQ8PLUS-72-2-US MICROINVERTERS(N) STRING A(7) HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+/T 400MODULES(8) ENPHASE IQ8PLUS-72-2-US MICROINVERTERS(N) STRING B(8) HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+/T 400MODULESTOMOUNTINGSTRUCTUREL1L2(N) JUNCTIONBOXL1L2GGL1L2N(N) IQ COMBINER BOX10A/2P OR15A/2PENVOYNGG20A/2PL1L220A/2PL1L26AWGBARECOPPER32145 (N) 60A NON-FUSEDAC DISCONNECT240V, NEMA 3R,UL LISTEDL1L2NGL1L2NG( ) MAIN SERVICEPANEL, AL2L1L2L1L2L1L2L1(E) GROUNDELECTRODECONDUCTORL1L2NTO UTILITYGRID( ) BI-DIRECTIONALUTILITY METER30A/2P(N) BACKFEEDBREAKER( ) MAIN BREAKERTO HOUSE, AL2L1L2L1L1L2N200175ENE(E) SOLAR PANEL SYSTEM(10) HYUNDAI 355W MODULES(E) SUNNY BOYSB3.0-1SP-US-40INVERTER(E)JUNCTIONBOX(E) FUSEDACDISCONNECT(E) BACKFEEDBREAKER20A/2PKARL KLEIN RESIDENCE PROJECT #: P-0088870 1869 SEA OATS DRIVE ATLANTIC BEACH, FL, 32233 METER #: 20194409SHEET NUMBERSHEET TITLELOCATIONDRAWN BY:DATE:REVISIONSREVDATEDESCRIPTIONLUMIO HX INC 1550 W DIGITAL DRLEHI, UT 840431 (888) 586-4649LIC #: EC13011870A.A.10/12/23DESIGN TEMPERATURE SPECIFICATIONSRECORD LOW TEMP1°CAMBIENT TEMP. (HIGH TEMP. 2%)34°CCONDUIT HEIGHT1.0"CONDUCTOR TEMP. RATE (ROOF)55°C3-LINEDIAGRAME002THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY OMAR TIRADO ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEAL, AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES KARL KLEIN RESIDENCE PROJECT #: P-0088870 1869 SEA OATS DRIVE ATLANTIC BEACH, FL, 32233 METER #: 20194409SHEET NUMBERSHEET TITLELOCATIONDRAWN BY:DATE:REVISIONSREVDATEDESCRIPTIONLUMIO HX INC 1550 W DIGITAL DRLEHI, UT 840431 (888) 586-4649LIC #: EC13011870A.A.10/12/23·ANSI Z535.4-2011 PRODUCT SAFETY SIGNS AND LABELS,PROVIDES GUIDELINES FOR SUITABLE FONT SIZES,WORDS, COLORS, SYMBOLS, AND LOCATIONREQUIREMENTS FOR LABELS. NEC 110.21(B)(1).·THE LABEL SHALL BE OF SUFFICIENT DURABILITY TOWITHSTAND THE ENVIRONMENT INVOLVED. NEC110.21(B)(3).·ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IFPROPERLY ADHERED. VINYL SIGNS SHALL BE WEATHERRESISTANT.·ALL LABELS AND MARKINGS FOR PHOTOVOLTAICSYSTEMS WILL BE REFLECTIVE AND MEET ALLREQUIREMENTS.NOTESLABEL LOCATION:POINT-OF-INTERCONNECTION OR AT MAINSERVICE DISCONNECT (MSP)PER CODE: NEC 705.12(B)(2)(3)(b)! WARNING !POWER SOURCE OUTPUT CONNECTION.DO NOT RELOCATE THIS OVERCURRENTDEVICE.LABELSE003LABEL LOCATION:POINT OF INTERCONNECTIONPER CODE: NEC 2017, 705.12(B)WARNINGDUAL POWER SOURCESOURCES: UTILITY GRID ANDPV SOLAR ELECTRIC SYSTEMLABEL LOCATION:AC DISCONNECTPER CODE: NEC2017, 690.54RATED AC OUTPUT CURRENT18.15NOMINAL OPERATING AC VOLTAGE240PHOTOVOLTAIC AC DISCONNECTAVLABEL LOCATION:COMBINER BOX/ EMTENCLOSURES/ AC DISCONNECT/MAIN SERVICE PANELPER CODE: NEC 2017, 690.13(B)WARNINGDO NOT TOUCH TERMINALSTERMINALS ON BOTH THE LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONELECTRIC SHOCK HAZARDLABEL LOCATION:RAPID SHUTDOWN (AC DISCONNECT)PER CODE: NEC 690.56 (C)(1) &NFPA1 11.12.2.1.1.1.1, 11.12.2.1.4SHALL BE REFLECTIVE, WITH ALLLETTERS CAPITALIZED AND HAVING AMINIMUM HEIGHT OF 3/8 IN. (9.5 MM), INWHITE ON RED BACKGROUND.TURN RAPID SHUTDOWNSWITCH TO THE "OFF"POSITION TO SHUTDOWN THE ENTIRE PVSYSTEMSOLAR ELECTRICPV PANELSEMERGENCY RESPONDERSOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNLABEL LOCATION:CONDUIT/ RACEWAY/ ENCLOSURES/COMBINER BOX/ AC DISCONNECTPER CODE: NEC2017, 690.31(G)(3)(4)WARNING: PHOTOVOLTAICPOWER SOURCELABEL LOCATION:AC DISCONNECT/ BREAKER/POINTS OF CONNECTIONPER CODE: NEC2017, 690.13(B)PHOTOVOLTAICAC DISCONNECTLABEL LOCATION:RAPID SHUTDOWN(AC DISCONNECT)PER CODE: NEC 690.58 (C)(3)RAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEMTHIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY OMAR TIRADO ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEAL, AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES 2052 6156 watts 2 3000 watts 1 1500 watts 9600 9600 watts 0 0 watts 0 0 watts 4550 4550 watts 5400 5400 watts 1200 1200 watts 500 500 watts 0 0 watts 0 0 watts 11500 11500 watts 1500 1500 watts 750 750 watts 0 watts 0 watts 0 watts 0 watts 45656 watts 9200 1000 10200 watts 10000 watts 14262.4 watts 10200 watts 34462.4 watts = =amps sq. ft. @ 3 watts sq. ft Small Appliance Circuits @ 1500 watts ea. (Minimum is two) Existing Loads Oven (Nameplate Rating) Electric Water Heater Laundry Circuit(s) @ 1500 watts ea. (Minimum is one) Range (Nameplate Rating) Cooktop (Nameplate Rating) Owner name: Address: Total Calculated Load (less HVAC) Dishwasher Disposal Sump Pump Sewage Pump Pool Equipment Microwave Oven Garage Door Opener Electric Clothes Dryer HVAC Load HVAC Load Compute the HVAC load and enter the LARGER of these air-conditioning or space heating loads. Air Conditioning Load (Volts X Amps = Watts)wattsFurnace/Air Handler (Volts X Amps = Watts) watts(Central electric furnace, electric baseboard heaters, ceiling radiant heat, etc.) OR Heat Pump with Central Electric Furnace (Volts X Amps = Watts)watts(Nameplate rating of heat pump compressor plus electric furnace) 34462.4 watts 240 volts 143.59 Residential Load Calculation Worksheet (Based on NEC 220.83) 1869 Sea Oats Drive Atlantic Beach, FL 32233 Karl Klein Calculated Service Load Service Voltage Minimum Service Ampacity Total Computed Load (NEC 220.83) First 10kw of Total Calculated Load (less HVAC) @ 100% Remainder of Total Calculated Load (less HVAC) @ 40% HVAC Load @ 100% Calculated Service Load Service Demand OR Electric Space Heating Load (Volts X Amps = Watts) THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY OMAR TIRADO ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEAL, AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES ROOF 1FRONT OF RESIDENCE BACK OF RESIDENCE EXISTING SYSTEM NKARL KLEIN RESIDENCE PROJECT #: P-0088870 1869 SEA OATS DRIVE ATLANTIC BEACH, FL, 32233 METER #: 20194409SHEET NUMBERSHEET TITLELOCATIONDRAWN BY:DATE:REVISIONSREVDATEDESCRIPTIONLUMIO HX INC 1550 W DIGITAL DRLEHI, UT 840431 (888) 586-4649LIC #: EC13011870A.A.10/12/23SAFETYPLANNOT FORPERMITSAFETY PLAN CHECKLISTABBR.Work ZoneWZIndicate parking location for company vehiclesCVIndicate location of safety documentsSDFire extinguisher locationFEFirst aid kit locationFAEye wash locationEWDrinking water locationDWIdentify hard hat zoneHHZDraw fall protection anchor locationsXDraw ladder & roof access pointsLDraw ladder anchor locationLAElectrical ZoneEZIndicate other hazard locations and specify (e.g.water, tripping, animals, insects, etc.)WEATHER FORECASTHourly HeatIndexHeat Illness Protection Measures7 am8 am9 am10 am11 am12 amOther weather related hazards & measures1 pmWet or icy surfaces2 pmHigh winds3 pmThunderstoms4 pmWildfire smoke5 pmOtherIn case of workplace injury, notify your supervisor immediately.Supervisors Immediately Call Medcor 844.871.8630If you think it's a serious or life-threatening injury call 911 andnotify your supervisor immediately.CREW SIGNATURES & DATE(S)NOTE: Crew Lead must conduct a daily meeting to review all safety items.123456NOTE: For multiple day jobs, safety meetings must be conducted each day. Indicate by initialing next to your signature for each additional day.FALL RESCUE PLAN (To be completed by the Roof Lead)ADDRESS & PHONE NUMBER OF CLOSEST URGENT CARE FACILITY