ABCC P2 - Bldg 1 - 1-M0.13_1SUPPLY DUCTRETURN DUCT ROOF ASSEMBLY. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR INFORMATION ROOF CURB, SEE SCHEDULES, SPECIFICATIONS AND ROOF CURB INSTALLATION DETAIL FOR REQUIREMENTS ROOFTOP UNIT. PROVIDE ALL MANUFACTURER'S CLEARANCES FOR MAINTENANCE AND OPERATION OUTSIDE AIR INTAKE, SEE SCHEDULES FOR BALANCING REQUIREMENTS. OA INTAKE SHALL NOT BE LOCATED WITHING 10'-0" OF AN EXHAUST OR VENT OUTLET FLEXIBLE EQUIPMENT CONNECTION. SEE AIRSIDE FLEXIBLE EQUIPMENT CONNECTION DETAIL FOR REQUIREMENTS SMOKE DETECTOR WITH REMOTE TEST STATION WHERE INDICATED ON FLOOR PLANS, SCHEDULES OR SPECIFICATIONS INTERNALLY LINED DUCTWORK WHERE INDICATED ON FLOOR PLANS, SCHEDULES OR SPECIFICATIONS SD SD SD COVER VENT WITH HARDWARE CLOTH FLOOR STEEL SUPPORT 24" HIGH ANGLE IRON STAND FILTER ACCESS FAN COIL UNIT REFRIGERANT PIPES BOD 24" AFF LINED RA PLENUM FLEXIBLE CONNECTION CEILING TO CENTRAL RA DUCT OA DUCT W/ MANUAL DAMPER EXTEND CONDENSATE DRAIN TO FLOOR DRAIN SUPPLY DUCT UP TO ATTIC RETURN AIR DUCT SECONDARY DRAIN PAN 1-1/2" DEEP & 3" LARGER THAN UNIT IN ALL DIRECTIONS. PROVIDE FLOAT SWITCH TO SHUT DOWN UNIT UPON CONTACT CLOSURE. SMOKE DETECTOR (WHERE APPLICABLE) PROVIDE DOUBLE NUTS WITH LOCKWASHER AT TOP & BOTTOM OF FLANGE CEILING 3/8" DIA THREADED ROD, TYP 4 SIZE OR TRANSITION TO MATCH FAN FLANGE EXHAUST FAN BACKDRAFT DAMPER IN FAN BOX GRILLE IN-LINE FAN DISCHARGE DUCT - SEE FLOOR PLAN DIMENSIONS SMACNA DUCT TRANSITION (TYP. OF 2) FLEXIBLE CONNECTION (TYP. OF 2) THREADED ROD - CONNECT TO STRUCTURE ABOVE - TYP. NEOPRENE HANGING ISOLATOR (TYP. OF 4) MANUFACTURER'S PROVIDE CONTROL DAMPER W/120 VAC ACTUATOR. PITCH DOWN TOWARD DRAIN SAME SIZE AS THE NIPPLE ON THE DRAIN LINE SHALL BE AT LEAST THE 1" (25 MM) CLEAN OUT DRAIN PAN OPEN DRAIN B A DRAIN PAN DESIGNER'S NOTE: WHERE X = STATIC PRESSURE IN PAN BLOW THRU DRAW THRU 1" (25 MM) 2" (50 MM) UNIT TYPE A 2X X B PLUS X MINIMUM ROUTE RS&L ABOVE CEILING. INSTALL PER MANUFACTURER'S RECOMMENDATIONS PRIMARY CD TO EXTERIOR OF BUILDING FULL SIZE OF UNIT OUTLET-FIELD ROUTE. PROVIDE SMOOTH OUTLET TRANSITIONS TO MEET WITH DUCT SIZES SHOWN ON FLOOR PLANS - TYP. FLEXIBLE DUCT CONNECTION SUPPLY DUCT FAN COIL UNIT FINISHED CEILING THREADED ROD, SIZE PER MANUFACTURER'S RECOMMENDATIONS AND UNIT WEIGHT WITH VIBRATION ISOLATION. RETURN DUCT STRUCTURE -REFER TO ARCH/STRUCTURAL DWGS FOR DETAILS. SECONDARY CD DRAIN TO SECONDARY DRAIN PAN, ROUTE FULL SIZE OF UNIT OUTLET. SECONDARY DRAIN PAN 1-1/2" DEEP & 3" LARGER THAN UNIT IN ALL DIRECTIONS. PROVIDE FLOAT SWITCH TO SHUT DOWN UNIT UPON CONTACT CLOSURE. ROOF STRUCTURE CONDENSING UNIT OR HEAT PUMP SEAL OPENING AIR AND WATER TIGHT WITH EXPANDING FOAM AND INSULATION MIAMI TECH AS14 ALUMINUM CONDENSING UNIT STAND, OR APPROVED PRE-ENEGINEERED EQUAL, CERTIFIED TO MEET FLORIDA/MIAMI DADE WIND CONSTRAINT REQUIREMENTS. STAND TO BE ATTACHED TO ROOF STRUCTURE AND INSTALLED PER MANUFACTURER'S RECOMMENDATIONS. INSULATED REFRIGERANT LINE SET, TYPICAL SUPPORT RS & RL 6" OC WITH MIFAB MODEL C PIPE SUPPORT ON ROOFING WALKPAD MATERIAL -SECURE PIPE WITH PIPE CLAMP WATERTIGHT REFRIGERANT LINE SET CHASE NOTES: 1. MIFAB PIPE PIPE SUPPORT TO HAVE 14 GA. X 3/16" WIDE GALVANIZED CHANNEL. LENGTH TO SUIT QUANTITY OF PIPING SUPPORTED. PROVIDE INSULATION SHIELD WHERE STRUT CLAMP COMES IN CONTACT WITH INSULATION. 2. DELEGATED DESIGN SUBMITTAL: FOR EACH WIND-LOAD PROTECTION DEVICE, SUBMIT THE FOLLOWING: a. WIND-LOAD RESTRAINT SYSTEM SELECTION b. WIND-LOAD DESIGN CALCULATIONS: SUBMIT ALL STATIC AND DYNAMIC LOADING CALCULATIONS c. QUALIFIED PROFESSIONAL ENGINEER: ALL DESIGNATED- DESIGN SUBMITTALS FOR WIND-RESTRAINT CALCULATIONS ARE TO BE SIGNED AND SEALED BY QUALIFIED PROFESSIONAL ENGINEER RESPONSIBLE FOR THEIR PREPARATION. d. WIND-RESTRAINT DETAIL DRAWING: INDICATE FABRICATION AND ARRANGEMENT. DETAIL ATTACHMENTS OF RESTRAINTS TO RESTRAINED ITEMS AND TO THE STRUCTURE. SHOW ATTACHMENT LOCATIONS, METHODS, AND SPACING. DRAWN BY: PROJECT NO.: SCALE: REVISION NO.DATE DESCRIPTION THE INFORMATION SHOWN ON THESE DRAWINGS IS OWNED BY AND IS THE PROPERTY OF SHEPPHIRD ASSOCIATES, ARCHITECTS + ENGINEERS. NO PART THEREOF SHALL BE COPIED, ADAPTED, OR DISTRIBUTED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF SHEPPHIRD ASSOCIATES, ARCHITECTS + ENGINEERS. COPYRIGHT © 2023 26560 AGOURA ROAD, SUITE 106 CALABASAS, CA 91302 310.670.9144 A S S O C I A T E S ARCHITECTS + ENGINEERS S H E P P H I R D will.s@shep-ae.com 1 12-02-22 SD PRICING 2 2-10-23 DD PRICING 3 9-07-23 PHASE 2 90% CD Atlantic Beach Country Club Phase 2 Construction Documents 1600 Selva Marina Drive Atlantic Beach, FL 32233 12" = 1'-0" 1-M0.13PHASE 2 -MAIN CLUBHOUSE MECHANICALDETAIL2022-352 Author N.T.S.1-M0.13 1 ROOFTOP DX UNIT INSTALLATION DETAIL N.T.S.1-M0.13 2 VERTICAL FAN COIL UNIT N.T.S.1-M0.13 3 CEILING EXHAUST FAN DETAIL N.T.S.1-M0.13 4 INLINE EXHAUST FAN N.T.S.1-M0.13 5 RTU CONDENSATE DRAIN TRAP N.T.S.1-M0.13 6 HORIZONTAL FAN COIL UNIT N.T.S.1-M0.13 7 ROOF MOUNTED OUTDOOR UNIT