Loading...
ABCC P2 - Bldg 1 - 1-M0.31_1LOW INTENSITY, NATURAL GAS-FIRED RADIANT HEATERS (INFRARED TUBE TPE) MARK SERVICE REFLECTOR ANGLE (DEGREES) TUBE LENGTH (FT) HI/LOW INPUT (MBH) MOUNTING HEIGHT APPROX WEIGHT (LB)MODEL NOTES RH 1-1 COVERED PATIO 45 10.0 58/37.5 8'-0" 105 ETS60 1,2,3,4 RH 1-2 COVERED PATIO 45 10.0 58/37.5 8'-0" 105 ETS60 1,2,3,4 RH 1-3 COVERED PATIO 45 10.0 58/37.5 8'-0" 105 ETS60 1,2,3,4 RH 1-4 COVERED PATIO 45 10.0 58/37.5 8'-0" 105 ETS60 1,2,3,4 RH 1-5 DINING PATIO 45 10.0 58/37.5 8'-0" 105 ETS60 1,2,3,4 RH 1-6 DINING PATIO 45 10.0 58/37.5 8'-0" 105 ETS60 1,2,3,4 RH 1-7 DINING PATIO 45 10.0 58/37.5 8'-0" 105 ETS60 1,2,3,4 RH 1-8 DINING PATIO 45 10.0 58/37.5 8'-0" 105 ETS60 1,2,3,4 BASIS OF DESIGN: IR ENERGY ACCEPTABLE EQUALS: RAYWALL, INDECCO, BERKO, MARLEY, QMARK GENERAL NOTES APPLICABLE TO ALL: A SELECTIONS BASED ON A PROJECT ELEVATION OF 10'. FOR PROJECTS ABOVE 2000', EQUIP WITH HIGH ALTITUDE CONVERSION KIT. B HEATERS SHALL BE CERTIFIED FOR INDOOR AND OUTDOOR USE. C UNIT SHALL BE EQUIPPED WITH A TWO-STAGE GAS VALVE, DIRECT SPARK IGNITION AND 100% LOCKOUT. D RADIANT PIPING (HEAT EXCHANGER) TUBES SHALL BE CONSTRUCTED OF 316 MARINE GRADE STAINLESS STEEL. E UNITS SHALL BE WARRANTED FOR A MINIMUM OF 3 YEARS. NUMBERED NOTES: 1 REFLECTOR END COVERS 2 TWO-STAGE WALL MOUNTED HEATING THERMOSTAT AND 24-VOLT CONTROL TRANSFORMER 3 SUSPENSION KIT WITH TUBE/REFLECTOR HANGERS, S-HOOKS, TURNBUCKLES AND CHAINS 4 DISCONNECT SWITCH FURNISHED BY MECHANICAL; INSTALLED BY ELECTRICAL DEDICATED OUTDOOR AIR UNIT SCHEDULE MARK SERVICE NOMINAL TONS SUPPLY (CFM) ESP (IN WC) FAN MOTOR (HP) COOLING CAPACITY HOT GAS REHEAT HEATING CAPACITY EFFICIENCY (EER/IEER)FILTER WEIGHT (LBS)MODEL NOTESTOTAL (MBH) SENSIBLE (MBH) EAT (DB °F) EAT (WB °F) LAT (DB/WB°F) TOTAL (MBH) LAT (DB °F) INPUT (MBH) OUTPUT (MBH)EAT (°F) LAT (°F) TURNDOWN RATIO DOAU-1 MAIN CLUB 40 5,000 1.50 5.0 457.1 163.9 82.8 78.8 50.0/49.8 113.6 72.0 600.0 480.0 29.6 118.2 10:1 10.2/13.5 MERV 11 5000.00 RN-040-D-0 1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17 BASIS OF DESIGN: AAON ACCEPTABLE EQUALS: TRANE, CARRIER, DAIKIN ,GREENHECK GENERAL NOTES APPLICABLE TO ALL: A PROVIDED WITH THRU BASE NON-FUSED ELECTRICAL DISCONNECT TO BE INSTALLED BY ELECTRICAL CONTRACTOR. REFER TO ELECTRICAL PLANS FOR VOLTAGE AND PHASE. B PROVIDE WITH CLASS 1, LOW-LEAKAGE TYPE SHUTOFF DAMPERS W/ BLADE AND JAMB SEALS. C PROVIDE 2" MERV 11 PLEATED DISPOSABLE FILTERS, DIRTY FILTER MONITOR & ALARM, CONDENSATE OVERFLOW SWITCH, SS DRAIN PAN, SINGLE POINT POWER CONNECTION, 100% OA WEATHER HOOD W/ ALUMINUM FILTERS. D FANS SHALL BE DIRECT DRIVE PLENUM TYPE WITH PREMIUM EFFICIENCY MOTORS AND VARIABLE SPEED DRIVE. E HEATING SECTION SHALL HAVE A STAINLESS STEEL HEAT EXCHANGER W/ DIRECT SPARK IGNITION, 10 YEAR WARRANTY, AND MIN. 80% STEADY STATE COMBUSTION EFFICIENCY, MIN. 10:1 TURNDOWN. F PROVIDE MANUFACTURER'S STARTUP AND REPORT. G MODULATING HOT GAS REHEAT COIL. H R410A REFRIGERANT, INTEGRAL FILTER DRYER, AND HIGH/LOW PRESSURE SWITCHES. I REFER TO FLOOR PLANS FOR SYSTEM ORIENTATIONS. NUMBERED NOTES: 1 LAT IS MEASURED AT COIL DISCHARGE. 2 PROVIDE BAS MS/TP CONTROLLER WITH ALL REQUIRED SENSORS. THESE SHALL INCLUDE, BUT ARE NOT LIMITED TO, SUPPLY AIR TEMPERATURE SENSOR, OUTSIDE AIR TEMPERATURE SENSOR, AND OUTSIDE AIR HUMIDITY SENSOR. 3 SMOKE DETECTOR (SUPPLIED BY ELECTRICAL) INSTALLED BY THE MECHANICAL CONTRACTOR IN THE SUPPLY AIR DUCTWORK, SHALL PROBIDE UNIT SHUTDOWN ON DETECTION OF SMOKE AND SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM. SEE ELECTRICAL DRAWINGS. 4 14" HIGH ROOF CURB, MANUFACTURER'S SUPPLIED. 5 UNIT MOUNTED DISCONNECT. 6 MODULATING DAMPERS SHALL BE LOW LEAKAGE (LESS THAN 1%) PARALLEL BLADE WITH NEOPRENE SEALS AND 24 VOLT ACTUATORS, WITH RAIN HOOD. 7 UNITS SHALL HAVE HINGED ACCESS WITH QUARTER TURN LATCHES FOR FANS, FILTERS, COILS, CONTROLS, ETC. 8 REFRIGERANT CIRCUITS SHALL UTILIZE TXV EXPANSION VALVES ONLY. 9 COMPRESSORS SHALL BE DIGITAL SCROLL TYPE. 10 UNITS SHALL HAVE SINGLE POINT POWER CONNECTION. 11 UNIT CONSTRUCTION SHALL BE DOUBLE WALL WITH FULLY INSULATED PANELS, INSULATION SHALL BE CONTINUOUS, NON-HYDROSCOPIC, AND ANTI-BACTERIAL TREATED. 12 MOTORS ARE PREMIUM EFFICIENCY. 13 REFER TO ELECTRICAL SHEETS FOR VOLTAGE AND PHASE. 14 DOWNFLOW UNIT OR HORIZONTAL UNIT AS INDICATED ON PLANS. 15 PROVIDE CONDENSER COIL HAIL GUARDS. 16 PROVIDE BYPASS DAMPERS FOR ECONOMIZER OPERATION. 17 PROVIDE POLYMER E-COATING PACKAGED ROOFTOP UNIT SCHEDULE MARK SERVICE NOMINAL TONS SUPPLY (CFM) OUTDOOR (CFM) ESP (IN WC) FAN MOTOR (HP) COOLING CAPACITY HOT GAS REHEAT HEATING CAPACITY EFFICIENCY (EER/IEER)FILTER WEIGHT (LBS)MODEL NOTESTOTAL (BTUH) SENSIBLE (BTUH) EAT (DB °F) EAT (WB °F) LAT (DB/WB °F) TOTAL (MBH) LAT (DB °F) INPUT (MBH) OUTPUT (MBH)EAT (°F) LAT (°F) TURNDOWN RATIO RTU-1 KITCHEN 30 6,000 3,000 0.75 5.0 334.5 154.9 78.9 71.4 52.7/52.5 125.0 72.0 405.0 328.1 49.8 100.4 13:1 108/13.2 MERV 11 3000 RN-030-8-A 1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18 BASIS OF DESIGN: AAON ACCEPTABLE EQUALS: TRANE, LENNOX, CARRIER, DAIKIN, GREENHECK GENERAL NOTES APPLICABLE TO ALL: A COOLING CAPACITY AND EFFICIENCY RATINGS BASED ON AHRI VALUES FOR EAT LISTED AND OUTDOOR UNIT EAT OF 95 °F. B PROVIDED WITH ELECTRICAL DISCONNECT AND SINGLE POINT, THRU-THE-CURB CONNECTION. REFER TO ELECTRICAL PLANS FOR VOLTAGE AND PHASE. C PROVIDE WITH CLASS 1, LOW-LEAKAGE TYPE SHUTOFF DAMPERS W/ BLADE AND JAMB SEALS. D PROVIDE 2" MERV 11 PLEATED DISPOSABLE FILTERS, DIRTY FILTER MONITOR & ALARM, CONDENSATE OVERFLOW SWITCH, SS DRAIN PAN, SINGLE POINT POWER CONNECTION, 100% OA WEATHER HOOD W/ ALUMINUM FILTERS. E FANS SHALL BE DIRECT DRIVE PLENUM TYPE WITH PREMIUM EFFICIENCY MOTORS AND VARIABLE SPEED DRIVE. F HEATING SECTION SHALL HAVE A STAINLESS STEEL HEAT EXCHANGER W/ DIRECT SPARK IGNITION, 10 YEAR WARRANTY, AND MIN. 80% STEADY STATE COMBUSTION EFFICIENCY, MIN. 10:1 TURNDOWN. G PROVIDE MANUFACTURER'S STARTUP AND REPORT. H MODULATING HOT GAS REHEAT COIL. I R410A REFRIGERANT, INTEGRAL FILTER DRYER, AND HIGH/LOW PRESSURE SWITCHES. J PROVIDED WITH CRANKCASE HEATER, HARD START CAPACITOR AND RELAY K REFER TO FLOOR PLANS FOR SYSTEM ORIENTATIONS. NUMBERED NOTES: 1 PROVIDE ENERGY CODE COMPLIANT, 7-DAY PROGRAMMABLE THERMOSTAT WITH MANUAL CHANGEOVER CONTROL, TIME-DELAY RELAY, AND ANTI-SHORT CYCLE CONTROLS. PROVIDE WITH VENTED, LOCKING COVER. 2 LAT IS MEASURED AT COIL DISCHARGE. 3 PROVIDE BAS MS/TP CONTROLLER WITH ALL REQUIRED SENSORS. THESE SHALL INCLUDE, BUT ARE NOT LIMITED TO, SUPPLY AIR TEMPERATURE SENSOR, DUCT-MOUNTED RETURN AIR TEMPERATURE SENSOR, DUCT-MOUNTED RETURN AIR HUMIDITY SENSOR, OUTSIDE AIR TEMPERATURE SENSOR, AND OUTSIDE AIR HUMIDITY SENSOR. 4 SMOKE DETECTOR (SUPPLIED BY ELECTRICAL) INSTALLED BY THE MECHANICAL CONTRACTOR IN THE SUPPLY AIR DUCTWORK, SHALL PROBIDE UNIT SHUTDOWN ON DETECTION OF SMOKE AND SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM. SEE ELECTRICAL DRAWINGS. 5 14" HIGH ROOF CURB, MANUFACTURER'S SUPPLIED. 6 UNIT MOUNTED DISCONNECT. 7 MODULATING DAMPERS SHALL BE LOW LEAKAGE (LESS THAN 1%) PARALLEL BLADE WITH NEOPRENE SEALS AND 24 VOLT ACTUATORS, WITH RAIN HOOD. 8 UNITS SHALL HAVE HINGED ACCESS WITH QUARTER TURN LATCHES FOR FANS, FILTERS, COILS, CONTROLS, ETC. 9 REFRIGERANT CIRCUITS SHALL UTILIZE TXV EXPANSION VALVES ONLY. 10 COMPRESSORS SHALL BE SCROLL TYPE. 11 UNITS SHALL HAVE SINGLE POINT POWER CONNECTION. 12 UNIT CONSTRUCTION SHALL BE DOUBLE WALL WITH FULLY INSULATED PANELS, INSULATION SHALL BE CONTINUOUS, NON-HYDROSCOPIC, AND ANTI-BACTERIAL TREATED. 13 MOTORS ARE PREMIUM EFFICIENCY. 14 REFER TO ELECTRICAL SHEETS FOR VOLTAGE AND PHASE. 15 DOWNFLOW UNIT OR HORIZONTAL UNIT AS INDICATED ON PLANS. 16 PROVIDE CONDENSER COIL HAIL GUARDS. 17 PROVIDE WITH ENTHALPY ECONOMIZER. PROVIDE AIR-SIDE ECONOMIZER CONTROLS INCLUDING IECC COMPLIANT HIGH LIMIT CUTOFF AND FAULT DETECTION AND DIAGNOSTICS SYSTEM. 18 PROVIDE POLYMER E-COATING AIR DISTRIBUTION DEVICES SCHEDULE MARK SERVICE FACE SIZE NECK SIZE NC BASIS OF DESIGN NOTES A SUPPLY 24 "x 24" SEE DWGS <25 TITUS TMS-AA 1,2,3 B SUPPLY 12 "x 12" SEE DWGS <25 TITUS TMS-AA 1,2,3 C RETURN/EXHAUST/TRANSFER 24 "x 24" SEE DWGS <25 TITUS 50F 1,2,3 D RETURN/EXHAUST/TRANSFER 12 "x 12" SEE DWGS <25 TITUS 50F 1,2,3 E RETURN/EXHAUST/TRANSFER 24"x 12" SEE DWGS <25 TITUS 50F 1,2,3 F SUPPLY 36" SEE DWGS <25 TITUS ML-39 1,2,3,4 BASIS OF DESIGN: TITUS ACCEPTABLE EQUALS: PRICE, NAILOR, TUTTLE & BAILEY, METALAIRE GENERAL NOTES: A. FACE AND NECK SIZES ARE NOMINAL DIMENSIONS. ACTUAL DIMENIONS SHALL BE VERIFIED WITH MANUFACTURE'S LITERATURE. B. NC VALUES ARE BASED UPON MAXIMUM CFM SHOWN ON FLOOR PLANS. C. NECK SIZE SHALL BE FULL SIZE OF CONNECTING DUCTWORK. REFER TO FLOOR PLAN FOR SIZES. NUMBERED NOTES: 1 FINISH TO BE APPROVED BY ARCHITECT. PROVIDE MANUFACTURER WHITE SHOP FINISH IF NOT OTHERWISE SPECIFIED. 2 ALUMINUM CONSTRUCTION 3 DUCT RUNOUT SIZE TO BE THE SAME AS NECK SIZE UNLESS OTHERWISE NOTED. 4 3 FT LONG LINEAR SLOT DIFFUSE WITH ONE (2) SLOTS AT 1" SLOT SPACING. PROVIDE SUPPLY DIFFUSERS WITH INSULATED PLENUM BOX AND RETURN GRILLES WITH UNINSULATED PLENUM BOX. LOCATION : ATLANTIC BEACH, FL WEATHER DATA : MAYPORT NAF, FL LAT : 30.400N LONG : 81.417W CLIMATE ZONE : 2A SUMMER DESIGN CONDITION DRY BULB/WET BULB(0.4%) : 93.4/77.0 WINTER DESIGN CONDITION DRY BULB(99.6%) : 34.6 SUMMER DESIGN INDOOR BULB/%RH : 75/50% WINTER DESIGN INDOOR BULB: 70 BASED ON 2021 ASHRAE HANDBOOK FUNDAMENTALS DESIGN CONDITION DRAWN BY: PROJECT NO.: SCALE: REVISION NO.DATE DESCRIPTION THE INFORMATION SHOWN ON THESE DRAWINGS IS OWNED BY AND IS THE PROPERTY OF SHEPPHIRD ASSOCIATES, ARCHITECTS + ENGINEERS. NO PART THEREOF SHALL BE COPIED, ADAPTED, OR DISTRIBUTED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF SHEPPHIRD ASSOCIATES, ARCHITECTS + ENGINEERS. COPYRIGHT © 2023 26560 AGOURA ROAD, SUITE 106 CALABASAS, CA 91302 310.670.9144 A S S O C I A T E S ARCHITECTS + ENGINEERS S H E P P H I R D will.s@shep-ae.com 1 12-02-22 SD PRICING 2 2-10-23 DD PRICING 3 9-07-23 PHASE 2 90% CD Atlantic Beach Country Club Phase 2 Construction Documents 1600 Selva Marina Drive Atlantic Beach, FL 32233 1/4" = 1'-0" 1-M0.31PHASE 2 -MAIN CLUBHOUSE MECHANICALSCHEDULES2022-352 Author