ABCC P2 - Bldg 1 - 1-M0.32_1MAKE-UP AIR UNIT SCHEDULE MARK SERVICE TOTAL SUPPLY CFM ESP (IN WC)SUPPLY FAN HP HEAT INPUT MBH FILTER WEIGHT (LBS)BASIS OF DESIGN: GREENHECK NOTESHEAT INPUT MBH HEAT OUTPUT MBH AIR DELTA T °F TURNDOWN RATIO KSF-1 KITCHEN HOOD MAKE-UP AIR 2,350 1.0" 1.5 137.3 109.8 46.9 4:1 MERV 8 1200 IGX-P115-H12-MF-E 1,2,3,4,5 KSF-2 KITCHEN HOOD MAKE-UP AIR 2,860 1.0" 1.5 183.1 146.4 51.3 4:1 MERV 8 1200 IGX-P115-H12-MF-G 1,2,3,4,5 BASIS OF DESIGN: GREENHECK APPROVED EQUALS: CAPTIVE-AIRE, ACCUREX NOTES: 1. HORIZONTAL UNIT WITH OUTDOOR AIR INTAKE HOOD AND END DISCHARGE. 2. PROVIDE FULL PERIMETER ROOF CURB. 3. PROVIDE DISCONNECT SWITCH. 4. PROVIDE MOTORIZED INTAKE DAMPER AND V-BANK FILTER SECTION. 5. PROVIDE ON/OFF RELAYS FOR BAS MONITORING. CONNECT MONITORING RELAY TO BAS GENERAL I/O PANEL. VRF HEAT RECOVERY UNIT SCHEDULE VRF HEAT RECOVERY UNIT BRANCH SELECTOR UNIT NOTES MARK COOLING HEATING REFRIGERANT MODEL NUMBER NUMBER OF MODULES VOLTAGE MCA MAX FUSE WEIGHT LBS MARK MODEL NUMBER VOLTAGE MCA MAX FUSE WEIGHT LBSOUTDOOR AMBIENT °F NORMAL MBH ACTUAL MBH IEER AT 95°F SCHE AT 95°F OUTDOOR AMBIENT °F NORMAL MBH ACTUAL MBH COP AT 47°F REFRIGERANT TYPE ADDITIONAL CHARGE TOTAL CHARGE VRF-1 95.0 72.2 59.0 23.0 22.0 32.0 86.1 85.0 3.58 R-410A - 23.37 REYQ72AATJA 1 208/3 27.3 30.0 550 BS-1 BSF6Q54TVJ 208/1 0.6 15.0 90 1,2,3,4,5 BASIS OF DESIGN: DAIKIN ACCEPTABLE EQUALS: MITSUBISHI, DAIKIN GENERAL NOTES APPLICABLE TO ALL: A COOLING CAPACITY AND EFFICIENCY RATINGS BASED ON AHRI VALUES FOR EAT LISTED AND OUTDOOR UNIT EAT OF 95 °F. HEAT PUMP HEATING CAPACITY BASED ON OUTDOOR UNIT EAT OF 47 °F. SUPPLY AIRFLOW REFLECTED FOR HIGH SPEED OPERATION. B INVERTER COMPRESSOR, R-410A. PROVIDE AND INSTALL REFRIGERANT SUPPLY AND RETURN LINES PER MANUFACTURERS RECOMMENDATIONS. C PROVIDED WITH ELECTRICAL DISCONNECT FOR INDOOR UNIT. PROVIDE ELECTRICAL DISCONNECT FOR OUTDOOR UNIT TO BE INSTALLED BY ELECTRICAL CONTRACTOR. REFER TO ELECTRICAL PLANS FOR VOLTAGE AND PHASE. D PROVIDE ADAPTIVE TOUCH CONTROLLER, OR EQUAL, WITH BACNET MS/TP INTERFACE. NUMBERED NOTES: 1 REFER TO ELECTRICAL SHEETS FOR VOLTAGE AND PHASE. 2 INSTALLING CONTRACTOR SHALL BE TRAINED AND CERTIFIED THROUGH THE MANUFACTURER. 3 PROVIDE AND INSTALL REFRIGERANT SUPPLY AND RETURN LINES PER MANUFACTURER'S RECOMMENDATIONS AND REQUIREMENTS. 4 REFER TO VRV RISER DIAGRAMS FOR ADDITIONAL REQUIREMENTS. 5 PROVIDE MANUFACTURER'S SUPPLIED REFRIGERANT LINE SETS. VRF CONCEALED DUCTED UNIT SCHEDULE MARK (INDOOR/OUTDOOR)SERVICE SUPPLY CFM OUTSIDE AIR CFM ESP (IN WC) COOLING CAPACITY HEATING CAPACITY (MBH) ELECTRICAL ASSOCIATED OUTDOOR AIR UNIT ASSOCIATED OUTDOOR CONDENSING UNIT BRANCH SELECTOR UNIT MODEL NOTESTOTAL (MBH) SEN. (MBH)VOLTAGE MCA MOCP FCU-1 BREAK ROOM 600 100 0.5 17.4 14.0 28.0 208 1.8 15.0 DOAS-1 VRF-1 BS-1 FXSQ24TAVJU 1,2,3,4,5,6,7,8,9,10,11 FCU-2 CORRIDOR 850 295 0.5 7.7 5.7 14.0 208 0.8 15.0 DOAS-1 VRF-1 BS-1 FXSQ30TAVJU 1,2,3,4,5,6,7,8,9,10,11 FCU-3 LEVEL 1 OFFICES 730 50 0.5 13.3 12.3 14.0 208 0.8 15.0 DOAS-1 VRF-1 BS-1 FXSQ24TAVJU 1,2,3,4,5,6,7,8,9,10,11 FCU-4 POOL RESTROOM 500 500 0.5 4.5 4.5 89.0 208 0.8 15.0 DOAS-1 VRF-1 BS-1 FXSQ15TAVJU 1,2,3,4,5,6,7,8,9,10,11 FCU-5 LEVEL2 OFFICES 525 70 0.5 11.2 9.8 17.7 208 1.4 15.0 DOAS-1 VRF-1 BS-1 FXSQ15TAVJU 1,2,3,4,5,6,7,8,9,10,11 FCU-6 LEVEL2 CONFERENCE ROOM 220 85 0.5 7.4 5.8 17.7 208 1.4 15.0 DOAS-1 VRF-1 BS-1 FXSQ09TAVJU 1,2,3,4,5,6,7,8,9,10,11 BASIS OF DESIGN: DAIKIN ACCEPTABLE EQUALS: MITSUBISHI, DAIKIN, LG GENERAL NOTES APPLICABLE TO ALL: A REFER TO FLOOR PLANS FOR SYSTEM ORIENTATIONS. B CONDENSATE PIPING TO BE SIZED BASED ON UNIT CONNECTION, TRAPPED, AND ROUTED PER PLANS. IN LIEU OF TRAP, AN INLINE CHECK VALVE MAY BE PROVIDED. C PROVIDED WITH ELECTRICAL DISCONNECT FOR INDOOR UNIT. PROVIDE ELECTRICAL DISCONNECT FOR OUTDOOR UNIT TO BE INSTALLED BY ELECTRICAL CONTRACTOR. REFER TO ELECTRICAL PLANS FOR VOLTAGE AND PHASE. D PROVIDED 1" MERV 8 FILTER. NUMBERED NOTES: 1 REFER TO ELECTRICAL SHEETS FOR VOLTAGE AND PHASE. 2 INSTALLING CONTRACTOR SHALL BE TRAINED AND CERTIFIED THROUGH THE MANUFACTURER. 3 EACH ZONE SHALL BE SERVED BY AN INDIVIDUAL HEAT RECOVERY OR CHANGEOVER BOX. SAID BOX SHALL NOT PRODUCE CONDENSATION. 4 PROVIDE AND INSTALL REFRIGERANT SUPPLY AND RETURN LINES PER MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS. 5 REFER TO VRV RISER DIAGRAMS FOR ADDITIONAL REQUIREMENTS. 6 PROVIDE AN AIR FILTER BOX WITH FILTER. 7 UNITS TO HAVE INTEGRAL CONDENSATE PUMPS. 8 DISCONNECT PROVIDED BY ELECTRICAL. 9 PROVIDE MANUFACTURER'S SUPPLIED REFRIGERANT LINE SETS. 10 CHANGEOVER BOXES TO BE OPERABLE WITHOUT CONDENSATE LINES. 11 PROVIDE VERDANT WIRELESS ENERGY MANAGEMENT THERMOSTATS AND ONLINE CONNECTION KIT; MODELS VX-TW-KT AND OL-KT FOR REMOTE MANAGEMENT CAPABILITIES. EXHAUST FAN SCHEDULE MARK SERVICE TYPE CFM ESP (IN WC) MAX RPM MAX HP SONES WEIGHT (LBS)DRIVE BASIS OF DESIGN: GREENHECK NOTES EF-1 MEN'S LOCAKER ROOM INLINE 525 1.0" 1,597 388 WATTS 4.3 50 DIRECT CSP-A780 1,2,4,5,6 EF-2 WOMEN'S LOCKER ROOM INLINE 525 1.0" 1,597 388 WATTS 4.3 50 DIRECT CSP-A780 1,2,4,5,6 EF-3A MEN'S RESTROOM INLINE 225 1.0" 1,696 83 WATTS 4.0 40 DIRECT SQ-A390-VG 1,2,4,5,6 EF-3B WOMEN'S RESTROOM INLINE 225 1.0" 1,696 83 WATTS 4.0 40 DIRECT SQ-A390-VG 1,2,4,5,6 EF-5A MEN'S POOL RESTROOM INLINE 250 1.0" 1,704 91 WATTS 4.2 40 DIRECT SQ-A390-VG 1,2,4,5,6 EF-5B WOMEN'S POOL RESTROOM INLINE 250 1.0" 1,704 91 WATTS 4.2 40 DIRECT SQ-A390-VG 1,2,4,5,6 EF-8 KITCHEN RESTROOMS CEILING 75 0.75" 901 80 WATTS 3.0 25 DIRECT SP-B110 1,2,3,4,5,14 EF-9 KITCHEN RESTROOMS CEILING 75 0.75" 901 80 WATTS 3.0 25 DIRECT SP-B110 1,2,3,4,5,14 EF-10 POOL STORAGE CEILING 125 0.5" 950 80 WATTS 2.0 30 DIRECT SP-B110 1,2,3,4,5,14,15 KEF-1 KITCHEN HOOD EXHAUST ROOF MOUNTED 2,910 1.25" 1,725 2 23 170 DIRECT CUE-160-VG 1,2,5,7,8,9,10,16,17,18,19,10,21 KEF-2 KITCHEN HOOD EXHAUST ROOF MOUNTED 3,580 1.25" 1,289 3 23 260 DIRECT CUE-200-VG 1,2,5,7,8,9,11,16,17,18,19,10,21 KEF-4 DISHWASHER EXHAUST ROOF MOUNTED 975 1.0" 1,337 3/4 11 1/2 140 DIRECT CUE-140-VG 1,2,5,9,13,16,18,20 BASIS OF DESIGN: GREENHECK APPROVED EQUALS: PENN, COOK NOTES: 1.REFER TO ELECTRICAL SHEETS FOR VOLTAGE AND PHASE. 2. MANUFACTURER-PROVIDED DISCONNECT. 3. INTERLOCK FAN WITH LIGHT SWITCH 4. PROVIDE VIBRATION ISOLATION SUPPORTS. 5. SPEED CONTROLLER 6. TIME CLOCK 7. PROVIDE GREASE CONTAINER. 8. PROVIDE DRAIN CONNECTION. 9. MIAMI-DADE HIGH WIND RATED CONSTRUCTION. 10. INTERLOCK WITH KSF-1. 11. INTERLOCK WITH KSF-2. 13. ALUMINUM BACKDRAFT DAMPER. 14. BACKDRAFT DAMPER. 15. COOLING ONLY THERMOSTAT CONTROL SET TO 85 DEGREES F. 16. ALUMINUM HOUSING. 17. UL 705 LISTED. 18. STAINLESS STEEL BIRDSCREEN. 19. HINGED ROOF CURB. 20. 14" ROOF CURB. 21. CLEAN OUT PORT. DRAWN BY: PROJECT NO.: SCALE: REVISION NO.DATE DESCRIPTION THE INFORMATION SHOWN ON THESE DRAWINGS IS OWNED BY AND IS THE PROPERTY OF SHEPPHIRD ASSOCIATES, ARCHITECTS + ENGINEERS. NO PART THEREOF SHALL BE COPIED, ADAPTED, OR DISTRIBUTED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF SHEPPHIRD ASSOCIATES, ARCHITECTS + ENGINEERS. COPYRIGHT © 2023 26560 AGOURA ROAD, SUITE 106 CALABASAS, CA 91302 310.670.9144 A S S O C I A T E S ARCHITECTS + ENGINEERS S H E P P H I R D will.s@shep-ae.com 1 12-02-22 SD PRICING 2 2-10-23 DD PRICING 3 9-07-23 PHASE 2 90% CD Atlantic Beach Country Club Phase 2 Construction Documents 1600 Selva Marina Drive Atlantic Beach, FL 32233 1-M0.32PHASE 2 -MAIN CLUBHOUSE MECHANICALSCHEDULES2022-352 Author