1600 Selva Marina Dr MECH23-0013 COAB Permit Form with ConditionsOWNER:ADDRESS:CITY:STATE:ZIP:
ATLANTIC BEACH
COUNTRY CLUB INC 1600 SELVA MARINA DR ATLANTIC BEACH FL 32233
COMPANY:ADDRESS:CITY:STATE:ZIP:
BENDER & MODLIN FIRE
SPRINKLER 170 -G C COLLEGE DR ORANGE PARK FL 32065
TYPE OF
CONSTRUCTION:
REAL ESTATE
NUMBER:ZONING:BUILDING USE
GROUP:SUBDIVISION:
172000 0010 SELVA MARINA UNIT 05
JOB ADDRESS:PERMIT TYPE:DESCRIPTION: VALUE OF WORK:
1600 SELVA MARINA DR MECHANICAL COMMERCIAL
SEPARATE PLANS OTHER Fire Sprinkler System $10000.00
FEES
DESCRIPTION ACCOUNT QUANTITY PAID AMOUNT
FIRE DEPARTMENT FEE 45500002080800 0 $100.00
FIRE SPRINKLER SYSTEM 455-0000-322-1000 0 $17.25
MECHANICAL BASE FEE 455-0000-322-1000 0 $55.00
STATE DBPR SURCHARGE 455-0000-208-0700 0 $2.00
LIST OF CONDITIONS
Roll off container company must be on City approved list . Container cannot be placed on City right-of-way.
NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property
that may be found in the public records of this county, and there may be additional permits required from other
governmental entities such as water management districts, state agencies, or federal agencies.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT
IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF
COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST
INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN
ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
MUST CALL INSPECTION PHONE LINE (904) 247-5814 BY 4 PM FOR NEXT DAY INSPECTION.
ALL WORK MUST CONFORM TO THE CURRENT 6TH EDITION (2017) OF THE FLORIDA BUILDING
CODE, NEC, IPMC, AND CITY OF ATLANTIC BEACH CODE OF ORDINANCES .
ALL CONDITIONS OF PERMIT APPLY, PLEASE READ CAREFULLY.
1 of 2Issued Date: 11/27/2023
PERMIT NUMBER
MECH23-0013
ISSUED: 11/27/2023
EXPIRES: 5/25/2024
MECHANICAL COMMERCIAL
SEPARATE PLANS PERMIT
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
STATE DCA SURCHARGE 455-0000-208-0600 0 $2.00
TOTAL: $176.25
2 of 2Issued Date: 11/27/2023
PERMIT NUMBER
MECH23-0013
ISSUED: 11/27/2023
EXPIRES: 5/25/2024
MECHANICAL COMMERCIAL
SEPARATE PLANS PERMIT
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
Final Plumbing
Final Electrical
Final HVAC
CC Final
Final Building*
Swimming Pool Steel
Swimming Pool Safety
Electrical Grounding & Bonding
Swimming Pool Final (Bldg)
Swimming Pool Final (PW)
Formed Columns/ Beams*
Masonry Cell Fill
Structural Steel*
OTHER:
OTHER:
OTHER:
OTHER:
OTHER:
Power Pole
Silt Fence
Piers/ Stem Walls
Underground Plumbing
Underground Electric
Foundation/ Footing
Slab**
Retaining Wall Footing
Driveway
Sewer (Building Dept)
Sewer Tap (Utilities Dept)
Rough Electric*
Rough Plumbing/ Top Out*
Rough Mechanical*
House Wrap
Wall Sheathing
Roof Sheathing
Tie-down Framing Connections
Rough Framing
Roofing In Progress
Window/Door In-Progress
Insulation Ceiling
Insulation Wall
Exterior Lath
Stucco Scratch Coat
Exterior Siding In-Progress
Brick Flashing & Ties
Early Power
Gas Rough
Gas Final*
* When all rough electric, plumbing, mechanical are complete but before any work is
covered up.
* When all gas piping is complete and wallboard is installed but before gas is
attached to any appliance. All outlets must be capped and pipe pressurized at a
minimum of 15 lbs.
* For new living space: When all construction work including electrical, plumbing,
mechanical, exterior finish, grading, required paving and landscaping is complete
and the building is ready for occupancy, but before being occupied
Additional inspections may apply to your project if your project
contains these elements:
INSPECTIONS REQUIRED FOR BUILDING PERMITS
To verify compliance with building codes, inspections of the work authorized are required at various points of the construction.
The following inspections are typically required for residential projects:
Date: Initial: Date: Initial:
_____________________________________________________
Permit Type
____________________________________________________
Permit No.
__________________________________________________________
Job Address
____________________________________________________
Contractor
POST THIS CARD WITH PERMITS AND PERMIT
DOCUMENTATION IN FRONT OF BUILDING
Construction Hours per City Code: 7am—7pm Weekdays; 9am—7pm Weekends
Building Department Public Works/Utilities Fire Department
Phone: 904-247-5826 Phone: 904-247-5834 Phone: 904-630-4789
Fax: 904-247-5845 Fax: 904-247-5843 Fax: 904-630-4203
* When forms and reinforcing steel, anchor bolts, sleeves and inserts, and all
electrical, plumbing and mechanical work is in place, but before concrete is poured.
* When all structural steel members are in place and all connections are complete,
but before such work is covered or concealed.
** FORM BOARD ELEVATION CERTIFICATE MUST BE ON-SITE FOR SLAB INSPECTION
Fire Sprinkler System
1600 SELVA MARINA DR
BENDER & MODLIN FIRE SPRINKLER
MECH23-0013
MECH23-0013
STORAGE
009
LAUNDRY
137
MEN'S POOL
RESTROOM
142
WOMEN'S
POOL
RESTROOM
145
VESTIBULE
141
VESTIBULE
144
ACCESSIBLE
RESTROOM
142D
BREEZEWAY
010A
ACCESSIBLE
RESTROOM
145E
MEN'S
FITNESS
RESTROOM
152
EXERCISE
ROOM
154
YOUTH
155
MECH /
ELEC
149
ACCESSIBLE
RESTROOM
153B
RECEPTION
150
UNISEX
RESTROOM
157
CORRIDOR
148
CHECK-IN
156A
MANUAL
THERAPY
146
GROUP
FITNESS
151
9' - 0"9' - 0"
9' - 0"
9' - 0"10' - 5"
10' - 5"
9' - 0"
12' - 6"
CHECK-IN
156
WOMEN'S
FITNESS
RESTROOM
153
WC
153A
WC
152A
EXISTING 4" WET FIRE
SPRINKLER RISER
REMOVING AND
RELOCATING.
UNDERGROUND WORK
BY OTHERS.
X X X
XXX
X X X
X
X
X
X
X
X
R R
RR
R R
R
R
R
R
R
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
R
NEW CAP ON END OF 1-1/2"
LINE. RECONNECTING AT
NEW RISER LOCATION.
X X
NEW 4" WET FIRE
SPRINKLER RISER.
4" UNDERGROUND WORK
BY OTHERS.
RISER USING HEAT
TRACING IF UNPROTECTED
AREA. (WIRING BY OTHERS)
R
R
R
A R
A R
X
X
DRY HEADS (TYP)
A
TOR2
BOR2
333 303
309
S1
300
S2
301
S3
302
S4
304
S5
305
S9
340
S10
341
S14
325S15
S6
330
S7
331
S8
332
S11
321
S12
322
S13
323
324
345
307308
326
S16
350
335
S17
S18
320
335A
1. THIS CONTRACT IS TO RELOCATE EXISTING
HEADS TO ACCOMMODATE NEW CEILING
LAYOUT FOR TENANT BUILD-OUT.
2. WET SYSTEM RISER RELOCATING TO NEW
AREA. NEW LOCATION REQUIRED MORE
PRESSURE WITH CURRENT WATER
CONDITIONS. NEW 4" MAIN TYING INTO
EXISTING MAINS FOR HYDRAULIC PURPOSES.
3. ALL WORK TO BE PERFORMED AS PER
NFPA 13.
4. HANGERS TO BE PLACED EVERY 4TH
TRUSS OR +/- EVERY 8' FOR NEW 4" MAIN.
DRAWING NOTES
FLOW TEST DATA
FIRE PROTECTION CABANA/FITNESS 1ST FL
SLOPE
5 : 12
SLOPE
5 : 12
RIDGEVALL
E
Y
V
A
L
L
E
Y
SLOPE
5 : 12
SLOPE
5 : 12 RIDGEV
A
L
L
E
Y
VALL
E
Y RIDGESLOPE12 : 12SLOPE12 : 12SLOPE12 : 12SLOPE12 : 12SLOPE
7 : 12
GABLE ENDSLOPE
7 : 12
SLOPE
7 : 12
RIDGEGABLE END
GABLE
E
N
D
SLOPE12 : 12RIDGEGABLE ENDSLOPE7 : 12SLOPE
7 : 12
SLOPE
7 : 12
SLOPE7 : 12SLOPE7 : 12SHED DORMER
VALLEY
SHED DORMER
VALLEY
SHED DORMER
VALLEY
SHED DORMER
VALLEY
VALLEY VALLEY VALLEY VALLEY
CAPPED OFF AND
RECONNECTED AT
NEW RISER LOCATION
FIRE PROTECTION CABANA/FITNESS ATTIC
NEW RISER LOCATION
FEED FROM SYSTEM
BELOW.
ALL OTHER PIPING AND HEADS
EXISTING TO REMAIN.
200
201
202
204
205
206
207
208
213
209
210
211212
203
207A
DENOTES NEW PIPE
DENOTES EXISTING PIPE TO REMAIN
DENOTES RELOCATED/ADDED FIRE
SPRINKLER HEAD
DENOTES FIRE SPRINKLER HEAD TO
BE RELOCATED
DENOTES EXISTING PIPE TO
DENOTES FIRE SPRINKLER HEAD TO
BE REMOVED
DENOTES EXISTING FIRE SPRINKLER
HEAD TO REMAIN
27
DENOTES NEW CONNECTION
DENOTES HYDRAULIC NODE POINT
DENOTES PLUG
DENOTES CAP
DENOTES FIRE RISER LOCATION
SYMBOLS LEGEND
BE REMOVED
A
X
R R
X
MAXIMUM DISTANCE BETWEEN HANGERS
BM 24x36HFIRE SPRINKLER, INC.
bender & modlin FIRE SPRINKLER
170-G College Drive
Orange Park, FL 32065
(904) 298-2637
Job Name : REV #1 Atlantic Beach CC Area #3
Building : Tennis / Fitness Center
Location : Atlantic Beach‚ FL
System : 1
Contract :
Data File : REV #1 Atlantic Beach CC Area #3.WX3
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 1
REV #1 Atlantic Beach CC Area #3 Date 9/11/2023
Hydraulic Design Information Sheet
Name - REV #1 Atlantic Beach Country Club Area #3 Date - 9/11/2023
Location - Atlantic Beach‚ FL
Building - Tennis / Fitness Center System No. - 1
Contractor - bender & modlin FIRE SPRINKLER INC Contract No. -
Calculated By - Marcel Ardelean Drawing No. -
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height - 29'-10"
Occupancy - Attic
S (X) NFPA 13 (X) Lt. Haz. Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 ( ) Ex.Haz.
Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve
S Other
T Specific Ruling Made By Date
E
M Area of Sprinkler Operation - 5+2 SPK System Type Sprinkler/Nozzle
Density - .10 (X) Wet Make tyco
D Area Per Sprinkler - 240 ( ) Dry Model BB3
E Elevation at Highest Outlet - ( ) Deluge Size 1/2"
S Hose Allowance - Inside - ( ) Preaction K-Factor 5.6
I Rack Sprinkler Allowance - ( ) Other Temp.Rat.200
G Hose Allowance - Outside -
N
Note Design Criteria per Manuf.e req. (5) - BB3 plus (2) AP Spk.
Calculation Flow Required - 270.9 Press Required - 44.4 at TEST
Summary C-Factor Used: 150 Overhead 150 Underground
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - 10/10/2022 Cap. -
T Time of Test - - Rated Cap.- Elev.-
E Static Press - 46 @ Press -
R Residual Press - 42 Elev. - Well
Flow - 1000 Proof Flow
S Elevation -
U
P Location -
P
L Source of Information - CONTRACT DOCUMENTS
Y
C Commodity Class Location
O Storage Ht. Area Aisle W.
M Storage Method: Solid Piled % Palletized % Rack
M
( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap.
S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non
T A ( ) Mult. Row ( ) Open Shelf
O C
R K Flue Spacing Clearance:Storage to Ceiling
A Longitudinal Transverse
G
E Horizontal Barriers Provided:
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLERPage 2 REV #1 Atlantic Beach CC Area #3Date 9/11/2023 10203040E50R60U70S80S90E100R110P120130140150100 200 300 400 500 600 700 800 900FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 46 C2 - Residual Pressure: 42 C2 - Residual Flow : 1000 D1 - Elevation : 12.704 D2 - System Flow : 170.995 D2 - System Pressure : 44.438 Hose ( Demand ) : 100 D3 - System Demand : 270.995 Safety Margin : 1.205 D1D2D3Water Supply Curve CComputer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLERPage 3 REV #1 Atlantic Beach CC Area #3Date 9/11/2023 Fitting Legend Abbrev.Name ½¾11¼1½22½33½456810121416182024 A Alarm Rel E1 & E3 7.7 21.5 17 27 29 B NFPA 13 Butterfly Valve 00000671001291012192100000 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 F NFPA 13 45' Elbow 111122333457911131719212428 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N CPVC 90' Elbow Tyco 0456791213000000000000 O CPVC Tee - Branch 33568101215000000000000 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10121517202530355060718191101121 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 4
REV #1 Atlantic Beach CC Area #3 Date 9/11/2023
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
209 29.333 22.46 na
207A 29.333 21.78 na
335A 15.75 27.88 na
200 29.333 5.6 14.33 na 21.2 0.1 120 7.0
201 29.333 5.6 15.77 na 22.24 0.1 120 7.0
202 29.333 19.94 na
203 29.333 5.6 20.0 na 25.04 0.1 240 20.0
204 29.333 5.6 20.22 na 25.18 0.1 240 20.0
205 29.333 5.6 20.6 na 25.42 0.1 240 20.0
206 29.333 5.6 21.2 na 25.79 0.1 240 20.0
207 29.333 21.79 na
208 29.333 22.11 na
210 29.333 22.48 na
211 29.333 22.51 na
212 29.333 22.67 na
213 11.75 30.29 na
TOR2 13.333 29.61 na
BOR2 1.0 38.43 na
UG1 0.0 39.13 na
UG2 0.0 39.37 na
BKFL 0.0 39.43 na
HOSE 0.0 44.43 na 100.0
TEST 0.0 44.44 na
The maximum velocity is 14.75 and it occurs in the pipe between nodes 206 and 207A
Pressure / Flow Summary - STANDARD
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 5
REV #1 Atlantic Beach CC Area #3 Date 9/11/2023
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
209 13.38 2.003 2N 18.0 13.250 22.460
to 150.0 0.0 18.000 0.0
211 13.38 0.0018 0.0 31.250 0.055 Vel = 1.36
0.0
13.38 22.515 K Factor = 2.82
207A 145.80 4.26 T 26.334 13.583 21.777
to 120.0 0.0 26.334 5.883
335A 145.8 0.0056 0.0 39.917 0.222 Vel = 3.28
335A 0.0 4.26 2E 26.334 96.417 27.882
to 120.0 0.0 26.334 1.047
TOR2 145.8 0.0056 0.0 122.751 0.685 Vel = 3.28
0.0
145.80 29.614 K Factor = 26.79
200 21.20 1.101 2N 10.0 9.000 14.330 K Factor = 5.60
to 150.0 0.0 10.000 0.0
201 21.2 0.0757 0.0 19.000 1.439 Vel = 7.14
201 22.24 1.101 O 5.0 9.583 15.769 K Factor = 5.60
to 150.0 0.0 5.000 0.0
202 43.44 0.2857 0.0 14.583 4.166 Vel = 14.64
202 0.0 2.003 0.0 4.167 19.935
to 150.0 0.0 0.0 0.0
203 43.44 0.0156 0.0 4.167 0.065 Vel = 4.42
203 25.04 2.003 0.0 6.000 20.000 K Factor = 5.60
to 150.0 0.0 0.0 0.0
204 68.48 0.0360 0.0 6.000 0.216 Vel = 6.97
204 25.18 2.003 0.0 6.000 20.216 K Factor = 5.60
to 150.0 0.0 0.0 0.0
205 93.66 0.0642 0.0 6.000 0.385 Vel = 9.54
205 25.42 2.003 0.0 6.000 20.601 K Factor = 5.60
to 150.0 0.0 0.0 0.0
206 119.08 0.1002 0.0 6.000 0.601 Vel = 12.12
206 25.78 2.003 0.0 4.000 21.202 K Factor = 5.60
to 150.0 0.0 0.0 0.0
207A 144.86 0.1438 0.0 4.000 0.575 Vel = 14.75
207A -119.66 2.003 0.0 2.000 21.777 K Factor = 5.60
to 150.0 0.0 0.0 0.0
207 25.2 0.0055 0.0 2.000 0.011 Vel = 2.57
207 0.0 2.003 2N 18.0 28.750 21.788
to 150.0 O 10.0 28.000 0.0
208 25.2 0.0057 0.0 56.750 0.322 Vel = 2.57
208 0.0 2.003 O 10.0 51.958 22.110
to 150.0 0.0 10.000 0.0
209 25.2 0.0056 0.0 61.958 0.350 Vel = 2.57
209 -13.38 2.003 N 9.0 2.458 22.460
to 150.0 0.0 9.000 0.0
210 11.82 0.0014 0.0 11.458 0.016 Vel = 1.20
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 6
REV #1 Atlantic Beach CC Area #3 Date 9/11/2023
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
210 0.0 2.003 N 9.0 8.833 22.476
to 150.0 O 10.0 19.000 0.0
211 11.82 0.0014 0.0 27.833 0.039 Vel = 1.20
211 13.38 2.003 T 12.965 14.667 22.515
to 150.0 0.0 12.965 0.0
212 25.2 0.0056 0.0 27.632 0.156 Vel = 2.57
212 0.0 4.26 E 19.896 20.917 22.671
to 150.0 0.0 19.897 7.615
213 25.2 0.0001 0.0 40.814 0.006 Vel = 0.57
213 0.0 4.26 2E 39.793 10.750 30.292
to 150.0 0.0 39.792 -0.686
TOR2 25.2 0.0002 0.0 50.542 0.008 Vel = 0.57
TOR2 145.80 4.26 E 13.167 12.333 29.614
to 120.0 A 22.384 51.351 8.341 * * Fixed Loss = 3
BOR2 171.0 0.0075 B 15.8 63.684 0.477 Vel = 3.85
Fsp 0.0
BOR2 0.0 4.23 T 38.446 13.000 38.432
to 150.0 0.0 38.446 0.433
UG1 171.0 0.0051 0.0 51.446 0.264 Vel = 3.90
UG1 0.0 6.09 2F 21.583 250.000 39.129
to 150.0 0.0 21.583 0.0
UG2 171.0 0.0009 0.0 271.583 0.236 Vel = 1.88
UG2 0.0 6.09 0.0 73.000 39.365
to 150.0 0.0 0.0 0.0
BKFL 171.0 0.0009 0.0 73.000 0.064 Vel = 1.88
BKFL 0.0 6.09 0.0 3.000 39.429
to 150.0 0.0 0.0 5.000 * * Fixed Loss = 5
HOSE 171.0 0.0010 0.0 3.000 0.003 Vel = 1.88
HOSE 100.00 6.09 0.0 3.000 44.432 Qa = 100
to 150.0 0.0 0.0 0.0
TEST 271.0 0.0020 0.0 3.000 0.006 Vel = 2.98
0.0
271.00 44.438 K Factor = 40.65
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER
170-G College Drive
Orange Park, FL 32065
(904) 298-2637
Job Name : REV #1 Atlantic Beach CC Area #4
Building : Tennis / Fitness Center
Location : Atlantic Beach‚ FL
System : 1
Contract :
Data File : REV #1 Atlantic Beach CC Area #4.WX4
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 1
REV #1 Atlantic Beach CC Area #4 Date 9/11/2023
Hydraulic Design Information Sheet
Name - REV #1Atlantic Beach Country Club Area #4 Date - 9/11/2023
Location - Atlantic Beach‚ FL
Building - Tennis / Fitness Center System No. - 1
Contractor - bender & modlin FIRE SPRINKLER INC Contract No. -
Calculated By - Marcel Ardelean Drawing No. -
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height - 29'-10"
Occupancy - Fitness
S (X) NFPA 13 (X) Lt. Haz. Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 ( ) Ex.Haz.
Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve
S Other
T Specific Ruling Made By Date
E
M Area of Sprinkler Operation - 1976 System Type Sprinkler/Nozzle
Density - .10 (X) Wet Make tyco
D Area Per Sprinkler - 225 max ( ) Dry Model
E Elevation at Highest Outlet - ( ) Deluge Size 1/2"
S Hose Allowance - Inside - ( ) Preaction K-Factor 5.6
I Rack Sprinkler Allowance - ( ) Other Temp.Rat.155
G Hose Allowance - Outside -
N
Note
Calculation Flow Required - 426.1 Press Required - 35.8 at TEST
Summary C-Factor Used: 150 Overhead 150 Underground
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - 10/10/2022 Cap. -
T Time of Test - - Rated Cap.- Elev.-
E Static Press - 46 @ Press -
R Residual Press - 42 Elev. - Well
Flow - 1000 Proof Flow
S Elevation -
U
P Location -
P
L Source of Information - AHJ
Y
C Commodity Class Location
O Storage Ht. Area Aisle W.
M Storage Method: Solid Piled % Palletized % Rack
M
( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap.
S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non
T A ( ) Mult. Row ( ) Open Shelf
O C
R K Flue Spacing Clearance:Storage to Ceiling
A Longitudinal Transverse
G
E Horizontal Barriers Provided:
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLERPage 2 REV #1 Atlantic Beach CC Area #4Date 9/11/2023 10203040E50R60U70S80S90E100R110P120130140150100 200 300 400 500 600 700 800 900FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 46 C2 - Residual Pressure: 42 C2 - Residual Flow : 1000 D1 - Elevation : 10.394 D2 - System Flow : 326.138 D2 - System Pressure : 35.829 Hose ( Demand ) : 100 D3 - System Demand : 426.138 Safety Margin : 9.346 D1D2D3Water Supply Curve CComputer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLERPage 3 REV #1 Atlantic Beach CC Area #4Date 9/11/2023 Fitting Legend Abbrev.Name ½¾11¼1½22½33½456810121416182024 A Alarm Rel E1 & E3 7.7 21.5 17 27 29 B NFPA 13 Butterfly Valve 00000671001291012192100000 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 F NFPA 13 45' Elbow 111122333457911131719212428 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N CPVC 90' Elbow Tyco 0456791213000000000000 O CPVC Tee - Branch 33568101215000000000000 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10121517202530355060718191101121 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 4
REV #1 Atlantic Beach CC Area #4 Date 9/11/2023
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
S1 20.0 5.6 8.73 na 16.55 0.1 141 7.0
S2 20.0 5.6 9.08 na 16.88 0.1 141 7.0
S3 20.0 5.6 9.59 na 17.34 0.1 141 7.0
S4 10.417 5.6 15.06 na 21.73 0.1 144 7.0
S5 10.417 5.6 14.13 na 21.05 0.1 144 7.0
S6 24.0 5.6 7.01 na 14.83 0.1 141 7.0
S7 24.0 5.6 7.0 na 14.82 0.1 141 7.0
S8 24.0 5.6 7.39 na 15.22 0.1 141 7.0
S9 10.417 5.6 10.42 na 18.08 0.1 144 7.0
S10 10.417 5.6 11.05 na 18.61 0.1 144 7.0
S11 20.0 5.6 8.74 na 16.55 0.1 141 7.0
S12 20.0 5.6 9.04 na 16.84 0.1 141 7.0
S13 20.0 5.6 9.55 na 17.31 0.1 141 7.0
S14 12.5 5.6 14.65 na 21.43 0.1 117 7.0
S15 12.5 5.6 14.29 na 21.17 0.1 117 7.0
S16 12.5 5.6 14.56 na 21.37 0.1 45 7.0
S17 12.5 5.6 10.41 na 18.07 0.1 105 7.0
S18 12.5 5.6 10.67 na 18.3 0.1 105 7.0
350 15.75 14.24 na
345 13.75 11.07 na
340 13.75 10.15 na
341 13.75 10.89 na
303 15.75 15.12 na
335 15.75 15.26 na
333 15.75 15.24 na
320 25.0 7.3 na
330 25.0 6.81 na
331 25.0 6.8 na
332 25.0 7.2 na
335A 15.75 15.27 na
300 25.0 7.32 na
321 25.0 7.33 na
322 25.0 7.69 na
323 25.0 8.24 na
324 15.75 15.13 na
325 15.75 14.93 na
326 15.75 14.93 na
301 25.0 7.69 na
302 25.0 8.24 na
304 13.75 14.7 na
305 13.75 14.24 na
307 13.75 13.81 na
308 11.75 14.81 na
309 11.75 19.26 na
TOR2 11.75 19.28 na
BOR2 1.0 28.51 na
UG1 0.0 29.82 na
UG2 0.0 30.6 na
BKFL 0.0 30.81 na
HOSE 0.0 35.81 na 100.0
TEST 0.0 35.83 na
The maximum velocity is 12.36 and it occurs in the pipe between nodes 341 and 307
Pressure / Flow Summary - STANDARD
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 5
REV #1 Atlantic Beach CC Area #4 Date 9/11/2023
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
S1 16.55 1.101 N 5.0 5.792 8.732 K Factor = 5.60
to 150.0 O 5.0 10.000 -2.166
300 16.55 0.0479 0.0 15.792 0.757 Vel = 5.58
0.0
16.55 7.323 K Factor = 6.12
S2 16.88 1.101 N 5.0 5.583 9.081 K Factor = 5.60
to 150.0 O 5.0 10.000 -2.166
301 16.88 0.0497 0.0 15.583 0.775 Vel = 5.69
0.0
16.88 7.690 K Factor = 6.09
S3 17.34 1.101 N 5.0 5.583 9.589 K Factor = 5.60
to 150.0 O 5.0 10.000 -2.166
302 17.34 0.0523 0.0 15.583 0.815 Vel = 5.84
0.0
17.34 8.238 K Factor = 6.04
S4 21.73 1.101 N 5.0 3.625 15.063 K Factor = 5.60
to 150.0 O 5.0 10.000 -1.444
304 21.73 0.0793 0.0 13.625 1.081 Vel = 7.32
0.0
21.73 14.700 K Factor = 5.67
S5 21.05 1.101 2O 10.0 5.708 14.135 K Factor = 5.60
to 150.0 N 5.0 15.000 -1.444
305 21.05 0.0748 0.0 20.708 1.549 Vel = 7.09
0.0
21.05 14.240 K Factor = 5.58
S6 14.83 1.101 O 5.0 1.000 7.008 K Factor = 5.60
to 150.0 0.0 5.000 -0.433
330 14.83 0.0392 0.0 6.000 0.235 Vel = 5.00
0.0
14.83 6.810 K Factor = 5.68
S7 14.82 1.101 O 5.0 1.000 7.000 K Factor = 5.60
to 150.0 0.0 5.000 -0.433
331 14.82 0.0390 0.0 6.000 0.234 Vel = 4.99
0.0
14.82 6.801 K Factor = 5.68
S8 15.22 1.101 O 5.0 1.000 7.388 K Factor = 5.60
to 150.0 0.0 5.000 -0.433
332 15.22 0.0410 0.0 6.000 0.246 Vel = 5.13
0.0
15.22 7.201 K Factor = 5.67
S9 18.08 1.101 3N 15.0 5.792 10.424 K Factor = 5.60
to 150.0 0.0 15.000 -1.444
340 18.08 0.0565 0.0 20.792 1.174 Vel = 6.09
0.0
18.08 10.154 K Factor = 5.67
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 6
REV #1 Atlantic Beach CC Area #4 Date 9/11/2023
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
S10 18.61 1.101 2N 10.0 6.500 11.048 K Factor = 5.60
to 150.0 O 5.0 15.000 -1.444
341 18.61 0.0596 0.0 21.500 1.282 Vel = 6.27
0.0
18.61 10.886 K Factor = 5.64
S11 16.55 1.101 N 5.0 5.792 8.735 K Factor = 5.60
to 150.0 O 5.0 10.000 -2.166
321 16.55 0.0480 0.0 15.792 0.758 Vel = 5.58
0.0
16.55 7.327 K Factor = 6.11
S12 16.84 1.101 N 5.0 6.417 9.044 K Factor = 5.60
to 150.0 O 5.0 10.000 -2.166
322 16.84 0.0496 0.0 16.417 0.814 Vel = 5.67
0.0
16.84 7.692 K Factor = 6.07
S13 17.31 1.101 N 5.0 6.417 9.553 K Factor = 5.60
to 150.0 O 5.0 10.000 -2.166
323 17.31 0.0521 0.0 16.417 0.856 Vel = 5.83
0.0
17.31 8.243 K Factor = 6.03
S14 21.43 1.101 2N 10.0 6.833 14.649 K Factor = 5.60
to 150.0 O 5.0 15.000 -1.408
325 21.43 0.0774 0.0 21.833 1.689 Vel = 7.22
0.0
21.43 14.930 K Factor = 5.55
S15 21.17 1.101 2N 10.0 12.167 14.285 K Factor = 5.60
to 150.0 O 5.0 15.000 -1.408
325 21.17 0.0756 0.0 27.167 2.053 Vel = 7.13
0.0
21.17 14.930 K Factor = 5.48
S16 21.37 1.101 N 5.0 4.208 14.558 K Factor = 5.60
to 150.0 O 5.0 10.000 -1.408
350 21.37 0.0769 0.0 14.208 1.093 Vel = 7.20
0.0
21.37 14.243 K Factor = 5.66
S17 18.07 1.101 2N 10.0 11.292 10.407 K Factor = 5.60
to 150.0 0.0 10.000 -0.541
345 18.07 0.0564 0.0 21.292 1.200 Vel = 6.09
0.0
18.07 11.066 K Factor = 5.43
S18 18.30 1.101 N 5.0 6.167 10.675 K Factor = 5.60
to 150.0 O 5.0 10.000 -0.541
345 18.3 0.0576 0.0 16.167 0.932 Vel = 6.17
0.0
18.30 11.066 K Factor = 5.50
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 7
REV #1 Atlantic Beach CC Area #4 Date 9/11/2023
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
350 21.37 1.101 O 5.0 4.000 14.243
to 150.0 0.0 5.000 0.0
326 21.37 0.0769 0.0 9.000 0.692 Vel = 7.20
0.0
21.37 14.935 K Factor = 5.53
345 36.36 1.101 O 5.0 9.000 11.066
to 150.0 0.0 5.000 0.866
308 36.36 0.2056 0.0 14.000 2.879 Vel = 12.25
0.0
36.36 14.811 K Factor = 9.45
340 18.08 1.101 0.0 12.958 10.154
to 150.0 0.0 0.0 0.0
341 18.08 0.0565 0.0 12.958 0.732 Vel = 6.09
341 18.61 1.101 O 5.0 9.000 10.886
to 150.0 0.0 5.000 0.0
307 36.69 0.2091 0.0 14.000 2.927 Vel = 12.36
0.0
36.69 13.813 K Factor = 9.87
303 123.80 4.26 T 26.334 7.333 15.118
to 120.0 0.0 26.334 0.0
335 123.8 0.0041 0.0 33.667 0.138 Vel = 2.79
335 -250.92 4.26 0.0 4.250 15.256
to 120.0 0.0 0.0 0.0
333 -127.12 -0.0042 0.0 4.250 -0.018 Vel = 2.86
333 28.37 4.26 T 26.334 12.583 15.238
to 120.0 0.0 26.334 0.0
324 -98.75 -0.0027 0.0 38.917 -0.106 Vel = 2.22
0.0
-98.75 15.132 K Factor = -25.39
320 -16.49 1.101 T 9.563 0.792 7.303
to 150.0 0.0 9.562 0.0
330 -16.49 -0.0476 0.0 10.354 -0.493 Vel = 5.56
330 14.83 1.101 0.0 12.750 6.810
to 150.0 0.0 0.0 0.0
331 -1.66 -0.0007 0.0 12.750 -0.009 Vel = 0.56
331 14.81 1.101 0.0 12.750 6.801
to 150.0 0.0 0.0 0.0
332 13.15 0.0314 0.0 12.750 0.400 Vel = 4.43
332 15.22 1.101 N 5.0 16.458 7.201
to 150.0 T 9.563 14.562 4.006
333 28.37 0.1299 0.0 31.020 4.031 Vel = 9.56
0.0
28.37 15.238 K Factor = 7.27
335 250.92 4.26 0.0 1.000 15.256
to 120.0 0.0 0.0 0.0
335A 250.92 0.0160 0.0 1.000 0.016 Vel = 5.65
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 8
REV #1 Atlantic Beach CC Area #4 Date 9/11/2023
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
335A 0.0 4.26 T 26.334 96.917 15.272
to 120.0 2E 26.334 52.668 1.732
TOR2 250.92 0.0152 0.0 149.585 2.278 Vel = 5.65
0.0
250.92 19.282 K Factor = 57.14
300 -8.16 1.598 0.0 9.750 7.323
to 150.0 0.0 0.0 0.0
320 -8.16 -0.0021 0.0 9.750 -0.020 Vel = 1.31
320 16.49 1.598 0.0 11.000 7.303
to 150.0 0.0 0.0 0.0
321 8.33 0.0022 0.0 11.000 0.024 Vel = 1.33
321 16.55 1.598 N 7.0 14.958 7.327
to 150.0 0.0 7.000 0.0
322 24.88 0.0166 0.0 21.958 0.365 Vel = 3.98
322 16.84 1.598 0.0 12.750 7.692
to 150.0 0.0 0.0 0.0
323 41.72 0.0432 0.0 12.750 0.551 Vel = 6.67
323 17.31 1.598 N 7.0 16.458 8.243
to 150.0 T 11.656 18.656 4.006
324 59.03 0.0821 0.0 35.114 2.883 Vel = 9.44
324 -98.75 1.598 0.0 5.125 15.132
to 150.0 0.0 0.0 0.0
325 -39.72 -0.0394 0.0 5.125 -0.202 Vel = 6.35
325 42.60 1.598 N 7.0 7.792 14.930
to 150.0 0.0 7.000 0.0
326 2.88 0.0003 0.0 14.792 0.005 Vel = 0.46
326 21.37 1.598 3N 21.0 123.000 14.935
to 150.0 O 8.0 40.656 1.732
309 24.25 0.0158 T 11.656 163.656 2.592 Vel = 3.88
0.0
24.25 19.259 K Factor = 5.53
300 24.71 1.598 N 7.0 15.375 7.323
to 150.0 0.0 7.000 0.0
301 24.71 0.0164 0.0 22.375 0.367 Vel = 3.95
301 16.87 1.598 0.0 12.750 7.690
to 150.0 0.0 0.0 0.0
302 41.58 0.0430 0.0 12.750 0.548 Vel = 6.65
302 17.34 1.598 N 7.0 16.458 8.238
to 150.0 T 11.656 18.656 4.006
303 58.92 0.0818 0.0 35.114 2.874 Vel = 9.43
303 -123.80 1.598 N 7.0 6.125 15.118
to 150.0 0.0 7.000 0.866
304 -64.88 -0.0978 0.0 13.125 -1.284 Vel = 10.38
304 21.74 1.598 0.0 10.000 14.700
to 150.0 0.0 0.0 0.0
305 -43.14 -0.0460 0.0 10.000 -0.460 Vel = 6.90
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
bender & modlin FIRE SPRINKLER Page 9
REV #1 Atlantic Beach CC Area #4 Date 9/11/2023
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
305 21.05 1.598 N 7.0 25.083 14.240
to 150.0 0.0 7.000 0.0
307 -22.09 -0.0133 0.0 32.083 -0.427 Vel = 3.53
307 36.69 1.598 2N 14.0 7.292 13.813
to 150.0 0.0 14.000 0.866
308 14.6 0.0062 0.0 21.292 0.132 Vel = 2.34
308 36.37 1.598 T 11.656 59.417 14.811
to 150.0 0.0 11.656 0.0
309 50.97 0.0626 0.0 71.073 4.448 Vel = 8.15
309 24.24 4.26 E 19.896 1.250 19.259
to 150.0 0.0 19.897 0.0
TOR2 75.21 0.0011 0.0 21.147 0.023 Vel = 1.69
TOR2 250.93 4.26 E 13.167 12.333 19.282
to 120.0 A 22.384 51.351 7.656 * * Fixed Loss = 3
BOR2 326.14 0.0247 B 15.8 63.684 1.574 Vel = 7.34
Fsp 0.0
BOR2 0.0 4.23 T 38.446 13.000 28.512
to 150.0 0.0 38.446 0.433
UG1 326.14 0.0169 0.0 51.446 0.872 Vel = 7.45
UG1 0.0 6.09 2F 21.583 250.000 29.817
to 150.0 0.0 21.583 0.0
UG2 326.14 0.0029 0.0 271.583 0.780 Vel = 3.59
UG2 0.0 6.09 0.0 73.000 30.597
to 150.0 0.0 0.0 0.0
BKFL 326.14 0.0029 0.0 73.000 0.209 Vel = 3.59
BKFL 0.0 6.09 0.0 3.000 30.806
to 150.0 0.0 0.0 5.000 * * Fixed Loss = 5
HOSE 326.14 0.0030 0.0 3.000 0.009 Vel = 3.59
HOSE 100.00 6.09 0.0 3.000 35.815 Qa = 100
to 150.0 0.0 0.0 0.0
TEST 426.14 0.0047 0.0 3.000 0.014 Vel = 4.69
0.0
426.14 35.829 K Factor = 71.19
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
STORAGE
009
LAUNDRY
137
MEN'S POOL
RESTROOM
142
WOMEN'S
POOL
RESTROOM
145
VESTIBULE
141
VESTIBULE
144
ACCESSIBLE
RESTROOM
142D
BREEZEWAY
010A
ACCESSIBLE
RESTROOM
145E
MEN'S
FITNESS
RESTROOM
152
EXERCISE
ROOM
154
YOUTH
155
MECH /
ELEC
149
ACCESSIBLE
RESTROOM
153B
RECEPTION
150
UNISEX
RESTROOM
157
CORRIDOR
148
CHECK-IN
156A
MANUAL
THERAPY
146
GROUP
FITNESS
151
9' - 0"9' - 0"
9' - 0"
9' - 0"10' - 5"
10' - 5"
9' - 0"
12' - 6"
CHECK-IN
156
WOMEN'S
FITNESS
RESTROOM
153
WC
153A
WC
152A
EXISTING 4" WET FIRE
SPRINKLER RISER
REMOVING AND
RELOCATING.
UNDERGROUND WORK
BY OTHERS.
X X X
XXX
X X X
X
X
X
X
X
X
R R
RR
R R
R
R
R
R
R
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
R
NEW CAP ON END OF 1-1/2"
LINE. RECONNECTING AT
NEW RISER LOCATION.
X X
NEW 4" WET FIRE
SPRINKLER RISER.
4" UNDERGROUND WORK
BY OTHERS.
RISER USING HEAT
TRACING IF UNPROTECTED
AREA. (WIRING BY OTHERS)
R
R
R
A R
A R
X
X
DRY HEADS (TYP)
A
TOR2
BOR2
333 303
309
S1
300
S2
301
S3
302
S4
304
S5
305
S9
340
S10
341
S14
325S15
S6
330
S7
331
S8
332
S11
321
S12
322
S13
323
324
345
307308
326
S16
350
335
S17
S18
320
335A
1. THIS CONTRACT IS TO RELOCATE EXISTING
HEADS TO ACCOMMODATE NEW CEILING
LAYOUT FOR TENANT BUILD-OUT.
2. WET SYSTEM RISER RELOCATING TO NEW
AREA. NEW LOCATION REQUIRED MORE
PRESSURE WITH CURRENT WATER
CONDITIONS. NEW 4" MAIN TYING INTO
EXISTING MAINS FOR HYDRAULIC PURPOSES.
3. ALL WORK TO BE PERFORMED AS PER
NFPA 13.
4. HANGERS TO BE PLACED EVERY 4TH
TRUSS OR +/- EVERY 8' FOR NEW 4" MAIN.
DRAWING NOTES
FLOW TEST DATA
FIRE PROTECTION CABANA/FITNESS 1ST FL
SLOPE
5 : 12
SLOPE
5 : 12
RIDGEVALL
E
Y
V
A
L
L
E
Y
SLOPE
5 : 12
SLOPE
5 : 12 RIDGEV
A
L
L
E
Y
VALL
E
Y RIDGESLOPE12 : 12SLOPE12 : 12SLOPE12 : 12SLOPE12 : 12SLOPE
7 : 12
GABLE ENDSLOPE
7 : 12
SLOPE
7 : 12
RIDGEGABLE END
GABLE
E
N
D
SLOPE12 : 12RIDGEGABLE ENDSLOPE7 : 12SLOPE
7 : 12
SLOPE
7 : 12
SLOPE7 : 12SLOPE7 : 12SHED DORMER
VALLEY
SHED DORMER
VALLEY
SHED DORMER
VALLEY
SHED DORMER
VALLEY
VALLEY VALLEY VALLEY VALLEY
CAPPED OFF AND
RECONNECTED AT
NEW RISER LOCATION
FIRE PROTECTION CABANA/FITNESS ATTIC
NEW RISER LOCATION
FEED FROM SYSTEM
BELOW.
ALL OTHER PIPING AND HEADS
EXISTING TO REMAIN.
200
201
202
204
205
206
207
208
213
209
210
211212
203
207A
DENOTES NEW PIPE
DENOTES EXISTING PIPE TO REMAIN
DENOTES RELOCATED/ADDED FIRE
SPRINKLER HEAD
DENOTES FIRE SPRINKLER HEAD TO
BE RELOCATED
DENOTES EXISTING PIPE TO
DENOTES FIRE SPRINKLER HEAD TO
BE REMOVED
DENOTES EXISTING FIRE SPRINKLER
HEAD TO REMAIN
27
DENOTES NEW CONNECTION
DENOTES HYDRAULIC NODE POINT
DENOTES PLUG
DENOTES CAP
DENOTES FIRE RISER LOCATION
SYMBOLS LEGEND
BE REMOVED
A
X
R R
X
MAXIMUM DISTANCE BETWEEN HANGERS
BM 24x36HFIRE SPRINKLER, INC.