Loading...
1864 BEACHSIDE CT MCRS24-0002 Seth Dalton PLAN_1GENERAL NOTES AERIAL VIEW SHEET INDEX PV1 Cover Page PV2 Site Plan PV3 Mounting Detail PV4 Electrical Diagram PV5 Electrical Calcs PV6 Labels PV7 Placard Cutsheets APPLICABLE CODES:DESCRIPTION OF DESIGN: INSTALLATION OF GRID TIED, UTILITY INTERACTIVE PHOTOVOLTAIC SYSTEM. EQUIPMENT:DC SYSTEM SIZE:KW BIPV Shingle (PV Module): AC SYSTEM SIZE:KW Inverter: Inverter: ADDRESS:CONTRACTOR:EQUIPMENT:DATE REV 0 KW (DC)KW (AC)Delta M6-TL-US PV1 GAF Energy TLS-1 Delta M4-TL-US COVER PAGE (1)BY:ABrycelea (1)Delta M4-TL-US GAF Energy TLS-1 Delta M6-TL-US 8.004 10 (174) (1) 12/18/2023 Seth Dalton GAF Energy LLC (FL)8.004 10 Exposure Category: B Risk Category II Wind Speed: 129MPH (174) (1) (1) 1. INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE 690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING. 2. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110. 3. ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 4. THE BIPV SHINGLES (PV MODULES) ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES. 5. ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.8] 6. DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.31] 7. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE. atlantic beach FL 32233 1864 beachside court 973-628-3411 125 Mitchell Blvd, Suite D EC13011344 San Rafael CA 94903 2017 NATIONAL ELECTRICAL CODE (NEC) 2023 FLORIDA BUILDING CODE 7TH EDITION (FBC) 2023 FLORIDA FIRE PREVENTION CODE (FFPC) 2023 FLORIDA RESIDENTIAL CODE (FRC) Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Azimuth:°Pitch:/12 Energy Shingle Part Number:GAF Energy TLS-1 ADDRESS:CONTRACTOR:EQUIPMENT:DATE REV 0 KW (DC)KW (AC)Delta M6-TL-US PV2 GAF Energy TLS-1 Delta M4-TL-US SITE PLAN (1)BY:ABrycelea 270 6180 90 90 180 6 EC13011344 San Rafael CA 94903atlantic beach FL 32233 12/18/2023 Seth Dalton GAF Energy LLC (FL)8.004 973-628-3411 125 Mitchell Blvd, Suite D1864 beachside court (174) 10 (1) (1) 6 6 6 UTILITY METERM INV MSP AC LC J-BOX BAT PV MAIN SERVICE PANEL LOAD CENTER AC DISCONNECT METER SOCKET (FOR UTILITY PV METER) INVERTER JUNCTION BOX BATTERY(IES) FIRE ACCESS PATHWAY (3' TYP.) EQUIPMENT LEGEND MP#1 ↑ NORTH Pass FRONT OF HOME DRIVEWAY MP#1 MP#3 MP#2 MP#4 MP#5 TOTAL ROOF AREA: 3259 sq ft AREA OF PV MODULES: 548 sq ft %OF ROOF COVERED: 17% RIDGE SETBACKS 18" MINIMUM MP#2 MP#4 MP#6 MP#7 MP#8 MP#9 MP#10 MP#11 MP#12 MP#3 MP#5 MP#13 MP#14 MSP MINVACINVLC ADDRESS:CONTRACTOR:EQUIPMENT:DATE REV 0 KW (DC)KW (AC)Delta M6-TL-US PV3 GAF Energy TLS-1 Delta M4-TL-US MOUNTING DETAIL (1)BY:ABryceleaatlantic beach FL 32233 EC13011344 San Rafael CA 94903 1864 beachside court (174) 12/18/2023 Seth Dalton GAF Energy LLC (FL)8.004 973-628-3411 125 Mitchell Blvd, Suite D 10 (1) (1) INSTALLATION NOTES MINIMUM SHEATHING THICKNESS: 7/16" OSB or 15/32" PLYWOOD. FULL TEAR OFF REQUIRED PRIOR TO INSTALLATION TO VERIFY DECKING THICKNESS, CONDITION, AND CODE- COMPLIANT ATTACHMENT TO STRUCTURE. PLEASE SEE ATTACHED STAMPED STRUCTURAL ENGINEERING LETTER FOR ADDITIONAL EXPLANATION REGARDING PE REVIEW/ REQUIREMENTS FOR THE TIMBERLINE SOLAR PRODUCT. BIPV SHINGLES (PV MODULES) TOP VIEW (NOT TO SCALE) BIPV SHINGLES (PV MODULES)SIDE VIEW (NOT TO SCALE) Wire Schedule BIPV Shingle (PV Module) REF QTY Wire Size / Type QTY Wire Size / Type Conduit Notes QTY Make/Model Max output Power 1 (2)AWG PV WIRE, USE-2 COPPER N/A (OR CODE APPROVED EQUIVALENT)GAF Energy TLS-1 46W 2 (2)AWG THWN-2 (POS, NEG)(1)AWG THWN-2 (GND)EMT (OR CODE APPROVED EQUIVALENT)Rapid Shutdown Device 3A (3)AWG THWN-2 (L1,L2,N)(1)AWG THWN-2 (GND)EMT (OR CODE APPROVED EQUIVALENT)QTY Make/Model Max Output 3B (3)AWG THWN-2 (L1,L2,N)(1)AWG THWN-2 (EGC)EMT (OR CODE APPROVED EQUIVALENT)Delta GPI00010105 20A 3C Inverter(s) 4 (3)AWG THWN-2 (L1,L2,N)(1)AWG THWN-2 (EGC)EMT (OR CODE APPROVED EQUIVALENT)REF Make/Model AC Voltage Ground Rated Power Max Output Current 5 (3)AWG THWN-2 (L1,L2,N)(1)AWG THWN-2 (EGC)EMT (OR CODE APPROVED EQUIVALENT)INV1 Delta M6-TL-US 240V No 6 INV2 Delta M4-TL-US 240V No 7 INV3 8 Energy Shingle Part Number:GAF Energy TLS-1 ADDRESS:CONTRACTOR:EQUIPMENT:DATE REV 0 KW (DC)KW (AC)Delta M6-TL-US GAF Energy TLS-1 Delta M4-TL-US ELECTRICAL DIAGRAM (1)BY:ABrycelea 3/4in#10#6 32233 EC13011344 San Rafael CA (174) 6000W 4000W 24.0A 16.0A 10 (1) (1) atlantic beach FL 3/4in 3/4in 3/4in 3/4in#8 #10 #10 #10 #10 #10 #10 #10 PV4 #10 12/18/2023 (174) 94903 Seth Dalton GAF Energy LLC (FL) (6) 8.004 1864 beachside court 973-628-3411 125 Mitchell Blvd, Suite D FUSED AC DISCONNECT FUSED, AIC 10kA VISIBLE, LOCKABLE, LABELED, OPEN 240V, 2 -POLE 50 A 60 A 5 COMBINER LOAD CENTER (N)125 A BUSBAR 30 A/2P 20 A/2P (N) (N) 4 30 A/2P 20 A/2P (N) (N) 4 GROUNDING & GENERAL NOTES (CONT'D) 5.TRANSITION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD - TRANSITION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS. 6.AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT. 7.CONDUIT CARRYING THE DC WIRES ARE BONDED AT THE INVERTER. 8. INVERTERS ARE UL 1741 COMPLIANT. INTERCONNECTION NOTES 1. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9] & [NEC 230.95] 2. SUPPLY SIDE INTERCONNECTION ACCORDING TO[NEC 2014, 2017 -705.12(A), NEC 2020, 2023 -705.11] WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH [NEC 240.21(B)] DISCONNECT NOTES 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH GROUNDING & GENERAL NOTES TIMBERLINE SOLAR USES BIPV SHINGLES (PV MODULES) THAT ATTACH DIRECTLY TO THE ROOF DECKING LIKE ORDINARY ASPHALT SHINGLES.THE BIPV SHINGLES HAVE NO METAL FRAME AND ARE NOT RACK MOUNTED.THE SYSTEM HAS NO EXPOSED, CONDUCTIVE METAL AND REQUIRES NO EQUIPMENT GROUND CONDUCTOR (EGC) FOR THE BIPV SHINGLES, WIRE COVERS OR TRANSITION BOX.THE EGC PATH BEGINS AT THE CONNECTION OF THE CONDUIT (EMT OR FMC, TYPICALLY) AT THE TRANSITION BOX OR PASS THROUGH DEVICE AND TERMINATES AT THE MAIN SERVICE PANEL. TIMBERLINE SOLAR AS A SYSTEM HAS BEEN LISTED TO MEET THE RAPID SHUTDOWN REQUIREMENTS OF ARTICLE 690.12 IN THE 2020, 2017 AND 2014 NEC (ANSI/NFPA 70).ANY LOSS OF CONNECTION TO THE UTILITY GRID WILL TRIGGER RAPID SHUTDOWN OF THE DELTA MCI AND/OR DELTA RSS PV RAPID SHUTDOWN EQUIPMENT (PVRSE) LISTED TO ANSI UL 1741 AND AS A PV HAZARD CONTROL SYSTEM (PVHCS) LISTED TO ANSI/CAN/UL 3741. 1.A SECOND FACILITY GROUNDING ELECTRODE IS NOT REQUIRED PER [NEC 690.47(C)(3)] 2.PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE. 3.DC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTING ELECTRODE 4.ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. string(s)of string(s)of 3B INV2148 1 42 MAIN SERVICE PANEL (E)200 A BUSBAR (E)200 A MAIN BREAKER 200 A/2P(E) NEC 705.11 string(s)of1 20 string(s)of1 40 string(s)of1 24 3A string(s)of1 20 string(s)of1 40 string(s)of1 24 INV1 Max. Ambient Temperature (degF):PV Module Power (W): DC System Summary INVERTER INV 1 INV 2 INV 3 MPPT 1 2 3 4 1 2 3 4 1 2 3 4 QTY OF MODULES IN SERIES STRING VMP (V) STRING VOC (V) STRING IMP (A) STRING ISC (A) COMBINED STRING IMP (A) COMBINED STRING ISC (A) STRING REFERENCE LETTER ADDRESS:CONTRACTOR:EQUIPMENT:DATE REV 0 KW (DC)KW (AC)Delta M6-TL-US PV5 GAF Energy TLS-1 Delta M4-TL-US ELECTRICAL CALCS (1)BY:ABryceleaEC1301134494903 1864 beachside court 973-628-3411 125 Mitchell Blvd, Suite D atlantic beach FL 32233 San Rafael CA (174)(1) 12/18/2023 Seth Dalton GAF Energy LLC (FL)8.004 10 (1) 4691.4 5.16 5.16 153.42 306.84 184.10 368.21 322.18 20 40 24 48 42 5.16 5.16 5.16 557.21 487.56232.17 464.34 278.60 5.40 5.405.40 5.40 5.40 A1 B1 C1 E1 F1 ADDRESS:CONTRACTOR:EQUIPMENT:DATE REV 0 KW (DC)KW (AC)Delta M6-TL-US PV6 GAF Energy TLS-1 Delta M4-TL-US LABELS (1)BY:ABryceleaEC13011344San Rafael CA 94903atlantic beach FL 32233 12/18/2023 Seth Dalton GAF Energy LLC (FL)8.004 (174)125 Mitchell Blvd, Suite D1864 beachside court 973-628-3411 10 (1) (1) LABEL 1 AT EACH JUNCTION BOX, COMBINER BOX, DISCONNECT, AND DEVICE WHERE ENERGIZED UNGROUNDED CONDUCTORS MAY BE EXPOSED DURING SERVICE. NEC. 690.35(F) LABEL 2 FOR PV DISCONNECTING MEANS WHERE ALL TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION.NEC 690.17(E), NEC 705.22 LABEL 3 AT POINT OF INTERCONNECTION, MARKED AT AC DISCONNECTING MEANS.NEC 690.54, NEC 690.13 (B) LABEL 4 AT POINT OF INTERCONNECTION FOR EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUTS SUPPLYING POWER TO A BUSBAR OR CONDUCTOR SUPPLIED FROM MULTIPLE SOURCES, EACHSERVICE EQUIPMENT AND ALL ELECTRIC POWER PRODUCTION SOURCE LOCATIONS.NEC 705.12(D)(3 LABEL 6 PLACED ADJACENT TO THE BACK-FED BREAKER FROM THE INVERTER IF TIE IN CONSISTS OF LOAD SIDE CONNECTION TO BUSBAR.NEC 705.12(D)(2)(3)(B) LABEL 7 SIGN LOCATED AT UTILITY SERVICE EQUIPMENT.NEC 690.56(C) LABEL 8 SIGN LOCATED AT PV COMBINER PANEL. NEC 705.12(B)(2)(3)(C) 240 40 LABELING NOTES: 1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. 2. LABELING REQUIREMENTS BASED ON THE (NFPA 70) 2017 National Electric Code 3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.21] 5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY AFFIXED [IFC 605.11.1.1] LABEL 5 AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS.NEC 690.31(G)(3&4) LABEL 9 -INVERTER AT PV DISCONNECTING MEANS. TO BE USED IF NEC 2014 APPLIES. NEC 690.53 LABEL 10 -INVERTER 1 AT PV DISCONNECTING MEANS. TO BE USED IF NEC 2017 APPLIES. NEC 690.53 557.2 5.40 380 5.16 557. 5.40 LABEL 12 SIGN LOCATED AT INVERTER RAPID SHUTDOWN SWITCH. NEC 690.56(C)(2) LABEL 11 FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND CONDUCTORS LEAVING THE ARRAY NEC 690.56(C)(1). CEC 690.56(C)(1)(A) RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM INVERTER ADDRESS:CONTRACTOR:EQUIPMENT:DATE REV 0 KW (DC)KW (AC)Delta M6-TL-US GAF Energy TLS-1 Delta M4-TL-US PLACARD (1)BY:ABryceleaatlantic beach FL 32233 12/18/2023 Seth Dalton GAF Energy LLC (FL)8.004 1864 beachside court San Rafael CA 94903 PV710(1) EC13011344 CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS SHOWN: 1864 beachside court, atlantic beach FL 32233 (174)973-628-3411 125 Mitchell Blvd, Suite D (1) FRONT OF HOME DRIVEWAY MP#1 MP#3 MP#2 MP#4 MP#5 TOTAL ROOF AREA: 3259 sq ft AREA OF PV MODULES: 548 sq ft %OF ROOF COVERED: 17% RIDGE SETBACKS 18" MINIMUM MP#2 MP#4 MP#6 MP#7 MP#8 MP#9 MP#10 MP#11 MP#12 MP#3 MP#5 MP#13 MP#14 MSP MINVACINVLC MAIN DISTRIBUTION UTILITY DISCONNECT AC DISCONNECT PV ARRAY (2x) INVERTERS & RAPID SHUTDOWN DC DISCONNECT SWITCH Solar Inverter for North AmericaSingle Phase Solar Inverter for North AmericaM4-TL-US | M5-TL-US | M6-TL-US | M8-TL-US | M10-TL-US | M10-4-TL-USKey Features: xSmart inverter with BLE, optional WiFi, Ethernet, 3G / 4G cellular communicationxOptional revenue grade meter(compliant with ANSI C12.20, Class 0.5)xSupport bi-directional cloud communication xSupport remote diagnosis and OTAxType 4 protection xBuilt-in AFCI & Rapid shutdown controllerxCEC efficiency 97.5%xUL 1741 SB, HECO compliantxCA Rule 21 Phase 1 & 2 & 3 compliantSolar Inverter for North AmericaRev 16.1 - 2/2022 © Copyright 2020 Delta Electronics (Americas), Ltd. All rights reserved. Specifications subject to change without prior notice. ModelM4-TL-US M5-TL-US M6-TL-US M8-TL-US M10-TL-US M10-4-TL-USINPUT (DC)Max. system voltage600 VNominal voltage380 VMax. operating voltage540 VOperating MPPT voltage range50 V to 480 VMax. input current per MPPT12 A 12 A 12 A 12 A 20 A 12 AMax. short circuit current per MPPT15 A 15 A 15 A 15 A 30 A 15 AMax. DC/AC ratio1)1.35DC disconnectIntegratedMPP tracker 223324Input strings available2 - 2 2 - 2 2 - 2 - 2 2 - 2 - 2 2 - 22 -2 -2 -2OUTPUT (AC)Nominal output power @ 240Vac3840 W 4800 W 5760 W 7680 W 9600 W 9600 WMax. output power@ 240Vac4000 W 5000 W 6000 W 8000 W 10000 W 10000 WNominal output power @ 208Vac3328 W 4160 W 4992 W 6656 W 8320 W 8320 WMax. output power@ 208Vac3648 W 4560 W 5472 W 7296 W 9120 W 9120 WAC operating voltage range183 Vac to 228Vac @ 208 Vac211 Vac to 264 Vac @ 240 VacMax. continuous current16 A20 A24 A32 A40 A40 ANominal operating frequency60 HzOperating frequency range59.3 Hz to 60.5 HzAdjustable frequency range50 Hz to 66 HzNight consumption< 1.5 W 2)THD @ nominal power< 3 %Power factor @ nominal power> 0.99Adjustable power factor range 0.85i to 0.85cGENERAL SPECIFICATIONMax. efficiency98%CEC efficiency97.0 % @ 208 V 97.5 % @ 240 V97.5 % @ 208 V 97.5 % @ 240 V97.0 % @ 208 V 97.5 % @ 240 V97.5 % @ 208 V 97.5 % @ 240 V97.5 % @ 208 V 97.5 % @ 240 V97.0 % @ 208 V 97.5 % @ 240 VOperating temperature range-22 °F to 149 °F (-30 °C to 65 °C)with derating above 113 °F (45 °C)Storage temperature range-40 °F to 185 °F (-40 °C to 85 °C)Humidity0% to 95%Max. operating altitude9,843 ft (3,000 m)Acoustic noise< 45 dB(A) @ 3 ft (1m) Solar Inverter for North AmericaRev 16.1 - 2/2022 © Copyright 2020 Delta Electronics (Americas), Ltd. All rights reserved. Specifications subject to change without prior notice. ModelM4-TL-US M5-TL-US M6-TL-US M8-TL-US M10-TL-US M10-4-TL-USMECHANICAL DESIGNDimensions (W x H x D)16.7 x 23.2 x 5.9 in (425 x 590 x 150 mm)DisplayLED indicatorsWeight3)41.9 lbs (19.0 kg) 41.9 lbs (19.0 kg) 44.3 lbs (20.1 kg) 45.2 lbs (20.5 kg) 47.6 lbs (21.6 kg) 47.6 lbs (21.6 kg)CoolingNatural convectionNatural convection with internal fanDC connectionSpring contact typeAC connectionSpring contact typeCommunication interfaceBLE, optional WiFi, Ethernet, 3G / 4G cellular communicationRemote diagnose/monitoringBi-direction via cloudRemote firmware updateVia cloud (optional)Enclosure materialDie-casting aluminumSTANDARDSEnclosure protection ratingType 4SafetyUL 1741, CSA-C22.2 No. 107.1-16Software approvalUL 1998Ground fault protectionUL 1741 CRDAnti-islanding protectionIEEE 1547-2018, IEEE 1547.1-2020EMCFCC part 15 Class BAFCIUL 1699B (Type 1), NEC 2020 Article 690.11Rapid shutdown protectionNEC 2020 690.12 4)Rapid shutdown transmitterOptional pre-installed5)Integrated meterANSI C12.20, Class 0.5Grid support regulationUL 1741 SB, California Rule 21 phase 1 & 2 & 3, HECO CompliantWARRANTYStandard warranty10 years1) Please refer to technical note for detailed string configuration 2) Without consumption of communication card3) Without weight of revenue grade meter4) Compliant with APS rapid shutdown system or Tigo rapid shutdown system. Compliant with Delta MCI or Delta Smart RSS as part of listed or field labeled PV Hazard Control System/PV Rapid Shutdown Array.5) Optional pre-installed with APS rapid shutdown transmitter or Tigo rapid shutdown transmitterDelta Electronics (Americas), Ltd.46101 Fremont Blvd, Fremont, CA 94538Sales Email: Inverter.Sales@deltaww.comSupport Email: Inverter.Support@deltaww.comSales Hotline: +1-877-440-5851 or +1-626-369-8021Support Hotline: +1-877-442-4832Support (Intl.): +1-626-369-8019Monday to Friday from 6am to 6pm PST (apart from Holidays)www.Delta-Americas.comResidential Energy Storage Solution for North AmericaRev 11 – 04/2022 © Copyright 2018 Delta Electronics (Americas), Ltd. All rights reserved. Specifications subject to change without prior notice.Accessory: Rapid Shutdown System (RSS)Features:zWith PLC, no additional wire needed for controlzComply with NEC 2020, Article 690.12*zString level rapid shutdownzType 4 protectionzSupport rack mount or solar module mountzSupport series connection up to 2 sub stringszWith high voltage DC relay, high reliabilityRATINGSModel NameSmart RSSDelta part numberGPI00010105Maximum system voltage 600 VdcMaximum current on controlled conductor25 A dc @70ºC, 18.7 A dc @80ºCRated input operating voltage50 Vdc to 550 VdcRated input operating current20 A @ 70 °C15 A @ 80 °CFuse RatingNASelf-power consumption <4 WGENERAL DATADimensions (W x H x D)6.0 x 7.9 x 2.1 in (152 x 201 x 53 mm)Weight3.77 lbs (1.708 kg)CoolingNatural convectionDC input/output connectorsMC4 and H4Enclosure materialDie cast aluminumOperating temperature-40 °F to 176 °F (-40 °C to 80 °C)Humidity0% to 95%Maximum operating altitude9,843 ft (3,000 m) above sea levelSTANDARD COMPLIANCEEnclosure protection ratingType 4SafetyUL 1741, CSA C22.2 No. 330-17Rapid shutdownNEC 2020 Article 690.12*EMCFCC Part 15 Class B*Installed with a listed or field labeled PV hazard control system CertificationsTrusted GAF products combined with advanced GAF Energy solar shingle technologyElectrical Characteristics1Pmax (±5%) 46 WVoc (±5%) 10.9 VIsc (±5%) 5.40 AVmp (±5%) 9.03 VImp (±5%) 5.16 AMax. System Voltage 600 V Max. Series Fuse 15 AProtection Class Class IIPositive + Negative Load Rating 1600 PaMax. Modules in Series 48Max. Parallel Strings 2Cell Type Monocrystalline PERCConnector Type Staubli EVO2: PV-KST4-EVO2/6II-URConnector Compatibility All Staubli MC4: PV-KBT4/2 – PV-KBT4/10Temp. Coeff. Isc+0.04%/°CTemp. Coeff. Voc-0.26%/°CTemp. Coeff. Pmax-0.35%/°CFor more information, visit gaf.energy/tls-info©2023 GAF ENERGY • SM210-0623Timberline Solar™ is a comprehensive building-integrated photovoltaic roofing system that incorporates energy shingles and roofing shingles to generate solar energy from either new or replacement roofs. It complies with all applicable building codes and is listed by Intertek to all required safety standards.Mechanical CharacteristicsEnergy Shingle Dimensions 64 1/4" x 17 1/8" x 1" (1,632 x 435 x 26 mm)Active Exposure 60" x 7.56" (1,524 x 192 mm)Energy Shingle Weight 10.1 lb. (4.58 kg)Energy Shingle Coverage Approximately 32 energy shingles per square (1.46 kW per square)Installed System Weight 3.36 lb./sq. ft.Allowed Roof Pitch 2:12 or greaterSheathing Minimums7/16" OSB or 15/32" plywoodMax. Installation Altitude 13,123 ft. (4,000 m)Avg. Ambient Temp. Range - 40°F to 104°F (- 40°C to 40°C)Q Fire Certification2UL 790 Class AQ Wind ClassificationASTM D3161 Class FQ Rapid ShutdownArticle 690.12 NEC UL 3741Q Module Certifications3UL 61730-1, -2 SECT 30UL 1703Q BIPV System CertificationUL 7103Q Impact ResistanceUL 2218 Class 11 All electrical data shown under Standard Test Conditions (STC) (1000 W/m2, 25°C ±2°, 1.5 AM). 2 See installation manual for requirements to achieve a System Fire Class Rating with this product.3 UL 61730-1 & UL 61730-2 superseded UL 1703 effective 12/4/19CREATINGAMERICAN JOBSASSEMBLED INAMERICAApplies to Timberline Solar ES™ and Timberline Solar HDZ™Approved for installation in Los Angeles County. See Research Bulletin 13 (RB13). Meets requirements of LAC 2023 Codes: Building, Residential, Electrical & Green Building Standards and 2022 Building Energy Efficiency Standards.Approved for installation in High Velocity Hurricane Zones (HVHZ) per Florida Product Approval FL41599.Meets requirements of theTexas Department of Insurance (TDI).&&5564 1/4 in (1,632 mm)1 in (26 mm)7.56 in (192 mm)17 1/8 in (435 mm)64 1/4 in (1,632 mm)60 in (1,524 mm)60 in (1,524 mm)Model TLS-17/6ETL Listed PV Hazard Control System 8/Florida Product Approval FL41599