1025 EAST COAST DR RES24-0032 ProductApproval_Foam Ins level R-value 450-106 State Rd 13 N Suite 132 Jacksonville Fl. 32259 Ph. (904) 807-3540 www.jaxbuildingscience.com Monday, June 01, 2020 Re: Providence Homes Foam Attic Insulation Levels Providence Homes Inc. 4901 Belfort Rd. Ste 140 Jacksonville Fl 32256 To Whom it May concern: We have been asked to address the insulation level used for the roof deck insulation in the load calcs we provide to Providence Homes. We have used R-21 insulation in these load calcs due to the fact that the foam is sprayed to a level of 6 inches over the roof deck and roof joists. We are comfortable using this level since we inspect the insulation in every Providence home and ensure that the foam has been applied to an average depth of 6 inches or better. If it does not meet this level we require that the Builder have insulation contractor spray over to bring it up to 6 inches or better. In some cases it has been measured to be as deep as 10 inches. 450-106 State Rd 13 N Suite 132 Jacksonville Fl. 32259 Ph. (904) 807-3540 www.jaxbuildingscience.com The data sheet submitted with the foam states that 5 inches has R value R-19. That is equivalent to R3.8 per inch. It follows that 6 inches has R-value of R22.8 so in fact we are understating the insulation level by using R-21 in the calcs. Sincerely, Michael S. O’Donoughue Jacksonville Building Science