469 ATLANTIC BLVD COMM24-0001 Hood System REV 4-3-24Jacksonville Office
REGION 65
PHONE: (904) 463 - 6242
EMAIL: reg65@econair.com
FOR QUESTIONS, CALL THE
HOOD INFORMATION - JOB#6210635
1
5424
EX-2-PSP-F
ECON-AIR 11' 0"
600
DEG
I HEAVY 235 2585 4"16"2585 1851 -0.634"2068
430 SS
WHERE EXPOSED
ALONE ALONE
HOOD
NO
TAG MODEL MANUFACTURER LENGTH
MAX
COOKING
TEMP
TYPE
APPLIANCE
DUTY
DESIGN
CFM/FT
TOTAL
EXH CFM
EXHAUST PLENUM
RISER(S)
WIDTH LENG HEIGHT DIA CFM VEL SP
TOTAL
SUPPLY
CFM
HOOD
CONSTRUCTION
HOOD CONFIG
END TO
END
ROW
HOOD INFORMATION
1
SS BAFFLE WITH
HANDLES
8 16"16"30%4 L55 SERIES E26 NO LEFT 12"x54"x24"TANK FS 4.0/4.0 SC-311110MA
1 LIGHT
1 FAN
YES
947
LBS
HOOD
NO
TAG
FILTER(S)
TYPE QTY HEIGHT LENGTH
EFFICIENCY @ 7
MICRONS
LIGHT(S)
QTY TYPE
WIRE
GUARD
UTILITY CABINET(S)
LOCATION SIZE
FIRE SYSTEM
TYPE SIZE
ELECTRICAL
MODEL #
SWITCHES
QUANTITY
FIRE
SYSTEM
PIPING
HOOD
HANGING
WEIGHT
HOOD OPTIONS
1
FIELD WRAPPER 18.00" HIGH FRONT, LEFT, RIGHT.
BACKSPLASH 80.00" HIGH X 144.00" LONG 430 SS VERTICAL.
RIGHT QUARTER END PANEL 23" TOP WIDTH, 0" BOTTOM WIDTH, 23" HIGH 430 SS.
LEFT QUARTER END PANEL 23" TOP WIDTH, 0" BOTTOM WIDTH, 23" HIGH 430 SS.
HOOD
NO
TAG OPTION
PERFORATED SUPPLY PLENUM(S)
1 Front 144"16"
MUA
MUA
MUA
12"
12"
12"
28"
28"
28"
689
689
689
0.180"
0.180"
0.180"
HOOD
NO
TAG POS LENGTH WIDTH HEIGHT TYPE
RISER(S)
WIDTH LENG DIA CFM SP
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
1
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
GREASE DUCT & CHIMNEY SPECIFICATIONS:
PROVIDE GREASE DUCT EQUAL TO ECON-AIR MODEL "EDW"
ROUND 20 GAUGE 430 STAINLESS STEEL DUCTWORK. MODEL "EDW"
IS LISTED TO UL-1978 AND IS INSTALLED USING "V" CLAMP LOCKING
CONNECTIONS SEALED WITH 3M FIRE BARRIER 2000 PLUS. MODEL "EDW"
DOES NOT REQUIRE WELDING PROVIDING IT HAS BEEN INSTALLED PER
THE MANUFACTURES INSTALLATION GUIDE.
PROVIDE RATED ACCESS DOORS AT EVERY CHANGE IN DIRECTION AND EVERY 12' ON CENTER.
PER MANUFACTURES LISTING MODEL "EDW" HORIZONTAL RUNS LESS THAN 75 FT. CAN BE
SLOPED 1/16" PER 12", HORIZONTAL RUNS MORE THAN 75 FT. CAN BE SLOPED 3/16" PER 12".
DUCT SHOULD BE SLOPED AS MUCH AS POSSIBLE TO REDUCE THE CHANCE OF GREASE
ACCUMULATION IN HORIZONTAL RUNS.
IF THE DUCT OR CHIMNEY IS WITHIN 18 INCHES OF COMBUSTIBLE MATERIAL, PROVIDE
UL-2221 OR UL-103 HT LISTED DOUBLE WALL GREASE DUCT OR DOUBLE WALL CHIMNEY
EQUAL TO ECON-AIR MODEL "EDW- 2R, 2R TYPE HT, 3R, OR 3Z" ROUND 20 GAUGE 430
STAINLESS INNER DUCT INSULATED WITH A 24 GAUGE 430 STAINLESS OUTER SHELL.
§
ECON-AIR RECOMMENDS THE USE OF LISTED,
PRE-FABRICATED ROUND GREASE EXHAUST DUCT
TO REDUCE STATIC PRESSURE IN THE SYSTEM,
MINIMIZE INSTALLATION AND INSPECTION TIMES,
AND ENSURE DUCT IS LIQUID TIGHT
CUSTOMER APPROVAL TO MANUFACTURE:
APPROVED AS NOTED
APPROVED WITH NO EXCEPTION TAKEN
REVISE AND RESUBMIT
SIGNATURE
YOUR TITLE DATEHEIGHT REQUIRED TO VERIFY THAT HOOD FITS SPACE AND TO SIZE THE ENCLOSURE PANELS
___' - ___"
VERIFY CEILING HEIGHT
HVAC DISTRIBUTION NOTE
HIGH VELOCITY DIFFUSERS OR HVAC RETURNS
SHOULD NOT BE PLACED WITHIN TEN (10) FEET
OF THE EXHAUST HOOD. PERFORATED
DIFFUSERS ARE RECOMMENDED.
PATENT NUMBERS
AC-PSP WALL (CANADA) - CA PATENT 2820509.
AC-PSP (UNITED STATES) - US PATENT 7963830 B2.
AC-PSP ISLAND (CANADA) - CA PATENT 2520330.
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
2
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
11' 0"NOM./11' 0.00"OD.
12'-0.00" OVERALL LENGTH
54"
12"
UTILITY
CABINET.
24
X
1
8
X
8
.
6
2
B
O
X
16"
24"
8"
12"
28"
48"
8"
12"
28"
48"
8"
12"
28"
3"
§
66"66"
12"
∅16"
U.L. LISTED L55 SERIES E26 CANOPY
LIGHT FIXTURE - HIGH TEMP ASSEMBLY.
PLAN VIEW - HOOD #1
11' 0.00" LONG 5424EX-2-PSP-F
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT.
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER.
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUTS.
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER.
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL ALL-THREAD.
HOOD CORNER
HANGING ANGLE
(WEIGHT BEARING
ANCHOR POINT
FOR HOOD).
HOOD CORNER
HANGING ANGLE
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUTS.
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER.
ASSEMBLY INSTRUCTIONS
HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI
GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING
ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5
(MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI
GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE
DOUBLED HEX NUT CONFIGURATION BENEATH HOOD HANGING
ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN 1/4" OF
EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE
ALL HEX NUTS TO 57 FT-LBS.
(HARDWARE BY INSTALLER)
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT.
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER.
FULL LENGTH
HANGING ANGLE
(WEIGHT BEARING
ANCHOR POINT
FOR HOOD).
FULL LENGTH
HANGING ANGLE
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL ALL-THREAD.
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUTS.
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER.
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT.
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER.
ASSEMBLY INSTRUCTIONS
HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI
GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING
ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5
(MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI
GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE
DOUBLED HEX NUT CONFIGURATION ABOVE CEILING
ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS
ACCEPTABLE FOR FULL LENGTH HANGING ANGLES.
MAINTAIN 1/4" OF EXPOSED THREADS BENEATH BOTTOM
HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS.
(HARDWARE BY INSTALLER)
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT.
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER.
SUPPLY PLENUM
HANGING ANGLE
(WEIGHT BEARING
ANCHOR POINT
FOR SUPPLY
PLENUM).
SUPPLY PLENUM
HANGING ANGLE
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL ALL-THREAD.
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUTS.
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER.
1/2" - 13 TPI
GRADE 5 (MINIMUM)
STEEL HEX NUT.
1/2" GRADE 5
(MINIMUM) STEEL
FLAT WASHER.
ASSEMBLY INSTRUCTIONS
HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI
GRADE 5 (MINIMUM) ALL-THREAD. SANDWICH HANGING
ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5
(MINIMUM) STEEL FLAT WASHERS AND 1/2" - 13 TPI
GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE
DOUBLED HEX NUT CONFIGURATION ABOVE CEILING
ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS
ACCEPTABLE FOR PSP HANGING ANGLES. MAINTAIN 1/4" OF
EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE
ALL HEX NUTS TO 57 FT-LBS.
(HARDWARE BY INSTALLER)
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
3
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
3" INTERNAL STANDOFF.
GREASE DRAIN
WITH REMOVABLE CUP.
SEE HOOD TABLE.
§
EXHAUST RISER.
HANGING ANGLE.
L55 SERIES E26 CANOPY LIGHT FIXTURE -
HIGH TEMP ASSEMBLY, INCLUDES CLEAR THERMAL
AND SHOCK RESISTANT GLOBE (L55 FIXTURE).
23.5% OPEN STAINLESS
STEEL PERFORATED PANEL.
ATTACHING
PLATES.
SUPPLY RISER
WITH VOLUME DAMPER.
6"
2 3/4"
16"
18"
BACKSPLASH 80.00" HIGH
X 144.00" LONG.
FIELD WRAPPER 18.00" HIGH
(SEE HOOD OPTIONS TABLE).
23"
23"
LEFT AND RIGHT QUARTER END PANELS.
EQUIPMENT
BY OTHERS.
48.0" MAX.
80"
24" NOM.
54"
SECTION VIEW - MODEL 5424EX-2-PSP-F
HOOD - #1
IT IS THE RESPONSIBILITY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED-COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
16" SS BAFFLE WITH
HANDLES AND HOOK.
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
4
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
BACKSPLASH
HEIGHT
- BACKSPLASH IS NOT
INSULATED AND IS UNSUITABLE
FOR INSTALL AGAINST
COMBUSTIBLE WALLS
BACKSPLASH PANELS
SLIDE INTO DIVIDER
BAR
NON-COMBUSTIBLE WALL
LENGTH
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
5
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
FIRE SYSTEM INFORMATION - JOB#6210635
1 TANK FS 4.0/4.0 40 32 FIRE CABINET LEFT LEFT, HOOD 1
FIRE
SYSTEM
NO
TAG TYPE SIZE MAX FP
DESIGN
FP
INSTALLATION
SYSTEM LOCATION ON HOOD
FIRE SYSTEM PARTS LIST KEY
1
0 - 0 - TANK FIRE SUPPRESSION POST-DISCHARGE PROCEDURE UTILITY CABINET LABEL SHEET.
0 - 0 - TANK FIRE SUPPRESSION MAINTENANCE GUIDE UTILITY CABINET LABEL SHEET.
0 - 0 - 12-F28021-32144-OT-360 DUCT FIRE THERMOSTAT WITH 12 FOOT WIRE LEADS. NO,
CLOSE ON TEMP RISE AT 360°F.
0 - 0 - 4429K153 1/2" MALE NPT TO 1/2" FEMALE NPT ELBOW, BRASS.
0 - 0 - 4429K422 1/2" X 1/4" BRASS REDUCING BUSHING.
0 - 0 - 79525 1/2" 90 PRO-PRESS ELBOW WITH 1/2” NPT FEMALE CONNECTION, VIEGA.
0 - 0 - 79580 1/2" X 1/2" PRO-PRESS TEE X 1/2” NPT FEMALE CONNECTION, VIEGA.
0 - 0 - 87-120042-001 SECONDARY ACTUATOR VALVE (SVA) - SINGLE ACTUATOR, REQUIRES
PRIMARY RELEASE ACTUATOR, TANK FIRE SUPPRESSION.
0 - 0 - 87-120045-001 HOSE, SECONDARY ACTUATOR HOSE, 7.5" BRAIDED STAINLESS STEEL,
TANK FIRE SUPPRESSION.
0 - 0 - 87-300001-001 TANK - PRESSURIZED TANK USED FOR TANK FIRE SUPPRESSION.
0 - 0 - 87-300030-001 PRIMARY ACTUATOR KIT (PAK) - ACTUATOR AND RELEASE SOLENOID
ASSEMBLY, ONE NEEDED PER FIRE SYSTEM, SUPERVISED, TANK FIRE SUPPRESSION.
0 - 0 - 87-300152-001 HARDWARE, SVA BOLTS, TANK FIRE SUPPRESSION.
0 - 0 - 9055455PC PRO PRESS 1/2 PRESS X PRESS 90 ELBOW LD.
0 - 0 - 9097200PC PRO PRESS PC611 1/2 PRESS TEE LD.
0 - 0 - 98694A115 HARDWARE, DATANKLOCK LOCKING BRACKET SQUARE NUTS 5/16" ZINC, TANK
FIRE SUPPRESSION.
0 - 0 - A0034332 JUNCTION BOX FOR MANUAL PULL STATION. 1.5" DEEP BACK BOX, RED COLOR.
0 - 0 - A31484 1/4" NPT SCHRADER VALVE AND CAP, JB INDUSTRIES. 1/4" FLARE X 1/4"
MPT HALF UNION. USED ON TANK SERVICE PORT.
0 - 0 - BI145 3/8" BLACK IRON 90 ELL.
0 - 0 - DATANKLOCK DISCHARGE ADAPTER TANK LOCKING PLATE FOR FIRE SYSTEM TANK INSTALLATION
IN UTILITY CABINETS, TANK FIRE SUPPRESSION.
0 - 0 - TANK STRAP TANK STRAP - USED FOR TANK FIRE SUPPRESSION.
0 - 0 - TFS-UCTANKBRACKET TANK BRACKET FOR FIRE SYSTEM TANK INSTALLATION IN UTILITY
CABINETS, TANK FIRE SUPPRESSION.
0 - 0 - WK-283952-000 DISCHARGE ADAPTER, TANK FIRE SUPPRESSION.
16 - 16 - 79210 1/2" X 3/8" NPT MALE ADAPTER, VIEGA.
16 - 16 - OL-F NOZZLE - TANK PROTECTION APPLIANCE COVERAGE NOZZLE (INCLUDES METAL
BLOW OFF CAP, LANYARD, USED WITH CHROME-PLATED PIPE).
26 - 26 - QSA-3/8 QUIK SEAL - 3/8" (UL).
34 - 34 - A0034331 24VDC SINGLE ACTION MANUAL ACTUATION DEVICE (PUSH/PULL STATION)
WITH PROTECTIVE COVER, ONE (1) NORMALLY OPEN CONTACT. RED COLOR.
1
1
1
2
1
1
2
1
1
2
1
8
7
6
4
1
1
3
2
6
2
2
7
7
7
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
FIRE
SYSTEM
NO
TAG KEY NUMBER - PART DESCRIPTION
QTY BY
FACTORY
QTY BY
DIST
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
6
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
FACTORY PIPING EXTENDS A MAXIMUM
OF 6" ABOVE THE TOP OF THE HOOD.
12"
∅16"
HOOD FRONT
HOOD BACK
HOOD # 1 JOB # 6210635 FS # 1
MODEL: ND-2-PSP-F SIZE: 54"x24" LENGTH: 11' 0"
TA
N
K
O
V
E
R
L
A
P
P
I
N
G
PR
O
T
E
C
T
I
O
N
-
36
/
S
H
E
L
F
HI
G
H
P
R
O
X
I
M
I
T
Y
13
2
.
0
0
"
L
X
3
0
.
0
0
"
D
DUCT
S
360
OL-F
OL-F OL-F
25.00"
27.50"
OL-F
SHI
P
L
O
O
S
E
*
27.50"
OL-FSHIP LOOSE*27.50"
OL-F
SHI
P
L
O
O
S
E
*
27.50"
OL-F
NOZZLE HEIGHT
35-50" FROM
COOKING SURFACE.
(45.25")
SHI
P
L
O
O
S
E
*
12.00"36.00"36.00"36.00"12.00"
- SYSTEM REQUIRES A MINIMUM OF 7 FT OF
EQUIVALENT PIPE LENGTH BETWEEN TANK AND
NEAREST APPLIANCE NOZZLE FOR MOST APPLIANCES.
EACH 90 DEGREE ELBOW ADDS 1.3 FT OF
EQUIVALENT LENGTH. SEE MANUAL FOR DETAILS
7
1
631
2 5
PL
E
N
U
M
PL
E
N
U
M
NOTES
- FIELD PIPE DROPS AS SHOWN
PIPING, ELBOWS, TEES, AND NOZZLES SUPPLIED BY CAS.
- FIELD INSTALLED DROP: FACTORY WILL PROVIDE QTY 2 60IN LONG PIECES OF CHROME
PLATED PIPING SHIPPED LOOSE TO BE FIELD-INSTALLED.
- SHIP LOOSE DROP: FACTORY WILL PROVIDE THE EXACT CHROME PIPE LENGTH NEEDED
SHIPPED LOOSE TO BE FIELD-INSTALLED.
- RELOCATE NOZZLES IF FLOW PATTERN IS BLOCKED BY SHELVING,
SALAMANDERS, ETC.
- OVERLAPPING COVERAGE SHALL NOT BE USED ON ANY APPLIANCE WITH AN OBSTRUCTION.
- IF APPLICABLE, EXTENDED PRE-PIPED DROPS ARE SHIPPED LOOSE.
- FACTORY PIPING EXTENDS A MAXIMUM OF 6" ABOVE THE TOP OF THE HOOD.
- APPLIANCE DIMENSIONS LISTED REPRESENT THE COOKING SURFACE
SIZE, NOT THE OVERALL APPLIANCE SIZE.
- THIS FIRE SYSTEM COMPLIES WITH U.L. 300 REQUIREMENTS.
- OL-F NOZZLE PART NUMBER REPLACES 3070-3/8H-10-SS
JOB #: 6210635.
JOB NAME: AREPA PLEASE - ATLANTIC BEACH.
SYSTEM SIZE: TANK-SP-2 DESIGN FP: 32. MAXIMUM FP: 40.
HOOD # 1 11' 0.00" LONG x 54" WIDE x 24" HIGH.
RISER # 1 SIZE: 16" DIA.
HOOD # 1 METAL BLOW-OFF CAPS INCLUDED.
- HEAVY-DUTY APPLIANCES (RATED 600°F) WILL REQUIRE AN ADDITIONAL
DOWNSTREAM FIRESTAT IN THE EVENT THAT THE DUCTWORK CONTAINS ANY
HORIZONTAL RUNS OVER 25 FT IN LENGTH.
- MEDIUM TO LIGHT-DUTY APPLIANCES (RATED 450°F) WILL NOT REQUIRE
ANY ADDITIONAL DOWNSTREAM DETECTION.
PRESSURE SUPERVISION SWITCH.
PRIMARY ACTUATOR RELEASE.
4 GALLON TANK.
7
6
5
4
2
1
LEGEND - FIRE CABINET TANK SYSTEM
PRIMARY HOSE ASSEMBLY.
SECONDARY ACTUATOR RELEASE.3
SECONDARY HOSE ASSEMBLY.
REMOTE MANUAL ACTUATION DEVICE.
3" INTERNAL STANDOFF.
GREASE DRAIN
WITH REMOVABLE CUP.
SEE HOOD TABLE.
§
EXHAUST RISER.
HANGING ANGLE.
L55 SERIES E26 CANOPY LIGHT FIXTURE -
HIGH TEMP ASSEMBLY, INCLUDES CLEAR THERMAL
AND SHOCK RESISTANT GLOBE (L55 FIXTURE).
23.5% OPEN STAINLESS
STEEL PERFORATED PANEL.
ATTACHING PLATES.
SUPPLY RISER WITH
VOLUME DAMPER.
6"
2 3/4"
16"
18"
BACKSPLASH 80.00" HIGH
X 144.00" LONG.
FIELD WRAPPER 18.00" HIGH
(SEE HOOD OPTIONS TABLE).
23"
23"
LEFT AND RIGHT QUARTER END PANELS.
EQUIPMENT
BY OTHERS.
48.0" MAX.
80"
24" NOM.
54"
SECTION VIEW - MODEL 5424EX-2-PSP-F
HOOD - #1
IT IS THE RESPONSIBILITY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED-COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
16" SS BAFFLE WITH
HANDLES AND HOOK.
27 1/2"
INCLUDES: FIELD INSTALLATION AND HOOKUP DURING NORMAL BUSINESS HOURS
BY CERTIFIED INSTALLERS ONLY IN THE LOCATION NOTED ABOVE, TWO SITE
VISITS ONLY (ONE VISIT TO SET PULL STATION & SYSTEM HOOKUP AND ONE
VISIT FOR ONE TEST; ADDITIONAL VISITS WILL RESULT IN ADDITIONAL
CHARGES), ONE MECHANICAL OR ELECTRICAL GAS VALVE PER SYSTEM AT A
MAXIMUM SIZE OF 2", PERMIT, AND SYSTEM TEST.
EXCLUDES: UNION LABOR & PREVAILING WAGE (LABOR & WAGES WILL BE
ADDED IF APPLICABLE), GAS VALVE INSTALLATION, ELECTRICAL HOOKUP AND
CONNECTIONS, HANGING OF FIRE CABINET, SHUNT TRIP, HANDHELD
EXTINGUISHER(S), ON-SITE RE-PIPING DUE TO EQUIPMENT LAYOUT CHANGES.
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
7
Atlantic Beach, FL, 32233
3/16" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
EXHAUST FAN INFORMATION - JOB#6210635
1 1 EADU180H ECON-AIR 2585 1.000 1062 TEFC,PREMIUM 1.500 0.9430 3 208 6.5 597 FPM 185 11.2
FAN
UNIT
NO
TAG QTY FAN UNIT MODEL #MANUFACTURER CFM ESP RPM
MOTOR
ENCL
HP BHP PHASE VOLT FLA
DISCHARGE
VELOCITY
WEIGHT
(LBS)
SONES
MUA FAN INFORMATION - JOB#6210635
2 1 EA-A2-20D 20MF-2-MOD A2 1500 2068 0.500 907 ODP,PREMIUM 1.000 0.4070 3 208 3.8 4.8A 15A 389 7.5
FAN
UNIT
NO
TAG QTY FAN UNIT MODEL #BLOWER HOUSING
MIN
CFM
DESIGN
CFM
ESP RPM
MOTOR
ENCL
HP BHP PHASE VOLT FLA MCA MOCP
WEIGHT
(LBS)
SONES
FAN OPTIONS
1
2
1
1
1
1
1
1
1
GREASE BOX
FAN BASE CERAMIC SEAL - SHIP LOOSE - FOR GREASE DUCTS
MIAMI DADE CERTIFICATION - NOA-1 ALUMINUM UPBLAST
2 YEAR PARTS WARRANTY
SIZE 2 UNTEMPERED COMMERCIAL DOWN DISCHARGE FOR DIRECT DRIVE AHUS
MIAMI DADE CERTIFICATION - NOA-2 SUPPLY
2 YEAR PARTS WARRANTY
FAN
UNIT
NO
TAG QTY DESCRIPTION
FAN ACCESSORIES
1 YES
FAN
UNIT
NO
TAG
EXHAUST
GREASE
CUP
GRAVITY
DAMPER
WALL
MOUNT
SUPPLY
SIDE
DISCHARGE
GRAVITY
DAMPER
MOTORIZED
DAMPER
WALL
MOUNT
CURB ASSEMBLIES
1
2
# 1
# 2
53 LBS
42 LBS
CURB
CURB
26.500"W X 26.500"L X 26.000"H VENTED HINGED 16 GAUGE.
31.000"W X 37.000"L X 20.000"H INSULATED.
NO
ON
FAN
WEIGHT ITEM SIZE
MIAMI-DADE NOA1 ALUMINUM UP-BLAST FANS
INSTALLATION FASTENER TYPES
FAN TO CURB WOOD (SG = 0.42MIN.)STEEL (12 GAUGE MIN.)CONCRETE (2500 PSIMIN. CRACKEDCONCRETE)
FASTENER 5/16"-18 X 2" SELFDRILLING SCREW (ELCODRIL-FLEX OR BETTER)
3/8" DIA. ZINCPLATED LAG BOLT 1/4"-14 DRIL-FLEX SELFDRILLING SCREW
3/8" DIA. SS HILTIKWIK BOLT TZEXPANSION ANCHORMINIMUM THREADPENETRATION N/A 2-1/2"12 GAUGE 2"
MINIMUM EDGEDISTANCE N/A 1-1/2"3/8"3"
MINIMUM ENDDISTANCE N/A 2-5/8"3/8"3"
MINIMUM SPACING N/A 1-1/2"3/4"5-1/2"
INSTALLATION FASTENER QTY
CURB TO FAN
(ROOF)
CURB TO FAN
(WALL)WOOD (ROOF)WOOD (WALL)STEEL (ROOF)
STEEL
(WALL)
CONCRETE
(ROOF)
CONCRETE
(WALL)
FAN MODEL PER SIDE TOTA
L PER SIDE TOTA
L
PER
SIDE
TOTA
L
PER
SIDE
TOTA
L
PER
SIDE
TOTA
L
PER
SIDE
TOTA
L
PER
SIDE TOTAL PER
SIDE
TOTA
L
DU180 3 12 3 12 5 20 5 20 6 24 6 24 5 20 5 20
DESIGN PRESSURE: +150.0 / -150.0 PSF.
LARGE MISSILE IMPACT RESISTANT.
GENERAL NOTES:
1. THIS APPROVAL IS FOR THE STRUCTURAL CAPACITY AND IMPACT RATING OF THE EXTERIOR
HOUSING ONLY; IT DOES NOT INCLUDE ANY INTERIOR MECHANISM OR ELECTRICAL PART.
2. THESE FANS HAVE NOT BEEN WIND TESTED FOR WIND DRIVEN RAIN TEST PER FLORIDA
BUILDING CODE, TAS100 (A)-95.
3. TESTED IN ACCORDANCE TO FLORIDA BUILDING CODE TEST PROTOCOL TAS201, TAS202, TAS203.
4. TESTED FOR AREAS INCLUDING HIGH VELOCITY HURRICANE ZONES.
5. TESTED UNDER MIAMI-DADE COUNTY NOTIFICATION NUMBER ATI-08033.
CURB MATERIAL:
20" HIGH & LESS = 20 GA. STEEL.
ABOVE 20" THRU 42" = 16 GA. STEEL.
1
2
INSTALLATION INSTRUCTIONS:
1. SECURE LID TO FAN USING (8)
1/4"-14 X 1" ZINC PLATED STEEL SELF
DRILLING SHEET METAL SCREWS WITH
RUBBER WASHER SPACED EVENLY
AROUND LID.
2. SECURE FAN BASE TO CURB USING
1/4"-14 X 2" GALVANIZED SELF DRILLING
SCREWS (A307 OR BETTER) THROUGH
PRE-PUNCHED HOLES IN THE FAN BASE.
(SEE TABLE BELOW FOR QTY).
3. SECURE CURB TO ROOF OR WALL BY
DRILLING 1/4" DIA PILOT HOLES IN THE CURB
FLANGE AT LOCATIONS SHOWN IN THE
DIAGRAM. SEE TABLE BELOW FOR FASTENER
TYPE. USE TABLE BELOW FOR FASTENER QTY.
3
FULLY WELDED CURB CORNERS
(ABOVE 20" HEIGHT).
MAX CURB
HEIGHT 42".
MIN END DISTANCE.
MIN SPACING.
MIN EDGE DISTANCE.
MIAMI-DADE COUNTY -
CURB ROOF INSTALLATION GUIDE
ROOF OPENING.
MIN EDGE
DISTANCE.
MIN END
DISTANCE.
MIN SPACING.
ROOF SUBSTRATE.
CURB.
WOOD: SG =0.42 MIN.
CONCRETE: 2500 PSI MIN.
STEEL: 12 GAUGE MIN.
CURB.
WOOD: 4 X JOIST MIN SG = 0.42 MIN.
STEEL: 12 GAUGE TRUSS MIN.
ROOF OPENING.
A
DETAIL A
SEE SPECIFIC FAN MODEL
FASTENER TABLES FOR
FASTENER TYPE AND QTY.
WASHER (STEEL ZINC PLATED)
FOR SCREW SIZES 3/8" TYP.
CURB.
1/4" PILOT
HOLE.
WALL SUBSTRATE.
1/4" PILOT HOLE.
ROOF OPENING.
A
DETAIL A
CURB.
MIN EDGE
DISTANCE.
STEEL: 12 GAUGE TRUSS MIN.
WOOD: 4X JOIST MIN SG = 0.42.
STEEL: 12 GAUGE MIN.
CONCRETE: 2500 PSI MIN.
WOOD: SG = 0.42 MIN.
WALL SUBSTRATE:
FASTENER TYPE AND QTY.
FASTENER TABLES FOR
SEE SPECIFIC FAN MODEL
FOR SCREW SIZE 3/8" TYP.
WASHER (STEEL ZINC PLATED)
ROOF
OPENING.
MIN SPACING.
MIN END
DISTANCE.
MIN EDGE
DISTANCE.
WALL CURB INSTALLATION GUIDE
MIAMI-DADE COUNTY -
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
8
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
- VARIABLE SPEED CONTROL.
- THERMAL OVERLOAD PROTECTION (SINGLE PHASE).
- HIGH HEAT OPERATION 300°F (149°C).
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING AIR AT 300°F (149°C)
UNTIL ALL FAN PARTS HAVE REACHED
THERMAL EQUILIBRIUM, AND WITHOUT ANY
DETERIORATING EFFECTS TO THE FAN WHICH
WOULD CAUSE UNSAFE OPERATION.
NORMAL TEMPERATURE TEST
26"
28"
37 3/8"
16 1/2"
2"
22 5/8"
- INTERNAL WIRING.
- ROOF MOUNTED FANS.
- RESTAURANT MODEL.
FEATURES:
- DIRECT DRIVE CONSTRUCTION (NO BELTS/PULLEYS).
TOP VIEW
37 3/8"
28"
- NEMA 3R SAFETY DISCONNECT SWITCH.
33 3/4"
GREASE DRAIN.
- GREASE CLASSIFICATION TESTING.
- UL705 AND UL762 AND ULC-S645
ABNORMAL FLARE-UP TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING BURNING GREASE VAPORS
AT 600°F (316°C) FOR A PERIOD OF
15 MINUTES WITHOUT THE FAN BECOMING
DAMAGED TO ANY EXTENT THAT COULD CAUSE
AN UNSAFE CONDITION.
26"
26"
ROOF OPENING
DIMENSIONS.
26"
26 1/2"
16 GAUGE
CONSTRUCTION.
STEEL
3" FLANGE.
26 1/2"
HINGE KIT
VENTED
CURB.
FAN #1 EADU180H - EXHAUST FAN
OPTIONS
- GREASE BOX.
- FAN BASE CERAMIC SEAL -
SHIP LOOSE - FOR GREASE
DUCTS.
- MIAMI DADE CERTIFICATION -
NOA-1 ALUMINUM UPBLAST.
- 2 YEAR PARTS WARRANTY.
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
9
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
37"
FLEX
CONDUIT
FOR FIELD
WIRING.
BLOWER DISCHARGE.
16"
10"
18 3/4"
8 5/8"
LIFTING LUG.
3 3/4"
AIRFLOW.
BLOWER/MOTOR
ACCESS DOOR
24" SERVICE
CLEARANCE REQ.
SERVICE DISCONNECT
SWITCH.
AIRFLOW.
37 3/8"
16 1/4"
31"
20" EQUIPMENT CURB.
40 1/8"
36 3/4"
93 3/4"
MIN. 20"
MINIMUM
STRAIGHT
DUCT
PER AMCA*
FAN #2 EA-A2-20D - SUPPLY FAN
1. UNTEMPERED SUPPLY UNIT WITH 20" MIXED FLOW DIRECT DRIVE FAN IN SIZE #2 HOUSING.
2. INTAKE HOOD WITH EZ FILTERS.
3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT.
4. DOWN DISCHARGE CONSTRUCTION FOR SIZE 2 UNTEMPERED DIRECT DRIVE AHUS.
5. MIAMI DADE IMPACT AND WIND LOAD CERTIFICATION +30 / -130 PSF - MIAMI DADE COUNTY PRODUCT CONTROL APPROVED.
FLORIDA BUILDING CODE APPROVAL. ROOF MOUNT EXHAUST CURBS UP TO 20" HIGH MUST BE 18 GAUGE ALUMINIZED.
6. HINGED DOUBLE WALL INSULATED DOOR ASSEMBLY (BURNER/BLOWER SECTION).
7. 2 YEAR PARTS WARRANTY.
*NOTE: SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS. A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED
DOWNSTREAM OF UNIT DISCHARGE AS OUTLINED IN AMCA PUBLICATION 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST
BE RADIUS THROAT, RADIUS BACK WITH TURNING VANES. FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE BACK ELBOWS SHOULD
NOT BE USED. ANY TRANSITION AND/OR TURNS IN THE DUCTWORK WILL CAUSE SYSTEM EFFECT. SYSTEM EFFECT WILL
DRASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFLOW. DO NOT RELY ON UNIT TO SUPPORT DUCT IN ANY WAY. FAILURE
TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT.
SUGGESTED STRAIGHT DUCT SIZE IS 20" x 20".LETSDI
R
ROOF OPENING 2" SMALLER THAN CURB DIMENSION.
3" FLANGE.
20 GAUGE
CONSTRUCTION.
STEEL
20"
31"37"
OPTIONS:
- FULL BOTTOM CORNERS.
CURB.
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
10
Atlantic Beach, FL, 32233
1/4" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
GREASE DUCT & CHIMNEY SPECIFICATIONS:
PROVIDE GREASE DUCT EQUAL TO ECON-AIR MODEL "EDW"
ROUND 20 GAUGE 430 STAINLESS STEEL DUCTWORK. MODEL "EDW"
IS LISTED TO UL-1978 AND IS INSTALLED USING "V" CLAMP LOCKING
CONNECTIONS SEALED WITH 3M FIRE BARRIER 2000 PLUS. MODEL "EDW"
DOES NOT REQUIRE WELDING PROVIDING IT HAS BEEN INSTALLED PER
THE MANUFACTURES INSTALLATION GUIDE.
PROVIDE RATED ACCESS DOORS AT EVERY CHANGE IN DIRECTION AND EVERY 12' ON CENTER.
PER MANUFACTURES LISTING MODEL "EDW" HORIZONTAL RUNS LESS THAN 75 FT. CAN BE
SLOPED 1/16" PER 12", HORIZONTAL RUNS MORE THAN 75 FT. CAN BE SLOPED 3/16" PER 12".
DUCT SHOULD BE SLOPED AS MUCH AS POSSIBLE TO REDUCE THE CHANCE OF GREASE
ACCUMULATION IN HORIZONTAL RUNS.
IF THE DUCT OR CHIMNEY IS WITHIN 18 INCHES OF COMBUSTIBLE MATERIAL, PROVIDE
UL-2221 OR UL-103 HT LISTED DOUBLE WALL GREASE DUCT OR DOUBLE WALL CHIMNEY
EQUAL TO ECON-AIR MODEL "EDW- 2R, 2R TYPE HT, 3R, OR 3Z" ROUND 20 GAUGE 430
STAINLESS INNER DUCT INSULATED WITH A 24 GAUGE 430 STAINLESS OUTER SHELL.
§
CUSTOMER APPROVAL TO MANUFACTURE:
APPROVED AS NOTED
APPROVED WITH NO EXCEPTION TAKEN
REVISE AND RESUBMIT
SIGNATURE
YOUR TITLE DATE
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
11
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
OPEN POSITION
3 3/4
17 1/8
5 1/16
GREASE
BOX.
3 APPROX.
GREASE BOX INSTALLATION
COVER.
BOX
GREASE
GREASE
PIPE.
CURB.
(OPTIONAL).
KIT
HINGE
FAN.
CLOSED POSITION
INSTALL GREASE PIPE AS SHOWN ON PIC. 4.
GREASE PIPE.
GREASE BOX.
STEP 3)
PIC. 3
PIC. 4
COVER.
GREASE
BOX
HOLD 3" DIMENSION AS SHOWN ON PIC. 1.
SCREW GREASE BOX COVER TO CURB USING (3) LONG (3/4" LG.)
ATTACH GREASE BOX COVER TO THE CURB,
GREASE BOX FIELD INSTALLATION
ATTACH GREASE BOX TO GREASE BOX COVER, SLIDE AND DROP.
COVER.
BOX
GREASE
PIC. 1
COVER.
GREASE
BOX
3
AS SHOWN ON PIC. 3.
STEP 2)
CURB.
SCREWS AS SHOWN ON PIC. 2.
PARTS INCLUDED
GREASE BOX.
GREASE PIPE.
GREASE BOX COVER.
SHEET METAL SCREWS
3 - LONG (3/4" LG.).
STEP 1)
CURB.
PIC. 2
CURB.
08/19/02
GREASEBOX
REV.#2
*NOTE: UL 705 INSTALL.
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
12
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
ELECTRICAL PACKAGE - JOB#6210635
1 SC-311110MA UTILITY CABINET LEFT
UTILITY CABINET
LEFT
HOOD # 1
1 LIGHT
1 FAN
SMART CONTROLS THERMOSTATIC CONTROL
W/ RELAY ON/OFF WITH SUPPLY
EXHAUST
SUPPLY
3
3
1.500
1.000
208
208
6.5
3.8
NO TAG PACKAGE #LOCATION
SWITCHES
LOCATION QUANTITY
OPTION
FANS CONTROLLED
TYPE ɸ HP VOLT FLA
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
15
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach
SYSTEM DESIGN VERIFICATION (SDV)
IF ORDERED, CAS SERVICE WILL PERFORM A SYSTEM DESIGN VERIFICATION (SDV) ONCE ALL
EQUIPMENT HAS HAD A COMPLETE START UP PER THE OPERATION AND INSTALLATION MANUAL.
TYPICALLY, THE SDV WILL BE PERFORMED AFTER ALL INSPECTIONS ARE COMPLETE.
ANY FIELD RELATED DISCREPANCIES THAT ARE DISCOVERED DURING THE SDV WILL BE BROUGHT TO
THE
ATTENTION OF THE GENERAL CONTRACTOR AND CORRESPONDING TRADES ON SITE. THESE ISSUES
WILL BE DOCUMENTED AND FORWARDED TO THE APPROPRIATE SALES OFFICE. IF CAS SERVICE HAS
TO
RESOLVE A DISCREPANCY THAT IS A FIELD ISSUE, THE GENERAL CONTRACTOR WILL BE NOTIFIED AND
BILLED FOR THE WORK. SHOULD A RETURN TRIP BE REQUIRED DUE TO ANY FIELD RELATED
DISCREPANCY THAT CANNOT BE RESOLVED DURING THE SDV, THERE WILL BE ADDITIONAL TRIP
CHARGES.
DURING THE SDV, CAS SERVICE WILL ADDRESS ANY DISCREPANCY THAT IS THE FAULT OF THE
MANUFACTURER. SHOULD A RETURN TRIP BE REQUIRED, THE GENERAL CONTRACTOR AND APPROPRIATE
SALES OFFICE WILL BE NOTIFIED. THERE WILL BE NO ADDITIONAL CHARGES FOR MANUFACTURER
DISCREPANCIES.
LOCATION
DATE
DWG #
REV.
JOB
DRAWN BY
JOB #
SCALE
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
SLI DTE
R
C US
3/19/2024
26
Atlantic Beach, FL, 32233
3/8" = 1'-0"
6210635
reg65
Arepa Please - Atlantic Beach