Permit Mech Fire 2010 CITY OF ATLANTIC BEACH
r ;y 800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5826
App on Number . . . . . 1p0pp-nn00000983 Date 8/23/10
Rr.QPcrt�� Add—arms S 1 S SSR@SHViEli3A
1"tT �T
RE number . . . . . . . . . . 169399-0400-
NCR OLD ACCOUNT NUMBERS . . .
Application type description MECHANICAL FIRE PERMIT
Subdivision Name . . . . . .
Property Use . . . . . . . .
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 3335
Owner Contractor
------------------------ ------------------------
SEVILLA CONDOMINIUM SIMPLEX GRINNELL, LP
1800 SEVILLA BOULEVARD 10255 FORTUNE PARKWAY
ATLANTIC BEACH FL 32233 BLDG 500, SUITE 120
JACKSONVILLE FL 32256
(904) 486-1200
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL FIRE PERMIT
Additional desc . .
Sub Contractor . . SIMPLEX GRINNELL, LP
Permit Fee . . . . 55 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 8/23/10
Qty Unit Charge Per Extension
BASE FEE 55 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 55 . 00 55 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Grand Total 55 . 00 55 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
Printing :: CR 120085 Page 1 of 1
Mike Hogan, Tax Collector
Duval County,City Of Jacksonville City of Jacksonville/Duval CcContr of 4 500377.0001 of 0001
Mike Hogan,Tax Collector Irate 08/23/2010
231 E.Forsyth Street
dack%onviile.FL 32202 Oper US
Till P03
General Collection Receipt 4lfwunt 425460T
,Type -.CR CR - CR120085
Account No:CR 120085 Date:8/11/2010
User:Prevention,Fire Email:FirePrevCa)coj.net
FIRE MARSHALL FEE FOR SERVICES PROVIDED
Name:Simplex Grinnell
Address: 10255 Fortune Pkwy
Description:CR for plans review of elevator recall for Atlantic Beach.
TranCode IndexCode SubONect GLAcct SubsidNo UserCode Project ProjectDd Grant GrantDtl DocNo Amount
701 I FRFP159FI 1 34222 1 1 1 1 1 1 1 1 1 125.00
Total Due:$125.00
Mike Hogan ,Tax Collector
General Collections Receipt
City of Jacksonville,Duval County
Account No:CR 120085 Date:8/11/2010
FIRE MARSHALL FEE FOR SERVICES PROVIDED
Name:Simplex Grinnell
Address:10255 Fortune Pkwy
Description:CR for plans review of elevator recall for Atlantic Beach.
Total Due:$125.00
http://financeweb.cqi.net/TCCR/printing-aspx?cr--CRI20085 8/11/2010
City of Atlantic Beach APPLICATION NUMBER
Building Department (To be assigned by the Building Department.)
800 Seminole Road G r
Atlantic Beach,Florida 32233-5445
Phone(904)247-5826 • Fax(904)247-5845
Dill" E-mail: building-dept@coab.us Date routed:
City web-site: http:Uwww.coab.us 11
APPLICATION REVIEW AND TRACKING FORM
lhh Property Address: �
Department review required Yes No
t Building
Applicant: Planning &Zoning
• Tree Administrator
Project: cam--- Public Works
J Public Utilities
t Public Safety:
ire Services
Signature
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified B
Florida Dept.of Environmental Protection
Florida Dept.of Transportation
St.Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLI TION STATUS
Reviewing Department First Review: Approved. ElDenied.
(Circle one.) Comments:
BUILDING
PLANNING&ZONING --- - 2
Reviewed Date: r
TREE ADMIN. Second Review: Approved as revised. ❑Denied
PUBLIC WORKS Comments:
PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: QApproved as revised. ❑Denied.
Cominents:
Reviewed by: Date:
Revised 05/14/09
Aug 03 10 12;10p Information SystemsCITY O 904-247-5845 p.1
ELECTRICAL PERNUT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd, Atlantic Beach, FL 32233 (�
Ph (904) 247-5826 Fax (904) 247-5845 ..�
iOB ADDRESS: Sey,l'12j _&A dc,�•��n,,�S- 7,300 _ 5etir�'tl 4 &1/0 PERMYr# �`
47-LeA ,x fir',:.- Pa PL- 3 Z Z 3 `-->
VEW SERVICE E]Overhead Underground F7 Underground up Pole
❑Residential(Main) Service
❑0-100 amps ❑101-15 Damps ❑151-200amps 0-amps # of Meters
❑Commercial(Main) Service
❑0-100 amps 0101-150amps ❑151-200amps ❑ amps ❑CT Service amps
Conductor Type Size
❑Multi-Family (Main) Service
00-100 amps 0101-150amps ❑151-200amps ❑ amps #of Unit Meters
Temporary Pole ❑ amps
SERVICE UPGRADE 11amps ❑ CT Service amps
NEW FEEDER(ADDITIONS,ACCESSORY STRUCTURES,ETC.)
❑100 amps ❑150amps 0200amps ❑ amps ❑CT Service amps
ADDITIONS,REMODELS,REPAIRS, BUILD-OUTS,ACCESSORY STRUCTURES, ETC.
Outlets/Switches: 0-3 Damps 31-l 00amps 101-200amps
Appliances: 0-30amps 31-100amps 101-200amps
A/C Circuits: 0-60amps 61-100amps
Heat Circuits: # circuits @ kw
Number of Lighting Outlets, Including Fixtures:
OTHER ELECTRICAL PROJECTS
❑Swimming Pool ❑ Sign ❑Smoke Detectors Qty ❑Transformers KVA ❑Motors hp
FIRE ALARM SYSTEM (Requires 3 sets of plans& Fire Alarm hecklist)
Qty�_voltslamps 0 i to✓b ter VALUE OF WORKS 43 ; 33S-- 00
REPAIRSIMISCELLANEOUS
❑Replace Burnt/Damaged Meter Can ❑Safety Inspection ❑Panel Change El 011 to UG
❑Other:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months. I hereby certify that I have
read this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will he complied with whether
specified or not The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of
construction.
Properly Owners Name Sef�1\a Co r\Jo AA A vA--S Phone Number l'1-
Electrical Company Office Phone `Vq-'q9&-/LaoFax 90•(-36$`U(,7"(
Co.Address: SA,( l20 City-aa- State f7t Zip 32Z S(o
License Holder (Print)• • 'a tate Certification/Registration# E F 600 C) l
Notarized Signature of License Holder
rn
Swoand bscribed befo e s day ofd 20 (U
Signature of Notary Public
Notary Public State of Florida
Christina L Parker
My Commission DD662530
or�` Expires 04/12/2011
/P
SEVILLA
CONDOMINIUM
ELEVATOR RECALL
FIRE ALARM SUBMITTAL
August 4, 2010
ALLSTATE ELECTRIC
7447 SALISBURY ROAD
JACKSONVILLE, FLORIDA 32256
PREPARED BY:
Simplexlsrinnell
10255 FORTUNE PARKWAY
BUILDING 500, SUITE 120
JACKSONVILLE, FLORIDA 32256
904-486-1200
DAVID SELLERS
SALES REPRESENTATIVE
FARSHID POURGOLAFSHAN
DISTRICT MANAGER
SIMPLEX PNIECT VONTA
MAIN OFFICE: (904)486-1200
TO REQUEST SYSTEM STARTUP OR CHECKOUT:
1. CALL THE SERVICE DEPARTMENT INSTALLATION
SCHEDULER
2. REQUEST THE FOLLOWING:
A. PRELIMINARY CHECKOUT
B. PANEL STARTUP
C. ONGOING SUPPORT
D. FINAL CHECKOUT
YOUR REQUEST WILL BE CONFIRMED WITH THE SIMPLEX
TECHNICIAN ASSIGNED TO THE JOB. WE REQUEST AT
LEAST5 BUSINESS DAYS ADVANCED NOTICE WHEN
SCHEDULING A TECHNICAL REPRESENTATIVE FOR FINAL
CHECKOUT SCHEDULING.
3. CONFIRMATION WILL BE MADE WITHIN 24 HOURS.
4. IF A SCHEDULED TIME OR DATE CANNOT BE
SATISFACTORILY RESOLVED, PLEASE CONTACT THE
BRANCH MANAGER.
fir. FIRE ALARM
RECORD OF COMPLETION
AND TAG
AS A SUPPLIER OF EQUIPMENT, PART OF OUR COMMITMENT TO
YOU, OUR CUSTOMER, IS TO KEEP YOU INFORMED OF CRITICAL
INFORMATION PERTINENT TO YOU AS AN INSTALLING CONTRACTOR.
FOR MANY YEARS THE STATE OF FLORIDA HAS HAD IN PLACE A
RULE WHICH REQUIRES CONTRACTORS TO FURNISH CERTAIN DOC-
UMENTS REGARDING THE INSTALLATION OF FIRE ALARM EQUIPMENT. WE
HOPE THE FOLLOWING WILL HELP.
NFPA 72 SECTION 4-5.1.2 STATES "THE INSTALLING CONTRACTOR
SHALL FURNISH A WRITTEN STATEMENT THAT THE SYSTEM HAS BEEN
INSTALLED IN ACCORDANCE WITH APPROVED PLANS AND TESTED IN
ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND
APPROPRIATE NFPA REQUIREMENTS." THIS IS THE RECORD OF
COMPLETION.
THE FLORIDA DIVISION OF STATE FIRE MARSHAL'S UNIFORM FIRE
SAFETY RULES AND STANDARDS; SECTION 69A-48.005 STATES,
"INFORMATION APPLICABLE TO NFPA STANDARDS SHALL BE A MINIMUM
REQUIREMENT AND SHALL BE CONTAINED IN THE RECORD OF
COMPLETION PROVIDED TO THE CONSUMER WHEN A FIRE ALARM
SYSTEM IS INSTALLED OR IMPROVED "(see figure 4-5.2.1 NFPA 72 2002 edition).
SECTION 69A-48.006 STATES "A STANDARD FIRE ALARM TAG MEETING THE
REQUIREMENTS OF THIS RULE SHALL BE SECURELY AFFIXED TO THE FIRE
ALARM CONTROL PANEL OF EACH FIRE ALARM SYSTEM WHICH IS
INSTALLED" (see Florida rule 69A-48.006 for specifics).
SIMPLEXGRINNELL, FURNISHES TECHNICAL INSTALLATION
SUPPORT FOR SYSTEMS PURCHASED FROM US AND IN MOST CASES OUR
TECHNICIANS CAN FURNISH BLANK COPIES OF THESE FORMS UPON
REQUEST.
PLEASE CONTACT YOUR SIMPLEXGRINNELL REPRESENTATIVE AT
(904) 486-1200 IF YOU HAVE ANY QUESTIONS REGARDING THIS MATTER.
SEVILLA CONDOMINIUM
ELEVATOR RECALL
Table of Contents
Section I: Equipment List
Section II: Equipment Datasheets
Section III: Hardware Warranty
Section IV: Testing
Section V: Technical Installation Support
40010,
Fire,Security,Communications,Workforce Solutions,Sales&Service
Offices&Representatives in Principle Cities throughout the World
*yco
Fire&
Security
Simp/exGrinne//
Equipment List & Equipment
Datasheets
Fire Alarm System
Quantity Product ID Product Description
1 4005-9101 FIRE ALARM CONTROL PANEL
2 2081-9274 10AH BATTERY
3 4098-9601 SMOKE DETECTOR HEAT
3 4098-9788 DETECTOR BASE
3 4098-9613E HIGH HUMIDITY HEAT DETECTOR HEAD
3 4098-9788E HIGH HUMIDITY DETECTOR BASE
3 2088-9007 MR-101 RELAY
1 DK-120HW SURGE SUPPRESSOR
Fire,Security,Communications,Workforce Solutions,Sales&Service
Offices&Representatives in Principle Cities throughout the World
13®Simplex LifeAlarm° Fire Alarm Control Panels
UL, ULC, CSFM Listed; FM Approved; 4005 Series Fire Alarm Control Panels
MEA (NYC) Acceptance* Providing 8 to 36 IDCs and 4 NACs
RIM M_
Standard features: """"""rrrrrr"""•"""""
• 80 Character, alphanumeric LCD readout with wide
viewing angle
• Eight, Class B Initiating Device Circuits(IDCs)
• Four, Class B Notification Appliance Circuits(NACs)
• 4 A power supply/battery charger a
• Power-limited design
• Pluggable terminal blocks
• Internal DACT is included on UL listed models;
available separately as required for ULC listed models
Simplex®system accessory compatibility:
rrrrruuurrrrurrrurrrrr■urrru
4602 Series Remote Control Unit(RCU)and Status ■........."...r.........".."""
. . ...................................
Command Unit(SCU),two-wire serial
communications
Model 4005 Fire Alarm Control Panel
• 4601 Series Annunciators
• 4003 Voice Control Panels woo
• 4009 NAC Power Extenders 111140161 '
Software features: For areas requiring eight to thirty-six IDC zones, Simplex
• Menu-driven programming 4005 series fire alarm control panels provide flexible
On-site programmable custom labels initiating circuit monitoring,extensive programmable
• control capability,and LCD annunciated circuit-specific
• Four operator access levels custom labels. Surface mount components,efficient
• Historical event logs microprocessor programming, and easy-to-use control
• Circuit selectable alarm verification panel operation combine to provide an extensive feature
WALKTESTT"'one-person system testing** list in a compact,"installation friendly"package.
•
• Selectable active status reminder Panel status and circuit information is efficiently
indicated by an alphanumeric LCD readout featuring two
Optional expansion: lines of 40 characters each.The panel control switches are
• Two circuit IDC,two circuit NAC/relay t clearly marked for intuitive operation.Programming of
• Four circuit NAC/relayt the selectable features is performed by using the display
• Four circuit IDC(low current and high current and the panel control switches while in the programming
versions)
mode.
• Four circuit Class A NAC or IDC zone conversion • • •
• Eight circuit I/O module The 4005 series fire alarm control panel provides
• Remote station/city connection protection for a wide variety of mid-size facilities in the
• Additional 5 A power supply following fields: Educational, Health Care,Business,
Storage,Hospitality, Residential,and General Assembly.
UL Listed to Standard 864 Its modular design allows IDCs and NACs to be
incremented in groups of two or four to satisfy circuit
requirements without specifying excess capacity. If the
system expands,then additional"snap-in-place"modules
' Refer to page 6 for additional ULC listing information.This product has been approved by can be easily installed on-site.
the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California
Health and Safety Code.See CSFM Listing 7165-0026:212 for allowable values and/or
conditions concerning material presented in this document.It is subject to "WALKTEST performance testing is protected under US Patent No.4,725,818.
re-examination,revision,and possible cancellation.Accepted for use—City of New York
Department of Buildings—MEA35.93E.See page 7 for ULC designations.Additional t NACs may be individually configured for dry contact relay operation,
listings may be applicable;contact your local Simplex product supplier for the latest NOTE: Contact your local Simplex product supplier for fire alarm control panels suitable for
status.Listings and approvals under Simplex Time Recorder Co.are the property of Tyco
Release Control applications.
Safety Products Westminster.
X11 • • X11 • •M ni zin • �•
The CPU board contains the main microprocessor and IDC operation is individually programmable with
panel programming, evaluates the status of all I/O the following 28 operating mode choices(the abbreviated
modules,processes the required responses, and provides a description is part of the IDC display information):
watchdog timer that resets the panel in the event of an
abnormal operation. Additional details are below. Point Type Description Point Type Description
Fire Monitor FPUMP Fire Pump
• Controls the LCD readout and switches that comprise FIRE Zone Monitor
the operator interface WATER SFPUMP WaterFlow Supervised Fire
• Controls the flash EPROM that contains the non-volatile Monitor pump
site-specific programming information HEAT Heat Detector S2STAGE 2 Stage Monitor
Sprinkler
• 4-Wire Smoke Detector Power provides a 5 second DUCT Duct Detector SO Normally Open
reset;rated 500 mA @ 24 VDC, open collector output, Sprinkler
and is power-limited and short circuit protected FLAME Flame Detector Sc Normally Closed
• Remote Unit Serial Interface(RUI)output provides PULL WSO Waterflow/
Sprinkler Open
connections for up to 16,Class B supervised remote Station Manual Pull
annunciators,Remote Control Unit(RCU)model SMOKE Smoke Detector WSC Waterflow/
Sprinkler Closed
4602-9102,or Status Command Unit(SCU)model EMERG Monitor-Fire SUPV Supervisory
4602-9101;(see additional description under Emergency Monitor
Accessories on page 5) Monitor-
SFIRE Smoke/Fire UTIL Utility Monitor
Power Distribution Board Features: Smoke/FireMonitor-Veri
• Provides connections for up to 5 plug-in module cards VFIRE Smoke/Pull TROUBLE Trouble Monitor
• Auxiliary power connections. Two power-limited SPULL Monitor-Smoke/Pull VSMOKE Verified Smoke
Detector
connections are provided,each rated for 2 A @ 24 VDC;
connections are isolated from NAC power VSPULL Verified GVMON Generic Verified
Smoke/Pull Zone
Power Supply/Battery Charger features: GENMON Generator LATSUPV Superyisory
Monitor Latching
• Switch Selectable for 120 or 240 VAC
SGENMON Supervisory STYLEC Monitor-Style C
• 24 VDC Power,regulated and power-limited, is Generator Monitor
available specifically for notification appliances and
auxiliary output use via two taps of 2 A each;rated 4 A VNIH94M . • •MIT mmm=
for Special Application Appliances and 2 A for
Regulated 24 DC power One,4 circuit NAC/Relay plug-in module is standard,
providing 4,Class B NACs that can be individually
• Internal System Operating Power is supplied via reconfigured for dry contact relay operation.
separate power-limited connections.
• Battery Charging for up to 18 Ah batteries mounted NAC operation is individually programmable as
within the 4005 cabinet and up to 33 Ah batteries when Steady Signaling,Temporal Pattern,March Time @
mounted in an external battery cabinet. 20 BPM,or March Time @ 120 BPM,and with the
following 17 operating modes(the abbreviated
• Function Monitoring. Includes: missing,depleted,and description is part of the NAC display information):
low battery, Earth fault detection,AC power loss,AC
power brownout(low input voltage),signal power Point Type Description Point Type Description
overload,supply voltage monitoring,and charger failure. SSIGNAL RWATER Fire Signal(On WaterFlow(On
• Depleted Battery Trouble Indication advises when until Silence) until Reset)
standby operation has exceeded battery capacity. Fire Signal(On Sprinkler
RSIGNAL until Reset) SUPV Supervisory
Internal DACT Module features: Signal
• Reports Alarm, Supervisory,Trouble,and AC Failure TSIGNAL until Clear)Trouble(On PRIMARY Elevator Capture
(primary
• Dual line operation with automatic 24 hour test and RSIGNAL Trouble(On Elevator Capture
programmable power fail report delay until ACK) ALTERN (alternate)
Visual(On until AHUR AHU Rela
Eight, Initiating Device Circuits (IDCs)features: SVISUAL Silence) y
• Two,4 circuit IDC plug-in modules are standard, RVISUAL Visual(On until gHUO AHU On Relay
providing 8, Class B IDCs Reset)
• Standard IDCs are low current and support up to 20 CODED Coded Signal AHUF AHU Off Relay
Simplex detectors per IDC at 2 mA maximum(for SIGNAL ISignal Circuit DHOLDER Door Holder
detectors with relay bases,use high current expansion SWATER WaterFlow(On
modules,see chart on page 7) luntilSilence)
CAnnc nnn� n �i�nnn
01MM FIM Ji • • -791 ell a el I rel11 • • - • .11 Ma O -�
NAC/Relay Selection. Each NAC can be on-site Typical Displays. Figure 2(below)represents typical
selected for NAC operation or for unsupervised, dry fire alarm display screens.For this example,the presence
contact,auxiliary relay operation. When operating in the of three fire alarm conditions is shown in the top screen—
relay mode,either the normally open or the normally fire zones 2, 7,and 6,displayed in chronological order of
closed contact can be connected to the output terminal occurrence(up to 10 zones may be shown). The display
block. Contacts are rated at 2 A @ 32 VDC, for transient will alternate with the one shown below it as the operator
suppressed loads. is prompted to assist with the next required action.
Relay Operation is individually programmable with the FIRE=3 SUPERVISORY=O TROUBLE=O
following 17 operating mode choices(the abbreviated FIRE ZONES: 02 07 06
description is part of the relay display information).
Relay Modes: FIRE=3 SUPERVISORY=O TROUBLE=O
Point Type Description Point Type Description CWF I REM* Press ACK to Review
RELAY Auxiliary Relay BRELAY Trouble Relay Figure 2.Typical 4005 Displays with Alarm Activity
(On until Ack)
PRIMARY Elevator Capture DHOLDER Door Holder
(Primary) • • 211111 r• • -
ALTERN Elevator Capture SVISUAL Visual(On until -
(Alternate) Silence) Operator Actions. The ALARM ACK,SUPV ACK, or
Visual(On until TROUBLE ACK key will silence the local tone-alert,
AHUR AHU Relay RVISUAL Reset) corresponding to the type of abnormal condition.
AHUO AHU On Relay CODED Coded Relay Subsequent entry of the appropriate ACK key will
Waterflow Relay chronologically scroll through the specifics for each
AHUF AHU Off Relay SWATER (On until abnormal condition. Screen information includes custom
Silence) labels for each zone that provides a detailed report of the
Fire Relay(On Waterflow Relay
SRELAY, until Silence) RWATER (On until Reset) location,device type description,device condition,and
RRELAY Fire Relay(On SUPV Supervisory list count for the first point in the Alarm, Supervisory,or
until Ack) Relay Trouble list.
TRELAY Trouble Relay(On Custom Label Display.Figure 3 represents a typical
until Clear) screen that would appear after using the ALARM ACK
key to scroll to the first fire condition. It displays the zone
location as"First Floor East Wing Room 12",the device
type as"Smoke Detector"and the device condition of
• 1 1 ' ' ' "Alarm".The 1/3 indicates that the displayed alarm is the
Display Indications. Upon receiving an abnormal first of three alarms present in the panel at this time.
condition of alarm, supervisory, or trouble,the 80 Site-specific labels can be upper or lower case and can
character backlit LCD will identify the quantity and type provide discrete annunciation that can assist fire response
of abnormal indications. With the locked door closed,the With clearly defined zone locations and device types.
display,status LEDs and primary operator switches are
visible through the transparent door viewing panel as
shown in Figure 1 below.This figure represents the LCD First Floor East Wing Room 12
during normal conditions showing normal status,time, Smoke Detector ALARM 1/3
and date.
Figure 3.Typical 4005 Fire Alarm Information Custom
Label Display
SYSTM IS MORM L Alarm Silence.The ALARM SILENCE key will
12:35: 15 as iED 11-MAR-99 silence the notification appliances programmed for
on-until-silence(typically audible notification appliances)
a and the ALARM SILENCED LED will remain
illuminated until the panel is reset.
E System Reset. When the source of the abnormal
condition is corrected,the SYSTEM RESET key will
Figure 1. Basic Operator Function Keys with Normal reset the panel and return the status to normal
Display of Status,Time, and Date
QAnAr nnnl 0 aiw%nn
X11 • . • - • • • - • • • • • • • •
SYSTEM IS NORMAL
12: 35: 15 a m WED 11-MAR-09
n ,�= A
Figure 4.The Complete 4005 Operator Interface
Level 1 is basic access and is available by unlocking the NOTE: During programming,monitoring remains active
door.Access includes the standard operator functions and and the 4005 will perform enabled responses.
historical log information. Programmable operations include:
Levels 2 and 3 are on-site programmable to control • Abort Enable;30 second delay allows zone status
functions required by local needs such as clock set, confirmation before enabling
enable/disable, WALKTEST system test,and custom • Alarm Cutout time delay
label changes. • Active Status Reminder(Alarm/Supervisory/Trouble
Level 4 access provides passcode programming of Resound every 8 hours)
critical life safety functions, access level programming, • Alarm Silence Inhibit Timer
and service level diagnostics and programming. . Assignment and selection of passcodes and access
levels
• Custom control equations
Unlocking the door provides access to the operator • Custom label generation and revision
control panel and reveals nine additional keys used for • Doorholder time delay(drop upon Alarm,drop upon
expanded operator functions and for circuit type and AC power loss)
programming selections(refer to Figure 4 above). • IDC circuit type(reference list on page 2)
The following expanded operator functions are available: • Module allocation and identification
Circuit Disable/Enable,available for each individual • NAC or Relay circuit type(reference lists on pages 2
and 3)
IDC,NAC,or relay circuit. . NAC/Relay output coding of: Steady Signaling,
WALKTEST Performance Testing allows a single Temporal Pattern,March Time @ 20 BPM,or March
fire alarm system tester to manually initiate remote alarms Time @ 120 BPM
and troubles and obtain a verification output from the • Setting of time and date, and selection of 12 or 24
NACs with an automatic Reset.Alarms are initiated to hour format
produce a pulse count that identifies the zone. With the _
zone number confirmed,troubles can be then initiated • •
with a common pulse output for a complete functional test The 4005 LCD provides menu driven prompts for
of each zone. performing functions.Navigating through the menu is
Indicator Test confirms that all panel LED and LCD easily performed by using the operator keys at the bottom
indicators are properly functioning. of the interface panel(see Figure 4 above).
History Logs provide up to 50 fire alarm logs and up to Menu always produces the main menu.
100 trouble logs. They are available for chronological Function provides a list of the available actions that can
review as fire,trouble,or fire and trouble combined. be performed depending on which programming or
functional area is being displayed.
(continued next page)
A CAnnr nnnl n 9/Onnn
Disable/Enable toggles status of the displayed circuit. • Two circuits, individually on-site selectable as either
Exit/Clear provides a path out of the chosen menu and Class B NAC, or N.O.or N.C.relay circuits
allows manual entries to be cleared. • Combined on one plug-in module
• Operation and programming is the same as the standard
Enter confirms the selection made and.enters program control panel IDCs and NAC/Relay circuits
changes into memory.
Left, Previous, Next, and Right arrow keys move the 4 Circuit IDC Module (4005-9804):
display cursor or select screens or specific choices, • Four,standard low current IDCs on one plug-in module,
depending on the displayed functional area. for up to 20 detectors per IDC,2 mA maximum
• • Operation and programming is the same as the standard
control panel IDCs
Class A,4 Circuit Adaptor Module for either IDCs 4 Circuit NAC/Relay Module(4005-9805):
or NACs (4005-9806): • Four,NAC/Relay Circuits on one plug-in module
• Individually isolated circuit design adapts either IDCs or • Operation and programming is the same as the standard
NACs for Class A operation allowing a combination of control panel NAC/Relay circuits
circuit types
• Mounts on top of the module,maintaining full module 8 Circuit I/O Module(4005-9808):
• Select each circuit as either an input or output
capacity
Power Distribution Module(4005-9807): • Input mode supervises hard wired connections to 4601
• Extends 4005 capacity to ten plug-in modules Series annunciator switches or utility switch inputs
• Mounts on left side of 4005 chassis • Output mode is rated 24 VDC, 150 mA open collector
Required when plug-in module requirements extend driver,short circuit protected,UL listed for pilot duty
•
beyond five and/or for connection of expansion power • Output mode provides supervised auxiliary control of a
supply 4005-9813 compatible annunciator or remote relay for emergency
City Circuit Module(4005-9809): control in accordance with NFPA 72 and NFPA 101
• Single circuit,selectable as local energy,reverse 4 Circuit IDC, High Current, Required for
polarity,or form"C"contact Detectors with Relay Bases (4005-9824):
• Reverse polarity is selectable for Alarm/Trouble,Alarm, • Four,high current IDCs on one plug-in module
Supervisory,or Trouble only reporting • High current operation for up to 30 detectors per IDC,
• Up to two modules mount directly to 4005 chassis below 3 mA maximum detector power(required for detectors
the CPU assembly with relay bases)
Expansion Power Supply (4005-9813): • Operation and programming is the same as the standard
• Provides power-limited and regulated 24 VDC to control panel IDCs
Expansion Module 4005-9807;rated 5 A for Special • -
Application Appliances and 2 A for Regulated 24 DC
4602 Series Annunciators:
power
• Installs on the left side of the 4005 chassis and fits • Supervised serial communications using twisted,
behind expansion modules,allowing full module shielded pair
capacity • SCU has 16 LED zone status indicators
• Switch selectable for 120 VAC or 240 VAC • RCU has 8 LED zone status indicators, Power-On LED
• Provides additional power for notification appliances, and Trouble LED, Local tone-alert,and keyswitch
4-wire detectors,annunciator power,or other fire alarm enabling of Trouble and Alarm Silence, System Reset,
auxiliary functions and Manual Evacuation
El 1 • 4601 Series Annunciators:
• Provides LED status indications and switches for
Optional and expansion modules can be easily installed and acknowledge,silence,and reset
programmed on-site.Their"snap-in-place"design installs • Modular design allows sizing as needed
without tools or hardware,allowing configuration for the
initial system capacity or for later system expansion. 4005-9150 and 4002 Adapter Kits for Retrofit:
2 Circuit IDC with 2 Circuit NAC/Relay • Replace existing 4002 Fire Alarm Control Panels with
(4005-9803): the 4005 panel features, supplied with high current IDC
modules for convenient retrofit
• Two,standard low current IDCs,for up to 20 detectors
per IDC,2 mA maximum • Cabinet,door,and electronics may be ordered separately
to satisfy early cabinet(backbox)installation
requirements
c QAnAr nnni n 'nnnn
K111141.1;=6 • - - • •.•- • •- • •-
., Category ModelDescription
Panel with 4005-9101* Beige cabinet 4005 Fire Alarm Control Panel; includes 8 standard IDCs,4 NAC/Relay
Cabinet circuits,4 A power supply/battery charger,cabinet and door, and internal Dual
4005-9102 d cabinet Line DACT with two RJ45 plug DACT Cables, 14 ft long(4.3 m)
*4005-9101C is the ULC English version;Ncutoe��a__tion.
F is the ULC French version;both 4005-9101C and 4005-9101 CF models delete the
Dual Line DACT and include low battery
Category Model De
Electronics Only 4005-9150 4005 Fire Alarm Control Panel, 8 high current IDCs,4 NAC/Relay Circuits,4 A power supply,
internal Dual Line DACT; requires 4002 Adapter Kit or separately ordered cabinet and door
4005-9806 Four Circuit Class A Adapter Module for IDC and/or NAC modules,standard or expansion;
mounts on top of plug-in IDC/NAC module;circuits convert either NAC or IDC, or combination
4005-9807 Additional Five Slot Power Distribution Module, required when plug-in Qty, 1 Max.
module count exceeds five, or for connection of Expansion Power Supply
Optional Modules 4005-9809** Single(1)Circuit City Module,chassis mounted, below CPU Qty, 2 Max.**
4005-9810** Internal Dual Line DACT;aftermarket add-on;for connecting to RJ31X Telco Qty, 1 Max.**
jacks, includes two DACT Cables with RJ45 Plug, 14 ft long(4.3 m)
Expansion Power Supply,24 VDC, 5 A, regulated; chassis mounted beneath
4005-9813 left side modules; requires 4005-9807 Power Distribution Module and Qty, 1 Max.
provides power to 4005-9807 only
** DACT module is standard equipment on 4005-9101 and 4005-9102.Operation allows for either a DACT module or one or two City
Connection modules.The DACT is programmed using a terminal or a laptop computer in terminal emulation mode.Connection and
programming details are provided with Installation Instructions 574-049.
Expansion 4005-9803 Standard Operation,2 Circuit IDC with 2 NAC/Relay circuits
Modules 4005-9804 Standard Operation,4 Circuit IDC Module
(capacity is 10 4005-9805 4 Circuit NAC/Relay Module
expansion slots, 3
expansion slots are 4005-9808 8 Circuit Programmable 1/0 Module
used in base panel) 4005-9824 4 Circuit IDC Module, high current operation,Class B, for detectors with relay bases
Cabinets 2975-9209 Beige 4005 Cabinet
2975-9210 Red 4005 Cabinet Order cabinets if required for pre-installation. 4005-9150
Electronics only model requires a cabinet and door or a 4002
Doors 4005-9857 Beige Door Adapter Kit.
4005-9858 Red Doo
Model Des ion Model Description
Batteries
select one model 2081-9272 4 W'Ah Battery, 12 VDC 2081-9288 12.7 Ah Battery, 12 VDC
number;two 2081-9274 10 Ah Battery, 12 VDC 2081-9275 18 Ah Battery, 12 VDC
required for 2081-9271 33 Ah Battery, 12 VDC; requires External Battery Cabinet 4009-9802
24 VDC system
power;see page 7 External Battery Cabinet,beige with solid door; includes battery harness; mounts close-nippled
for currents 4009-9802 to 4005 cabinet;for up to 33 Ah batteries;cabinet size:
25-3/4"W x 20-3/4"H x 4-1/8"D(654 mm x 527 mm x 105 mm)
4002 Adapter Kits 4005-9850 Two Unit
(for mounting 4005-9851 Four Unit 4002 Cabinet size Includes 4005 chassis adapter plate with beige retainer
4005-9150 panel
electronics into a 4005-9852 Six Unit
Simplex Model 4002
cabinet) 4005-9854 Four Unit 4002 Cabinet size, includes 4005 chassis adapter plate with red retainer panel
4081-9004 6.8 W, 1/2W, End-of-Line Resistor Harness for standard IDCs; (ref. 733-886)
4081-9002 3.3 ko, 1 W, End-of-Line Resistor Harness for high current IDCs; (ref. 733-893)
4081-9008 10 ko, 1/2 W, End-of-Line Resistor Harness for NACs; (ref. 733-894)
4081-9001 2.2 kQ, 1/2 W, End-of-line Resistor Harness for 8 Pt 1/0 input mode; (ref. 733-892)
4005 Accessory 4081-9007 1.2 kf2, 1 W, End-of-Line Resistor Harness for N.O.tamper switch monitoring; (ref.733-891)
Selection 4602-9101 Status Command Unit(SCU), 16 LED serial connection annunciator
Reference Remote Command Unit(RCU),8 LED serial connection annunciator with remote tone-alert and
4602-9102 control panel status LEDs, and switch control for Trouble and Alarm Silence,System Reset,
and Manual Evacuation(4602 Series Annunciators are available for multiple packaging
applications, for further information, refer to data sheets S4602-0001 and S4602-0004)
4601 Series LED/Switch Annunciators, modular design allows selection of required LEDs and control
switches(refer to data sheet S4601-0002)
c CAnnc nnn4 n 'IMM)n
• •
Electrical
{ Standard Panel Input(Switch Selectable) 102-132 VAC,60 Hz;2 A maximum
204-264 VAC, 50/60 Hz; 1 A maximum
Main Power Supply Output* 4 A for Special Application Notification Appliances
2 A for Regulated 24 VDC Notification Appliances
Expansion Power Supply Input(Switch Selectable) 102-132 VAC,60 Hz;3 A maximum
204-264 VAC,50/60 Hz; 1.5 A maximum
Expansion Power Supply Output* 5 A for Special Application Notification Appliances
2 A for Regulated 24 VDC Notification Appliances
NAC Operation, Per Circuit 2 A maximum
Simplex 4901,4903,4904,and 4906 Series non-addressable horns, strobes,
Special Application Appliances and combination horn/strobes and speaker/strobes(contact your Simplex
product representative for compatible appliances)
Regulated 24 DC Appliances Power for other applicable UL listed appliances; use associated external
synchronization modules where required
8 Circuit 1/0 Module Input Mode Dry Contact,supervised with 2.2 kQ end-of-line resistor 4081-9001
Output Mode 24 VDC, 150 mA,open collector
Relay Operation, N.O./N.C. 2 A @ 32 VDC
Resettable 4-Wire Smoke Detector Power 24 VDC,500 mA,open collector
Auxiliary Power Connections(two taps) 2 A; maximum each tap,power-limited; 18.7 to 32 VDC
Wiring Terminal Blocks Pluggable type,wire size is 18 to 12 AWG(0.82 mm2 to 3.31 mm2)
Wiring and
Environmental Operating Temperature 32° F to 120°F(0°C to 49°C)
Operating Humidity Range Up to 93%RH, non-condensing @ 100°F(38°C)
*NOTE: Power supply output currents listed are entirely available for NAC appliances and auxiliary equipment.4005 modules are
powered from separate circuits.See Field Wiring Diagram 841-990 and Installation Instructions 574-068 for additional detail.
Supv. Supv. Alarm Alarm
Module (mA) Quantity Total (mA) Quantity Total
4005-9101 &-9102t Includes 2,4005-9804&1,4005-9805 135 293
4005-9101C&CF t Includes 2,4005-9804&1,4005-9805 168 Sonet 328 Select one
4005-9150 t Includes 2,4005-9824&1,4005-9805 141 330
Separate Modules;Standard,Optional,and Expansion;see NOTES()below
4005-9806, Class A Adapter 1 x = 33 x =
4005-9807,Expansion Power Distribution Module 1 x = 1 x =
4005-9809, 1 Circuit Remote Station/City Connect 11 x = 22 x =
4005-9813, Expansion Power Supply 12 x = 12 x =
4005-9803,2 IDC, Low Current,and 2 NAC/Relay (1,2,3,4,5) 10 x = 34 x =
4005-9804,4 IDC, Low Current (1,2,3) 22 x = 57 x =
4005-9805,4 NAC/Relay (5) 8 x = 53 x =
4005-9808,8 Circuit 1/0 Module 1 x = 1 x =
4005-9824,4 IDC, High Current (1,2,4) 28 x = 94 x =
Internal DACT(aftermarket PID 4005-9810) (6) 35 1 x = 50 x =
Total,4005 Modules
t Standard panels and 4005-9150 include Total,4-Wire Detector Power + +
IDC loop currents for both supervisory Total,Other Auxiliary Power + +
and alarm. Total,Notification Appliance Power + +
Total Supervisory Current Total Alarm Current
NOTES:
1. IDC supervisory currents include loop currents of 2 mA/circuit for"low"current IDCs and 3 mA/circuit for"high"current IDCs.
2. IDC Alarm currents,add as required.Low current IDCs=13 mA/circuit;High current IDCs=50 mA/circuit.
3. Add 8 mA supervisory current per SC,WSC point used.
4. Add 10 mA supervisory current per SC point used.
5. Add 8 mA supervisory current per circuit if used as auxiliary relay and programmed for normally on.
& DACT Current is 50 mA when reporting.
7 cennc nnn4 n cionnn
Mounting Dimensions
Conduit knockouts are provided on top and bottom
Reference, 24"stud centers Knockouts are provided for
nailing. Two on each side and
Box width=22-1/2"(572 mm) one each on top and bottom.
onMa000aa0M0on'
Drywall markers indicate
1/2"(13 mm)depth,two
on each side
24"
(610 mm) Box includes an 0.048"
(1.2 mm)thick trim for semi-
flush mounting. Height and
width are same as door.
23"
(584 mm)
■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■ Y
MEMO Now*man NOME■■■■NOME NONE■Mr■■■■■
�IIF
23-3/8"(594 mm) 1/2„ 3-7/8"
(13 mm) (98 mm)
NOTE: A system ground must be provided for Earth Detection and transient protection devices.This connection
shall be made to an approved,dedicated Earth connection per NFPA 70,article 250, and NFPA 780.
JOVA
Tyco is a registered trademark of Tyco Inlernational Services GmbH and i.s used under license.Simplex the Simplex logo,LifeAlarm,and WAUTEST are Irademarks of Tyco
International Ltd and its affiliates and are used under license.NITA 70,Nl,PA 71,and National Fire Alarm Code are registered trademarks of the National Fire Protection
Association(NEPA).
f3 Simplex Tyco Safety Products Westminster•Westminster,MA•0 144 1-0001•USA S4005-0001-9 3/2009
® www.tycosafetyproducts-usa-wm.com
2'2009 Two Safely Products Wesnninster.All rights reserved All sneci0catirn7.s and ocher information.shown were current as ofdocument revision date and are.subiecl to chance withoutnotice.
0®Simplex Fire Alarm Control Panel Accessories
Listings* System Batteries, Sealed Lead-Acid; with Applications
Reference for Battery Cabinets, and Battery Cabinets with Charger
Rechargeable,sealed lead-acid batteries:
• Lead-calcium grid structure with immobilized
electrolyte in absorbent separator
• Low maintenance with no need to add water
• Low self-discharge characteristics
• One-piece, high impact polystyrene cell cover with high
reliability dual seal construction
• UL 924 recognized pressure relief valves
Available in a variety of capacities:
• Batteries for internal mounting range from 6.2 Ah up to
50 Ah,depending on control panel cabinet size
• Larger batteries,up to 110 Ah,mount in external battery
cabinets that are available with internal chargers
• Includes battery chargers with communications
compatibility for use with 4010 Series fire alarm control
panels and with 4100U Series fire alarm control panels
,i
Simplex rechargeable sealed-lead acid batteries provide Compatible Sealed Lead-Acid Batteries can be
reliable and repeatable discharge and recharge Installed Inside Fire Alarm Control Panel Cabinets
characteristics for use in fire alarm and other systems
applications. They are designed with immobilized
electrolyte in an absorbent separator,allowing them to
provide rated capacity on the first cycle.
Because of their sealed construction,packaging is allowed
within the system electronics enclosure(see illustration
on page 2). When this is applicable,the quantity of
system cabinets and the battery wiring distances are both
minimized. Where required,external battery cabinets can
be close-nippled to the control panel to house larger Remote Battery Cabinets are Available for
batteries with battery chargers available in some battery Larger Battery Requirements
cabinet sizes.
Charging.These batteries are intended to be used with Shipping. Sealed lead-acid batteries are shipped via
compatible Simplex battery chargers. ground or sea transportation only.They are not shipped
Series Connections.These batteries are required to be via air.
connected in series to produce 24 V system voltage. Disposal.Battery chemicals and materials can be
Battery sets must be of identical voltage,model number, recycled.Refer to information shipped with the battery or
appearance,and approximately the same date of on its case.Return to the battery manufacturer or to a
manufacture for proper operation. similarly qualified battery processing facility for proper
Testing. Battery capacity testing is recommended to be disposal.
performed by using a sealed lead-acid battery tester
designed to withdraw a minimum of battery charge.The * Refer to details on page 4 and to the referenced individual product data
preferred tester applies a variety of amplitude and sheets for agency listing status of battery cabinets and chargers.The batteries
duration controlled test pulses that compares terminal detailed in this document meet the requirements of UL,ULC,and Factory
Mutual for use with respective equipment battery chargers as listed on page 3.
voltage against those predicted for the specific battery Contact your local Simplex product supplier for proper battery selection per
size.(Testing is available through your local Simplex system requirements.Listings and approvals under Simplex Time Recorder
product supplier.) Co.are the property of Tyco Safety Products Westminster.
•
Actual appearance will vary with battery size.
Sealed outer cover
Quick connect or post type terminal Vent hole
(type varies with battery size) Potting material,black for
negative,red for positive
0 0 (polarity is also clearly
marked with+and-)
Pressure relief valve
Inner cover
Absorbent separator used
to immobilize electrolyte
Semi-permeable
Lead-calcium grids membrane separator
Cell group
Cell case(high impact
polystyrene)
FMUMIZTT •WMEM
Battery Model Capacity @ 20 Hour Width* Depth" Height with Approximate
Discharge Rate Terminals Weight"
2081-9272 6.2 Ah 6-1/8"(156 mm) 2-5/8"(67 mm) 4" (102 mm) 5.75 lbs(2.6 kg)
2081-9274 10 Ah 6"(153 mm) 4-1/16"(103 mm) 4"(102 mm) 9.2 lbs(4.2 kg)
2081-9288 12.7 Ah 6"(153 mm) 4"(102 mm) 4"(102 mm) 9 lbs(4.1 kg)
2081-9275 Ah 7-1/4"(184 mm) 3-3/8"(86 mm) 6-5/8"(168 mm) 14.3 lbs(6.5 kg)
2081-9287 25 6-5/8"(168 mm) 5"(127 mm) 7"(178 mm) 19.4 lbs(8.8 kg)
2081-9271 IV
(rectangular case, 33 Ah 12-1/2"(318 mm) 3-3/8"(86 mm) 7-1/16"(179 mm) 26.6 lbs(12.1 kg)
typically for service)
2081-9276
("square"case, 33 Ah 7-3/4"(197 mm) 5-1/4"(133 mm) 6-3/4"(171 mm) 26.5 lbs(12 kg)
use for new)
2081-9296 50 Ah 9-1/2"(241 mm) 5-1/2"(140 mm) 8-7/8"(225 mm) 41.8 lbs(19 kg)
2081-9279 110 Ah 11-3/16"(284 mm) 10-1/2"(267 mm) 9"(230 mm) 82 Lbs(37 kg)
Dimensions and weight are per battery and are for reference only. Exact size may vary. Refer to the tables on page 3 mounting
compatibility.These batteries are 12 V each and series connected for 24 V system use.
NOTE: When wired in series for 24 V output,these batteries are to be of identical voltage,appearance,model number,and
approximately the same date of manufacture.
• •
Nominal Voltage Rating 12 Volts per battery
Discharge Rating 20 Hour Rate
Typical Charge/Discharge Cycles 100 to 150
Preferred Charge Temperature Range 60° F to 90° F(15.6°C to 32.2°C)
creno, nnnc in ,nvmno
. . .
NOTE: Refer to individual fire alarm control panel product data sheets for additional battery application information
Battery Simplex Control Panel Model Series(see legend and notes below)
Model Capacity
4006& 4009 4100&4120 4020
4003 4004 4004R 4005 4010 41000
4008 (all models) (2,4 or 6-Unit) (2,4 or 6-Unit)
2081-9272 6.2 Ah ✓ J J ✓ J J J 1,2,or 3 bay ✓ J
2081-9274 10 Ah ✓ J ✓ J J J ✓ 1,2,or 3 bay ✓ we
2081-9288 12.7 Ah J NA J ✓ ✓ J J 1,2,or 3 bay ✓ ✓
2081-9275 18 Ah J NA Note 3 ✓ Ext Ext Note 2 1,2,or 3 bay ✓ J
2081-9287 25 Ah NA NA Note 3 Ext Ext NA J 1,2,or 3 bay ✓ Ext
2081-9271 33 Ah NA NA Note 3 Ext NA NA Note 3 1,2,or 3 bay Ext Note 4
(rectangular)
2081-9276 33 Ah NA NA Note 3 Ext NA NA Note 3 1,2,or 3 bay J Ext
("square')
2081-9296 50 Ah NA NA Note 3 NA I NA NA Note 3 2 or 3 bay Ext Ext
2081-9279 110 Ah Requires external battery cabinet
✓ =Can be placed in the respective equipment cabinet
Ext=External battery cabinet is required, refer to selection chart on page 4
NA=Not applicable/not compatible
NOTES:
1. These batteries meet the requirements of UL, ULC,and Factory Mutual for use with respective equipment battery chargers
listed above. Contact your local Simplex product supplier for proper battery selection per system requirements.
2. 4010 Cabinets will accommodate 2081-9275, 18 Ah batteries,but will not allow bottom entry conduit.
3. Use 4081 series companion cabinet and charger, refer to page 4.
4. 4020 Cabinets will accommodate 2081-9271, 33 Ah batteries,but will not allow bottom entry conduit.
5. Some control panel models are listed for battery replacement reference only.
. . .
Battery Cabinets without Chargers (connects to charger in panel)
2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279
Cabinet Panel Compatibility 18 Ah* 25 Ah Rectangular 33 Ah Square 33 Ah 50 Ah 110 Ah
2081-9270 multiple ✓ ✓ J ✓ ✓ NA
2081-9280 41000/4100+ NA NA NA NA NA V
2081-9281 multiple J J ✓ J J NA
2081-9282
4009-9801 multiple ✓ ✓** NA NA NA NA
4009-9802 multiple ✓ NA ✓ NA NA NA
Battery Cabinets with Chargers
2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279
Cabinet Panel Compatibility 18 Ah* 25 Ah Rectangular 33 Ah Square 33 Ah 50 Ah 110 Ah
4081-9301 4004R and 4010 ✓ J J J J NA
4081-9302
4081-9306 41000 NA NA NA NA ✓ ./
4081-9308
*Batteries smaller than those listed are normally mounted in the product cabinet
**25 Ah capacity was effective as of 7/2005.
J=Can be placed in the respective equipment cabinet
NA=Not applicable/not compatible
� c�no� nnna �n ani�nno
Battery Cabinets Without Chargers; Shallow Design with Front Door
Model Color Listings Description Dimensions
2081-9281 Beige UL and 2-Unit, 4100 style cabinet without charger;with locking 25-3/4"W x 20-3/4" H x 6-3/4"D
FM solid door and battery shelf,primarily for use with 50 Ah (654 mm x 527 mm x 171 mm)
2081-9282 Red batteries
UL and For up to 25 Ah External battery cabinet without charger, 16-1/4"W x 13-1/2" H x 5-3/4" D
4009-9801* Beige FM batteries* 413 mm x 343 mm x 146 mm
with locking solid door and battery ( *)
TI For up to 33 Ah harness;for close-nippled mounting to 25-3/4"W x 20-3/4"H x 4-1/8" D
4009-9802 Beige UL batteries fire alarm control panel cabinet (654 mm x 527 mm x 105 mm)
*Depth increased for 25 Ah batteries effective 7/2005.
Battery Cabinet Without Charger; Deep Design with Hinged Lid
Model Color Listings Description Dimensions
2081-9270 Red Not listed Battery cabinet without charger; cabinet has vented front, 26-1/2"W x 12" H x 12"D
and hinged lid with support rod and lock on top (673 mm x 305 mm x 305 mm)
Chargers for use with 4010 Fire Alarm Control Panels and 4004R Suppression Release Systems
(refer to data sheet S4081-0001)
Model Color Input Voltage Description Dimensions
4081-9301 Beige Battery cabinet with charger for the 4010 and
4004R fire alarm control panel;for up to 50 Ah
120 VAC batteries;with front door (572 "W x425 m"H x 8-3/8" D
4081-9302 Red
Listings include:UL, ULC, FM, CSFM, and MEA (572 mm x 425 mm x 213 mm)
(NYC), see data sheet for details
Battery Cabinet Without Charger for 110 Ah Batteries; for use with compatible panel mounted chargers
(refer to data sheet S2081-0012)
Model& Compatible
Color Cabinet Description Charger Description Dimensions
Listings Chargers
4100-9xxx 41000 System Power Supplies
Series (SPS)
4100-5111
Battery cabinet for 4100-5112 41000 Additional SPS
2081-9279, 110 Ah 4100-5113
2081-9280 batteries; includes 4100-5125 41000 Remote Power Supply
Listings Red 80 A battery fuse, 4100-5126 (RPS) 26-1/2"W x 12" H x 12"D
include: UL terminals and 4100-5127 (673 mm x 305 mm x 305 mm)
and CSFM battery connection 4100-5120
cables; see data 4100-5121 41000 TrueAlert Addressable
sheet for details 4100-5122 Power Supply(TPS)
4100-0104
4100-0114 4100 Legacy power supplies
4100-0124
41000 Compatible Battery Cabinet With Charger for 110 Ah Batteries(for ULC listed systems and for other
applications unable to use panel mounted power supply charger; refer to data sheet S4081-0002)
Model Color Input Voltage Description Dimensions
4081-9306 Red 120 VAC Battery cabinet with charger for up to 110 Ah
batteries;
NOTE: Required for ULC listed charging of 27-7/8"W x 13-1/2" H x 14-5/8"D
4081-9308 Red 220/230/240 VAC, 110 Ah batteries;Listings include:UL, ULC, FM, (708 mm x 343 mm x 371 mm)
multi-tapped CSFM, and MEA(NYC), see data sheet for
details
4100-9837 Green LED Power-on Indicator Kit, required for ULC listing,mounts above access panel using knockout provided
Tyco is a registered trademark of Tyco International Services GmbH and is used under license.Simplex,and the Simplex logo are tradmarks of Tyco International Ltd and its
affiliates and are used under license.
£3Tyco Safety Products Westminster-Westminster,MA-01441-0001-USA S2081-0006-19 10/2008
,,Simplex www.tycosafetyproducts-usa-wm.com
F:2008 Two Rafeir Products Westminster All ris'ht s reserved All snecifications and other information.shown were current as ofdocument revision date and are subject to chance without notice.
S®Simplex TrueAlarm Smoke Detectors
UL, ULC Listed; FM, CSFM, TrueAlarm Photoelectric Smoke Detectors
and MEA (NYC) Approved* for Two-Wire and Four-Wire Bases
r
Photoelectric smoke detector with on-board
TrueAlarm sensitivity drift compensations
UL listed to Standard 268
Functional chamber enclosure:
•
Louvered design enhances smoke capture by
directing flow to chamber
• Entrance areas are minimally visible when ceiling
mounted 4098-9601 TrueAlarm Photoelectric
Detector Mounted in Base
Multi-function indicator LED indicates normal
and alarm conditions 040
Magnetically operated functional test:
• Initiates alarm and verifies performance
• Identifies general sensitivity status using detector "I"s
•
LED
Voltage 15 to 32 VDC from Fire Alarm Control
Models available in two sensitivity settings: Panel IDC
• 4098-9601, Standard Sensitivity, nominal 2.8%/ft Standby Current 100 A @ 24 VDC
obscuration Up to 86 mA maximum,exact current is
• 4098-9605,Special Application Sensitivity, Alarm Current,2 Wire Operation determined by alarm current limiting of nominal 3.5%/ft obscuration connected IDC
Alarm Current,4-Wire 24 mA t 24 VDC
Available base options: Operation typical °�
• Bases for 2-wire or 4-wire operation Auxiliary Relay Ratings Refer to page 2 under Product Selection
• Auxiliary alarm relay output Air Velocity Range 0-2000 ft/min(0-610 m/min)
Optional remote alarm indicating LED UL Listed Temp.Range 32°to 100°F(0°to 38°C)
Operating Temp.Range 15°to 122°F(-9°to+50°C)
• • Humidity Range 10%to 95%RH from 32°to 122°F
PTE (0°to 50°C)non-condensing
Simplex TrueAlarm photoelectric detectors Color Frost White
provide many of the proven TrueAlarm analog sensing 4-7/8"Dia.x 1-7/8"H,mounted in base
features for applications where detectors are connected to Dimensions (124 mm x 48 mm);refer to page 3 for
conventional 2-wire or 4-wire initiating device circuits detail
(IDCs). Each TrueAlarm detector has an on-board
microprocessor that evaluates its photoelectric light
scattering chamber activity and makes an intelligent
decision based on light obscuration history as to whether
an alarm condition is present.
ULC listed models are designated with a"C°suffix such as 4098-9601C.This product has
TrueAlarm detectors are packaged in a patented been approved by the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of
housing that minimizes the visibility of the air intake the California Health and Safety Code.See CSFM Listing 7272-0026:219 for allowable
values and/or conditions concerning material presented in this document.It is subject to re-
louvers from the normal viewing locations while examination,revision,and possible cancellation.Accepted for use-City of New York
maintaining a high performance smoke capture ability Department Department of Buildings-MEA35-93E.Additional listings may be applicable;contact your
Bases are available for remote alarm LED indicator local Simplex product supplier for the latest status.
connections and auxiliary relay outputs. 1 TrueAlarm smoke detector operation is protected by one or more of the following U.S.
Patents:5,155,468;5,173,683;5,400,014;5,543,777;5,710,541;D383,407;D388,352;
D392,573.
S4098-0015-5 10/02
Intelligent Data Evaluation. Conventional smoke directly into alarm with the magnetic test.If there is an
detectors will typically drift toward being too sensitive off-normal condition,the LED pulses first to indicate the
due to the accumulation of dust and dirt. With TrueAlarm condition and then goes into alarm.(See page 3.)
analog detection, data from the photoelectric chamber is . • . •
monitored and analyzed at the detector to provide a
continuously shifting reference point. Detector Locations.Locations should be determined
Drift Compensation.The data evaluation and its only after careful consideration of the physical layout and
shifting reference point provide a software filtering contents of the area to be protected. Refer to NFPA 72,
the National Fire Alarm Code.On smooth ceilings,
process that compensates for environmental factors(dust, smoke detector spacing of 30 ft(9.1 m)may be used as a
dirt,etc.) and component aging,establishing an accurate
reference for evaluating new activity. With this guide. For detailed installation information,refer to 4098
filtering, Detectors, Sensors, and Bases Application Manual
the resulting drift compensation provides a significant (574-709).
reduction in the probability of false or nuisance alarms
caused by shifts in sensitivity—either up or down. Sensitivity Selection.The 4098-9601 standard
sensitivity detector is recommended for most applications.
Magnetic Test Information. Status information is When a special application for a reduced sensitivity
available by performing the magnetic test and observing
the detector LED pulses.The LED will normally go detector is required,the 4098-9605 should be considered.
Consult your local Simplex product supplier for
assistance in determining the proper selection.
. • Iloilo
Smoke Detector
Model cription Nominal Sensitivity Compatibility
4098-9601 2.8%/ft(standard) Compatible with bases:4098-9788,4098-9682, and
TrueAlarm Photoelectric Detector
4098-9605 3.5%/ft 4098-9683
Compatible Bases
Model Description Details*
4098-9788 2-Wire Base with connections for IDC and LED connections are screw terminals for in/out wiring,
Remote Alarm LED Indicator 18 to 14 AWG
14
re Base with Auxiliary Alarm Relay Ratings,Single Form"C",For Suppressed Loads:
Rel ontacts and connections for Power limited, 3 A @ 28 VDC; Non-power limited, 3 A @ 120 VAC
4098-9682 Remot D Alarm Indicator Wiring Connections(In/Out where required):
op ti Re s external 24 VDC for Relay contacts and IDC wiring, color coded 18 AWG leads;
operation
LED wiring,screw terminals for 18 to 14 AWG
2-Wire Base with Auxiliary Alarm Relay Ratings,Dual Form"C",For Suppressed Loads:
Relay&connections for Remote LED Power limited, 1 A @ 28 VDC; Non-power limited, 1/2 A @ 120 VAC
Indicator
4098-9683
N.aTF:Must be connected as the only Wiring Connections(In/Out where required):
device on the IDC to ensure relay Relay contacts and IDC(-),color coded 18 AWG leads;
operation. IDC(+)and LED wiring,screw terminals for 18 to 14 AWG
Detector Accessories
Model Description Details*
Required for mounting to surface mounted 4"(102 mm)square or
4"octagonal boxes, and to 4"square flush mounted boxes
4098-9832 Adapter Plate May be used when retrofitting existing bases
Compatible with detector bases 4098-9788, -9682, &-9683
4098-9830 Remote LED Indicator Mounted on single gang stainless steel plate
2098-9739 Encapsulated Dimensions:2-1/2"x 1-1/2"x 1" Required for 4-wire circuits using
24 VDC (64 mm x 38 mm x 25.4 mm) 4098-9682 base,one per circuit;select
End-of-Line Relay Mounted on single gang mounting type as required;wiring is
2098-9735 Plate Mounted stainless steel plate color coded 18 AWG wire leads
*Refer to paqes 3 and 4 for dimensions and additional mountinq details; 18 AWG=0.82 mm2; 14 AWG=2.08 mm2
2 S4098-0015-5 10/02
LED Indication Status
Pulses approximately every 4 seconds Normal
Steady On Alarm
LED Response to Magnetic Test
LED Indication Followed By Status Action
LED turns ON Alarm is initiated Normal,sensitivity is within None
compensation range
LED pulses quickly,
6 times in 3 seconds, Alarm is initiated. More sensitive,out of normal
then turns ON compensation range Cleaning or other
service is required
LED pulses slowly, Alarm is initiated Less sensitive,out of normal
4 times in 8 seconds, compensation range
then turns ON Does not initiate Alarm Detector is malfunctioning I Service is required
Testing requires placing a magnet at the designated location on the detector cover for 4 seconds.Refer to Application Manual 574-709 for
further test and maintenance information.
1/4"
(6.4 mm) 6-3/8"(162 mm)
I�
4098-9832 Adapter Plate
4-7/8"(124 mm) _l
Base height 1-7/8"
11/16" (48 mm)
(17 mm)
LED Status Indicator
(with clear lens)
4098-9601 &-9605 Dimensions Mounted on Base
0
ALARM
0
,00W 113SImplex
4098-9830 Remote LED Indicator(not to scale)
3 S4098-0015-5 10/02
Mountina Information
(Electrical boxes are supplied by others.)
Electrical Box Requirements:
Without relay(base 4098-9788):
4"octagonal or 4"square, 1-1/2"deep
Single gang, 2"deep
Wither lay(bases 4098-9682 and 4098-9683):
4"octagonal, 1-1/2"deep,with 1-1/2"extension ring
4"square, 1-1/2"deep,with 1-1/2"extension ring
Surface mount reference
4"(102 mm) 4" (102 mm)
square box 0octagonal box
-- +-- ------ -------- ------ --
1-1/2"(38 mm) Flush mount reference, mount even with final
minimum box depth surface, or with up to 1/4"(6.4 mm) maximum recess
4098-9832 Adapter Plate, required for mounting
to surface mounted boxes and to 4"square flush mount boxes
4098-9682 and 4098-9683
include a relay module that
mounts in base electrical box
Smoke Detector Bases
4098-9788,9682,&-9683
4098-9601,-9605 Smoke Detector
Tyco,Simplex,the Simplex logo,and TrueAlarm are Trademarks of Tyco International Services AG or its affiliates in the U.S.and or other countries. NEPA 72 and National Fire
Alarm Code are registered trademarks of the National Fire Protection Association(NFPA).
13®Simplex TEPG-US•91 Technology Drive•Westminster, Massachusetts•0 144 1-0001•USA S4098-0015-5 10/02
t)2002 77,TG-11S(a Tyco company).All rights reserved All specificalions and other information www.tepg.com
shown were current as of document revision date and are suhiect to change without notice.
PRODUCT INFORMATION 4098-9788 2 WIRE BADE WITH OMOKE DETECTORO AND REMOTE LED OUTPUT
FEATURES: 4'X 1 1/2'DEEP OCTAGONAL
•UL LISTED TO STANDARD 268 4'SQUARE X 1 i/2-DEEP WHICH REQUIRES
D14 IN1iC/D T�OpR C A 4098-9832 ADAPTER PLA1E (6 3/8 X 1/41
- ICA
DSE ES giLEDADIAGNOSTIC INF TION FOR BOX SUPPLIED BY CONTRACTOR O
- IDE FI DIRTY DETECTORS.ASSISTING WITH O
IIW pp� HIE PPgRIORITIES
•ACTIO REDCDESIG RE QRS E CAPTURE DETECTOR HEADS O
BY 6TECT FL 4098-9601 PHOTOELECTRIC STANDARD (2.8%)SMOKE DET TOR
- C�TRANC I6Nl Y VISIBLE tyliEN 4098-9602 PHOTOELECTRIC�(RH TRUE PHOTOELECTRIC/THERR DETECTgN ® Q
•MAGNETICALLY OPER FPo TpNAL ST E 4098-9603 IOI"gZAT10N )D SVO E
Liu
N yE fyE 4098-9605 PHOTOELECTRIC (3 6%) SMOKE DETECTOR
- IDE
DETECTOR
GENERAL SENSITIVITY STATUS DETECTOR LED
•DETECTOR MODELS AVAILABLE NOi S1ETrylT1 SETTINGS'
- 4908-9606 9601.SPEGAL APPRATIO
UCA�SENSITIVMALTY2. II L�6%/FT URATION
- 4098-9603 IO4IZATXN4 DETECTOR
•MOUNTING: CEAING OR WALL
•COLOR. FROST WHITE
FLUSH MOUNTING
SPECIFICATIONS: (BOX TO BE FLUSH OR RECESSED 1/4'MAXIMUM).
VOLTAGE:
TO 32 yDC
: IPU RIPPLE VOLTAGE 25X MAX
CURRENT: 86 mA O 24 yDC
CSURGE STANDBY URRENT:2 OtA O 2�
. AIR VELOCITY RANGE:Q-2000 Fr IN (0-610 0/04)
• ALTITUDE:8.00Q FT, (2438m)
• UL LISTED TEMPERATURE RANGE: 37F TO 100'F
• OPERATING TEMPERATURE RANGE 1liF TO 122f
OPERATING TEMPERATURE RANGE Ty/4098-9602: 15'F TO 100'F - - - - - - - -
HIDITY 10%TO 96% RH
• D NSIONS LTH HEAD: 4 7/8'0 X 1 7/8'H
DESCRIPTION:
TRUPHOTOELECTRIC DETECTORS PROVIDE MANY OF THE PROVEN
TRUEkAR ANALOG SENSING FEATURES FOR APPLICATIONS (HERE
DETECTORS ARE CONNECTED TO CO NT104AL INITIATING
VICE c�clnn poc:). EACH TRU DETECTOR HAS AN o4-BOARD
IIUC ESSOR THAT EVA,, TES ITS PHOTOELECTRIC LIGHT SCATTERING '
CHAMBER FOR ACTMTY AND�IAICES AN 1NTE T DECISION BASED ON LIGHT o
OBSCURA 4 HISTORY AS TO J�HETHER AN�CONDITION IS PR r
TRIkAtAR�I DETECTORS ARE PACKAGED IN A PATEN ED NG THAT INIMIZES I ° 0,
THEN uTr OF THE AIR INTAKE �H1yERS THE NOR VIEWING LOIiAT1pNS ° °
WHILE MAINTAINING A HIGH PERFORMANCE OKE CAPTURE LITY.
OPTIONS:
4098-9830: REMOTEALARM INDICATOR. PROVIDES A
REMOTE RED ALARM LED STATUS INDICATOR MOUNTED � I TO ADDITIONAL INfTWTINGp�yIC ES
ON A SINGLE GANG STAINLESS STEEL PLATE. F PREyIOUS� �� + OR RETURN TARE ALARA CONTROL
E PAN%L FQR TYLE APICA APPLICATION
WIRING: FIR ALAR S— _ � _ _ _ J � _ _ _ _ I _ J � _ _ _ — �CIRCU T I�NIITA 4 G E APPL TIO
1. ALL ONG TO COMPLY WITH LOCAL CODE. CONTROL PANEL - _ �N �� 3
2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS I (�EFEkE TO�IRIH-OD-U SE OVIDED
3. MAINTAIN CORRECT POLARITY FOR 4098-9830 REMOTE ALARM LED IVITH THE SYSTE P EL OR PROPER
4. REFER TO INSTALLATION INSTRUCTIONS 574-706 D-OF-LINNEE R SIST VALUES.
N ( )
5. REFER TO AM CAT04 MANUAL (574-709) TO REMOTE LED
6. BREAK RES BEFORE CO ECTI TO TERMINAL 4
RM -
1�h NN NG NAL 4098 9830 (IF USED)
7. TO MAINTAIN SUPERVIS04 DO NOT LOOP WIRE UNDERNEATH TERMINAL 4. SEE NOTE 13
S®Simplex Non-Addressable Initiating Peripherals
UL, ULC, CSFM Listed; FM Approved, Electronic Heat Detectors
MEA (NYC) Acceptance* for Two-Wire and Four-Wire Bases
1179
o
Accurate and reliable heat detection for
protection of property** t<`
UL listed to Standard 521 as a rate compensated
heat detector �� '�
Fixed temperature operation is suitable for most
applications:
• Thermistor based design is inherently rate
compensated due to minimal thermal lag
• Available for 135° F(57°C)or 200° F(93°C) Electronic Heat Detector Mounted in Base
• UL and ULC spacing distance is 70 ft(21.3 m)
Available with rate-of-rise temperature detection:
• Dual thermistor rate-of-rise operation • -•
• For use where anticipated ambient temperature Rate-of-rise detection is determined by comparing
changes are less than 6° F/minute(3.33°C/minute) two thermistor responses. By combining accurate
;poxy
UL and ULC spacing distance is 70 ft(21.3 m) thermistors with proper physical placement,this patentedt
rate-of-rise detection design achieves a high level of
encapsulated electronic design provides: performance not normally available with mechanical
• Easily tested,self-restoring operation with repeatable detection.
accuracy
• Alarm indicating LED located on detector
• Current limited alarm that is compatible with 15 to 32 VDC(filtered DC with 30%
Voltage PP le
two-wire initiating device circuits(IDCs) maximum ripple)
• Designed for EMI compatibility Standby Current 80 pA typical, 100 pA maximum
Optional remote alarm indicating LED Alarm Current,2-Wire Up to 86 mA maximum,exact
Operation current is determined by alarm
Available base options: current limiting of connected IDC
• Bases for 2-wire or 4-wire operation Alarm Current,4-Wire 24 mA typical @ 24 VDC
Operation
• Auxiliary relay output(refer to selection chart on
Meets FM requirements for
page 2 for relay ratings) Rate-of-Rise Operation operation between 15°and
• Remote alarm indicating LED output 25° F/min(8.33°and 13.88°C/min)
10%to 95%RH from 321 to 122°F
9 . 9 Humidity Range (00 to 50°C), not intended for
outdoor applications
Accurate Electronic Design.Simplex electronic Color Frost-White
heat detectors use a fast response,thermistor based design
to provide temperature sensing that quickly,accurately, Dimensions Refer to diagram on page 3
and consistently identifies when fixed temperatures are Ambient Temperature Operating Range
exceeded. The fixed temperature sensing thermistor 135° F Models 132°to 100° F(0°to 38°C)
readily tracks the local ambient temperature.This 200° F Models 32°to 150° F(0°to 66°C)
eliminates the time required to melt a lead pellet or heat a
bimetallic element as occurs in mechanical heat detector
designs and provides the required heat detection for most **WARNING: In most fires, hazardous levels of smoke
applications. and toxic gas can build up before a heat detection
device would initiate an alarm. In cases where Life
This product has been approved by the California State Fire Marshal(CSFM)pursuant to Safety is a factor,the use of smoke detection is highly
Section 13144.1 of the California Health and Safety Code,See CSFM Listing recommended.
7270-0026:221 for allowable values and/or conditions concerning material presented in this
document.It is subject to re-examination,revision,and possible cancellation.Accepted for
use—City of New York Department of Buildings—MEA35-93E.Additional listings may be
applicable,contact your local Simplex product supplier for the latest status.Listings and t Simplex electronic heat detector design is protected by U.S.Patent Numbers 5,450,066
approvals under Simplex Time Recorder Co.are the property of Tyco Safety Products and D377,460.
Westminster.
M. - • . - memr,
Heat detectors are used where property protection is desired 135° F(57° C)fixed temperature detectors are for
and where life safety protection is not required or is normal temperatures that do not exceed 100°F(38°Q.
perfonned by other equipment.Typical heat detector 200° F (93° C)fixed temperature detectors are for
applications are satisfied by use of these fixed temperature
electronic detectors. normal temperatures that exceed 100°F(38°C)but are
less than 150°F(66°Q.
The addition of rate-of-rise operation provides two forms of _
heat detection for use where temperature fluctuations are • • • •
controlled and are less than 6°F/min(3.33°C/min). Where When connecting these electronic heat detectors to a
temperatures may fluctuate more quickly,use fixed 2-wire initiating device circuit(IDC)that is providing
temperature detection. Alarm Verification for smoke detectors,use the
Refer to NFPA 72®,the National Fire Alarm Code'and 4098-9682,4-wire base. The 4-wire base provides an
publication 574-709,4098 Detectors, Sensors, and Bases alarm contact that is not current-limited.(Heat detectors
Application Manual,for additional guidance in applying in the 2-wire base present a current-limited alarm
and locating heat detectors. condition that is not compatible with Alarm Verification.
Initiating devices other than smoke detectors are required
V-11 F771-11 • • • • - • to activate the alarm without starting the alarm
The heat detector LED turns ON continuously when in verification cycle.)
alarm. During normal conditions the LED is OFF.
110M Ron I'm
FixedFM Ratings
Model Temper a Rate-of-Rise Operation RTI UL&ULC
Oper n at Maximum Spacing (Response Time Index) Maximum Spacing
4098-9612 1 (57°C) Not applicable 20 ft x 20 ft Quick
4098-96140° F(93°C) (6.1 m x 6.1 m)
low
4098-9613 135° F(57°C) 20 ft x 20 ft Quick 70 ft x 70 ft
21.3 m x 21.3 m
Between 15°&25° F/min (6.1 m x 6.1 m) ( )
4098-9615 200° F(93°C) (8.33°& 13.88°C/min) 50 ft x 50 ft Ultra Fast
(15.2 m x 15..2 m)
Model Description Connection Details
4098-9788 2-Wire Base, no options IDC connections Screw terminals for in/out wiring, 18 to 14 AWG
Wl ire Base with IDC connections Screw terminals for 18 to 14 AWG for in/out wiring of zone(+),
4098-9684 co ction for remote LED color coded 18 AWG leads for in/out wiring of zone(—)
alar dicator LED connections Color coded 18 AWG leads
Relay Operation Type Relay Ratings
2-Wire Bas ith auxiliary Power-limited 1 A @ 28 VDC
alarm relay o ut Nonpower-limited 3 A@ 120 AC Dual Form"C"contacts,for suppressed loads
4098-9683 NOTE: Must be connected Output Type Wiring Connections
as the only device on the Screw terminals for 18 to 14 AWG for in/out wiring of zone(+),
IDC to ensure relay IDC connections color coded 18 AWG leads for in/out wiring of zone(—)
operation.
Relay connections Color coded 18 AWG leads
Relay Operation Type Relay Ratings
Power-limited 3 A @ 28 VDC Single Form"C"contacts,for suppressed
4-Wire Base with auxiliary Nonpower limited 3 A @ 120 AC loads
alarm relay output Output Type Wiring Connections
4098-9682
NOTE: Requires separate IDC connections Color coded 18 AWG leads for in/out wiring
24 VDC power. Relay connections Color coded 18 AWG leads
Power connections Screw terminals for 18 to 14 AWG for in/out wiring of power(+),
color coded 18 AWG leads for in/out wiring of power(—)
Metric wire equivalents: 18 AWG=0.82 mm2; 14 AWG=2.08 mm2
7 CAnn4 nn9 A 0 7/7nnO
40' Description Details Base Compatibility
Required for surface or semi-flush mounting to 4"(102 mm)square 4098-9682
electrical box or for surface mounting to 4"octagonal box 4098-9683
4098-9832 Adapter Plate 4098-9684
May also be used when retrofitting to replace existing larger diameter 4098-9788
bases
4098-9830 Remote Red LED Mounted on single gang stainless steel plate,wiring connections are 4098-9684 only
Alarm Indicator 18 AWG color coded leads
2098-9739 End-of-Line Relay Epoxy
o18 AWG encapsulated
or odes Bads VDC operation,wiring connections For 4-wire IDCs
are using 4098-9682
Mounted on single gang stainless steel plate, 24 VDC operation, base,one per
2098-9735 End-of-Line Relay wiring connections are 18 AWG color coded leads circuit
Metric wire equivalent: 18 AWG=0.82 mm2
6-3/8"(162 mm)
�- 4098-9832 Optional Adapter Plate
1/4 (required for surface or semi-flush mounting to 4"(102 mm)
(6.4 mm) square box or for surface mounting to 4"octagonal box)
r 4-7/8"(124 mm) -�
2-3/8" Base Height
(60 mm) 11/16"(17 mm)
LED Status Indicator
B
ALARM
O
O Simplex
B
4098-9830 Remote Red LED Alarm Indicator(not to scale)
0Ann0 nnIA 0 oionno
. . .
Base Electrical Box Requirements The following table provides a reference for the
4"(102 mm)octagonal or 4"square box, maximum rectangular area covered for detectors rated
4098-9788 1-1/2"deep(38 mm) with the given spacing. For additional information,
Single gang box,2"deep(51 mm) including consideration of ceiling height,refer to
NFPA 72,the National Fire Alarm Code.
4098-9682 4"octagonal or 4"square box,
4098-9683 1-1/2"deep with 1-1/2"deep extension ring Maximum Rectangular Area Dimensions
4098-9684 (see diagram below) for Single Detector Coverage
20 ft Rated 50 ft Rated 70 ft Rated
Spacing(6.1 m) Spacing(15.2 m) Spacing(21.3 m)
20ftx20ft 50ftx50ft 70ftx70ft
4"(102 mm)octagonal or square box (6.1 m x 6.1 m) (15.2 m x 15.2 m) (21.3 m x 21.3 m)
Surface mount reference 15 ft x 23.9 ft 45 ft x 54.5 ft 65 ft x 74.6 ft
(4.5mx7.2m) (13.7 m x 16.6 m) (19.8 m x 22.7 m)
010 ftx26.4ft 40ftx58.2ft 8.3mx0 ft x 4
r�\ 7 ft
(3mx8m) (12.1mx17.7m) (18.32m)
/�l
5ftx27.8ft 35ftx61.4ft 55ftx82.3ft
(1.5mx8.4m) (10.6 m x 18.7 m) (16.7mx25m)
1-1/2"(38mm) f 1 ftx28.2ft 30ftx64ft 50ftx85.4ft
minimum box depth Flush mount reference,mount (0.3 m x 8.5 m) (9.1 m x 19.5 m) (15.2 m x 26 m)
even with final surface,or with up 25 ft x 66.1 ft 45 ft x 88.1 ft
to 1/4"(6.4 mm)maximum recess (7.6 m x 20.1 m) (13.7 m x 26.8 m)
20ftx67.8ft 40ftx90.5ft
(6.1 mx20.6m) (12.2 m x 27.5 m)
15ftx69ft 35 ftx92.6ft
4098-9832 Adapter Plate, required for surface or (4.5 m x 21 m) (10.6 m x 28.2 m)
semi-flush mounting to 4"square box or for 10 ft x 69.9 ft 30 ft x 94.3 ft
surface mounting to 4"octagonal box (3.5 m x 21.3 m) (9.1 m x 28.7 m)
5ftx70.5ft 25ftx95.7ft
Bases 4098-9682 and 4098-9683 include a relay (1.5 m x 21.4 m) (7.6 m x 29.1 m)
that mounts in base electrical box
1 ftx70.6ft 20ftx96.9ft
Base 4098-9684 includes a remote LED interface (0.3 m x 21.5 m) (6.1 m x 29.5 m)
module that mounts in base electrical box
15ftx97.8ft
(4.5mx29.8m)
Heat detector bases 10 ft x 98.4 ft
4098-9682,4098-9683, (3.05 m x 30 m)
4098-9684, &4098-9788
5ftx98.8ft
(1.5mx30.1 m)
1 ftx99ft
(0.3mx30.2m)
Heat detector
NOTE: Refer to Installation Instructions 574-706
for additional information.
Tyco is a registered trademark of Tyco International Services GMBH and is used under license.Simplex,and the Simple logo are trademarks of Tyco International Ltd.and its
affiliates and are used under license.NFPA 72 and National Fire Alarm Cade are trademarks of the National h re Protection Association(NFPA).
USimplex Tyco Safety Products Westminster•Westminster, MA•0 144 1-0001•USA S4098-0014-8 2/2008
m www.tycosafetyproducts-usa-wm.com
�c,2008 T hen Safety Products Wesnntnster.All riehis reserved All snecifications and other information shown were current as ofdocument revision dale and are suhiect ro chanee without notice.
PRODUCT INFORVATION 4098-9788 2 WIRE BASE WITH HEAT DETEC(TORO
FEATURES:
•UL LISTED TO STANDARD 521
•UL LISTED SPACING OF:
- 70 FT. FOR FIXED AND RATE-OF-RISE MODELS
•EPDXY TED ELECTRON DESIGN PROVIDES;
- THER ST BILSED FIXED TEMPERATURE SENSING 4'X 1 1/2'DEEP OCTAGONAL
- DUAL ISTOR RATE FTERISE SENSING OR WHICH REOUtt2ES
- RAPID TE PERATURE RESPONSE PROVIDES RATE COVPEOTKIN 4'SOUARE X i 1/2 DEEP,
- SELF-RESTORING OPERATION A 4098-9832 ADAPTER PI/�TE (6 3/8'x 1/4'
- REPEATABLE ACCURACY BOX SUPPLIED BY CONTRACTOR O
- CURRENT LIFTED ALARM COMPATIBLE WITH TWO-WIRE O
INITIATING DEVICE CIRCUITS
•ALARM INDICATING LED oN DETECTOR
•HEAT DETECTORS AVAILABLE: 0
-4098-9612 IMF FIXED TE098-9613 135• F FIXED MIMDQ RATE-OF-RISE HEAT DETECTORS H
-4098-9614 200' F FIXED TE PERATURE 4098-9512 135 FIXED TE HEM
-4098-9616 200' F FIXED AlADI RATE-OF-RISE 4098-9613 136 FIXED RATE-OF-RISE
•TEMPERATtDW
ELINES 4098-9614 200 FIXED ERATURE '•
-1A3R6� FURE,PETE.CTORS 4098-9616 100 FIXED �TE-OF-RISE
THAT FDOCEEDIMW�IEERO�TUA F ES ,rte
AFURF.DET�FCTORS
TFEXF BUT ARE LESS
THAN 160' F.
•MOUNTIIG:CERT OR WALL
COLOR' FROST FLUSH MOUNTING
SPECIFICATIONS: (BOX TO BE FLUSH OR RECESSED 1/4'MAXIMUM).
• VOLTAGE: 15 TO 32 VDC (FILTERED DC WITH 25%MAXIMUM RIPPLE.)
STANDBY CURRENT: 80uA 0 24 VDC
AIARY CURRENT:Bo mA 0 24 VDC
1FTM�ODE S ISTRF TO 100' F
200' F M ELS 37 F TO 160' F
• HUMIDIFY RANGE: 10%TO 95%RH
(NOT INTENDED FOR OUTDOOR APPLICATIONS)
•D*NSIONS WITH HEAD:4 7/8'H X 4 7/8*0
DESCRIPTION:THE 4098 SERIES ELEC T DETECTORS P PERFOri
THAT IS A SIGNIFIOANT I��NT OVER��ECHANET — — —
DETEC LECTRONIC F THE ORS DE Te
SE� T pUK ILLY,ACCURA LY,AND NTLY IDE TIFDI
FIXED PERATURES ARE EXCEEDED OR WHEN RATE-OF-R TURE I II
CHANGESOCCUR ��
RATE- RISE IS DETERONE. COMP ING Tg THERMISTOR RESP TO TURRj TLO fIRETI C ROL
BY CO BINING ACCURATE THERRMMISTORS PROPER PHYSICAL PLACE Ni, �+ PA L FOR STYLED TION
THIS PIE T�D RATE-OF-RI� pETECTIO DESIGNAC HIEVES A HIGH LEVEL
OF PERFONRMANCE NOT NORMALLY ACHI D ITH 10 CW#CAI HEAT DETECTORS --� IF LAST INITIATING XIE
01�1 cilurt IN A s Lt
�yIRING; CONNECT A E D-OF-LRESIST
1.ALL WILING TO COMPLY WITH LOCAL CODE, ITH THE RT P EL FOR RPpf 0DPEER
2.CONDUCTORS MUST TEST FREE OF ALL GROUNDS. I °u ' c c I END-Of-LIFE RESISTOR VALUES
3.SCREW TERMINALS FOR IN/OUT MING,/18 TO /14 AWG. I ,
4. REFER TO INSTALLATION INSTRUCTIONS (574-706)
5. REFER TO APPLICATION MANUAL (574-709)
6.THESE CANNOT BE INSTALLED ON ZONES PROVIDING ALARM VERIFICATION.
+ 1 i
FROM PRCMUS DEVICE OR
FIRE ALAR M CONTROL PANEL S— — — — — — J L — — — — — — J — —
93®Simplex System Accessories
olddL, CSFM Listed; Fire Alarm Control Relays, Track Mount and
;EA (NYC) Acceptance* Encapsulated; Model 4098-9843 and 2088 Series
UL listed under Standard 864 as Control Unit
Accessory (UOXX)
Track mount package availability: "
M C NG NC C NO NC C 4 C ON 0
NO � .
• Single relay module or four relay module, with or i° °
without cover, with SPDT or DPDT contacts x®. ® °Cog ,
tltlCCC199. CCtf £
• LED indicates relay module status o r o- o- o- o d o- 0 o- a s o- o- a .P
$ a
• Cover provide status LED viewing ports Y
• Multiple coil voltage inputs, diode polarized for DC `� "` `""'` ° `` '" •
• Modules are track mounted with snap-apart feature 2088-9020, MR204/C, Four DPDT Relay Package
design allowing the four relay module to be separated with Enclosure(shown with cover removed)
Single encapsulated SPDT relay package with
color coded 18 AWG wire leads, available in two
versions:
• 2088-9021 (PAM-1) Provides diode polarized multiple
input voltage ability and LED indication
• 4098-9843 (PAM-SD)Provides a diode polarized
24 VDC coil with in/out wiring
APdC-PAM SO
hese multi-purpose control relays offer SPDT or DPDT,
10 A (or 7 A)contacts in a variety of mechanical
packages. Models are available for coil operation by one
of four input voltages allowing a single relay to be Encapsulated Relay Package
energized from a voltage source of 18-35 VDC or VAC, (typical of 2088-9021, PAM-1 and 4098-9843, PAM-SD)
120 VAC, or 230 VAC(not available with 4098-9843).
Voltage selection is made by wiring to the appropriate
input terminals or wire leads. • ' • '•
Each relay model (except model 4098-9843)contains a Encapsulated Relays,see page 2 for dimensions
red LED which indicates that the relay is energized. 118 AWG(0.82 mm2
Connections )color-coded
wire leads
Mounting options are varied for application flexibility. Relay 2088-9021
Track mounted relays may be"snapped apart" from a
standard four-module assembly and used independently if Contact Ratings 10 A@ 120 VAC, resistive
desired. Coil Voltage 18-35 VAC/VDC, 120, or 240 VAC
Ratings 15 mA @ 24 VAC/VDC,
. - • g Current &@ 120 or 230 VAC
Track Mount Relays,see page 2 for dimensions Relay 4098-9843
Coil Voltage 18-35 VACNDC, 120,or 230 VAC Coil Ratings 18-32 VDC input, polarized, 15 mA
SPDT models= 18 mA @ 24 VDC
Coil Current DPDT models=40 mA 7 A at 0.35 p.f @ 28 VDC&
Terminal Blocks Up to 14 AWG(2.08 mm2) Contact Ratings 120 VAC
10 A@ 120 VAC 250 pA @ 5 VDC
Contact Ratings N.O. rated 1/6 HP, N.C. rated 1/8 HP Temperature Ratings
7A @ 28 VDC and @ 230 VAC UL Listed Range 1 32° F to 120° F(0°C to 49°C)
Temperature Ratings Operating Range -58°F to 185° F(-50°C to 85°C)
UL Listed Range 1 32° F to 120° F(0°C to 49°C) Humidity 85%RH Non-condensing
Operating Range -58°F to 185° F(-50°C to 85°C)
Humidity 85% RH Non-condensing `Product listings are by Air Products&Controls Inc.(www.ap-c.com)per model numbers
shown on page 2.These products are also available through Space Age Electronics Inc.
(www.lsae.com)with an SSU-prefix.
S2088-0010-8 3/2006 date
Module Reference Air Products Relay Packaging Dimensions
Positions Number Model Type
2088-9007 MR-101/T SPDT 3-1/4" H x 2-1/8"W x 1-1/2" D
One Track mount,without cover
2088-9009 14 -201/T DPDT (83 mm x 54 mm x 38 mm)
2088-9008 MR- C SPDT 5-1/8" H x 3-1/8"W x 2-1/2" D
Track mount with cover 131 mm x 79 mm x 64 mm
2088-9010 MR-201/ DPDT ( )
2088-9017 MR-104/T SPDT 3=1/4" H x 8-1/2"W x 1-1/2" D
Track mount,without cover 83 mm x 216 mm x 38 mm
2088-9019 MR-204/T DPDT ( )
Four
2088-9018 MR-104/C SPDT 5-1/8" H x 9-1/2"W x 2-1/2" D
Track mount with cover
2088-9020 MR-204/C DPDT (131 mm x 241 mm x 64 mm)
Encapsulated, multi-voltage coil 1-1/2" H x 1"W x 7/8" D
2088-9021 PAM-1 color coded 18 AWG (0.82 mm )wire (38 mm x 25.4 mm x 22 mm)
NA SPDT leads, with coil status LED
Encapsulated, 24 VDC coil,color coded 1- " H x 1-3/16"W x 13/16" D
4098-9843 PAM-SD 18 AWG (0.82 MM2)wire leads (no 1/21/2
LED) mm x 30 mm x 21 mm)
• r, •
SPDT contacts rated DPDT contacts rated
10 A @ 120 VAC, resistive 10 A @ 120 VAC, resistive
® NC C NO
NC C NO NC C NO
® ® ® tt 0000 ®
Relay energized
- LED -
0000 ® ® ®
® 0 18/24 115 230 ® ® 0 18/24 115 230
(18-35)VDC (-) (+) (18-35)VDC (-) (+)
Coil voltage Coil voltage
(note polarity (18-35)VAC AC AC (note polarity (18-35)VAC AC AC
for DC) 120 VAC N V for DC) 120 VAC N V
230 VAC V V 230 VAC V V
Terminal strip connections Terminal strip connections
SPDT models DPDT models
Tyco,Simplex,and the Simplcx logo are trademarks c f Tyco International Services AG or its affiliates in the U.S.and or other countries.Include any other pertinent trademark
information here.i.e.:NFPA 72 and National Fire Alarm Code are registered trademarks of the National Dire Protection Association(NFPA).
0,Simplex Tyco Safety Products Westminster•Westminster, MA•01441-0001•USA S2088-0010-8 3/2006
www.tycosafetyproducts-usa-wm.com
C 2006 7yco Safety Products Westminster All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice.
AIR PRODUOT$ MR-101/T $PDT OONTROL RELAY
PRODUCT INFORMATION (919PLEc 2088-9007)
FEATURES:
•UL LISTED
•IOULTIPLE COIL VOLTAGE INPLITS,DIODE POLARIZED
SPOT CONTACTS
•RELAY STATUS LED
•FETAL ENCLOSURES WITH LED VIEWING PORT
•IIIOUNT :WAIL. SURFACE
SPECIFICATIONS:
•COIL REQUIREMENT: 0.016A 0 18-35VDC/VAC, 115VAC,23WAC
•CONTACT RATING. 10.OA 0 115VAC
•TERMINAL BLOCK RATING,UP TO IIAA*G IbUNTING TRACK
•TEMPERATURE RANGE: -WF TO +1B6F(-WC TO MC) c
•DIMENSIONS (TRACK IIIOUINTED): 31H X 2 1/B'w X 1-1/2•D
(76.2mm H X 53.976mm W X 38.1mm D)
DESCRIPTION: MOUNTING SCREW
TH MR-101/T�CAOCNji RELAY OFFERS SPOT 10 0
OF FOUR TN%)VOLTAGES.�A SINGLE REUY BY L AY
BE ENERGIZED FROM A VOLTAGE SOURCE OF
18-35 VDC OR VAC. 115VAC, OR 230VAC BY
WIRING TO APPROPRIATE INPUT TERMINALS,EACH TRACK MOUNTING
RELAY CONTAINS A RED LED WHXH INDICATES THE
RELAY COIL IS ENERGIZED. THESE DEVICES ARE IDEAL
FOR APPLICATIONS LOCAL CONTACTS ARE
REQUIRED FOR SYSTEFSTATUS, REMOTE C014TACTS
FOR CONTROL OF ELECTRICAL, LOADS AND GENERAL
PURPOSE SWITCHING.
SPDT C014TACTS
WIRING: 1015 yAc°
1. ALL WIRING TO COMPLY WITH LOCAL CODE.
2, MAINTAIN CORRECT POLARITY OC 0 O
3. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. 1101101101
RELAY ENERGIZED LED
DDDD o
11011011011011
O 0 24 115230 O
1B-35 VDC — +
18-35 VAC ACP.. AC
115 VAC 5 H
230 VAC I H D<X H
INPUT CONTROL
VOLTAGE
SEVILLA CONDOMINIUM(4005 PANEL) FIRST FLOOR-ELECTRICAL ROOM
Standby Total Alarm Total
Module Qty Description Current Standby Current Alarm
Panel Equipment
4005-9101 1 ILIFEALARM FACP 8 IDS 4 NAC BG 0.135000 0.135000 0.293 0.293000
Total Panel Stby 0.135000 Total Panel Alarm 0.293000
Peripheral Devices
4098-9601 3 PHOTO SMOKE DETECTOR SSD 0.000100 0.000300 0.000 0.000000
4098-9788 3 2 WIRE DETECTOR BASE ' 0.000000 0.000000 0.000 0.000000
4098-9613E 3 SSD HEAT DET 135 ROR HUMID ENV ' 0.000080 0.000240 0.000 0.000000-
4098-9788E 3 SSD 2-WIRE DET REM LED BASE E ' 0.000000 0.000000 0.000 0.000000
2088-9007 3 TRACK MOUNTED SINGLE RELAY SPDT W/O ENCLOSURE 0.000000 0.000000 0.015 0.045000
Total Pe nph tby 0.001 Total Periph Alarm 0.045
Total Standby Ampsl 0.136 j Total Alarm Amps 0.338
Additional Current Draw Included Below With Device Addresses Used
2-wire detector alarm current is included in the alarm current of the Initiating Device Circuit.
Standby Alarm
Battery Calculations Current Current
Control Panel Card Power 0.135 0.293
Power For External Peripheral Devices 0.00054 0.04500
0.136 <--Totals > 0.338
Additional Battery Capacity Required 0% 0.000 0.000
Standby Time= 24 Hrs 3.253 Standby Ah
Alarm Time= 5 Mins. 0.028 Alarm Ah
Standby+Alarm= 3.281
Minimum Battery Required per NFPA 72 2010 2081-9272 6.2 3.937 20%Safety Margin
Calculabun Sheet
SEVILLA CONDOMINIUM(4005 PANEL)FIRST FLOOR-ELECTRICAL ROOM
NAC SCHEDULE/VOLTAGE DROP CALCULATION Oil, VOLTAGE DROP TOTALS
12.5 %MAXIMUM VOLTAGE DROP MR-101 TOTAL WIRE ESTIMATED ACTUAL ACTUAL 50hms
MAXIMUM
CIRCUIT OUTPUT VOLTAGE=19(FOR CALCULATIONS)' POWER RELAY CKT.LOAD GAUGE CIRCUIT VOLTAGE VOLTAGE ALLOWABLE
CIRCUIT DESCRIPTION SUPPLY 0.015 AMPS 18 16 14 12 LENGTH DROP% DROP VOLTS CKT.LENGTH
SIG1 PRIMARY ELEVATOR RECALL SPS1 0.015 14 350 ft. 0.12% 0.030 35435 ft.
SIG2 ALTERNATE ELEVATOR RECALL SPS1 1 0.015 14 350 ft. 0.12% 0.030 35435 ft.
SIG3 ELEVATOR CAB WARNING LIGHT SPS1 1 0.015 14
350 f±. 0.12% 0.030 35435 ft.
SIG4 SPARE SPS, 3 0.000 14 ft. 0.00% 0.000 ft.
METHOD USED TO CALCULATE VOLTAGE DROP: U.U45
[(CIRCUIT LENGTH IN FEET X 2)(AMPS)(OHMS/FT)]
AS RECOMMENDED BY THE NFPA 72 HANDBOOK,VOLTAGE DROPS ARE CALCULATED USING
Wire Resistance At A BATTERY VOLTAGE OF 20.4 VOLTS AND/OR LOW AC INPUT VOLTAGE AS DEFINED BY UL864.
50 Degrees Celsius THIS TOOL ALSO FACTORS IN INTERNAL LOSSES INCURRED WITHIN THE CONTROL PANEL
122 Degrees Fahrenheit HARNESSING AND CIRCUITRY RESULTING IN A MINIMUM STARTING VOLTAGE OF 19 VOLTS AT
Ohms/ft THE CIRCUITS TERMINALS FOR THESE CALCULATIONS.
10GA=0.001112
12GA=0.001774
14GA=0.002822
16GA=0.004495
18GA=0.007143
WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE(UNCOATED SOLID COPPER WIRE)
NOTE:
LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP.THIS METHOD ALLOWS FOR A SMALL MARGIN
OF SAFETY,TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN
ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT
LENGTH,CONTACT YOUR LOCAL SIMPLEXGRINNELL DISTRICT OFFICE.
Page 1
8/4/10 Sevilla Condominium
4005 FIRE ALARM ZONES
NO. LABEL DEVICE TYPE
ZONE 1 TOP OF SHAFT SMOKE DETECTOR SMOKE
ZONE 2 THIRD FLOOR ELEVATOR LOBBY HEAT DETECTOR HEAT
ZONE 3 SECOND FLOOR ELEVATOR LOBBY HEAT DETECTOR HEAT
ZONE 4 FIRST FLOOR ELEVATOR LOBBY HEAT DETECTOR HEAT
ZONE 5 ELEVATOR MACHINE ROOM SMOKE DETECTOR SMOKE
ZONE 6 SMOKE DETECTOR ABOVE FACP SMOKE
ZONE 7 SPARE
ZONE 8 SPARE
'BY
Third Floor
Second Floor
First Floor
2S S
JR /--I
SIG.2 SIG.3
ALTERNATE RECALL CAB WARNING LIGHT
Elevator Machine Room
Symbol Legend
Q (4098-9601) Smoke Detector w/
(4098-9788) Sensor Base
Q (4098-9613E) High Humidity Heat Detector w/
(4098-9788E) High Humidity Sensor Base
® (2088-9007) MR-101 Relay
3h 6.15.3.2) FS] (DK-120HW) Surge Suppressor
ire Alarm System,
automatic fire detection ZN.1 ZONE #
e connected to a dedicated SIGH SIGNAL CIRCUIT #
hat shall be designated
supervisory panel"
control unit Wire Legend
Z — 1 Blue #14AWG and 1 Yellow #14AWG (ZONE)
S — 1 Red #14AWG and 1 Black #14AWG (SIGNAL)
GRAM
f1Sim.na vas ems, VILLA NIU
plex ELEVATOR RECALL
mw
1800 Sevilla Boulevard
o Atlantic Beach Florida 32233
Me-Diagram
10255 Fortune Parkway
Jacksonville, Florida e
32256 SEUL A FA-1
ee1e1
ZN.1
TOP OF SHAFT Z
1 ZN.2
ELEVATOR LOB
2Z—___, ZN.3
ELEVATOR LOBBY
1
3z ZNA
ELEVATOR LOBBY
1
3S
4Z
� R
ZN.5 SIG.1
ELEVATOR MACHINE ROOM PRIMARY RECALL
Z,3S
2
ZN.6
FIRST FLOOR ELECTRICAL ROOM
2Z,3S
NOTE:
01
W`'`` NFPA 72 2002 Edition (Paragral
It
—r.-
Ir "In facilities without a building F
®oo ® e
these smoke detectors or other
o� LYtt 51as permitted by 6.15.3.7 shall b
fire alarm system control unit t
as "elevator recall control and
ELEVATOR • permanently identified on th(
RECALL and on the record drawings."
CONTROL
120VAC S . . . . ■
. . . . . . . . . . . . . RISER DIJ
. . . . . . . . . . . . .
. . . . . . . . . . . . . .
NTS
tyco
Fire&
Security
Simp/exGrinne//
HARDWARE WARRANTY
1) SIMPLEXGRINNELL WARRANTY STATEMENT:
a) SIMPLEXGRINNELL WARRANTS TO THE PURCHASER OF NEW SIMPLEXGRINNELL PRODUCT(S)
THAT THE PRODUCTS SHALL BE FREE FROM DEFECTS IN WORKMANSHIP AND MATERIAL.
2) WARRANTY PERIOD:
a) THE WARRANTY PERIOD WILL TERMINATE IMMEDIATELY FOLLOWING THE EARLIEST
OCCURRENCE OF EITHER OF THE FOLLOWING:
i) 18 MONTHS HAVE ELAPSED FOLLOWING SHIPMENT OF ANY SYSTEM OR SUB-SYSTEM
FROM SIMPLEXGRINNELL TO THE CUSTOMER, OR
ii) 12 MONTHS HAVE ELAPSED FOLLOWING THE FINAL CONNECTION OPERATION AND
BENEFICIAL USE OF ALL OR ANY PART OF THE SYSTEM.
iii) AS STATED IN THE SPECIFICATIONS AND/OR CONTRACT DRAWINGS
3) SIMPLEXGRINNELL OBLIGATION UNDER THE TERMS OF THE WARRANTY:
a) SIMPLEXGRINNELL'S SOLE RESPONSIBILITY SHALL BE TO REPAIR,ADJUST OR REPLACE,AT
ITS OPTION,ANY SIMPLEXGRINNELL PRODUCT WHICH FAILS DURING THIS PERIOD PROVIDING
PURCHASER HAS PROMPTLY REPORTED SUCH FAILURE TO SIMPLEXGRINNELL IN WRITING.
REPLACEMENT PARTS WILL BE WARRANTED ONLY FOR THE BALANCE OF THE EQUIPMENT
WARRANTY. SIMPLEXGRINNELL AGREES TO CONTINUE TO HONOR ALL OF THE UNEXPIRED
EXPRESSED WARRANTIES SPECIFIED ABOVE ON DEFECTIVE EQUIPMENT AFTER TRANSFER
OF THE EQUIPMENT TO PURCHASER'S CUSTOMER, PROVIDED PURCHASER'S CUSTOMER
ASSUMES THE PURCHASER'S OBLIGATIONS SPECIFIED BELOW.
b) EXCEPT FOR THE EXPRESSED WARRANTIES STATED HEREIN, SIMPLEXGRINNELL DISCLAIMS
ALL WARRANTIES ON PRODUCTS FURNISHED HEREUNDER, INCLUDING WITHOUT LIMITATION,
ALL IMPLIED WARRANTIES OF MERCHANT ABILITY AND FITNESS FOR A PARTICULAR PURPOSE,
AND THE STATED WARRANTIES ARE IN LIEU OF ALL OBLIGATIONS OR LIABILITIES ON THE
PART OF THE SIMPLEXGRINNELL ARISING OUT OF OR IN CONNECTION WITH THE
PERFORMANCE OF THE PRODUCTS. THE SELLER SHALL NOT BE LIABLE FOR ANY DIRECT,
INCIDENTAL OR CONSEQUENTIAL LOSS OR DAMAGE TO THE PRUCHASER OR USER OF THIS
EQUIPMENT ARISING OUT OF THE FAILURE OF THE EQUIPMENT TO OPERATE IN EXCESS OF
THE PURCHASE PRICE OF SAID EQUIPMENT.
c) SIMPLEXGRINNELL MAKES NO WARRANTY AND NO WARRANTY SHALL BE DEEMED TO EXIST,
THAT PURCHASER HOLDS THE GOODS FREE OF THE CLAIM OF ANY THIRD PERSON BYWAY OF
PATENT INFRINGEMENT OR THE LIKE.
4) PURCHASER'S OBLIGATIONS UNDER THE TERMS OF THE WARRANTY.
a) THIS WARRANTY IS CONTINGENT UPON THE PROPER INSTALLATION AND USE OF THE
PRODUCT(S). SUCH WARRANTY SHALL NOT APPLY IF THE PRODUCT FAILURE IS THE RESULT
OF ACCIDENT, UNUSUAL PHYSICAL,ELECTRICAL OR ELECTROMECHANICAL STRESS,
NEGLECT, MISUSE, USER PROGRAMMING ERRORS, FAILURE OF ELECTRICAL POWER,AIR
CONDITIONING OR HUMIDITY CONTROL, CONSTRUCTION DUST, DAMAGING FOREIGN
SUBSTANCES,TRANSPORTATION OR CAUSES OTHER THAN MANUFACTURING DEFECT.
PURCHASER AGREES TO PROVIDE FULL AND FREE ACCESS TO AUTHORIZED
SIMPLEXGRINNELL EMPLOYEES.
Fire,Security,Communications,Workforce Solutions,Sales&Service
Offices&Representatives in Principle Cities throughout the World
Nyco
Fire&
Security
Simp/exGrinne//
5) WARRANTY SERVICE HOURS:
a) SERVICES PROVIDED UNDER THIS WARRANTY WILL BE PERFORMED DURING THE HOURS OF
8:OOA.M. TO 5:OOP.M., MONDAY THROUGH FRIDAY, EXCLUDING LOCALLY OBSERVED
SIMPLEXGRINNELL HOLIDAYS. OFF HOURS RESPONSE IS AVAILABLE AS AN EXTRA COST
SERVICE OPTION.
6) WARRANTY EXCLUSIONS:
a) LABOR,TRAVEL,AND MILEAGE FOR:
i) SERVICE OUTSIDE OF SIMPLEXGRINNELL NORMAL BUSINESS HOURS.
ii) PROGRAMMING AND/OR LABEL CHANGES.
iii) FAILURE DUE TO EXTERNAL CAUSES(LIGHTNING SURGES, CONSTRUCTION DUST, ETC.)
OTHER THAN MANUFACTURING DEFECT.
b) ELECTRICAL WORK EXTERNAL TO THE EQUIPMENT SUPPLIED BY SIMPLEXGRINNELL OR
MAINTENANCE OF ACCESSORIES,ALTERATIONS,ATTACHMENTS OR OTHER DEVICES NOT
FURNISHED BY SIMPLEXGRINNELL.
c) BATTERIES
d) COVERAGE OF EQUIPMENT CLASSED AS A WATER FLOW MONITORING/CONTROL DEVICES
INSTALLED IN OR ON WATER PIPING.
Fire,Security,Communications,Workforce Solutions,Sales&Service
Offices&Representatives in Principle Cities throughout the World
tyco
Fire&
Security
Simp/exGrinne//
MANUFACTURER'S RECOMMENDATION
1. CONTRACTOR IS EXPECTED TO PULL AND TERMINATE ALL CONDUCTORS AND INSTALL ALL
DEVICES FOR A COMPLETE AND OPERATING SYSTEM,
2. WHERE FAN SHUTDOWN, ELEVATOR RECALL OR SPECIAL AUXILIARY FUNCTIONS ARE REQUIRED,
CONTRACTOR IS TO VERIFY WIRING REQUIREMENTS WITH THE SIMPLEXGRINNELL FACTORY
TECHNICIAN ASSIGNED TO THE PROJECT(IN MANY CASES, SPECIAL WIRING WILL NOT BE SHOWN
ON THE DRAWINGS).
3. WHERE POSSIBLE,THE CONTRACTOR IS TO USE COLOR CODE FOR ALL WIRING.
4. SMOKE DETECTORS ARE NOT TO BE MOUNTED WITHIN 2 FEET OF AIR OUTLETS.
5. CONTRACTOR SHOULD NOT INSTALL SMOKE DETECTOR HEADS IN BASES OR DUCT HOUSING
UNTIL FINAL CHECKOUT TIME TO INSURE THAT DIRT OR DUST DOES NOT CONTAMINATE THE
UNITS.
6. DO NOT POWER-UP SYSTEM UNTIL SIMPLEXGRINNELL FACTORY TECHNICIAN IS PRESENT.
7. A SEPARATE GROUND(ISOLATION FROM CONDUIT GROUND) MUST BE PULLED TO ALL CABINETS.
8. LOADS GREATER THAN 10 AMPS (FOR AUXILIARY FUNCTIONS)ARE NOT ALLOWED IN THE SAME
CONDUIT AS FIRE ALARM.
9. CONTRACTOR IS TO NOTIFY SIMPLEXGRINNELL ONE WEEK BEFORE FINAL CHECKOUT. (425-827-
3700)
10. CONTRACTOR 1S TO ENSURE THAT ALL WIRING AND SHIELDS ARE FREE OF SHORTS, GROUNDS
AND OPENS.
11. UNDERGROUND WIRING MUST MAINTAIN ONE MEGAOHM, 20F RESISTANCE TO GROUND.
12. ANY MANUFACTURER'S RECOMMENDATION IN CONFLICT WITH ENGINEERING DRAWINGS OR
SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER FOR CLARIFICATION.
CONTRACTOR SHALL ADVISE SIMPLEXGRINNELL OF ANY CHANGES.
13. PROTECTIVE COVERS ON SMOKE DETECTORS ARE NOT TO BE REMOVED UNTIL OWNERS
ACCEPTANCE OF THE SYSTEM. (PREVENTS CONTAMINATION OF SMOKE CHAMBER).
14. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REQUEST THE STATE OR LOCAL FIRE MARSHAL TO
BE ON SITE FOR FINAL ACCEPTANCE AND CHECK OUT IF REQUIRED.
15. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INVENTORY ALL EQUIPMENT RECEIVED FROM
SIMPLEXGRINNELL AGAINST THE CONTRACT DOCUMENTS AND REPORT ANY DISCREPANCIES
WITHIN THIRTY(30)DAYS OR SIMPLEXGRINNELL WILL ASSUME THE ORDER TO BE ACCURATE AND
COMPLETE.
a. *NOTE: IN THE EVENT OF DISCREPANCIES IN THE NUMBER OF DEVICES SUPPLIED,THE
FOLLOWING SIMPLEXGRINNELL POLICY WILL APPLY:
i. TOO FEW DEVICES: IF THE DEVICE IS SHOWN ON THE CONTRACT DOCUMENTS
AND HAS NOT BEEN ADDED AS A RESULT OF A POST BID ADDITION OR CHANGE
, * ORDER, SIMPLEXGRINNELL WILL SUPPLY THE DEVICE AT NO CHARGE TO THE
CONTRACTOR OR END USER PER SIMPLEXGRINNELL'S CONTRACT OBLIGATIONS.
Fire,Security,Communications,Workforce Solutions,Sales&Service
Offices&Representatives in Principle Cities throughout the World
*yco
Fire&
Security
Simp/exGrinne//
ii. TOO MANY DEVICES: IF THE DEVICE SHOWN IS EXTRA, DUE TO A POST BID
ADDITION OR CHANGE ORDER, IT REMAINS THE PROPERTY OF THE CONTRACTOR
OR END USER. IF THE DEVICE IS EXTRA DUE TO AN ERROR IN QUANTITIES
SUPPLIED,THE DEVICE MUST BE RETURNED TO SIMPLEXGRINNELL. NO CREDIT
WILL BE ISSUED FOR THE RETURN OF EXTRA EQUIPMENT ABOVE THE QUANTITIES
GIVEN IN THE CONTRACT DOCUMENTS.
16. OWNERS PRESENCE FOR FINAL DEMONSTRATION AND ACCEPTANCE.
SPECIAL INSTRUCTIONS-SIMPLEXGRINNELL
1. SIMPLEXGRINNELL WILL PROVIDE WIRING INSTRUCTIONS FOR INSTALLATION OF
SIMPLEXGRINNELL EQUIPMENT.
2. SIMPLEXGRINNELL WILL PROVIDE A FACTORY TRAINED TECHNICIAN TO REVIEW THE
OPERATION OF THE SYSTEM AND THE CORRECT METHOD BY WHICH THE EQUIPMENT SHALL
BE WIRED AND CONNECTED. PLEASE CALL(425)827-3700 FIVE(5)DAYS BEFORE VISIT IS
NEEDED.
3. SIMPLEXGRINNELL WILL PROVIDE A FACTORY TRAINED TECHNICIAN TO ASSIST IN TRAINING:
a. OPERATION OF THE CONTROL PANEL AND FUNCTIONS
b. ALARM TEST OF ALL SIMPLEXGRINNELL PERIPHERAL DEVICES(SMOKE DETECTOR,
MANUAL PULL STATION, ETC.)
c. SUPERVISE TEST OF ALL INITIATING, SIGNALING,AND CONTROL CIRCUITS.
4. SIMPLEXGRINNELL WILL PROVIDE (1) INSTRUCTION AT FINAL TEST OF THE SYSTEM TO:
a. OWNER REPRESENTATIVE
b. FIRE INSPECTOR AND ELECTRICAL INSPECTOR
c. ARCHITECT AND ENGINEER
5. UPON COMPLETION OF FINAL TEST, SIMPLEXGRINNELL WILL PROVIDE:
a. TEST REPORT
b. CERTIFICATION (IF REQUIRED)
c. ONE YEAR WARRANTY
Fire,Security,Communications,Workforce Solutions,Sales&Service
Offices&Representatives in Principle Cities throughout the World
*yco
Fire &
Security
Simp/exGrinne//
TESTING PROCEDURE FOR DEVICES
GENERAL:
FOR ALL DEVICES(SUPPLIED BY SIMPLEXGRINNELL)VISUALLY VERIFY PROPER LOCATION AND
INSTALLATION.
SMOKE DETECTOR:
ACTIVATE THE DEVICE USING A SMOKE GENERATOR AND VERIFY ALARM CONDITION ON PANEL.
RESET PANEL AND VERIFY RESET OF SMOKE DETECTOR AND PANEL. TEST FOR ALARM VERIFICATION
IF APPROPRIATE.
HEAT DETECTOR:
FIXED TEMPERATURE REPLACEMENT ELEMENT-REMOVE ELEMENT ON HEAT DETECTOR TO INITIATE
ALARM AND VERIFY ALARM CONDITION AT PANEL. REINSTALL ELEMENT, RESET SYSTEM,AND VERIFY.
NON-REPLACEABLE ELEMENT-NON-REPLACEABLE ELEMENT HEAT DETECTORS CAN ONLY BE
TESTED FOR CONTINUITY.
RATE-OF-RISE DETECTORS- RATE OF RISE DETECTORS ARE TESTED WITH A HEATER OR BLOW
DRYER UNTIL THEY INITIATE ALARM,THEN ALLOWED TO COOL. RESET PANEL AND VERIFY.
PULL STATIONS:
ACTIVATE STATION WITH THE T-HANDLE,VERIFY ALARM AND LABEL FOR LOCATION, RESET STATION,
RESET PANEL.
DUCT DETECTOR:
(PROVIDED BY SIMPLEXGRINNELL) REMOVE DUCT DETECTOR HOUSING COVER AND ACTIVATE DEVICE
WITH SMOKE,VERIFY ALARM, TEST ALL INDICATORS OR MANUAL TEST SWITCHES, RESET DETECTOR,
RESET PANEL, TEST SAMPLE AND REFERENCE TUBE FOR POSITIVE AIR FLOW. (IF NOT PROVIDED BY
SIMPLEXGRINNELL)VERIFY THAT ZONE CIRCUIT IS PRESENT AT THE DEVICE.
AUDIBLES AND VISIBLES:
ACTIVATE ALARM AND CONFIRM THAT ALL INDICATING APPLIANCES,AUDIBLES AND VISIBLES,ARE
OPERATING.
DOOR HOLDERS:
VERIFY THAT DOORS CLOSE ON ALARM.
VALVE SUPERVISORY SWITCHES(TAMPER):
(IF PROVIDED BY SIMPLEXGRINNELL)ACTIVATE SWITCH BY MOVING VALVE OFF NORMAL, VERIFY
STATUS CHANGE, RESET SWITCH, RESET PANEL. (IF NOT PROVIDED BY SIMPLEXGRINNELL)VERIFY
THAT ZONE CIRCUIT IS PRESENT AT THE SWITCH.
FLOW SWITCHES AND PRESSURE SWITCHES:
(IF PROVIDED BY SIMPLEXGRINNELL)ACTIVATE SWITCH (WITH SPRINKLER CONTRACTOR PRESENT)
BY A FLOW OF WATER,VERIFY STATUS CHANGE, RESET SWITCHES, RESET PANEL. (IF NOT PROVIDED
BY SIMPLEXGRINNELL)VERIFY THAT ZONE CIRCUIT IS PRESENT AND SUPERVISED AT THE SWITCH.
FAN/DAMPER CONTROL CIRCUITS:
VERIFY(WITH HVAC CONTRACTOR PRESENT)THAT THE CONTROL CIRCUIT IS OPERATING AND THE
DEVICES IS BEING CONTROLLED IN ACCORDANCE WITH THE SPECIFIED SEQUENCE OF OPERATION.
ELEVATOR CONTROL CIRCUITS:
VERIFY(WITH ELEVATOR CONTRACTOR PRESENT)THAT THE ELEVATOR IS BEING CONTROLLED IN
ACCORDANCE WITH THE SPECIFIED SEQUENCE OF OPERATION.
TRAINING:
SIMPLEXGRINNELL SHALL PROVIDE A ONE TRAINING SESSION TO THE CUSTOMER.
WARRANTY:
THE SYSTEM SHALL BE PROVIDED WITH A ONE YEAR HARDWARE WARRANTY.
Fire,Security,Communications,Workforce Solutions,Sales&Service
Offices&Representatives in Principle Cities throughout the World
Technical Installer Support (TIS)
Introduction Technical Installer Support(TIS)is provided as part of the cost of the equipment and is
designed to provide the expertise of a Simplex Technician to be available at key
scheduled times during the project. This service is available during normal Simplex
working hours,if scheduled five working days in advance.
TIS Activities TIS includes the following activities by a Simplex factory-trained technician,when
determined by Simplex to be appropriate:
• Pre-construction review of submittals and drawings with the installer
• Technical advice during initial start up of control panels before installer wiring is
connected
• Review of panel wiring,and preparation of a list of any items to be corrected by
the installer
• Checkout of Factory Program
• Program editing to correct minor errors and omissions
• System check in preparation for functional test
• Assistance with one complete,functional test of the system
• One training session for the owners representative(2-4 hrs.per control panel)
Additional support may be purchased. See other side for more information.
Installer's TIS contributes significantly to the installation of Simplex equipment but does not
alleviate the installer's responsibility to:
Responsibility . Provide skilled labor and supervision to complete the project
• Review and understand Simplex instructions for installing and testing Simplex
equipment
• Ensure that all wiring provided and installed meets equipment specification
requirements,UL,code compliance and is free of grounds and faults.
How to Avoid Potential problems can be avoided by following these recommendations:
• Do not initially power up the system,except in the presence of a Simplex
Potential Problems technician. Simplex assumes no liability for damaged equipment,and warranty
may be voided if this procedure is not followed.
• Do not install smoke detectors(unless protected by plastic bags)until final
construction clean up has occurred. This prevents damage caused by dust,dirt,
and paint. Detectors installed prior to clean up may require disassembly,cleaning,
or replacement which is not covered by warranty.
• Care must be taken to protect equipment during the installation and warranty
period. Failures due to external causes(power surges,construction dust,water
damage,etc.)will be repaired by Simplex only upon receipt of a valid written
Purchase Order.
• TIS includes one complete system test,which is coordinated by the installer. To
avoid additional charges,the installer should schedule this test so that all
appropriate parties such as the owner's representative and local fire officials,are
present.
7e.
,,Simplex