Permit Mech Fire 1 ocean 2011 � JJy
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
.� INSPECTION PHONE LINE 247-5814
•,f 13
Application Number . . . . . 11-00002914 Date 11/18/11
Property Address . . . . . . 1 OCEAN BLVD
Application type description MECHANICAL FIRE PERMIT
Property Zoning . . . . . . . COM GENERAL DISTRICT
Application valuation . . . . 1780
----------------------------------------------------------------------------
Application desc
REPLACING SPRINKLERS (NOT FOR AWNING)
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
1 OCEAN WAYNE AUTOMATIC FIRE SPRINKLER
HAZARD FIRE PROTECTION ENG
ATLANTIC BEACH FL 32233 222 CAPITOL COURT
OCOEE FL 34761
(904) 268-3030
----------------------------------------------------------------------------
Permit . . . . . . FIRE SPRINKLER
Additional desc . .
Permit Fee . . . . 85 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 11/18/11
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 85 . 00 85 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 89 . 00 89 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
City of Atlantic Beach APPLICATION NUMBER
Building Department (To be assigned by the Building Department.)
800 Seminole Road
10 Atlantic Beach, Florida 32233-5445
Phone(904)247-5826 • Fax(904)247-5845
E-mail: building-dept@coab.us Date routed:
City web-site: http://\uww.coab.us
APPLICATION REVIEW AND TRACKING FORM - -
Property Address: / �Cf d-71 ZlVb nt review required Yes No
B ildingApplicant: #/VS /����� ring-&Zoning
Tree Administrator
Project: / `f,e Public Works
Public Utilities
Public Safety
Fire Services
Review fee $ Dept Signature
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified By
Florida Dept.of Environmental Protection
Florida Dept. of Transportation
St.Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
Reviewing Department First Review: [Approved. ❑Denied.
(Circle one.) Comments:
Ld/i ?(�Y ��vz et I iYt r;{J Pc�,Z•y� l.'l.'� P n j C; �'� r S
BUILDING Co�►^� t� f��- I
PLANNING & ZONING Reviewed by: Date: //
TREE ADMIN. Second Review: [--]Approved as revised. ❑Denie .
PUBLIC WORKS Comments:
PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: ❑Approved as revised. [—]Denied.
Comments:
Reviewed by: Date:
Revised 05/14/09
MECHANICAL PERMIT APPLICATIL CITY OF ATLANTIC BEACH OC;' 5 20800 Seminole Rd Atlantic Beach, FL 32233 ��Ph (904) 247-5826 Fax (904) 247-5845 By
JOB ADDRESS: O CC A P `J LV P PERMIT
PROJECT VALUE $ l j C)
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI#
Air Conditioning: Unit Quantity Tons Per Unit REQUIRED
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity 3 5?f-%vj C-LF11j (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER: F I L Em"
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name Phone Number
Mechanical Company wA`EjjC JNLJ'T0#^A-1 le- rlP-C SQr-1NV-L 91 1 Office Phone 2V6 "'31 Fax Z(.`8-0-17-4
Co. Address: tk- Z(' DIS`Te9,&oTiaN hor-, Wiz S7 City-�AC(CSvv-utLtLF State Zip 37-2.S6
License Holder(Print): / State Certification/Registration#$iq'D-110oot2Oc�-
Notarized Signature of License Hold< n
Sworn and subscribed before me is 1 5 da of ���UbeV —20 //
SAMANTHA (30N3�1LES y
NOTARY PUBLIC
1*1-av
STATE OF FLORIDA Signature of Notary Public
Comm#EE043764
Expires 11/21/2014
Fire & Building
Products
Technical Services: Tel: (800)381-9312/Fax: (800)791-5500
Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed they
Description standard corrosion tests of the appli-
cable approval agencies,the testing is
The Tyco® Series TY-FRB, 2.8, 4.2, not representative of all possible cor- A>, j
5.6,and 8.0 K-factor,Upright and Pen- rosive atmospheres. Consequently, it
dent Sprinklers described in this data is recommended that the end user be
sheet are quick response - standard consulted with respect to the suitability
coverage, decorative 3 mm glass bulb of these coatings for any given corro-
type spray sprinklers designed for use sive environment.The effects of ambi-
in light or ordinary hazard,commercial ent temperature, concentration of
occupancies such as banks, hotels, chemicals, and gas/chemical velocity, `
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
chemical to which the
TY-FRB Pendent Sprinkler,where ap- sprinklers will be
exposed.
plicable, is intended for use in areas ex p
with a finished ceiling. It uses either a An intermediate level versions of the
two-piece Style 10 (1/2 inch NPT) or Series TY-FRB Pendent Sprinklers
Style 40(3/4 inch NPT)Recessed Es- are detailed in Technical Data Sheet
cutcheon with 1/2 inch (12,7 mm) of TFP356,and Sprinkler Guards are de-
recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780
(19,1 mm)of total adjustment from the
flush pendent position, or a two-piece WARNINGS
Style 20(1/2 inch NPT)or Style 30(3/4 The Series TY-FRB Sprinklers de- .
inch NPT) Recessed Escutcheon with scribed herein must be installed and
1/4 inch (6,4 mm) of recessed adjust maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen- ble standards of the National Fire Pro-
dent position. The adjustment pro- tection Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hav-
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may Model/Sprinkler
pipe drops to the sprinklers must be impair the performance of these de-
cut. vices. Identification
Corrosion resistant coatings, where The owner is responsible for maintain- Numbers
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.81K, 1/2"NPT
that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.81K, 112"NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2"NPT
with any questions. TY2231 - Pendent 4.21K, 1/2"NPT
IMPORTANT TY3131 - Upright 5.61K, 1/2"NPT
Always refer to Technical Data TY3231 - Pendent 5.61K, 1/2"NPT
Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.OK,3/4"NPT
WARNING" that provides cautions TY4231 - Pendent 8.OK, 3/4"NPT
with respect to handling and instal- TY4831- Upright 8.OK, 1/2"NPT
lation of sprinkler systems and com- TY4931- Pendent 8.OK, 1/2"NPT
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 AUGUST, 2007 TFP171
Page 2 of 10 TFP171
ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE NPT -IN ESCUTCHEON DEFLECTOR
/ 6
T_ 7/1 m
5
2-1/4" (11,1 mm) 4
(57,2 mm) NOMINAL
MAKE-IN 2
1-9/16" 2-3/16" g
(39,7 mm) WRENCH (55,6 mm)
FLATS 1
SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. —� 1/2"NPT 7
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1-Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to
2-Button Assembly 5-Compression 7-Bushing orifice seat on frame.
Screw
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1131)AND PENDENT(TY1231)SPRINKLERS
2-SK-FACTOR, 112 INCH NPT
ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20
PLATE SEATING 1/2" NOMINAL RECESSED SSU*
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
-r— — 6*
2-3/16" —� 7/16" 5
(55,6 mm) (11,1 mm)
NOMINAL 4
MAKE-IN
1-1/2" I
(38,1 mm) —11 2-3/16 2
"
WRENCH (55,6 mm)
FLATS 3
SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. —� 1/2"NPT 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1-Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to
2-Button Assembly 5-Compression orifice seat on frame.
Screw
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS
4.2 K-FACTOR, 112 INCH NPT
TFP171 Page 3 of 10
ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20
PLATE SEATING 1/2" NOMINAL RECESSED SSU*
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
6*
2-3/16" —� jr(N
" 5
(55,6 mm) mm)
NAL 4
-I N
1-1/2" 2-3116" 2
(38,1 mm) WRENCH (55,6 mm)
5FLATS 3
1
SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. —� 1/2"NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1-Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to
2-Button Assembly 5-Compression orifice seat on frame.
Screw
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS
5.6 K-FACTOR, 112 INCH NPT
ESCUTCHEON 1/2"(12,7 mm) STYLE 30 or 40
PLATE SEATING 3/4" NOMINAL RECESSED SSU*
SURFACE NPT DEFLECTOR ESCUTCHEON DEFLECTOR
1/2" 5
2-5/16" (12,7 mm)
(58,, m7 mm) NOMINAL
4
MAKE-IN
1-9/16" 2-1/4" 2
(39,7 mm) REN11 H (57,2 mm)LAT3
SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. 3/4"NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1-Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to
2-Button Assembly 5-Compression orifice seat on frame.
Screw
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
Page 4 of 10 TFP171
7116"(11,1 mm)
112„ NOMINAL SSU*
NPT MAKE-IN DEFLECTOR
* 6
5
-� 253!176"
2-1J4"
(57,2 mm) (5 ,6 mq
1-9/16"�
WRENCH 2
(39,7 mm) FLATS
3
SSP* 1
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1-Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to
2-Button Assembly 5-Compression orifice seat on frame.
Screw
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS
8.0 K-FACTOR, 112 INCH NPT
Technical Operation
Data The glass Bulb contains a fluid which
expands when exposed to heat.When
Approvals the rated temperature is reached, the
UL and C-UL Listed. fluid expands sufficiently to shatter the
FM, LPCB,and NYC Approved. glass Bulb, allowing the sprinkler to
(Refer to Table A and B for complete activate and water to flow.
approval information including corro-
sion resistant status.) Design
Maximum Working Pressure
Refer to Table C. Criteria
Discharge Coefficient
K=2.8 GPM/psi1/2 (40,3 LPM/barl/2) The Series TY-FRB Pendent and Up-
K=4.2 GPM/psil/2 (60,5 LPM/barl/2) right Sprinklers are intended for fire
K=5.6 GPM/psil/2 (80,6 LPM/bars/2) protection systems designed in ac-
K=8.0 GPM/psil/2(115,2 LPM/bars/ ) cordance with the standard installation
rules recognized by the applicable
Temperature Ratings Listing or Approval agency (e.g., UL
Refer to Table A and B Listing is based on the requirements of
Finishes NFPA 13, and FM Approval is based
Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre-
Recessed Escutcheon:White Coated, vention Data Sheets ). Only the Style
Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Physical Characteristics E
Frame . . . . . . . . . . . . . Bronze
Button . . . . . . . Brass/Copper
Sealing Assembly . r`
Beryllium Nickel w/Teflont m
Bulb . . . . . . . . . Glass iu
Compression Screw . . . . . Bronze
Deflector . . . . . Copper/Bronze a
Bushing(K=2.8) . . . . . . . Bronze
C
o_
O
TFP171 Page 5 of 10
SPRINKLER FINISH(See Note 7)
K TYPE TEMP. BULB NATURAL CHROME WHITE***
LIQUID BRASS PLATED POLYESTER
135°FI570C Orange
PENDENT 155°F/68°C Red
(TY1231) 1,2,3,5
and 175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
2.8 (TY1131)
286°F/141°C Blue
1/2"
NPT 135°F/57°C Orange
RECESSED 155°F/68°C Red
PENDENT
(TY1231)' 175°F/79°C Yellow
Figure 6 200°F/93°C Green 1,2,5
135°F/57°C Orange
RECESSED 155°F/68°C Red
PENDENT
(TY1231)** 175°F/79°C Yellow
Figure 7 200°F/93°C Green
135°F/57°C Orange
PENDENT 155°F/68°C Red
(TY2231)
and 175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
4.2 (TY2131)
286°Fl141°C Blue 1,2
1/2"
NPT 135°F/57°C Orange
RECESSED 155°F/68°C Red
PENDENT
(TY2231)* 175°F/79°C Yellow
Figure 8 200°F/93°C Green
135°F/57°C Orange
RECESSED 155°F/68°C Red
PENDENT
(TY2231)** 175°F/79°C Yellow
Figure 9 200°F/93°C rGreen
NOTES:
1.Listed by Underwriters Laboratories, Inc.(UL)as Quick Response Sprinklers.
2.Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL)as Quick Re-
sponse Sprinklers.
3.Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprin-
klers.
5.Approved by the City of New York under MEA 354-01-E.
7.Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment
Recessed Escutcheon,as applicable.
*'Installed with Style 20(1/2"NPT)or Style 30(314"NPT)1/2"Total Adjustment
Recessed Escutcheon,as applicable.
***Frame and Deflector only. Listings and approvals apply to color(Special Order).
NIA:Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Page 6 of 10 TFP171
SPRINKLER FINISH(See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD
LIQUID BRASS PLATED POLYESTER COATED
135°F/57°C Orange
PENDENT 155°F/68°C Red
(TY3231) 1,2,3,4,5,6,7 1,2,3,5
and 175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
5.6 (TY3131)
286°F/141°C Blue
1/2"
NPT 135°F/57°C Orange
RECESSED 155°F/68°C Red
PENDENT 1,2,4,5 N/A
(TY3231)* 175°F/79°C Yellow
Figure 10 200°F/93°C Green
135°F/57°C Orange
RECESSED 155°F/68°C Red
PENDENT 1,2,3,4,5 N/A
(TY3231)** 175°F/79°C Yellow
Figure 11 200°F/93°C Green
135°F/57°C Orange
PENDENT(TY4231) 155°F/68°C Red 1,2,5
and 175°F/79°C Yellow 1,2,3,4,5,6,7
UPRIGHT 200°F/93°C Green
8.0 (TY4131)
286°F/141°C Blue
3/4"
NPT 135°F/57°C Green
RECESSED 155°F/68°C Orange
PENDENT 1,2,4,5 N/A
(TY4231)* 175°F/79°C Red
Figure 12 200°F/93°C Yellow
135°F/57°C Orange
RECESSED 155°F/68°C Red
PENDENT 1,2,3,4,5 N/A
(TY4231)** 175°F/79°C Yellow
Figure 13 200°F/93°C Green
135°F/57°C Orange
PENDENT 155°F/68°C Red
8.0 (TY4931) 1,2,5
1/2" and 175°F/79°C Yellow 1,2,4,5,6
NPT UPRIGHT 200°F/93°C Green
(TY4831)
28;=F/1 41'CT Blue
NOTES:
1.Listed by Underwriters Laboratories, Inc.(UL)as Quick Response Sprinklers.
2.Listed by Underwriters Laboratories, Inc.for use in Canada(C-UL)as Quick Response Sprinklers.
3.Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4.Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers;however,the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5.Approved by the City of New York under MEA 354-01-E.
6.VdS Approved(For details contact Tyco Fire&Building Products, Enschede, Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377).
7.Approved by the Loss Prevention Certification Board (LPCB Ref.No.094a/06)as Quick Response Sprinklers.
8.Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers.Where Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable.
'*Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT) 1/2"Total Adjustment Recessed Escutcheon,as applicable.
***Frame and Deflector only.Listings and approvals apply to color(Special Order).
N/A:Not Available
TABLE 8
LABORATORY LISTINGS AND APPROVALS
5.6 AND&0 K-FACTOR SPRINKLERS
TFP171 Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL I CHROME I WHITE LEAD
BRASS PLATED POLYESTER COATED
PENDENT(TY3231)
and
2.8 UPRIGHT(TY3131) 175 PSI(12,1 BAR) N/A
112" RECESSED PENDENT
NPT (TY323)
PENDENT(TY4231)
and
4.2 UPRIGHT(TY4131) 175 PSI(12,1 BAR) N/A
3/4" RECESSED PENDENT
NPT (TY4231)
PENDENT(TY3231)
and 250 PSI(17,2 BAR) 175 PSI(12,1 BAR)
5.6 UPRIGHT(TY3131) OR
1/2" RECESSED PENDENT 175 PSI(12,1 BAR)
NPT (TY3231) N/A
(SEE NOTE 1)
PENDENT(TY4231)
and 175 PSI(12,1 BAR) 175 PSI(12,1 BAR)
80 UPRIGHT(TY4131)
3/4" RECESSED PENDENT
NPT (TY4231) N/A
8.0 PENDENT(TY4931)
1/2" and 175 PSI(12,1 BAR) 175 PSI(12,1 BAR)
NPT UPRIGHT(TY4831)
NOTES:
1.The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by
Underwriters Laboratories, Inc.for use in Canada(C-UL);and,the Approval by the City of New York.
TABLE C,MAXIMUM WORKING PRESSURE
tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting.
Installation (13,4 to 26,8 Nm). A maximum of 30 Step 3. Tighten the sprinkler into the
ft.lbs.(40,7 Nm)of torque is to be used sprinkler fitting using only the W-Type
The Series TY-FRB Sprinklers must to install sprinklers with 314 NPT con- 6 Sprinkler Wrench (Ref. Figure 14).
be installed in accordance with the fol- nections. Higher levels of torque may With reference to Figures 1, 2, 3, 4,
lowing instructions: distort the sprinkler inlet and cause and 5,the W-Type 6 Sprinkler Wrench
leakage or impairment of the sprinkler. is to be applied to the sprinkler wrench
NOTES 0o not attempt to make-up for insufff- flats.
the
not install any bulb type sprinkler if cient adjustment in the escutcheon The Series TY-FRB Recessed Pen-
the bulb is cracked or there is a loss er late b under- or over-tightening the dent Sprinklers must be installed in
Pen-
liquid from the bulb. With the sprinkler p y g g P
held horizontally, a small air bubble sprinkler. Readjust the position of the accordance with the following instruc-
should be present. The diameter of the sprinkler fitting to suit, tions.
air bubble is approximately 1116 inch The Series TY-FRB Pendent and Up- Step A. After installing the Style 10.
(1,6 mm) for the 135'F/57°C to 3132 right Sprinklers must be installed in 20, 30,or 40 Mounting Plate,as appli-
inch (2,4 mm) for the 286°F/141°C accordance with the following instruc- cable, over the sprinkler threads and
temperature ratings. tions. with pipe thread sealant applied to the
A leak tight 112 inch NPT sprinklerjoint Step 1. Pendent sprinklers are to be pipe threads, hand tighten the sprin-
should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting.
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- upright sprinklers are to be installed in Step B. Tighten the sprinkler into the
mum of 21 ft. lbs. (28,5 Nm)of torque the upright position. sprinkler fitting using only the W-Type
may be used to install sprinklers with Step 2. With pipe thread sealant ap- 7 Recessed Sprinkler Wrench (Ref.
112 NPT connections. A leak tight 314 plied to the pithreads, hand tighten Figure 15).With reference to Figure 1,
inch NPT sprinkler joint should be ob- pereas, an
2, 3, and 4, the W-Type 7 Recessed
Page 8 oll10 TFP171
2-7/8"DIA. 2-7/8"DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm)
1/2±1/8" 1/2"(12,7 mm)
(15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm)
2-1/4"DIA. 1/4"(6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
118" I 1/8"
(3,2 mm) (3,2 mm)
IN
MOUNTING
MOUNTING SURFACE
SURFACE
17
CLOSURE
SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm)
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 6 FIGURE 7
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.S K-FACTOR, 112 INCH NPT 2.8K-FACTOR, 112 INCH NPT
2-7/8"DIA. 2-7/8"DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm)
1/2±1/8" 1/2"(12,7 mm)
(15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
MOUNTING
SPRINKLER PLATE SPRINKLER
PLATE
FITTING FITTING
1/8" I 1/8"
(3,2 mm) ( m)
MOUNTING
MOUNTING SURFACE7
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm)
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 8 FIGURE 9
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 112 INCH NPT 4.2 K-FACTOR, 112 INCH NPT
Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi-
the sprinkler wrench flats. itcontrols,permission to shutdown the fied sprinklers must be replaced.
Step C.After the ceiling has been in- affected fire protection system must be Sprinklers that have been exposed to
stalled or the finish coat has been ap- obtained from the proper authorities corrosive products of combustion, but
plied,slide on the Style 10, 20, 30, or and all personnel who may be affected have not operated,should be replaced
40 Closure over the Series TY-FRB by this action must be notified. if they cannot be completely cleaned
Sprinkler and push the Closure over The owner must assure that the sprin- by wiping the sprinkler with a cloth or
the Mounting Plate until its flange klers are not used for hanging of any by brushing it with a soft bristle brush.
comes in contact with the ceiling. objects; otherwise, non-operation in Care must be exercised to avoid dam-
the event ofa fire or inadvertent opera- age to the sprinklers - before, during,
Care and tion may result. and after installation. Sprinklers dam-
Absence of an escutcheon, which is aged by dropping, striking, wrench
used to cover a clearance hole, may twist/slippage, or the like, must be re-
Maintenance
delay the time to sprinkler operation in placed. Also, replace any sprinkler
The Series TY-FRB Sprinklers must a fire situation. that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
be maintained and serviced in accord- Sprinklers that are found to be leaking Section).
ance with the following instructions: or exhibiting visible signs of corrosion
must be replaced. Frequent visual inspections are rec-
NOTES ommended to be initially performed for
Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers,
main control valve for maintenance painted, plated, coated or otherwise after the installation has been com-
TFP171 Page 9 of 10
2-7/8"DIA. 2-7/8"DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2" 12,7 mm)
(15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm)
FACE OF (57,2 mm) AlMOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PATE SPRINKLER PLATE
FITTING FITTING
1/8"
(3,2 mm) (3,2 m)
MOUNTING
MOUNTING SURFACE
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-114" 31,8 mm)
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 10 FIGURE 11
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 112 INCH NPT 5.6 K-FACTOR, 112 INCH NPT
2-7/8"DIA. 2-7/8"DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm
(15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 114"(6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" ( 1/8"
(3,2 mm) (3,2 mm)
MOUNTING
MOUNTING SURFACE
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 12 FIGURE 13
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314/NCH TOTAL ADJUSTMENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 314 INCH NPT 8.0 K-FACTOR, 314 INCH NPT
pleted,to verify the integrity of the cor- WRENCH
rosion resistant coating. Thereafter, RECESS
annual inspections per NFPA 25
should suffice; however, instead of in- WRENCH RECESS
specting from the floor level,a random (END"A"USED FOR
sampling of close-up visual inspec- 1/2"NPT MODELS)
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the 6
corrosion resistant coating, as it may WRENCH RECESS PUSH WRENCH
be affected by the corrosive conditions (END"B"USED FOR IN TO ENSURE
present. 3/4"NPT MODELS) ENGAGEMENT
WITH SPRINKLER
The owner is responsible for the in- FIGURE 14 WRENCHING AREA
spection, testing, and maintenance of W-TYPE 6 SPRINKLER
their fire protection system and de- WRENCH FIGURE 15
vices in compliance with this docu- W-TYPE 7 RECESSED
ment, as well as with the applicable SPRINKLER WRENCH
to an
standards of the National Fire Protec- er should be contacted relative
tion Association (e.g., NFPA 25), in to any questions.
addition to the standards of any other It is recommended that automatic Inspection Services accordance with
authorities having jurisdiction. The in- sprinkler systems be inspected, local requirements and/or national
stalling contractor or sprinkler manu- tested, and maintained by a qualified codes.
Page 10 of 10 TFP171
P/N 57 - XXX - X - XXX
TEMPERATURE
MODEL/SIN RATING
SPRINKLER
330 2.8K UPRIGHT(1/2"NPT) TY1131 135 135'F/57*C
331 2.8K PENDENT(1/2"NPT) TY1231 1 NATURAL BRASS 155 155*F/68*C
340 4.2K UPRIGHT(1/2"NPT) TY2131 4 WHITE POLYESTER 175 175*F/79°C
341 4.2K PENDENT(1/2"NPT) TY2231 3 WHITE(RAL9010)* 200 200*F/93*C
370 5.6K UPRIGHT(1/2"NPT) TY3131 9 CHROME PLATED 286 286°F/141°C
371 5.6K PENDENT(1/2"NPT) TY3231 7 LEAD COATED
390 8.OK UPRIGHT(3/4"NPT) TY4131
391 8.OK PENDENT(3/4-NPT) TY4231 *Eastern Hemisphere sales only.
360 8.OK UPRIGHT(1/2-NPT) TY4831*
361 8.OK PENDENT(1/2"NPT) TY4931*
TABLE D
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
In no event shall TFBP be liable, in
Limited
contract, tort, strict liability or under Ordering
any other legal theory, for incidental,
Warranty
indirect,special or consequential dam- Procedure
ages, including but not limited to labor
Products manufactured by Tyco Fire& charges, regardless of whether TFBP When placing an order, indicate the
Building Products (TFBP) are war- was informed about the possibility of full product name. Refer to the Price
ranted solely to the original Buyer for such damages, and in no event shall List for complete listing of Part Num-
ten(10)years against defects in mate- TFBP's liability exceed an amount bers.
rial and workmanship when paid for equal to the sales price. Contact your local distributor for avail-
and properly installed and maintained
under normal use and service. This The foregoing warranty is made in lieu ability.
warranty will expire ten (10) years of any and all other warranties. ex-
from date of shipment by TFBP. No Dress or implied, including warranties Sprinkler Assemblies with NPT
warranty is given for products or com- of merchantability and fitness forapar- Thread Connections:
ponents manufactured by companies ticular purpose. Specify: (Specify Model/SIN), Quick
not affiliated b ownership with TFBP Response, (specify K-factor), (specify
Y P This limited warranty sets forth the ex- temperature rating), Series TY-FRB
or for products and components which clusive remedy for claims based on (specify Pendent or Upright)Sprinkler
have been subject to misuse,improper failure of or defect in products, materi- with(specify type of finish or coating),
installation, corrosion, or which have als or components, whether the claim P/N (specify from Table D).
not been installed, maintained, modi- is made in contract, tort, strict liability
fied or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon:
plicable Standards of the National Fire
Protection Association, and/or the This warranty will apply to the full ex- Specify: Style (10, 20, 30, or 40) Re-
standards of any other Authorities tent permitted by law.The invalidity, in cessed Escutcheon with (specify*)fin-
Having Jurisdiction. Materials found whole or part, of any portion of this ish, P/N (specify*).
by TFBP to be defective shall be either warranty will not affect the remainder.
*Refer to Technical Data Sheet TFP770.
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor Sprinkler Wrench:
authorizes any person to assume for it, Specify: W-Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56-000-6-387.
the sale of products or parts of prod-
ucts.TFBP shall not be responsible for Specify: W-Type 7 Sprinkler Wrench,
sprinkler system design errors or inac- P/N 56-850-4-001.
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446
�00F—
0
m
O
r
-106 R .
uj
LM
i
tt
£s
... IA
l Y;moi r C9r1
i
SchedulemlO"/Schedulem4O"
Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-10/Schedule-40 sprinkler pipe you get a UL listed and FM approved product.Although these
products do not require separate approvals, Schedule-10/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10(1'/4"-8")pipe and Sch-40(1"-2'/Z")pipe have passed the same thorough lab testing as our other listed pipe
products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
Galvanized Pipe .0 Specifications
NPS Nominal I.D. Wt. Wt.(H20 Filled) Pcs/ Mitt(21') Wt/Lift(24') Waitt(25'
Schedule-"galvanized
product can be In;mm In;mm Lbs/Ft•Kg/m Lbs/Ft,•Kg/m Lift Lbs;Kg Lbs;Kg Lbs;Kg
"hot-dip"galvanized to meet FM
requirements for dry systems in 1" 1.049 1.680 2.05 70 2,470 2,822 2,940
accordance with the zinc coating 25 26.6 2.5 3.05 70 1,120 1,280 1,334
specifications of ASTM A-123. 1'/4° 1.380 2.270 2.93 51 2,431 2,778 2,894
32 35.1 4.36 4.36 51 1,103 1,260 1,313
Superior • • ■ 1'/z" 1.610 2.720 3.61 44 2,513 2,872 2,992
40 40.9 4.0 5.37 44 1,140 1,303 1,357
Our advanced formula mill coating of- 2" 2.067 3.650 5.13 30 2,300 2,628 2,738
fers a clean,durable surface. It is also 50 52.5 5.4 7.63 30 1,043 1,192 1,242
paint-ready for custom color applications 21/2" 2,469 5.790 7.86 19 2,310 2,640 2,750
without special preparation. 65 62.7 8.6 11.73 19 1,048 1,197 1,247
The internal surface of all black Allied
Tube&Conduit Fire Sprinkler pipe Specifications
products up to 4.5000"in diameter is
coated with our new Antibacterial For- NPS Nominal I.D. Wt. Wt.(H20 Filled) Pcs/ Wt/Lift(21') WVLift(24') Waift(25'
mula,"ABF". In scientific laboratory In,mm In;mm Lbs/Ft,Kg/m Lbs/Ft,Kg/m Lift Lbs,•Kg Lbs;Kg Lbs;Kg
test,ABS proved to have superior resis- 1" 1.097 1.400 1.81 91 2,675 3,053 3,185
tance to microbial colonization of pipe 25 27.9 2.1 2.70 91 1,213 1,385 1,445
walls,thereby delaying or possibly pre- 1'/4" 1.442 1.810 2.52 61 2,319 2,664 2,760
venting the onset of Microbiologically 32 36.6 2.7 3.75 61 1,052 1,208 1,252
Influenced corrosion(MIC)when the 1Yz" 1.682 2.080 3.04 61 2,664 3,045 3,172
First Sprinkler System is first installed. 40 42.7 3.1 4.52 61 1,208 1,381 1,439
American . • 2" 2.157 2.640 4.22 37 2,051 2,344 2,442
50 54.8 3.9 6.28 37 930 1,063 1,108
Meets"Buy American"requirement 2'/z^ 2.635 3.530 5.89 30 2,224 2,542 2,648
and is available through distributors in 65 66.9 5.3 8.77 30 1,009 1,153 1,201
the USA,Canada and Mexico. 3" 3.260 4.330 7.94 19 1,728 1,975 2,057
•ecifications80 82.8 6.4 11.82 19 784 896 933
S & Approvals
4" 4.260 5.610 11.78 19 2,238 2,558 2,665
Schedule-10/Schedule-40 pipe are in 90 108.2 8.3 17.53 19 1,015 1,160 1,209
compliance with the following: 5" 5.295 7.77 17.33 10 1,632 1,865 1,943
125 134.5 11.56 25.80 10 740 846 881
ASTM A-135, and NFPA 13.Both pipe 6" 6.357 9.290 23.03 10 1,951 2,230 2,322
products have a working pressure rating 150 161.5 13.8 34.27 10 885 1,012 1,053
of 300 psi maximum and also meet the 8• 8.249 16.490 40.15 7 2,424 2,770 2,885
stringent requirement for the following 200 209.5 24.5 59.75 7 1,100 1,256 1,309
tests:
•Welded Outlets U L <S> L�
•Hydrostatic Pressure Listed Approved Listed
•Side Wall Rupture
•Vibration Test
CO Flow Control n 16100 S. Lathrop• Harvey, IL 60426 Customer Service:
f
y l `T/ all1ed 11350 Norcom Rd. • Philadelphia, PA 19154 (800)882-5543
TUBE&CONDUIT 2525 N. 27 th Ave. • Phoenix,AZ 85009 Fax 708-339-1806
S5-3
D.I. THREADED FITTINGS
STAR"PIPEPRODUCTS
._._A--,. LISTED LISTED APPROVED
For fire protection services request submittal GRS 1.3
Ductile iron threaded fittings are UL,ULC listed and factory mutual approved for 500 psi
service.Ductile iron per ASTM A 536 grade 65-45-12.Dimensions conform to ANSI B16.3
class 150.Threads are NPT perANSI/ASME 131.20.1.
B NOTICE:Ductile iron fittings have higher tensile strength than that of steel pipe.Therefore,
over tightening can cause damage to pipe threads which may cause leakage.Ductile iron
fittingd should be tightened theree turns beyond hand tight,but no more than four turns.
DUCTILE IRON • 1 DEG. ELBOW
NOMINAL I ITEM MAX. DIMENSIONS WEIGHT
SIZE CODE WORIONG EACH
(INCH) # P.S.I. A B PIECE
1 DB90033 500 1.50 1.50 0.62
11/4 DB90044 500 1.75 1.75 0.90 + ,;
11/2 DB90055 500 1.94 1.94 1.20 `
2 DB90066 500 2.25 2.25 1.85
8
DUCTILE
IRON 45 DEG. ELBOW
NOMINAL ITEM MAX. DIMENSIONS WEIGHT
A � _ SIZE CODE WOPJQNG EACH
(INCH) # P.S.I. A B PIECE
1 DB45033 500 1.12 1.12 0.46
DUCTILE IRON RED.90 DEG. ELBOW11/4 DB45044 500 1.29 1.29 0.73
NOMINAL ITEM MAX. DIMENSIONS WEIGHT 11/2 DB45055 500 1.43 1.43 0.92
2 DB45066 500 1.68 1.68 1.50
SIZE CODE WORIQNG EACH
7-771
(INCH) # P.S.I. AT
PIECE
1X1/2 DB90031 500 1.26 1.36 0.44
1X3/4 DB90032 500 1.37 1.45 0.52 -
11/4X1/2 DB90041 500 1.34 1.53 0.64 I
1 1/4X3/4 DB90042 500 1.45 1.62 0.72
11/4X1 DB90043 500 1.58 1.67 0.75
1112X1 DB90053 500 1.65 1.80 0.92 DUCTILE IRON
11/2X11/4 DB90054 500 1.82 1.88 1.08 NOMINAL ITEM MAX. DIMENSIONS WEIGHT
2X1/2 DB90061 500 1.49 1.88 1.08 SIZE CODE WORFaNG EACH
2X3/4 DB90062 500 1.60 1.97 1.24
2X1 DB90063 500 1.73 2.02 1.40 (INCH) # P.S.I. A B PIECE
2X11/4 DB90064 500 1.90 2.10 1.52 1 DT333 500 1.50 1.50 0.85
2X11/2 DB90065 500 2.02 2.16 1.65 11/4 DT444 500 1.75 1.75 1.22
11/2 DT555 T 500 1.94 1.94 1.55
2 DT666 500 2.25 1 2.25 2.45
A
DUCTILE IRON • '
NOMINAL ITEM MAX. DtMBJSION WEIGHT DUCTILE
IRON RED.
SIZE CODE WORIQNG EACH
(INCH) # P.S.I. A PIECE NOMINAL ITEM MAX. DIMENSION WEIGHT
1 DCL033 500 1.67 0.40 SIZE CODE WORIQNG EACH
11/4 DCLO44 500 1.93 0.57 (INCH) # P.S.I. A PIECE
11/2 DCLO55 500 1 2.15 0.75 1X1/2 DRC 031 500 1.69 0.39
2 DCL066 500 2.53 1.15 1 1X3/4 DRC032 500 1.69 0.53
Page 21
D.I. THREADED FITTINGS
STAR®PIPEPRODUCTS
® a
LISTED LISTED APPROVED
For fire protection services request submittal GRS 1.3
DUCTILE IRONREDUCING
1,57
NOMINAL ITEM MAX. DIMENSIONS WEIGHT
SIZE CODE WORKING EACH
t f
(INCH) # P.S.1. AC PIECE
.A_-�. . _.8.,. 51.3715
1.50 0.71
50 .5 .5
5 --1795-
5 5 .37 1.62 0.90
fi 5 .75 .75
.., 5 .5
_. T.. fi.. --f.5-9-' .5
I
OUTSIDE HEAD INSIDE HEAD 5
I 1/2XIX112 DT5T7- 500 1.41 1.34 Tff-
1 1 ' • 5
NOMINAL ITEM DIMENSIONS 1 ii2xlxl H1.88 1.34- -
SIZE CODE
Arr.
# AFB C SME EACH1x1/2 DBUSH31 0.75 0.25 1.42 OUT 0.22 5
1x314 DBUSH32 0.75 0.25 1.42 OUT 0.17 5
1 114x1 DBUSH43 0.80 0.28 1.76 OUT 0.28
1112x1 DBUSH53 0.83 0.31 2.00 OUT 0.44 5
1 112x1 114 DBUSH54 0.83 0.31 2.00 OUT 0.30
&DBUSH65
DBUSH63 0.88 0.41 1.95 IN 0.66
DBUSH64 0.88 0.34 2.48 OUT 0.72 5
0.88 0.34 2.48 OUT 0.61
2XI 1/2X3/r- 5 .5
5
! A 2X2X1 1/4 Soo .90 75 IN
2X2X1 1/2 355 Z.UZ
DT667
A
• • • A
1
NOMINAL ITEM MAX. DIMENSIONS WEIGHT
SIZE CODE WORKING EACH DUCTILE • ,
(INCH) # P.S.1 A B PIECE
1 DX033 500 1.50 1.50 0.98 NOMINAL ITEM MAX. DIMENSION WEIGHT
1114 DX044 1 500 1.75 1.75 1.50 SIZE CODE WORIaNG EACH
1112 DX055 500 1.94 1.94 1.90 (INCH) # P.S.I. A PIECE
2 DX066 500 2.25 2.25 2.95 1 DCP003 500 1.16 0.32
11/4X1 DX043 500 1.58 1.67 1.27 1114 DCP004 500 1.28 0.43
1112X1 DX053 500 1.65 1.80 1.48 11/2 DCP005 1 500 1.33 0.60
2X1 DX063 500 1.73 2.02 2.10 2 1 DCP006 1 500 1.45 0.91
Page 22