Application Number 12- 00000561 Date 5/09/12
Property Address 800 SEMINOLE RD
Application type description MECHANICAL HVAC ONLY
Property Zoning RES SF DISTRICT
Application valuation . . . 7293
Application desc
CHANGE OUT 1 5TON, 4 3TON AND 3 4 TON SYSTEMS
Owner Contractor
CITY OF ATLANTIC BEACH B & G REFRIGERATION
800 SEMINOLE RD 3230 KLINE RD.
ATLANTIC BEACH FL 32233 JACKSONVILLE FL 32246
(904) 620 -0081
Permit MECHANICAL HVAC PERMIT
Additional desc . 8 UNITS 29 TONS TOTAL
Permit Fee . . . 447.00 Plan Check Fee . . .00
Issue Date . . . Valuation . . . . 0
Expiration Date . 11/05/12
Other Fees STATE MECH DCA SURCHARGE 6.71
STATE MECH DBPR SURCHARGE 6.71
Fee summary Charged Paid Credited Due
Permit Fee Total 447.00 447.00 .00 .00
Plan Check Total .00 .00 .00 .00
Other Fee Total 13.42 13.42 .00 .00
Grand Total 460.42 460.42 .00 .00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247 -5826 Fax (904) 247 -5845
JOB ADDRESS: C, \ A \ \\ A 7 L ), ; 1 . 9 d PERMIT #
PROJECT VALUE $ x .9 1. (7O
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI # y 3u 4LA 313 Ll31
Air Conditioning: Unit Quantity Tons Per Unit 5/3 / y REQUIR D
Heat: Unit Quantity --- B . 's Per Unit Seer Rating 1$
Duct Systems: Total CFM REQUIRED ____f_k_
FIRE PREVENTION
Fire Sprinkler System Quan > y (Requires 3 sets of plans) 7-"--
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans) j / -- 3
Fire Hose Cabinets Quantity (Requires 3 sets of plans) '7`
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans) .?, c
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps f L
# Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons) / j (.7)/k) Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months. I hereby certify that 1 have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name "1 D 0*1.0 1C C Q kI 1 Phone Number ck ‘DDIA7 • ¶ 4D
Mechanical Company \j‘k ae y a*11.Dn 1 Office Phonegt Ma OM Faxq .19au' qv S
Co. Address: 393D �> € 1a City 30A State M Zip ?jo A0
License Holder (Print): 111. \ r1$. C V. State Certification/Registration # n u $1?Nl0?'5
Notarized Signature o Lice s ' , o 1 er' ,,�%`� * t e4,� n
•
" p''% STEPHAN STRANAN worn and subscribed b me - i day of � 1
s a rt, r N otary Public -Sate of Floods / y �� � w. 20 / , My Comm. Expires Apr 12, 2015 gnature of Notary Public ,, j,/, /j / ,J/_ ice _
, rer0 Commission 0 EE 72055
�ai„a�
COMMERCIAL LOAD CALCULATIONS
Manual N
Air Conditioning Contractors of America
For: Name City Hall Phone
Address 850 Seminole Rd.
City Atlantic Beach State & Zip FL
By: Contractor Energy Design Systems, Inc. Phone (904)268 -3670
Address 12132 Weatherwood Estates Dr. W.
City Jacksonville State & Zip FL, 32223
COOLING LOAD
1. DESIGN CONDITIONS Time of Day 3 PM Dly Range 19
Latitude 30 a.Inside db 72 RH 50
b.Outside db 94 wb 77 Grains 49
Otsid db @ 3pm 94 - TOD corr - inside db 72
Equals 22 T.D. Daily Range Factor= M
2. SOLAR RADIATION HEAT GAIN THROUGH GLASS COOLING LOAD
Exposure Shading / NOTES
Sq. Ft. SolrFactr GlasFactr Sensible
N 450 X 19 X 0.7 = 5985
NE X 38 X 0.7 =
E 1000 X 56 X 0.7 = 39200
SE X 57 X 0.7 =
S 450 X 48 X 0.7 = 15120
SW X 88 X 0.7 =
W 1000 X 81 X 0.7 = 56700
NW X 39 X 0.7 =
3. TRANSMISSION GAINS
Equiv or
Exposure db
Sq. Ft. U Factor Temp Diff
Glass 2900 X 0.8 X 22 = 51040
N 500 X 0.09 X 22 = 990
NE X 0.09 X 26 =
E 1200 X 0.09 X 31 = 3348
Walls SE X 0.09 X 33 =
S 500 X 0.09 X 41 = 1845
SW X 0.09 X 47 =
W 1200 X 0.09 X 43 = 4644
NW X 0.09 X 28 =
Doors 62 X 0.58 X 18 = 642
Partition X 0.05 X 22 =
RA Cing X 0.09 X 22 =
Roof/Clng 6653 X 0.05 X 57 = 18961
Floors 350 X X 22 =
X X =
Use Table 9a to Determine the Temp. Dif. Across an RA Ceiling
PAGE TWO
4. INTERNAL HEAT GAIN
Latent
a. OCCUPANTS Number Sensible Latent
100 X 230 = 23000
X =
100 X 170 = 17000
X =
b. Lights & Others
NOTE:Use 600 of installed
watts for lights in
RETURN AIR CEILING
Watts
Incandescnt X 3.4 =
Flourescent 7100 X 4.1 = 29110
HP
Motors Btuh Usg Ftr
X =
X =
Appliances 60000
Other
5. INFILTRATION
Ft3 /Min db Temp Dif
222 X 22 X 1.1 = 5372
Grains Diff
222 X 49 X 0.68 = 7397
6. SUBTOTALS LOADS & SPACE LOADS 315957 24397
7. DUCT HEAT GAIN
Gain Line 6
Factor Sensible
0.1 X 315957 =
8. ROOM, SPACE OR DESIGN LOAD
Add Duct gain (7) to Subtotal (6) 315957
9. VENTILATION
Ft3 /Min db Temp Dif
2000 X 22 X 1.1 = 48400
Grains Diff
2000 X 49 X 0.68 = 66640
PAGE THREE
10. RETURN AIR LOAD FROM LIGHTING AND ROOF
NOTE: Use 40% of watts for lights recessed
in a return air ceiling
Incandescent X 3.4 =
Flourescent X 4.1 =
NOTE: Use 100% fo the roof load
for return air ceilings
(Roof Load)
Sq. Ft. U Factor ETD*
X 0.09X =
*(ETD correction based on plenum temp.)
11. TOTAL SENSIBLE LOAD ON EQUIPMENT (Btuh) - 364357
TOTAL LATENT LOAD ON EQUIPMENT (Btuh) 91037
12. TOTAL COOLING LOAD ON EQUIPMENT (Btuh) 1 455394
(Tons) 37.95
PAGE FOUR
HEATING LOAD
13. DESIGN LOADS
Inside db Outside db b Difference
72 - 32 = 40
14. TRANSMISSION LOSSES HEATING LOAD
db
Exp. Sq. Ft. Factor Temp Diff Heating Load
Windows 3400 x 1.13 x 40 = 153680
x x =
1200 x 0.09 x 40 = 4320
Walls 500 x 0.09 x 40 = 1800
x 0.09 x =
1200 x 0.09 x 40 = 4320
x 0.09 x =
Roof/ 6653 x 0.05 x 40 = 13306
Ceiling x 0.05 x =
x x =
Floor 350 x 0.81 x 40 = 11340
Other x x =
x x =
15. INFILTRATION
db
Ft3 /Min Temp Diff
333 X 40 X 1.1 = 14652
16. SUBTOTAL HEATING LOAD FOR SPACE 203418
17. DUCT HEATING LOSS
Loss Line 14
Factor Subtotal
0.15 X 188766 = 28315
18. VENTILATION
db
Ft3 /Min Temp Diff
200G X 40 X 1.1 = 88000
19. HUMIDIFICATION LOAD
Inside RH Desired ( ) Max ( )
Ft3 /Min Btu /Hr
/ 100 X =
(water) (air)
gal /day Ft3 /Min
X / 100 =
20. TOTAL HEATING LOAD ON EQUIPMENT (Btuh) I 319733 1
(Tons) 26.64
Energy Design Systems, Inc.
12132 Weatherwood Estates Dr. W.
Jacksonville, FL 32223