Permit Mech 449 Sailfish Dr 2012 1
, JA z � ` CITY OF ATLANTIC BEACH
s) 800 SEMINOLE ROAD
J =" ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247 -5814
Application Number 12- 00000614 Date 5/18/12
Property Address 449 SAILFISH DR
Application type description MECHANICAL HVAC ONLY
Property Zoning TO BE UPDATED
Application valuation . . . 2800
Application desc
CHANGE OUT 2.T TON SYSTEM
Owner Contractor
SPRUANCE, KIENAN SOLUTIONS HEATING AND AIR, INC
449 SAILFISH DR E 1570 CREEK POINT BLVD
ATLANTIC BEACH FL 32233 JACKSONVILLE FL 32218
(904) 349 -0026
Permit MECHANICAL HVAC PERMIT
Additional desc . CHANGE OUT 2.5 TON SYSTEM
Permit Fee . . . 95.00 Plan Check Fee . . .00
Issue Date . . . Valuation . . . . 0
Expiration Date . 11/14/12
Other Fees STATE MECH DCA SURCHARGE 2.00
STATE MECH DBPR SURCHARGE 2.00
Fee summary Charged Paid Credited Due
Permit Fee Total 95.00 95.00 .00 .00
Plan Check Total .00 .00 .00 .00
Other Fee Total 4.00 4.00 .00 .00
Grand Total 99.00 99.00 .00 .00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
5 Ph (904) 247 -5826 Fax (904) 247 -5845
JOB ADDRESS: W y 9 J C 11-1;5 OR PERMIT #
PROJECT VALUE $ akOO• as
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI# yatggi1
Air Conditioning: Unit Quantity 1 Tons Per Unit a , S - REQU &ED
Heat: Unit Quantity i BTU's Per Unit 30, 000 Seer Rating
Duct Systems: Total CFM ,S ,0 REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
# Vented Wall Furnaces Refrierator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months. I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name ^ \ Phone Number
Mechanical Company / - — "Ire_ Office Phone Fax
Co. Address: City State Zip
License Holder Prin GC t : F
( ) State Certification/Registration #
Notarized Signature o License Hi � , b.1 o y aef ■
"" ► "% DEBORAH AMANDA E 411 * <• MY COMM # EE and subscribed before . e this • . da f / / 20%
... EXPIRES: May 21, 2015
i /
II H)•.7L� Bonded Thai Notary Public •� • • i re of Notary Public id - . c '
Page 1 Residential Heat Loss and Heat Gain Calculation 5/17/2012
In accordance with ACCA Manual J
Report Prepared By:
Solutions Heating and Air, Inc.
1570 Creek Point Blvd
Jacksonville, FL 32218
CAC 1816876
For. KIENAN SPRUANCE
449 Sailfish Dr
Atlantic Beach, Florida
Design Conditions: Jacksonville
Indoor. Outdoor.
Summer temperature: 75 Summer temperature: 94
Winter temperature: 72 Winter temperature: 32
Relative humidity: 55 Summer grains of moisture: 114
Daily temperature range: Medium
Building Component Sensible Latent Total Total
Gain Gain Heat Gain Heat Loss
(BTUH) (BTUH) (BTUH) (BTUH)
Whole House 1,040 sq.ft. 26,577 4,005 30,582 41,007
(2.5tons)
First Floor 26,577 30,582 41,007
All Rooms 1,040 sq.ft. 26,577 4,005 30,582 41,007
Infiltration 2,369 3,315 5,684 11,715
- Tightness: Poor; Winter ACH: 1.71 ; Summer ACH: .73
Duct 2,416 0 2,416 1,953
- _Supply below 120; Exposed to outdoor ambient; R -6
People 3 900 690 1,590 0
Floor 1,040 sq.ft. 0 0 0 4,277
w Concrete slab on grade; Concrete; No edge insulation
E Wall 314 sq.ft. 1,923 0 1,923 3,404
- Wood frame, with sheathing, siding or brick; None; none
Window 24 sq.ft. 2,117 0 2,117 1,109
- Single pane; Metal frame; Clear glass
- No inside shading; Coating: None (clear glass); No outside shading.
Window (2) 4 sq.ft. 353 0 353 185
- Single pane; Metal frame; Clear glass
_No inside s hading; Coating: None (clear glass); No outside shading.
Door 18 sq.ft. 77 0 77 137
- Metal; Urethane; No storm
N Wall 468 sq.ft. 2,866 0 2,866 5,073
-Wood frame, with sheathing, siding or brick; None; none
W Wall 278 sq.ft. 1,703 0 1,703 3,014
r
Page 2 KIENAN SPRUANCE 5/17/2012
Building Component Sensible Latent Total Total
Gain Gain Heat Gain Heat Loss
(BTUH) (BTUH) (BTUH) (BTUH)
- Wood frame, with sheathing, siding or brick; None; none
Window _ 16 sq.ft. 1,411 0 1,411 739
- Single pane; Metal frame; Clear glass
- No inside shading; Coating: None (clear glass); No outside shading.
Window (2) 48 sq.ft. 4,234 0 4,234 2,218
- Single pane; Metal frame; Clear glass
- No inside shading; Coating: None (clear glass); No outside shading.
Door 18 sq.ft. 77 0 77 137
- Metal; Urethane; No storm
S Wall 210 sq.ft. 1,286 0 1,286 2,276
- Wood frame, with sheathing, siding or brick; None; none
Window 24 sq.ft. 1,133 0 1,133 1,109
- Single pane; Metal frame; Clear glass
_No inside shading; Coating: None (clear glass); No outside shading.
Ceiling 1,040 sq.ft. 3,712 0 3,712 3,661
- Under ventilated attic; R -11 (3 - 3.5 inch); Dark
Whole House 1,040 sq.ft. 26,577 4,005 30,582 41,007
(2.5 tons )
HVAC -Calc Residential 4.0 by HVAC Computer Systems Ltd. 888 736 -1101
Load calculations are estimates only, actual loads may vary due to weather and construction differences
*Change yGYa" ge � .
Q p N Ve y
� � Q pQ ry
o Ji ap�.
0 9
449 Sailfish Dr. �.�
4 `oc k `o R
� n�Cll -lf 40 OCU if eGM
Atlantic Beach, Fl
Manual J Calculation
By Solutions heating and Air, Inc
r ...., 1 ................1
UST
BAS
F CP `
L 16
3 -:‘---16----3- 24