Permit Mech 850 Seminole 2012 k o CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
'-) ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247 -5814
Olt C.
Application Number 12- 00000633 Date 5/23/12
Property Address 850 SEMINOLE RD
Application type description MECHANICAL HVAC ONLY
Property Zoning RES SF DISTRICT
Application valuation . . . 0
Application desc
2 cu 2 ahu
Owner Contractor
CITY OF ATLANTIC BEACH B & G REFRIGERATION
800 SEMINOLE RD 3230 KLINE RD.
ATLANTIC BEACH FL 32233 JACKSONVILLE FL 32246
(904) 620 -0081
Permit MECHANICAL HVAC PERMIT
Additional desc .
Permit Fee . . . 151.00 Plan Check Fee . . .00
Issue Date . . . Valuation . . . . 0
Expiration Date . 11/19/12
Other Fees STATE MECH DCA SURCHARGE 2.27
STATE MECH DBPR SURCHARGE 2.27
Fee summary Charged Paid Credited Due
Permit Fee Total 151.00 151.00 .00 .00
Plan Check Total .00 .00 .00 .00
Other Fee Total 4.54 4.54 .00 .00
Grand Total 155.54 155.54 .00 .00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247 -5826 Fax (904) 247 -5845 I C,6 1 \ JOB ADDRESS: p Q , j- '5f e..xyci.ti \d PERMIT #
PROJECT VALUE $ 1 s .
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATIO
ARI #'4 513 1 - 1L1' .)■•o1
Air Conditioning: Unit Quantity ► I I Tons Per Unit 1- \1 1 •V REQUIRE
Heat: Unit Quantity BTU's Per Unit Seer Rating 1 %
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators /Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
# Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
DTHER:
'emit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months. I hereby certify that I have read
his application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
)r not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
'roperty Owners Name 1 (4' l A, l mC Nex Phone Number 004,1.\--1. F
vlechanical Company ` 71 aec- (� (J,�'(i loo 1 \� Office Phonegba 4 9 •( ) Faxgw'1OW • R5<15
io. Address: 3930 Aline ( J City ICU State P Zip ,)moo N-AlD
License Holder (Print): iil. \ %i L 1 !' ■ State Certification/Registration # CR e, I R IN 03.5
Votarized Signature of License Holder" � ' ,.,'j + , ,� ►�� D i
Torn and subscribed befor e; • - day of 1 02 20
t 0' '' STEPHANEY STRAHAN / �
1 3 ,� = Notary Public -State of flori�ariature of Notary Public / ✓' _e ` ��/
E My Comm. Expires Apr 12, 2015
� i ,; o ' a;,' Commission . EE 72055 0
COMMERCIAL LOAD CALCULATIONS
Manual N
Air Conditioning Contractors of America
For: Name Police Phone
Address 850 Seminole Rd.
City Atlantic Beach State & Zip FL
By: Contractor Energy Design Systems, Inc. Phone (904)268 -3670
Address 12132 Weatherwood Estates Dr. W.
City Jacksonville State & Zip FL, 32223
COOLING LOAD
1. DESIGN CONDITIONS Time of Day 3 PM Dly Range 19
Latitude 30 a.Inside db 72 RH 50
b.Outside db 94 wb 77 Grains 49
Otsid db @ 3pm 94 - TOD corr - inside db 72
Equals 22 T.D. Daily Range Factor= M
2. SOLAR RADIATION HEAT GAIN THROUGH GLASS COOLING LOAD
Exposure Shading / NOTES
Sq. Ft. SolrFactr GlasFactr Sensible
N 20 X 19 X 0.7 = 266
NE X 38 X 0.7 =
E 35 X 56 X 0.7 = 1372
SE X 57 X 0.7 =
S 15 X 48 X 0.7 = 504
SW X 88 X 0.7 =
W 45 X 81 X 0.7 = 2552
NW X 39 X 0.7 =
3. TRANSMISSION GAINS
Equiv or
Exposure db
Sq. Ft. U Factor Temp Diff
Glass 115 X 0.8 X 22 = 2024
N 1200 X 0.09 X 22 = 2376
NE X 0.09 X 26 =
E 1345 X 0.09 X 31 = 3753
Walls SE X 0.09 X 33 =
S 1200 X 0.09 X 41 = 4428
SW X 0.09 X 47 =
W 1345 X 0.09 X 43 = 5205
NW X 0.09 X 28 =
Doors 254 X 0.58 X 18 = 2629
Partition X 0.05 X 22 =
RA Cing X 0.09 X 22 =
Roof/Clng 5420 X 0.05 X 57 = 15447
Floors 414 X X 22 =
X X =
Use Table 9a to Determine the Temp. Dif. Across an RA Ceiling
PAGE TWO
4. INTERNAL HEAT GAIN
Latent
a. OCCUPANTS Number Sensible Latent
50 X 230 = 11500
X =
50 X 170 = 8500
X =
b. Lights & Others
NOTE:Use 60% of installed
watts for lights in
RETURN AIR CEILING
Watts
Incandescnt X 3.4 =
Flourescent 6500 X 4.1 = 26650
HP
Motors Btuh Usg Ftr
X =
X=
Appliances 19500
Other
5. INFILTRATION
Ft3 /Min db Temp Dif
151 X 22 X 1.1 = 3654
Grains Diff
151 X 49 X 0.68 = 5031
6. SUBTOTALS LOADS & SPACE LOADS 101859 13531
7. DUCT HEAT GAIN
Gain Line 6
Factor Sensible
0.1 X 101859 =
8. ROOM, SPACE OR DESIGN LOAD
Add Duct gain (7) to Subtotal (6) 101859
9. VENTILATION
Ft3 /Min db Temp Dif
1000 X 22 X 1.1 = 24200
Grains Diff
1000 X 49 X 0.68 = 33320
PAGE THREE
10. RETURN AIR LOAD FROM LIGHTING AND ROOF
NOTE: Use 40% of watts for lights recessed
in a return air ceiling
Incandescent X 3.4 =
Flourescent X 4.1 =
NOTE: Use 100% fo the roof load
for return air ceilings
(Roof Load)
Sq. Ft. U Factor ETD*
X 0.09X =
*(ETD correction based on plenum temp.)
11. TOTAL SENSIBLE LOAD ON EQUIPMENT (Btuh) = 126059
TOTAL LATENT LOAD ON EQUIPMENT (Btuh) 46851
12. TOTAL COOLING LOAD ON EQUIPMENT (Btuh) 1 172911
(Tons) 14.41
PAGE FOUR
HEATING LOAD
13. DESIGN LOADS
Inside db Outside db b Difference
72 - 32 = 40
14. TRANSMISSION LOSSES HEATING LOAD
db
Exp. Sq. Ft. Factor Temp Diff Heating Load
Windows 1315 x 1.13 x 40 = 59438
X X =
1345 x 0.09 x 40 = 4842
Walls 1200 x 0.09 x 40 = 4320
x 0.09 x =
1345 x 0.09 x 40 = 4842
x 0.09 x =
Roof/ 5420 x 0.05 x 40 = 10840
Ceiling X 0.05 x =
x x =
Floor 414 x 0.81 x 40 = 13414
Other x x =
x x =
15. INFILTRATION
db
Ft3 /Min Temp Diff
227 X 40 X 1.1 = 9966
16. SUBTOTAL HEATING LOAD FOR SPACE 107662
17. DUCT HEATING LOSS
Loss Line 14
Factor Subtotal
0.15 X 97696 = 14654
18. VENTILATION
db
Ft3 /Min Temp Diff
1000 X 40 X 1.1 = 44000
19. HUMIDIFICATION LOAD
Inside RH Desired ( ) Max ( )
Ft3 /Min Btu /Hr
/ 100 X =
(water) (air)
gal /day Ft3 /Min
X / 100 =
20. TOTAL HEATING LOAD ON EQUIPMENT (Btuh) 1 166316 1
(Tons) 13.86
Energy Design Systems, Inc.
12132 Weatherwood Estates Dr. W.
Jacksonville, FL 32223
(904) 268 -3670