Permit Mech 459 Ocean Blvd 2012 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
............. INSPECTION PHONE LINE 247-5814
!tit
Application Number . . . . . 12-00000637 Date 5/23/12
Property Address . . . . . . 459 OCEAN BLVD
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
GRUNTHAL LEONARD H III & AIR TO AIR
ALISON J 11578 DAVIS CREEK CT
459 OCEAN BLVD JACKSONVILLE FL 32256
ATLANTIC BEACH FL 322335337 (904) 262-4279
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 99 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 11/19/12
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 99 . 00 99 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 103 . 00 103 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALI, CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (904) 247-5845
JOB ADDRFSS:eq 42,2zyl� PERmrr#
PROJECT VALUE $Aq-f
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI#_V q q 11,W
Air Conditioning: Unit Quantity Tons Per Unit 3 REQUIRED
Heat: Unit Quantity I BTU's Per Unit Seer Rating 13.0
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authorit, rovisions of any other state or local law regulation construction or the performance of construction.
y to violate the p
Property Owners Name J� 14,1,1 Phone Number
Mechanical Companyr,4 - 42b,., Office PhoneZk 4�'N Faxj��/ �,�z-
Co. Address: 11-5,79 D6"� J"/Wj, a,6"� city cl–z State—ZipfVZ
License Holder(Print). State Certification/Registration kj�,Q/944(�X
Notarized Signature of License Holder
DELENE STONER Sworn and subscribed before me this 1� nj day of��a 20/,-,2
MY COMMISSION#DD876309
EXPIRES:May 22,2013 Signature of Notary Public,,/,�,
1-800-.3-NOTARY F1 Notary Discount Amm.Co�
Job:
wrightsoft Project Summary Date: 05/23/12
Entire House By: JH
Air to Air Inc.
11578 Davis Creek Ct,Jacksonville,FL 32256 Phone:W4-262-4279 Fax:904-262-0772
Project Information
For: GRUNTHAL RESIDENCE
Notes: 459 OCEAN BLVD
Design Information
Weather: Jacksonville, Cecil Field NAS, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 34 OF Outside db 95 OF
Inside db 70 OF Inside db 75 OF
Design TD 36 OF Design TD 20 OF
Daily range M
Relative humidity 50 %
Moisture difference 40 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 30378 Btuh Structure 22240 Btuh
Ducts 2603 Btuh Ducts 2719 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
pipigg 0 Btuh
Equipment load 32982 Btuh Use manufacturers data n
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 24959 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Semi-tight
Fireplaces 0 Structure 1102 Btuh
Ducts 525 Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area(ft2) 3345 3345 Equipment latent load 1627 Btuh
Volume(W) 15415 15415
Air changes/hour 0.19 0.10 Equipment total load 26686 Btuh
Equiv.AVF(cfm) 49 26 R6q.total capacity at 0.70 SHR 3.0 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make
Trade Trade
Model Cond
AHRI ref no. Coil
AHRI ref no.
Efficiency 80AFUE Efficiency 0 SEER
Heating input 0 Btuh Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 OF Total cooling 0 Btuh
Actual air flow 1135 cfm Actual air flow 1135 cfm
Air flow factor 0.034 cfm/Btuh Air flow factor 0.045 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
Space thermostat Load sensible heat ratio 0.94
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2012-May-23 10:01:19
+ wr1ghtS0ft* Right-SuftaO universal 2012 12.0.07 RSU10246 Page i
AM ......WBIJILDER DATXB.11der DataICHANGE OUTSACKERMAN RES.rup Calc-MJ8 Front Door faces: