Permit Mech 307 4th St 2012 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-000006S2 Date 5/2S/12
Property Address . . . . . . 307 4TH ST
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------
------------------------
P & H BEACH PARTNERS LLC ONE HOUR AIR
2309 FIDDLERS LANE 101S ATLANTIC BLVD #249
ATLANTIC BEACH FL 32233 ATLANTIC BEACH FL 32233
(904) 222-8482
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 11/21/12
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 95 . 00 95 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (904) 247-5845
JOBADDRESS: _�0_7 Z_/7" S7- PERMIT
PROJECT VALUE $ ARI �ZS 2 e ,3 2�s
REQUIRED
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit _Z 3
Heat: Unit Quantity BTU's Per Unit�QI-100 Seer Ratiniz I
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name DA PC's-/ r I&a_-) -Phone Number 9 23-1(,�_CJ —
Mechanical Company niue_ �-b U C A I tz- —Office Phone2 V/-3/6 7 Fax.29-2-5_S'2C
Co. Address: C& JMA�Z(900� city -Y-State )C�_zip 32233
12.0
License Holder(Print): Caq I(f, -SUtcy,,Cer�?flcation/Registration#nqc/cq/��
Notarized Signature of License Holder
71/
Sworn and subscribed before t is d 20
Signature of Notary Public 0 -a, n
I C�
Job: 118386
wrightsolt Project Summary Date: 5/25/2012
Entire House By:
ONE HOUR AIR
1198 MAYPORT RD#1,ATLANTIC BEACH,FL 32233 Phone:904-241-3107 Fax:904-247-5526 License:118386
Project Information
For: DAVE PESTERFIELD
307 4TH ST,ATLANTIC BEACH, FL 32233
Phone: 904-923-1150
Notes:
Design Information
Weather: Jacksonville/Craig, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 35 'F Outside db 91 *F
Inside db 70 'F Inside db 75 'F
Design TD 35 *F Design TD 16 'F
Daily range M
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 14552 Btuh Structure 17789 Btuh
Ducts 0 Btuh Ducts 0 Btuh
Central vent(0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 14552 Btuh Use manufacturers data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 17789 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 1926 Btuh
Ducts 0 Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area(ft� 736 736 Equipment latent load 1926 Btuh
Volume (ft3) 5888 5888
Air changes/hour 0.61 0.32 Equipment total load 19715 Btuh
Equiv.AVF(cfmi) 60 31 Req.total capacity at 0.74 SHR 2.0 ton
Heating Equipment Summary Cooling Equipment Summary
Make GOODMAN Make GOODMAN
Trade ONE HOUR AIR Trade ONE HOUR AIR
Model GSZ130241 Cond GSZ130241
AHRI ref no.4526325 Coil
AHRI ref no.4526325
Efficiency 0 HSPF Efficiency 13SEER
Heating input Sensible cooling 17293 Btuh
Heating output 0 Btu h @ 47-F Latent cooling 6107 Btuh
Temperature rise 0 *F Total cooling 23400 Btuh
Actual air flow 810 cfm Actual air flow 810 cfm
Air flow factor 0.056 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
Space thermostat Load sensible heat ratio 0.90
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2012-May-25 05:47:16
wr,19htS40ft' Right-SuiteO universal 2012 12.0.04 Right JS Mobile Page I
Ak C:\WNDOWS\TEMP\wstmp\O9c4a8l8-a4b3-4652-86dl-lc8573al4b9f.rup Calc=MJ8 Front Door faces: N
CERTIFIEDTM
Lwww.ahridirectory.org A
CertLificate of Product Ratings
AHRI Certified Reference Number: 4526325 Date: 5/25/2012
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: GSZ130241B*
Indoor Unit Model Number: AR*F182416C*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN, JANITROL,AMANA DISTINCTIONS, EVERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system combination is GOODMAN MANUFACTURING CO., LP.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity (Btuh): 23400
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00
Heating Capacity(Btuh) @ 47 F: 23000
Region IV HSPF Rating (Heating): 7.70*
Heating Capacity(Btuh)@ 17 F: 13400*
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accornpanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the products),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products ofAHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents ofthis Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except forthe user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this cerdficate can be verified at www.ahridirectory.org, Ai r-Conditioning,Heating,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on 00 ILI and Refrigeration Institute
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below.
@2012 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 129824261369938032