Permit Mech 5611 Fleet Landing 2012 CITY OF ATLANTIC UACH
800 SEMINOLI,E ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE �47-5814
r
Application Number . . . . . 12-00000705 Date 6/06/12
Property Address . . . . . . 1 FLEET LANDING BLVD MAIN
Tenant nbr, name . . . . . . UNIT 5611
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
---------------------------------------------------------
-------------
Application desc
1 CU 1 AHU
-------------------------------------------------------------- -------------
Owner Contractor
------------------------ -------------------
NAVAL CONTINUING CARE DAVID GRAY HEATING AND AIR INC
FLEET LANDING 6491 POWERS AVENUE :i
1 FLEET LANDING BOULEVARD JACKSONVILLE FL 32217
ATLANTIC BEACH FL 32233 (904) 724-7211
-------------------------------------------------------------- -------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc
Permit Fee . . . . 99 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . 0
Expiration Date 12/03/12
-------------------------------------------------------------- -------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
---------------------------------------------------------------- -------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ----------
Permit Fee Total 99 . 00 99 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 103 . 00 103 . 00 . 00
. 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND TIH� FLORIDA
BUILDING CODES.
CERTIFIEDTIA
www.ahrldirectory.org
L
Certificate of Product Ratings
AHRI Certified Reference Number: 4261913 Date: 6/6/2012
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: GSZ1 30361 B*
Indoor Unit Model Number: AR*F363616C*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN,JANITROL,AMANA DISTINCTIONS, EVERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system combination is GOODMAN MANUFACTU!RING CO., LP.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 35000
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00
Heating Capacity(Btuh) @ 47 F: 33600
Region IV HSPF Rating (Heating): 8.00
Heating Capacity(Btuh) @ 17 F: 20800
Ratings followed by an asterisk indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary r I orate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),orthe
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory at wWw.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwillse utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information forthe model cited on this certificate can be verified atwww.ahridirectory.org, "Imp,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on 'al Air-ConditIoning,Heating,
0%200 and Refrigeration Institute
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below. I
@2012 Air-Conditioning, Heating,and Refrigeration Institute CERTIFICATE NO.: 1298 1�4652306627498
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (904) 247-5845
JoB ADDRESS
PERMI't#
Ilk PROJECT VALUE $
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM AEQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI # _cl,2 4,1 9P/3
Air Conditioning: Unit Quantity Tons Per Unit REQU
Heat: Unit Quantity I- BTU's Per Unit-'35-,ono, Seer Rating
Duct Systems: Total CFM AEQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER: V\-
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I heieby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name A yi)Ion Phone Number AN 70 0
Mechanical Company a)CSj-1) cyc'�;c Cg r,� Office Phone i I i Fax ;72-q 5-?-;z 5
Co. Address: 661f�- rcwe 0 A.,Je in t",e city State:-E--c Zip *SZZ 17-
License Hol int): C-irrcs-A 'iu r-k-er/-7 State Cerd bwation/Registration# C PC 0,;7�7-1 ec
OV
"ZA
Notarijg Cense Holder
Sworn and subscribed before this da of 20
my Comm.apir" y
Jsn-rY 10,2014
No.DD VaMia Signature of Notary Public 7-'4A �A
X-Pt
Au \0
L .., LN
F I f
III lit%
Job:
wrightsoft- Right J8 Mobile Report Date: 616/2012
Entire House By:
David Gray Heating and Air, INC.
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:rzabinsky@davidgrayonline.com Web:www.davidgrayonline.com Ucens
J
Project Information
For: Fleet Landing
1 Fleet Landing Boulevard-Unit#5611,Atlantic Beach, FL 32233
Phone: 904-246-9900 Fax: 904-246-9455
Design Conditions
Location: Indoor: Heating Cooling
Jacksonville/Cra FL, US Indoor temperature(T) 70
75
it
Elevation: 4 ft Design TD(T) 35 16
Latitude: 30*N Relative humidity 30 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 8.4
52.8
Dry bulb(T) 35 91 Infiltration:
Da i ly ra nge(*F) - 17 M Method Simplified
Wet bulb(T) - 77 Construction quality Average
Wind speed(mph) 15.0 7.5 Fireplaces 0
Heating
Component Btu h/fI2 Btuh %of load
Walls 8.3 12205 39.2 hiltraficn
Glazing 19.8 4262 13.7
Doors 13.5 433 1.4
VW1
Ceilings 1.7 2438 7.8
Floors 6.2 8963 28.8 R03S
Infiltration 2.1 2869 9.2
Ducts 0 0
Piping 0 0
Humidification 0 0 (Wirgs
Ventilation 0 0 Gaarg CtIff
Adjustments 0
Total 31170, 100.0
Component Btu h/ft2 Btu h %of load
Walls 4.0 5915 26.1 Interne(Gins
Glazing 48.0 10325 45.5 V\/A infiltraticrt
Doors 11.4 367 1.6
Ceilings 2.6 3720 16.4 Ceilings
Floors 0 0 0
Infiltration 0.5 691 3.0
Ducts 0 0 her
Ventilation 0 0
Internal gains 1660 7.3
Blower 0 0
Adjustments 0
Gadng
Total 22678, 100.0
L
Latent Cooling Load 1784 Btuh
Overall U-value=0.152 Btuh/ftl-'F
Data entries checked.
wrightSOft' Right-Suite@ Universal 2012 12.0.04 Right JS Mobile :0012-Jun-06 04:39:00
Page I
C:\WINDOWS\TEMP\wstmpk6b8b4O8e-f6fe-4d7a-9ec9-4f74879125d I.rup Calc MJ8 Front Door faces: N
Job:
wrightsoft Project Summary Date: 61612012
Entire House By:
David Gray Heating and Air, INC.
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:rzabinsky@davidgrayonline.com Web:www.davidgrayonline.com Ucens
Project Information
For: Fleet Landing
1 Fleet Landing Boulevard-Unit#5611,Atlantic Beach, FL 32233
Phone: 904-246-9900 Fax: 904-246-9455
Notes:
Design Information
Weather: Jacksonville/Craig, FL, US
Winter Design Conditions Summer Design Conditions
1 .
Outside db 35 'F Outside db 9111 F
Inside db 70 *F Inside db 75 *F
Design TD 35 'F Design TD 16 *F
Daily range M
Relative humidity 50 %
Moisture difference 53, gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
1
Structure 31170 Btuh Structure 22678 Btuh
Ducts 0 Btuh Ducts 0 Btuh
Central vent (0 cfm) 0 Btuh Central vent(0 cfm) Btuh
Humidification 0 Btuh Blower Btuh
Piping 0 Btuh
Equipment load 31170 Btuh Use manufacturers data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 22670 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average i
Fireplaces 0 Structure 1784 Btuh
Ducts 0 BtUh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area(ft2) 1438 1438 Equipment latent load 1784 Btuh
Volume(ft3) 10066 10066
Air changes/hour 0.45 0.23 Equipment total load 24462 Btu h
Equiv.AVF (cfm) 75 39 Req.total capacity at 0.70 SHR 2.7 ton
Heating Equipment Summary Cooling Equipment Summary
Make Goodman Make Goodman
Trade Trade
Model ARUF Cond GSZ
AHRI ref no. Coil
AHRI ref no.
Efficiency 0 AFUE Efficiency 13SEER
Heating input 0 Btuh Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 *F Total cooling 0 Btuh
Actual air flow 1032 cfm Actual air flow 1032 cfm
Air flow factor 0,033 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
Space thermostat Load sensible heat ratio 0.93
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2012-Jun-06 04:39:00
AS— + wrightSOft- Rig ht-S.itee U niv ersal 2012 12.0.04 Right JO Nb bile Page 1
C:\WINDO\AfS\TEMP\wstmp\6b8b4O8e-f6fe-4d7a-9ec9-4f74879125d 1.rup Calc=MJ8 Front Door faces: N
wr4htwft- Right-X) Worksheet Job:
Entire House Date: 616/2012
By:
David Gray Heating and Air, INC.
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:rzabinsky@davidgrayonline.com Web:www.davidgrayonline.com Licens
I Room name Entire House First Floor
2 Exposed wall 190.8 ft 190.8 ft
3 Room height 9.0 ft 9.0 ft heat/cool
4 Room dimensions 1.0 x J438.0 ft
5 Room area 1438.0 ft' 1438.0 ft2
Ty Construction U-value or HTM Area (ft2) Load) Area (ft2) Load
number Btuhfftl�-'F) (Bt uh/ft or perimeter (ft) (Btuh or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool:1
6 15A-2s3oc-2 0269 n 8.32 4.05 594 517 4300 2092 594 517 14300 2092
1 Dc2ow 0,570 n 19.72 20.91 45 0 887 941 45 0 887 941
11DO 0.390 n 13.49 11.43 32 32 433 367 32 32 433 367
1. V[_f 15A-2s3oc-2 0.269 a 8.06 3.68 252 174 1402 641 252 174 1402 641
1 1 D-c2ow 0.570 a 19.72 63.01 30 0 592 1890 30 0 592 1890
I D-c2owd 0.570 a 19.72 63.01 48 0 947 3024 48 0 947 3024
15A-2s3oc,2 0.269 a 8.42 4.20 612 597 5029 2505 612 597 15029 2505
t-G 1 D�c2ow 0.570 s 19.72 25.16 is 0 296 377 15 0 296 377
5A-2s3oc-2 0.269 w 8.13 3.78 234 171 1390 647 234 171 1390 647
VL:� 11013-w 0.600 w 20.76 33.03 18 0 374 595 18 0 374 595
1 D-c2ow 0.570 w 19.72 63.01 45 0 887 2835 45 0 887 2835
15A-2s3oo-2 0.269 nw 7.37 2.71 25 11 83 31 25 11 83 31
t--G ID-c2ow 0.570 nw 19.72 46.75 14 0 279 662 14 0 ii 279 662
C 16B-19ad 0.049 1.70 2.59 1438 1438 2438 3720 1438 1438 2438 3720
F 22Acph 1.358 46.99 0.00 1438 191 8963 a 1438 191 18963 0
'61 c)AED excursion 1 01 1 1 1 01
Envelope losstgain 1 283011 203271 1 1 28301 1 203271
12 a) Infiltration 2869 691 2869 691
b) Room ventilation 0 0 01 0
13 Internal gains: Occupants @ 230 2 460 2 460
Appliances/other 1200 1200
Subtotal(lines 6 to 13) 31170 22678 311701 22678
Less external 11 ad 0 0 0 0
Less transfer 0 0
0 0
Redistribution 0 0 0 0
14 Subtotal 31170 22678 31170 22678
15 Duct loads 0% 0% 0 0 _0% 0% 0 0
Total room load 1 3111701 226781 1 1 3111701 226781
Air required(cfm) 032 1032 0321 10321
Calculations atpDroved by ACCA to meet all reauirements of Manual J 8th Ed.
:2012-Jun-06 04:39:00
wrightsoft' Right-Suite@ Universal 2012 12.0.04 Right JS Mobile Page 1
Afti,C:\VIANDOWS\TEMP\wstmp\6b8b4O8e-f6fe-4d7a-9eeg-4f74879125dl.rup Calc=MJ8 Front Door faces: N
wrightsoft' Component Constructions Job:
Date: 61612012
Entire House By:
David Gray Heating and Air, INC.
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:r-zabinsky@davidgrayonline.com Web:www.davidgrayonline.com�icens
Project Information
For: Fleet Landing
1 Fleet Landing Boulevard-Unit#5611,Atlantic Beach, FL 32233
Phone: 904-246-9900 Fax: 904-246-9455
Design Conditions
Location: Indoor: Heating Cooling
Jacksonville/Craig, FL, US Indoor temperature(T) 70 75
Elevation: 43 ft Design TD(T) 35 16
Latitude: 30*N Relative humidity(%) 30 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 8.4 52.8
Dry bulb(T) 35 91 Infiltration:
Dailyrange (T) - 17 M Method Simplified
Wetbulb(*F) - 77 Construction quality Average
Wind speed (mph) 15.0 7.5 Fireplaces 0
Construction descriptions Or Area Ll-value Insul R Htg HTM Loss
Clg HTM Gain
ft2 Btuh/W-T ft2-OF/Btuh Btuh/W Btuh BtuhlfF Btuh
Walls
15A-2s3oc-2:Bg wall,heavy dry or light damp soil,empty core, n 517 0.157 2.0 8.32 4300 4.05 2092
concrete block wall,r-2 ins,10"thk e 174 0.157 2.0 8.06 1402 3.68 641
s 597 0.157 2.0 8.42 5029 4.20 2505
w 171 0.157 2.0 8.13 1390 3.78 647
nw 11 0.157 2.0 7.37 83 2.71 31
all 1470 0.157 2.0 8.30 12205 4.02 5915
Partitions
(none)
Windows
1 D-c2ow:2 glazing,clr outr,air gas,wd frm mat,cir innr,1/4"gap, n 45 0.570 0 19.7 887 20.9 941
1/8"thk e 30 0.570 0 19.7 592 63.0 1890
e 48 0.570 0 19.7 947 63.0 3024
s 15 0.570 0 19.7 296 25.2 377
w 18 0.600 0 20.8 374 33.0 595
w 45 0.570 0 19.7 887 63.0 2835
nw 14 0.570 0 19.7 279 46.8 662
all 215 0.570 0 19.8 4262 48.0 10325
Doors
11 DO:Door,wd sc type n 32 0.390 0 13.5 433 11.4 367
Ceilings
16B-1 gad:Attic ceiling,asphalt shingles roof mat,r-1 9 ceil ins, 1/2" 1438 0.049 19.0 1.70 2438 2.59 3720
gypsum board int fnsh
Floors
22A-cph:Bg floor,heavy damp soil,on grade depth,carpet fir fnsh 191 1.358 0 47.0 8963: 0 0
2012-Jun-06 04:39:00
A Right-SuiteO Universal 2012 12.0.04 Right JS Wbile
L Ir wrightsoft Page I
AM C:\VIANDOWS\TEMP\wstmp\6b8b4O8e-f6fe-4d7a-9ec9-4f74879125dl.rup Calc=MJ8 Front Doorfaces: N
wrightsoft. AED Assessment Job:
Date: 6/612012
Entire House By:
David Gray Heating and Air, INC.
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:r7abinsky@davidgrayonline.com Web:www.davidgrayonline.corn WcWs
Project Information
For: Fleet Landing
1 Fleet Landing Boulevard-Unit#5611,Atlantic Beach, FL 32233
Phone: 904-246-9900 Fax: 904-246-9455
Design Conditions
Location: Indoor: Heating Cooling
Jacksonville/Craig, FL, US Indoor temperature(T) 70 75
Elevation: 43 ft Design TD(T) 35 16
Latitude: 30*N Relative humidity 30 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 8.4 52.8
Dry bulb(T) 35 91 Infiltration:
Daily range (T) - 17 M
Wet bulb('F) - 77
Wind speed(mph) 15.0 7.5
Test for Adequate Exposure Diversity
Hourly Glazing Load
14YOOG
12700c.
10700a
8,OOC
6,OOC-
4100&
2)00
0
8 9 10 11 12 13 14 15 16 17 18 19 20
Hour of Day
.,oe Hmsiy Aerage AEDliMt
Maximum hourly glazing load exceeds average by 16.6%.
House has adequate exposure diversity (AIED), based on AIED limit of 30%.
AED excursion: 0 Btuh
*2-jun-06 04:39:00
wirightSOft' Rig ht-Su itee U niv ersal 2012 12.0.04 Right J@ Mo bile
Page I
C:\WINDOWS\TEMP\wstmp\6b8b4O8e-f6fe-4d7a-9ec9-4f74879125dl.rup Calc=MJ8 FrontDoorfaces: N I