2329 Seminole Rd 2012 Hvac CIT� OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00000772 Date 6/21/12
Property Address . . . . . . 2329 SEMINOLE RD
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
-----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
---------------------------------------- ------------------------------------
Owner Contractor
------------------------ ------------------------
KNABB, FRANKIE C. TRUST TROPIC AIRE OF NORTH FLORIDA
3703 ORTEGA BLVD 9969 OLD KINGS ROAD
JACKSONVILLE FL 32210 JACKSONVILLE FL 32219
(904) 719-9600
-----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 95 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 12/18/12
-----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
-----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- --- ------ ---------- ----------
Permit Fee Total 95 . 00 95 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 99 . 00 99 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Bcach, FL 32233
Ph(904) 247-5826 Fax(904) 247-5845
JOB ADDRESS: 202—f�'i 4W PERMIT#
PROJECT VALUE $ ARI 39 2— -
REQ UIRED
NEW AIR CONDITIONING & HEATING SYSTENI INSTALLATION
Air Conditioning: Unit Quantity >�� Tons Per Uni- >��
Heat: Unit Quantity BTU's Per U it Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unil Z",5 13
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity - (Requires 3 sets of plans)
Underground Fire Main Value - (Requires 3 sets of plans)
Fire Hose Cabinets Quantity - (Requires 3 sets of plans)
Commercial Hoods Quantity - (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MIS,�ELLANEOUS:
Prefabricated Fireplace Qty Autor lobile Lifts
Gas Piping Outlets Boilei s BTU's
Eleval ors/Escalators
ALL OTHER GAS PIPING Heat l,"Xchanger
Quantity of Outlets Pump"
#Vented Wall Furnaces Refrig erator Condenser BTU's
# Water Heaters Solar 2ollection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is�uspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and oi dinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name ��— �<"A-� Phone Number
Mechanical Company C– 4-t Office Phone--Ij�� LeCuFax'7(v5-45,54
Co. Address: 01'Q �C"k &kQ Je\t'-jL1-5 C4J city -j4ael- State�--� Zip3--->7—t7
License Holder(Print): State Certification/Registration# C4(f 05736
Notarized Signature of License Ho r A"'
Sworn and suted redn ay o 20
Signature of Not ublic -L/
DesignStar Load Calculation
Results are intended for use with Rheern heating and cooling systems only
4("Orntorl"
Location: AL, Fl-32233
Street Address 2329 sernincle rd., DUV
Latitude, Longitude 30.3375',-81.7686-
House Square Footage: 1200 sq.ft
Name: FRAME KNABB
Phone:
Email:
Outdoor Heating Cooling
Dry bulb('F) 32 93
Daily range M
Relative humidity 50%
Moisture difference 53
Indoor Heating Cooling
Indoor tomperabire F) 70 75
Design temperature difference(*F) 38 18
Heating Loads
Area Btuh % of load
wall 2647 9.9
Floor 10541 39.6
Ceiling 2417 9.1
Windows 3002 11.3
Infiltration 5598 21
System Efficiency Loss 2420 9.1
Total: 26625
Heating Loads
26,625 BTU/hr
Ceiling
System Efficiency LosE
lx�
Floor
Wall
Windows
Infiltration
Cooling Loads
Area Btuh % ofload
Wall 1254 4.7
Ceiling 1145 4.3
Windows 13791 52.2
Sensible Infiltration 1989 7.5
Latent Infiltration 3620 13.7
System Efficiency Gain 2180 8.2
Internal 1346 5.1
Sensible People Load 552 2.1
Latent People Load 552 2.1
Total: 26428
Sensible load 22256
Latent load 4172
SHR 0.84
Capacity at.75 SHR 2A7 Tons
Cooling Loads
26,428 BTU/hr
Sensible Pe I Load
Latent People Load
Ceiling
Wall
Internal
Sensible Infiltrath
Windows
System Efficiency
Latent Infiltration
AED Graph
i 30000
20000
V
9
10000
0
8am 9am 10am 11am 12pm Ipm 2pm 3pm 4pm 5prn 6pm 7pm 8pm
Hourly Loads Av?rage
ACCA Manual S
System equipment selection will be made using the following I Aanual S derived values.
Summer Outdoor 93*F
Summer Wet Bulb 77'F
Summer Indoor 75*F
Summer Design Grains 50%
Winter Outdoor 32*F
Winter Indoor 70*17
Sensible Cooling 22,256 Btuh
Latent Cooling 4,172 Btuh
Required Cooling Airflaw 1,012 CFIVI
Sensible Heating 26,625 Btuh
Required Heaing Airflaw 346 CFM
All calculations are based upon approved hvac industry standards and proced ires,and comply vAth all local,state and
federal code requirements.All computed results are Estimates.Product provided by Energy Design Systems and Idea
Tree
............
CERTIFIEDTIA
www.ah rid i rec to ry�org
Cerfifi
i cate of Produc Ration
� �, 3gs
AHRI Certified Reference Number: 3874552 Da e: 6/21/2012
Product: Split System: Heat Pump with Remote Outdoor Un t-Air-Source
Outdoor Unit Model Number: 25HBB33OC31
Indoor Unit Model Number: FB4CNF030
Manufacturer: CARRIER AIR CONDITIONING
Trade/Brand name: BASE 13 PURON HP
Manufacturer responsible for the rating of this system combination is CARRIER AIR CONDITIONING
Rated as follows in accordance with AHRI Standard 210/240..2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 30000
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00
Heating Capacity(Btuh)@ 47 F: 30000
Region IV HSPF Rating (Heating): 8.00
Heating Capacity(Btuh)@ 17 F: 19400
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless aci ornpanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages ofa y kind arising out of the Use or performance of the product($),or the
unauthorized afteration of data listed on this Certificate.Certified ratings are valid only for mo leis and configurations listed in the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only h�used for individual,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;clissemin�ited;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential n ference.
CERTIFICATE VERIFICATION
The information forthe model cited on this certificate can be verified atwww.ahridirectory.org "IMP, Air-Conditioning,Heating,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date c n
which the certificate was issued,which is listed above,and the Certificate No.,which is listed l:slow. A"" ON ILI and Refrigeration Institute
@2012 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 129847629166749313
............
-J- .,Mull