Permit Mech 716 Ocean Blvd 2012 �51 1 1 -
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00000809 Date 6/29/12
Property Address . . . . . . 716 OCEAN BLVD
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
3 cu 2 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
CITY OF ATLANTIC BEACH B & G REFRIGERATION
800 SEMINOLE RD 3230 KLINE RD.
ATLANTIC BEACH FL 322335428 JACKSONVILLE FL 32246
(904) 620-0081
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 227 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date - - 12/26/12
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 3 .41
STATE MECH DBPR SURCHARGE 3 .41
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 227 . 00 227 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
other Fee Total 6 . 82 6 . 82 . 00 . 00
Grand Total 233 . 82 233 . 82 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC 13EACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247-5826 Fax (904) 247-5845
JOB ADDRESS:
�P ERMT
PROJECT VALUE $
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM
REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATI?�
Air Conditioning: Unit Quantity -3 1 1 a ART P�
Heat: Unit Quantity Tons Per Unit 4 REQUIRED
Duct Systems: Total CFM — BTU's Per Unit— Seer Ratini—Lla—
REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Su�pression Systems Quantity
p (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
Vented Wall Furnaces Refrigerator Condenser BTU's
Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
C)THER:
)ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I�hae read
his application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
)r not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
)roperty Owners Name Phone Number
0echanical Company \kl, wrr�un �\-,\c Office PhoneqAb -k�b
�o. Address:3A,;(-) city State P Zip 226—L�-o
.�icense Holder(Print): PA�rx 0-k t ertification/Registration#taLW1Lj2j-)&
Votarized a Arc 1)(e
STEPHANEY STRAHAN
rn an &e in' 0 day of 20,e��
wav public-state of Flo' d su scribed be
IIAV COMM.Expites Apt 12,2015
Comngssjoip EE 72065Si ature of Notary Public
�V,I-*
COMMERCIAL LOAD CALCULATIONS
Manual N
Air Conditioning Contractors of America
For: Name Adele Grage Phone
Address 716 Ocean Blvd.
City Atlantic Beach State & Zip FL
By: Contractor Energy Design Systems, Inc. Phone (904)268-3670
Address 12132 Weatherwood Estates Dr. W.
City Jacksonville State & Zip FL, 32223
COOLING LOAD
1. DESIGN CONDITIONS Time of Day 3 PM Dly Range 19
Latitude 30 a.Inside db 72 RH 50
b.Outside db 94 wb 77 Grains 49
Otsid db @ 3pm 94 - TOD corr inside db 72
Equals 22 T.D. Daily Range Factor= M
2. SOLAR RADIATION HEAT GAIN THROUGH GLASS COOLING LOAD
Exposure Shading NOTES
Sq. Ft. SolrFactr Gla3Factr Sensible
N X 19 X 0.7
NE 94 X 38 X 0.9 3215
E X 56 X 0. 7
SE 183 X 5-7
1 X 0. 9 9388
S X 48 X 0.-/
Sw 70 X 88 X 0. 9 5544
w X 81 X 0.7
NW 147 X 39 X 0. 9 5160
3. TRANSMISSION GAINS
Equiv or
E:xposure db
Sq. Ft. U Factor Temp Diff
Glass 494 X 0.8 X 22 8694
N X 0.09 X 22
NE 806 X 0.4 X 26 8382
E X 0.09 X 31
Wa113 SE 227 X 0.4 X 33 2996
S X 0.09 X 4 1
Sw 809 X 0.4 X 47 15209
w X 0.09 X 43
NW 263 X 0.4 X 28 2946
Doors 21 X 0.58 X 18 217
Partition X 0.05 X 22
RA Clng X 0.09 X 22
Roof/Clng 3779 X 0.09 X 57 19386
Floors 262 X X 22
X X
Use Table 9a to Determine the Temp. Dif. Across an RA Ceiling
PAGE TWO
4. INTERNAL HEAT GAIN
a. OCCUPANTS Number Sensible Latent Latent
150 x 230 34500
x
150 x 1-70 25500
x
b. Lights & Others
NOTE:Use 60% of installed
watts for lights in
RETURN AIR CEILING
Watts
Incandescnt 2500 x 3.4 = 8500
Flourescent 3500 X 4 .1 = 14350
HP
Motors Btuh Usg Ftr
x
x
Appliances
Other
5. INFILTRATION
Ft3/Min db Temp Dif
126 x 22 X 1.1 = 3049
Grains Diff
126 x 49 X 0.68 = 4198
6. SUBTOTALS LOADS & SPACE LOADS 141537 29698
7. DUCT HEAT GAIN
Gain Line 6
Factor Sensible
0.1 x 141537
8. ROOM, SPACE OR DESIGN LOAD
Add Duct gain (7) to Subtotal (6) 141537
9. VENTILATION
Ft3/Min db Temp Dif
3000 x 11 x 1.1 = 36300
Grains Diff
3000 x 25 X 0.68 = 51000
PAGE THREE
10. RETURN AIR LO-AD—ER--OMLIGHTING AND ROOF
NOTE: Use 40% of watts for lights recessed
in a return air ceiling
Incandescent x 3.4 =
Flourescent x 4. 1 =
NOTE: Use 100% fo the roof load
for return air ceilings
(Roof Load)
Sq. Ft. U Factor ETD*
x 0.09 x
* (ETD correction based on plenum temp. )
11. TOTAL SENSIBLE LOAD ON EQUIPMENT (Btuh) 177837----------_
TOTAL LATENT LOAD ON EQUIPMENT (Btuh) 8
12. TOTAL COOLING LOAD ON EQUIPMENT (Btuh) 258536
(Tons) 21.54
PAGE FOUR
HEATING LOAD
13. DESIGN LOADS
Inside db Outside db b Difference
72 - 32 40
14. TRANSMISSION LOSSks HEATING LOAD
db
Exp. Sq. Ft. Factor Temp Diff Heating Load
Windows 1300 x 1 . 13 x 40 58760
x x
x 0.09 X
Walls x 0.09 x
809 x 0.4 x 40 12944
x 0.09 x
263 x 0.4 x 40 4208
Roof/ 3779 x 0.09 x 40 13604
Ceiling X 0.05 X
x x
Floor 262 x 0.81 x 40 8489
Other x x
x x
15. INFILTRATION
db
Ft3/Min Temp Diff
189 X 40 X 1.1 8316
SUBTOTAL HEATING LOAD FOR SPACE 106321
DUCT HEATING LOSS
Loss Line 14
Factor Subtotal
0. 15 X 98005 14701
18. VENTILATION
db
Ft3/Min Temp Diff
3000 X 40 X 1.1 132000
17 HUMIDIFICATION LOAD
Inside RH Desired Max
Ft3/Min Btu/Hr
100 X
(water) (air)
gal/day Ft3/Min
X 100
20. TOTAL HEATING LOAD ON EQUIPMENT (Btuh) 253022
(Tons) 21.09
Energy Design Systems, Inc.
12132 Weatherwood Estates Dr. W.
Jacksonville, FL 32223
(904) 268-3670
This combination qualifies for a Federal Energy
T, Effic Tax Credit when placed in service
sual C E RTI A E D
www.ahridirectory.org =en Feb 17, 2009 and Dec 31, 2011.
J1110"A 9-ft
Certificate of Product Ratinuz
AHRI Certified Reference Number: 3654899 Date: 6/29/2012
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: DSZC180481A*
Indoor Unit Model Number: CHPF4860D6D*+MBVC2000**-lA*+TXV
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN, JANITROL,AMANA DISTINCTIONS, EVERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system combination is GOODMAN MANUFACTURING CO., LP.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 47500
EER Rating (Cooling): 13.00
SEER Rating (Cooling): 18.00
Heating Capacity(Btuh)@ 47 F: 47500
Region IV HSPF Rating (Heating): 9.50
Heating Capacity(Btuh) @ 17 F: 29600
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),orthe
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRL This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, "Imp,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on AIWIM an ILI Air-Conditioning,Heating,
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below. and Refrigeration Institute
@2012 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 129854474197241775
This combination qualifies for a Federal Energy
CERTIFIED,. ,! Effic Tax Credit when placed in service
WWW.ahridir ectory.org =en Feb 17, 2009 and Dec 31, 2011.
Certificate of Proauct Rationgs
AHRI Certified Reference Number: 4651107 Date: 6/29/2012
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: DSZC180601B*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Indoor Unit Model Number: A(E,F)M614+TDR
Manufacturer: ASPEN MANUFACTURING
Trade/Brand name:ASPEN
Manufacturer responsible for the rating of this system combination is ASPEN MANUFACTURING
Rated in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source Heat Pump
Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent, third party testing:
Cooling Capacity(Btuh): 57500
EER Rating (Cooling): 12.70
SEER Rating (Cooling): 18.00
Heating Capacity(Btuh) @ 47 F: 56500
Region IV HSPF Rating (Heating): 9.50
Heating Capacity(Btuh) @ 17 F: 35000
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibillty for
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the Use or performance of the product(s),orthe
unauthorized atteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory atwwmahricilrectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only be used for individuall,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, "IMP, A' C
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on Ifil an Iki ir- onditioning,Heating,
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below. and Refrigeration Institute
@2012 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 129854474658205825