672 Ocean Blvd HVAC 2012 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00001021 Date 8/07/12
Property Address . . . . . . 672 OCEAN BLVD
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
TAYLOR BROGAN B & NATALIE V SERVICE EXPERTS
672 OCEAN BLVD. 8475 WESTERN WAY STE 100
ATLANTIC BEACH FL 32233 JACKSONVILLE FL 32256
(904) 641-2333
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 103 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 2/03/13
---------------------------------------- ------------------------------------
Other Fees . . . . . . . . . STAIE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
---------------------------------------- ------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---- ------ ---------- ----------
Permit Fee Total 103 . 00 103 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 107 . 00 107 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT�APPLICATION
CITY OF ATLANY c BEACH
800 Seminole Rd Atlantic Bi ach, FL 32233
Ph (904)247-5826 Fax (9(4) 247-5845
JoB ADDRESS: 0,�:e4r-j 6`&Vn � PERMT
JOROJECTVALUE $
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Ur't Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI# 4(t/. //-7/&9
Air Conditioning: Unit Quantity Tons Per Unit R-E!qUIRED
Heat: Unit Quantity BTU's Per Ur it Seer Rating
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Autorr obile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat F xchan ger
Quantity of Outlets Pump�
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
----------
Perrait becornes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or'ocal law regulation construction or the performance of construction.
Property Owners Name—VAIAI-I e T --PboneNumber -a416-3�7,1
if 44 Z-0/-L-
Mechanical Compan Ioee47-5- Office Phone 1,L) Aff�Fax
Co. Address: to -f-)LAj I-(-- ICO__ City,��d��j) A'- StateFj zip f�9)5,,
License Holder(Print):
I State Certification/Registration A 11-4-4-C 1'71
0-#-"e- , " - %7- --
iYotarized Sk-nature ofLicense 11older ;?� - ---�
Swom and ribed be-fore Die this day of --�?4 20
S/s C
n
,,CAROL A BRESSLER ature of Notary Public
ry P c Slat,
of
olary Public .
"y Co F
State of Florida
'd
AAY COMM Expirr-s J,,f 5, 2014
k C
orrim
..........%
Cornmis."irin FF
1191,12
a osure Diversit
7,.
AED Graph
40000
30000
20000,
10000
0
8 a ri i 9am 10')r I 11,11)1 1 [)11, 1, r 2 p r 1) r n 1,r I 1wn) 11 w,I
Hnuily Lnads — Av.-rage
ACCA Manual S
System equipment selection will be made using the following Manual S,ierived values.
Summer Outdoor 930F
................................................-........... ............. ............. ................................. .............
Summer Wet Bulb 770F
.............._'1....-1.".'---..-................ ........... ..................... '..'..-.................
Summer Indoor 7 5"F
............. .......... ..........................................................................................-�.................................................. ....................
Summer Design Grains 50%
................ .... ... ..........
Winter Outdoor 320F
1111-1---1........................ ........... ............... ..................... ..........................................
Winter Indoor 70OF
.......................................- ....................... .......... ..........
Sensible Cooling 35,953 Btuh
Latent Cooling 8,462 Btuh
............... ............................................ ................................................ ............- ................ -
Required Cooling Airflow 1,634 CFM
....................... ........................ ..................................... ............. ........ .......... ........................
Sensible Heating 39,819 Btuh
Required Heaing Air-flow 517 (.-.,F.M
All calculations are based upon approved hvac industry standards and procedures,and comply with all local,
state and federal code requirements,All computed results are Estimates, Product provided by Energy Design
Systems and Idea Tree
C061ing Loads
Area Btuh % of load
............. ...............
Wall 1785 4
....................-.-.................................
Ceiling 1314 3
......................................................... ......................................................-.- -.- ...................
Windows 21383 48.1
I--.......................................................... ......................................................
Sensible Infiltration 4034 9.1
........................................
Latent Infiltration 7342 16.5
............. .........
System EfficiencyGain 3586 8.1
...........
Internal 2731 6.1
-.11.1-1-11.1..............11-11 -.1-............................................ ................................... .............
Sensible People Load 1120 2.5
I............................................................ ................................... ................ ..........
Latent People Load 1120 2.5
..............
................ .................. .......... ........... ......... .................
Total: 44415
......................... ............... ..........I........................ ...........
Sensible load 35953
............-........... ..............
Latent load 8462
............ ...................................
SHR 0.81,
Capacity at .75 SHR 3.99 Tons
............... ........... ................... .............
Cooling Loads
411 F T 1)j
Sensible People Load
I Latent People Load
r Ceiling
Wall
Internal
System Efficienc)
Windows
Sensible Infiltratio
V"j'�
Latent Infiltration
4�'
�He-ating Loads
Area Btuh % of load
............. ........... ......--.............
Wall 3769 9.5
.............. ......................--........1-1-1-1-.......
Floor 11651 29.3
.......... ............
Ceiling 2775 7
Windows 6650 16.7
-'........................ ........... '---"-.......................
infiltration 11354 28.5
System Efficiency Loss 3620 9,1
........... ............................................ ...............
Tota 1: 39819
Heating Loads
3(),819 B-1(J/hr
Ceiling
System Efficiency Loss
Floor
V
Wall
Windows
Infiltration
0 !'N"
............
'44"- Ni. m a b 6;
W '"' �I IN,it 11"1
..........'Q!
'g, AR
AW
Street Address 4881 Deeder Ct., DUVAL, FL 32258
",Nq
M, pr� ..........
16, N
Zil
....................
House Square Footage: 2434 sq. ft.
............ ............. ............. .............
Name: wil 14 am� Fo, nt i
u,' ain
.............
Phone: 904-641-2333
..................................................... ..........- 7 --, ........................... .......................... .................................. ........................... .............................
Email: exampie@mail.com
.................... ........................ ............ ......................... .......... ...................... ...............................
iD-esign Conditions
Outdoor Heating Cooling
.................. ............. ...................... ................... .............................
Dry bulb (OF) 32 93
..............................
Daily range M
......................................................-...........................-............................. ...................... ............---.......... ................
Relative humidity 50%
.......... ......................................................- ............ ...........--................................
Moisture difference 53
...........
Indoor Heating Cooling
...................................... ................. ............... ........... ...............
Indoor temperature ('F) 70 75
Design temperature difference(OF) 38 18
CERTIFIEDT.
www.ahridirectory.org I
Certificate of Product Ratings
AHRI Certified Reference Number: 4611769 Dab 1: 8/7/2012
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: 13HPX-042-230-17
Indoor Unit Model Number: CBX26UH-042*+TDR
Manufacturer: LENNOX INDUSTRIES, INC.
Trade/Brand name: 13HPX SERIES
Manufacturer responsible for the rating of this system combination is LENNOX INDUSTRIES, INC.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 40500
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00
Heating Capacity(Btuh)@ 47 F: 40000
Region IV HSPF Rating (Heating): 8.00
Heating Capacity(Btuh)@ 17 F: 26200
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless ac mmpanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AM does not endorse the product(s)listed on this Certificate and makes m representatim�,warranties or guarantees as to,and assumas no responsibility for,
the product(s)listed an this Certificate.AHRI expressily discialms&I Kabilky for danmws of a ny"arislin out of tho use or performance of the product(s),or the
uniurthortzed afteration of data Rated on"Certificate,Certified ratings am valid only for mt Khft and configurations In the directory at www.ahridirecWry.org.
TERMS AND CONDITIONS
This Certificate and No contents are proprietary products ofAHRL This Certificate shall only I a used for indilvidual,personal and confidential reference purposes.
The contents ofthis CartIftaft may not,In whole or In part,be reproduced,copied;dissamir Od;entered Into a computer database;or otherwise utilized,In any
form or manner or by,any means,excepit for the user's Individual,personal and confidential i ftrance.
CERTIFICATE VERIFICATION
The Information for the model cited on this certificate can be verified atwww.ahridirectory.or "IMF,
click on"Verify Certificate"Knk and enter the AHRI Certified Relaiance Number and the data m a Air-Conditioning,Heating,
which the certificate was Issued,which Is listed above,and the Certificate No.,which Is Hatedmilow. A110M 00 ILE and Refrigeration Institute
02012 Air-Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 129888152692048068