5301 Fleet Landing Blvd 2012 HVAC IS CIT)r OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
Application Number 12-00001072 Date 8/16/12
Property Address . . . . . . 1 FLEET LANDING BLVD MAIN
Tenant nbr, name . . . . . . UNIT 5301
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 1 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
NAVAL CONTINUING CARE DAVID GRAY HEATING AND AIR INC
FLEET LANDING 6491 POWERS AVENUE
1 FLEET LANDING BOULEVARD JACKSONVILLE FL 32217
ATLANTIC BEACH FL 32233 (904) 724-7211
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL H PERMIT
Additional desc . . Vt
Permit Fee . . . . 99 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 2/12/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 99 . 00 99 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 103 . 00 103 . 00 . 00 . 00
i
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF LANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT,,APPLICATION
CITY OF ATLANTjC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (9C4) 247-5845
JOB ADDRESS: &J_r--( PERMIT#
PROJECT VALUE $ ARI
REQUIRED
NEW AIR CONDITIONING & HEATING SYSTE1\4INSTALLATION
Air Conditioning: Unit Quantity Tons Per Uni,
Heat: Unit Quantity BTU's Per Ujdt Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEAT114G SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Uni,
Heat: Unit Quantity BTU's Per Uj lit 15;-coz Seer Rating
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Autor iobile Lifts
Gas Piping Outlets Boilei s BTU's
Eleva ors/Fscalators
ALL OTHER GAS PIPING Heat I`.Xchanger
Quantity of Outlets Pump 3
#Vented Wall Furnaces RefriE erator Condenser BTU's
#Water Heaters Solar C-ollection Systems
Tanks (gallons)
Wells
OTHER: 1114± 4�_
Permit becomes void if work does not commence within a six month period or w uspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and oidinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the rovisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name _IeW L4 P-07 PhoneNumber 2qc-�qcc
Mechanical Company 0,,/ C,�, r Office Phone Aq-9�,-f Fax 9 2
Co. Address: City 9-"iv-j te StatejE-T-Zip 7224-2
License HoW State Certification/Registration# G?C,05;7,&
Notarizef'-
Wi4�se Holder
MY Comm.Eypk"
E January 10,2014 Sworn and subscribed before) this Cd—dayf /1-IL L,5 4 20j2,
No.M 95MI 3
(P
Signature of Notary Public 7
P! E3L\
11,4111111%
Right J@ Mobile Report Job:
wrightsoft Date: 811612012
Entire House By:
David Gray Heating and Air, INC.
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:rzabiiky@davidgrayonline.com Web:www.davidgrayonline.cDm Licens
Project Information
For: Fleet Landing
I Fleet Landing Boulevard-Unit#530 1,Atlantic Beach, FIL 32233
Phone: 904-246-9900 Fax: 904-246-9-55
Design Conditions
Location: Inc oor: Heating Cooling
Jacksonville/Craig, FL, US ndoor temperature(OF) 70 75
Elevation: 43 ft )esign TD(OF) 35 16
Latitude: 30 ON Relative humidity 30 50
Outdoor: Heating Cooling Aoisture difference(gr/lb) 8.4 52.8
Dry bulb(OF) 35 91 Inf Itration:
Dailyrange(OF) - 17 ( M ethod Simplified
Wet bulb(*F) - 77 onstruction quality Average
Wind speed(mph) 15.0 7.5 ireplaces 0
Heatincl
Component Btu h/ft" Btuh %of load
Walls 8.3 12641 41.2 Irthralon
Glazing 19.7 3320 10.8
Doors 13.5 433 1.4
Ceilings 1.7 2438 8.0 MW I
Floors 6.2 8963 29.2 Rms
Infiltration 2.1 2869 9.4
Ducts 0 0 All
Piping 0 0
Humidification 0 0 0ifirgs
Ventilation 0 0 Ga6r(i
Adjustments 0
Total 1 30663, 100.0
CoOlin
Component Btu h/ft2 Btuh %of load
Walls 4.1 6169 26.3
Glazing 51.5 8672 36.9 Irtemal Girs
Doors 11.4 367 1.6 W41
Ceilings 2.6 3720 15.8 Infiltirctiorl
Floors 0 0 0
Infiltration 0.5 691 2.9
Ducts 0 0 Ca
Ventilation 0 0
Internal gains 3860 16.4
Blower 0 0 Cther
Adjustments 0
Total 23479, 100.0 1 Ga&g
Latent Cooling Load 1784 Btuh
Overall U-\ra lue=0.147 Btuh/ft'-'F
Data entries checked. I
2012-Aug-1 6 06:30:12
wright"ft* Rig ht-Su its(&U niv ersal 2012 12.0.12 Right JS Nb bile Page 1
I&I C-.\WINDOWS\TEMP\wstmp\39c36552-fO95-4418-gf5c-I d5778c,1309.nip Calc=MJ8 Hausa Front faces: N
Job:
wrightsoft Project Summary Date: 811612012
Entire House By:
David Gray Heating and Air, INC. i
t
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:rzabiniky@davidgrayonline.com Web:www.davidgrayonline.com Licens...
Project Inforrration
For: Fleet Landing
1 Fleet Landing Boulevard-Unit#r 301,Atlantic Beach, FIL 32233
Phone: 904-246-9900 Fax: 904-246-9455
Notes:
I
I
Design Information
Weather: Jacksonville/Cr g, FL, US
Winter Design Conditions I Summer Design Conditions
Outside db 35 'F Ou:side db 91 *F
Inside db 70 *F Ins de db 75 *F
Design TD 35 'F De 5ign TD 16 *F
Da ly range M
Re ative humidity 50 %
Mc isture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 30663 Btuh Stricture 23479 Btuh
Ducts 0 Btuh Du,-ts 0 Btuh
Central vent(0 cfm) 0 Btuh Ceitral vent (0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 30663 Btuh Usa-manufacturer's data y
Rate/swing multiplier 1.00
Infiltration Eq jipment sensible load 23479 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average f
Fireplaces 0 S' cture 1784 Btuh
D ts 0 Btuh
Heating Cooling C tral vent(0 cfm) 0 Btuh
Area(ft2) 1438 1438 Eq ipment latent load 1784 Btuh
Volume(ft) 10066 10066 t
Air changes/hour 0.45 0.23 Eqipment total load 25263 Btuh
Equiv.AVF(cfm) 75 39 R, total capacity at 0.70 SHR 2.8 ton
Heating Equipment Summary Cooling Equipment Summary
Make Goodman Make Goodman
Trade Tr,ide
Model ARUF36C Ccnd GSZ1 3036
AHRI ref Ccil
AF RI ref
Efficiency 0 AFUE Efl ciency 13SEER
Heating input 0 MBtuh Se isible cooling 0 Btuh
Heating output 0 Btuh La ent cooling 0 Btuh
Temperature rise 0 'F Toal cooling 0 Btuh
Actual air flow 1069 cfm Acual air flow 1069 cfm
Air flow factor 0.035 cfm/Btuh AiF flow factor 0.046 cfm/Btuh
Static pressure 0 in H20 St�tic pressure 0 in H20
Space thermostat Lo) d sensible heat ratio 0.93
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2012-Aug-1 6 06:30:12
wrifilhitSOft Right-Suites Universal 2012 12.0.12 Right JS Wbil Page 1
Ak C:XWINDOWS\TEMP\wstmp\39c36552-fO95-4418-9f5c-ld5778o43d79.rup Calc=MJ8 use Front faces: N
"it wrwftoft- Right-A) Worksheet Job:
Entire House Date: 811612012
By:
David Gray Heating and Air, INC.
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:rzabin sky@davidgrayonline.com Web:www.davidgrayonline.com Licens
I Room name Entire House First Floor
2 Exposed wall 190.8 ft 190.8 ft
3 Room height 9.0 ft d 9.0 ft heat/cool
4 Room dimensions 1.0 x 1438.0 ft
5 Room area 1438.0 ft2 1438.0 ft2
I I I I I
Ty � Construction U-value Or HTM Area (ft2) I Load) Area (ft2) Load
number Bt uh/ft2-'F) (Btuh/ft or ped eter lift) (Btuh or perimeter (ft) (Btuh)
Heat Cool Gross i N/R S Heat Cool Gross N/P/S Heat Cool
6 ISA,2s3oc-2 0.269 n 8.35 4.10 234 212 1767 867 234 212 1767 867
1 D-c2ow 0.570 n 19.72 20.91 22 0 444 471 22 0 444 471
15A-2s3oc-2 0.269 ne 8.35 4.09 25 23 192 94 25 23 192 94
t-'. 1 D-c2ow 01570 ne 19.72 46.75 3 0 49 117 3 0 49 117
11 '�= 15A,2s3oc-2 0269 a 8.29 4.01 594 504 4183 2024 594 504 4183 2024
1D-c2ow 0 570 a 19.72 63.01 57 a 1134 3623 57 0 1134 3623
11DO 0 390 a 13.49 11.43 32 32 433 367 32 32 433 367
'5A-2s3oc-2 0269 s 8.35 4.09 252 227 1896 929 252 227 1896 929
t--G I D-c2ow 0'570 a 19.72 25.16 25 0 493 629 25 0 493 629
15A-Woc�2 0269 w 8.35 4�09 612 551 4603 2256 612 551 4603 2256
t-G 1D-c2ow 0,570 w 19.72 63.01 61 0 1200 3833 61 0 1200 3833
C 16B-19ad 0.049 1.70 2.59 1438 1438 2438 3720 1438 1438 2438 3720
F 22A-cph 1.358 46.99 0�00 1438 191 8963 0 1438 191 8963 0
1 61 c)AED excursion 1 01 1 1 1 0
Envelope losstgain 277941 189291 1 1 277941 11892�9
12 a) Infiltration 2869 691 2869 691
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 2 460 2 460
Appliances/other 3400 3400
Subtotal(lines 6 to 13) 30663 23479 30663 23479
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 30663 23479 30663 23479
15 Duct loads 0% 0% 0 0 -0% 0% 0 0
Total room I ad 306631 234791 306631 234791
1 Air requiredo(cfm) 10691 10691 106
Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed.
2012-Aug-16 06:30:12
wrIgh"'o"L- Right-SuiteO Universal 2012 12.0.12 Right JS Mobile Page I
A&K C:\WINDOWS\TEMP\wstmp\39c36552-fO95-4418-gf5c-I d5778c43d79.nip Calc=MJ8 Hi Puse Front faces: N
i
Component Constructions: Job:
wrightsoft- Date: 811612012
Entire House By:
David Gray Heating and Air, INC.
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:rzabi�ky@davidgrayonline.com Web:www.davidgrayonline.com Licens...
Project Information
For: Fleet Landing
I Fleet Landing Boulevard-Unit#530 1,Atlantic Beach, FIL 32233
Phone: 904-246-9900 Fax: 904-246-9,155
Design Conditions
Location: Indoor: Heating Cooling
Jacksonville/Craig, FL, US Indoor temperature(T) 70 75
Elevation: 43 ft Design TD(*F) 35 16
Latitude: 30'N Relative humidity(%) 30 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 8.4 52.8
Dry bulb(T) 35 91 In iltration:
Daily range(*F) - 17 M Method Simplified
Wetbulb(*F) - 77 Construction quality Average
Wind speed(mph) 15.0 7.5 Fireplaces 0
Construction descriptions Or Area U-value Insul R Htg HTM Loss Cig HTM Gain
N BtuhtR2-OF fF-'F/Btuh Btuh/ft2 Btuh Btuh/f[2 Btuh
Walls
15A-2s3oc-2:Bg wall,heavy dry or light damp soil,empty core, n 21, 0.157 2.0 8.35 1767 4.10 867
concrete block wall,r-2 ins,10"thk ne 2: 0.157 2.0 8.35 192 4.09 94
e 50, 0.157 2.0 8.29 4183 4.01 2024
s 2Z 0.157 2.0 8.35 1896 4.09 929
w 55, 0.157 2.0 8.35 4603 4.09 2256
all 151' 0.157 2.0 8.33 12641 4.07 6169
Partitions
(none)
Windows
I D-c2ow:2 glazing,clr outr,air gas,wd frm mat,clr innr,1/4"gap, n 2' 0.570 0 19.7 444 20.9 471
1/8!'thk ne 0.570 0 19.7 49 46.8 117
e 5f 0.570 0 19.7 1134 63.0 3623
S 2! 0.570 0 19.7 493 25.2 629
w 6' 0.570 0 19.7 1200 63.0 3833
all 16 0.570 0 19.7 3320 51.5 8672
Doors i
11 DO:Door,wd sc type a 31 0.390 0 13.5 433 11.4 367
Ceilings
16B-1 9ad:Attic ceiling,asphalt shingles roof mat,r-1 9 ceil ins,1/2" 1431 0.049 19.0 1.70 2438 2.59 3720
gypsum board int frish
Floors
22A-cph:Bg floor,heavy damp soil,on grade depth,carpet flr fnsh 19 1.358 0 47.0 8963 0 0
2012-A.ug-1 6 06:30:13
wright"ft' Right-S.itell)Universal 2012 12.0.12 Right JQD Nbbile Page 1
C:%WINDOWSkTEMP\wstmp\39c36552-fO95-4418-9f5c-ld5778c43d7g.rup Calc=MJ8 F ouse Front faces: N
Job:
wrightsofr AED Assessment
Date: 811612012
By:
Entire House
David Gray Heating and Air, INC.
6491 Powers Avenue,Jacksonville,FL 32217 Phone:904-724-7211 Fax:904-724-5925 Email:rzabir*ky@davidgrayonline.com Web:www.davidgrayonline.com Licens
Project Information
For: Fleet Landing
1 Fleet Landing Boulevard-Unit#530 1,Atlantic Beach, FL 32233
Phone: 904-246-9900 Fax: 904-246-9455
Design Conditions
Location: Iniloor: Heating Cooling
Jacksonville/Craig, FL, US Indoor temperature(*F) 70 75
Elevation: 43 ft Design TD(*F) 35 16
Latitude: 30ON Relative humidity 30 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 8.4 52.8
Dry bulb(T) 35 91 Infiltration:
Daily range(T) - 17 ( M
Wetbulb(*F) - 77
Wind speed(mph) 15.0 7.5
Test for Adequate Exposure Diversity
Hourly Glaz ng Load
11,00&
10'00&
9,OOE-
8,00E
7,OOE-
6,00(-
5,00(-
4,OOE-
3,OOE-
2,00(-
1,00(
0
8 9 10 11 12 13 14 15 16 17 18 19 20
Hour of Day
HoWy / Aerage PEDlirrit
Maximum hourly glazing load exceeds average by 22.6%.
House has adequate exposure diversity(AED), ba r ed on AED limit of 30%.
AED excursion: 0 Btuh
2012-Aug-1 6 06:30:13
wrighift0ft' Right-Suite(&Universal 2012 12.0.12 Right M Mob a Page 1
,0&C:\V\ANDOWS\TEMP\wstmp\3gc36552-fO95-4418-9f5c-ld5778c43d79.rup Calc=MJ8 House Front faces: N
CERTIFIEDTM
am IL
www.ahridirectory.org J
Certificate of Product Ratinas
AHRI Certified Reference Number: 5358272 DT�e: 8/16/2012
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: GSZ130361B*
Indoor Unit Model Number: ARUF36C14A*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN,JANITROL,AMANA DISTIN TIONS, EVERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system com )ination is GOODMAN MANUFACTURING CO., LP.
Rated as follows in accordance with AHRI Standard 210/2411-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating iccuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(13tuh): 34800
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00 1
Heating Capacity(Btuh)@ 47 F: 34000
Region IV HSPF Rating (Heating): 8.00
Heating Capacity(Btuh)@ 17 F: 20800
Ratings followed by an asterisk indicate a voluntary rerate of previously published data,unles�accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no represental lons,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),or the
unauthorized afteration of data listed on this Certificate.Certified ratings are valid only fc,-models and configurations listed in the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products ofAHRL This Certificate shall o ly be used for individual,personal and confidential reference purposes.
s
The contents ofthis Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and conficlen jai reference.
CERTIFICATE VERIFICATION 04 "Imp, Air-Conditioning,Heating,
The information for the model cited on this certificate can be verified at www.ahridirector I.org,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the(ate on iM On ILI and Refrigeration Institute
which the certificate was issued,which is listed above,and the Certificate No.,which is lifed below.
@2012 Air-Conditioning,Heating, and Refrigeration Institute I CERTIFICATE NO.: 129896129045162237