1563 Linkside Dr 2012 HVAC A CITY OF ATLANTIC BEACH
S
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
-5814
INSPECTION PHONE LINE 247
Application Number . . . . . 12-00001086 Date 8/22/12
Property Address . . . . . . 1563 LINKSIDE DR
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO EE UPDATED
Application valuation . . . . 0------------------------------
---------------------------------------- -----
Application desc
1 cu 1 ahu
------------------------------------
Owner Contractor
------------------------
------------------------
NICHOLSON, TIMOTHY COOL R US
1563 LINKSIDE DR 8210 HAWKS LANDING DRIVE
ATLANTIC BEACH FL 32233 JACKSONVILLE FL 32217
(904) 790-9110
-- ------------------------------------ -------------------------------------
Permit MECHANICAL HVAC PERMIT
Additional desc 103 . 00 Plan Check Fee . 00
Permit Fee . . . . Valuation . . . . 0
Issue Date . . . .
Expiration Date . - 2/18/13 ------
-- ------------------------------------ -------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
-- -------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 103 . 00 103 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 107 . 00 107 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY 0 - ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANT]c BEACH
800 Seminole Rd Atlantic & ach, FL 32233
Ph(904) 247-5826 Fax (9(4)247-5845
JOB ADDRESS: — 1563 LINKSIDE DR ATLANTIC BEACH L PERMIT #
32233
PROJECT VALUE $ 5725.00
NEW AIR CONDITIONING & HEATING SYSTEN" INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit Seer Rating---
Heat: Unit Quantity BTU's Per U nit REQUIRED
Duct Systems: Total CFM
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI# ��Sg
Air Conditioning: Unit Quantity I Tons Per Un It 3.5 !?EQUIRED
Heat: Unit Quantity I BTU's Per t nit 42000 Seer Rating 15.25
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MI'$CELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boil-rs BTU's
EleN a�ors/Escalators
ALL OTHER GAS PIPING Hea, Exchanger
Punins
Quantity of Outlets IV
#Vented Wall Furnaces Reim gerator Condenser BTU's
# Water Heaters Sol Collection Systems
T s (gallons)
Wels
44
OTHER:
e or abandoned for S�i X months.I hereby certify that I have read
Permit becomes void if work does not commence within a six month period or work s suspencle
this application and know the same to be true and correct. All provisions of laws anc ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other statc or local law regulation construction or the performance of construction.
Property Owners Name TIM NICHOLSON
Phone Number 904-616-6117
Mechanical CornTan� COOL R US,INC CAC 1815614
1
—OfficePhone 04 9l-2l08_Fax904-28l-21U9--
Co. Address: 6900 PHILIPS HWY#46 City JACKSONVILLE—
State FL__:�jp _____L2216
MECHANICAL PERMITAPPLICATION
CITY OF ATLANT ic BEACH
800 Seminole Rd Atlantic B.-ach, FL 32233
Ph (904) 247-5826 Fax (904) 247-5845
JOB ADDRESS: — 1563 LINKSIDE DR ATLANTIC BEACH FL PERMIT #
32233
License Holder(Print): LEK GJOKA
State Certification/Registration CAC1815614
Notarized Signature of License Holder
Sworn and subscribed b
4av of
Signature of Notary Public
PATRICIA A STARK
MY COMMISSION#EE138680
EXPIRES October 17,2015
3 FlwidallotaryService.eom
MECHANICAL PERMIT APPLICATION
CITY OF ATLANT c BEACH
800 Seminole Rd Atlantic B ach, FL 32233
1
Ph(904) 247-5826 Fax(9 ) 247-5845
JOB ADDRESS: 1563 LINKSIDE DR ATLANTIC BEACH L
32233 PERMIT #
License Holder(Print): LEK GJOKA
State Certification/Registration# CAC18
Notarized Signature of License Holder
Sworn and subscribed b -ne this 4:?— 4ay of 20
f N
I
Signature of Notary Publics.-
PATRICIA A STARK
MY COMMISSION#EE 138680
EXPIRES October 17,2015
3 FWidalloteryService.com
This combination qualifies for a Federal Energy
"IMP, Efficiency Tax Credit when placed in service
^man SI CERTIFIEDT. between Feb 17,2009 and Dec 31,2011.
www.a h r i dire ctory.org 4
Certificate of Producl Ratings
W1W=
AHRI Certified Reference Number: 5495901 Dae: 8/20/2012
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: 4TWR5042G1
Indoor Unit Model Number: *AM7AOC48H41
Manufacturer:TRANE
Trade/Brand name: XR15 WEATHERTRON
Manufacturer responsible for the rating of this system combination is TRANE
Rated as follows in accordance with AHRI Standard 210/24C-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity (13tuh): 41500
EER Rating (Cooling): 12.50
SEER Rating (Cooling): 15.25
Heating Capacity(Btuh) @ 47 F: 40000
Region IV HSPF Rating (Heating): 9.00
Heating Capacity(Btuh) @ 17 F: 25600
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unleE 5 accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no represents ions,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this CeMcate.AHRI expressly disclaims all liability for damaget of any kind arising out of the use or performance of the product(s),or the
unauthorized alteration of data listed on this certificate.Certified ratings are valid only fc r models and configurations listed in the directory at www.ahridirectory-org.
TERMS AND CONDITIONS rpos
This Certificate and its contents are proprietary products of AHRI.This Certificate shall ly be used for individual,personal and confidential reference pu as.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;diss minated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's Individual,personal and confidOF jai reference.
CERTIFICATE VERIFICATION
The Information for the model eked on this certificate can be verified at www.ahridirecto V.org, "Imp, A' C riditioning,Heating,
click on'Verify Certificate"link and enter the AHRI Certified Reference Number and the,late on no'ILI an"d Roefrigeration Institute
which the cettficate was Issued,which is listed above,and the Certificate No.,which is It ted below.
02012 Air Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 129899627470895634
Job:
wrighWoft. Load Short Form Date: Aug 20,2012
Entire House By:
Energy Design sowtions, Inc.
4925 Ata Vista Ave,St.Augustine,FL 32080 Phone-:904-669-6571 Email:kimurray9ayahoo.com I
Project Information
For: Timothy Nicholson, Cool R Us Inc
1563 Linksie DR,Atlantic Beach, FL 32233
Design Information
Htg cig Infiltration Simplified
Outside db (*F) 33 93 Method Average
Inside db('F) 68 75 Constriction quality 1 (Average)
Design TD(*F) 36 18 Fireplaces
Daily range - M
Inside humidity 50 50
Moisture difference(gr/lb) 29 51
HEATING EQUIPMENT COOLING EQUIPMENT
Make Trane Make Trane
Trade XR15WEATHERTRON Tri ide XR15 WEATHERTRON
Model 4TWR5042G1 Cc id 4TWR5042G1
AHRI ref 5495901 Cc I *AM7AOC48H41
AF RI ref 5495901
Efficiency 9 HSPF Ef ciency 12.5 EER, 15.3 SEER
Heating input SE isible cooling 29050 Btuh
Heating output 40000 Btuh @ 47*F La ent cooling 12450 Btuh
Temperature rise 26 'F Tc :al cooling 41500 Btuh
1383 cfm A( :ual air flow 1383 cfm
Actual air flow 0.047 cfm/Btuh
Air flow factor 0.045 cfm/Btuh Ai flow factor 0 in H20
Static pressure 0 in H20 S tic pressure 0.88
Space thermostat Lc ad sensible heat ratio
ROOM NAME Area EHtg load Cig load Htg AVF Cig AVF
(cfm) (cfm)
M (Btuh) (Btuh)
1383
Whole House ?1741 30576 29632 1383"
Entire House d 1741 30576 29632 1383 1383
Other equip loads 0 0
Equip. @ 0.98 RSM 28951
Latent cooling 4146
TOTALS 1741 3057E 33097 1383 1383
Calculations approved by ACCA to mee all requirements of Manual J 8th Ed.
2012-Aug-20 14:19:58
wrightS431ft Rig ht-Suiteg u niversal 2012 12.0.12 RSU1 2605 Page 1
AM C:\Users\Keith\nicholson.rup Calc=MJ8 Front Door faces: W
Job:
Building Analysis Date- Aug 20,2012
wrightsoft Entire House By:
Energy Design solutions, Inc.
4925 Aita Vista Ave,St.Augustine,FL 32080 Phone:904-669-6571 Email:kjmurray9@vahoo.com
For: Timothy Nicholson, Cool R Us Inc
,I c C ,
1563 Linksie DR,Atlantic Beach, FL 32 33
Desiqn Conditions
M IIIIIIIIIIIIIIII01 Heating Cooling
Ini"ploor:
Location: Indoor temperature CF) 68 75
Jacksonville Intl AP, FL, US esign TD('F) 36 18
Elevation: 33 ft 'elative humidity 50 50
Latitude: 30'N 51.2
Outdoor: Heating Cooling loisture difference(gr/lb) 29.4
Dry bulb(*F) 33 93 InIf itration: Simplified
Dailyrange (*F) - 18 ( M Aethod Average
Wet bulb(*F) - 77 �onstruction quality 1 (Average)
Wind speed(mph) 15.0 7.5 -ireplaces
Heatinci
Component Btu h/ft' Btuh %of load
Walls 3.2 3970 13.0
Glazing 30.9 6856 22.4
Doors 13.8 581 1.9
Ceilings 1.7 3028 9.9
Floors 3.8 6661 21.8
Infiltration 3.2 4221 13.8
Ducts 5258 17.2
Piping 0 0
Humidification 0 0
ventilation 0
Adjustments 0
Total 30576 100.0
Coolinu
Com onent Btu h/ft' Btuh %of load We" Internal Gains
Walls 2.2 2686 9.1
Glazing 61.7 13706 46.3 ucts
Doors 11.8 495 1.7
15.5
100
0
0
Btu h h of load
I
0
ails 22 2686 9-1
azing 6 7 1 3706 46-3
G 1 495 1.7
1 1 8 5
Doors A st 1 15
Ceilings 2.6 4581
Floors 0 0 0
Infiltration 0.7 903 3.0 nfillrabon
Ducts 5881 19.8
ventilation 0 0 Glazing
Internal gains 1380 4.7 Ceilings
Blower 0 0
Adjustments 0 Mer
Total 1 29632 100.0
Latent Cooling Load=4146 Btuh
Overall U-value=0.119 Btuh/ft'-oF
Data entries checked.
2012-Aug-20 14:19:58
wrightSOft' Rig ht-Suiteg U niversal 2012 12.0.12 RSU1 2605 Page i
Ad& CAUsers\Keiftnicholson.rup Calc=MJ8 Front Door faces: W
Job:
Component Constructions Date: Aug 20,2012
welightsoft' Entire House By:
Energy Design Solutions, Inc.
4925AJta Vista Ave,St.Augustine,FL 32080 Phone:904-669-6571 Email:kjmurrayg@yahoo.com I
Project Information
For: w7mothy Nicholson, Cool R us Inc
1563 Linksie DR,Atlantic Beach, FL 32233
Design Conditions
In", or: Heating Cooling
Location: door temperature(OF) 68 75
Jacksonville Intl AP, FL, US I
esign TD(OF) 36 18
Elevation: 33 ft 50
Latitude: 30oN elative humidity 50
Outdoor: Heating Cooling loisture difference(gr/lb) 29.4 51.2
Dry bulb(OF) 33 93 Inf Itration:
Dailyrange(OF) - 18 M Aethod Simplified
Wet bulb(OF) - 77 '-onstruction quality Average
wind speed (mph) 15.0 7.5 ::ireplaces 1 (Average)
- Or Area U-value Insul R Htg HTM Loss Cig HTM Gain
Construction descriptions ff BkhlW-'F ft2-'F/Btuh BbhMF Btuh BtUhMF Btuh
Walls 3.23 1541 2.29 1094
12C-Osw:Frm wall,stucco ext,r-1 3 cav ins,1/2"gypsum board int n 4T 0.091 13.0
e 16A 0.091 13.0 3.23 530 2.29 376
fnsh,2"x4"wood frm s 36A 0.091 13.0 3.23 1176 2.29 835
w 7-1 0.091 13.0 3.23 249 2.29 177
all 108, 0.091 13.0 3.23 3495 2.29 2481
Partitions 3.23 475 1.39 205
12C-Osw:Frm wall,M 3 cav ins,1/2"gypsum board int fnsh,2"x4" 14 0.091 13.0
wood frm
Windows 30.9 2780 71.7 6452
1 D-c2om:2 glazing,cir outr,air gas,mtl no brk frm mat,clr innr,1/4" e 9 0.870 0
gap,1/8"thk;50%outdoor insect screen;2 ft overhang(5 ft window w 31 0.870 0 30.9 927 71.7 2151
all 12) 0.870 0 30.9 3706 71.7 8603
ht,2 ft sep.) 1297 79.7 3346
1 D-c2omd:2 glazing,clr outr,air gas,mtl no brk frm mat,cir innr,1/4" e 4 0.870 0 30.9
gap,1/8"thk;2 ft overhang(7 ft window ht,2 ft sep.)
I D-c2om:2 glazing,cir outr,air gas,mtl no brk frm mat,clr innr,1/4" s 6) 0.870 0 30.9 1853 29.3 1758
gap,1/8"thk;2 ft overhang(5 ft window ht,2 ft sep.)
Doors w 21 0.390 0 13.8 291 11.8 247
11 DO:Door,wd sc type n 21 0.390 0 13.8 291 11.8 247
all 42 0.390 0 13.8 581 11.8 495
Ceilings 1.74 3028 2.63 4581
11613-1 9ad:Attic ceiling,asphalt shingles roof mat,r-1 9 ceil ins, 1/2" 17,-1 0.049 19.0
gypsum board int fnsh
Floors 41.9 6661 0 0
22A-cpm:Bg floor,heavy dry or light damp soil,on grade depth,carpet 1 1.180 0
fir fnsh
2012-Aug-20 14:19:58
wirlght"ft Right-Suitee U niversal 2012 12.0.12 RSU1 2605 Page 1
C:\Users\Keith\nicholson.rup Calc=MJ8 Front Door faces: W
Now
Job:
wrighWoft. Project Summary Date: Au920,20i2
Entire House By:
Energy Design Solutions, Inc.
4925AJta Vista Ave,St.Augustine,FL 32080 Phone:904-669-6571 Email:kimurray9@yahoo.com
For: Timothy Nicholson, Cool R Us Inc
1563 Linksie DR,Atlantic Beach, FL 32233
Notes:
Desicin Information
Weather: Jacksonville Intl AP, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 33 OF Ou side db 93 OF
Inside db 68 OF Ins de db 75 OF
Design TD 36 OF Deign TD 18 OF
Da ly range M
Re ative humidity 50 %
Mc isture difference 51 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
25318 Btuh Stricture 23751 Btuh
Structure 5881 Btuh
Ducts 5258 Btuh DL 1S 0 Btuh
Central vent(0 cfm) 0 Btuh CE ntral vent(10 cfm) 0 Btuh
Humidification 0 Btuh BI(wer
Piping 0 Btuh
Equipment load 30576 Btuh Use manufacturer's data n
RE te/swing multiplier 0.98
Infiltration Ec uipment sensible load 28951 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
I (Average) St ucture 2813 Btuh
Fireplaces Dt cts 1333 Btuh
Heating Cooling C( ntral vent (0 cfm) 0 Btuh
Area 1741 1741 E(uipment latent load 4146 Btuh
Molume(ft3) 13928 13928 total load 33097 Btuh
Air changes/hour 0.47 0.20 E 'uipment
Equiv.AVF (cfm) 108 46 q.total capacity at 0.70 SHR 3.4 ton
Heating Equipment Summary Cooling Equipment Summary
Make Trane M ake Trane
Trade XR15WEATHERTRON Ti ade XR15WEATHERTRON
Model 4TWR5042G1 C)nd 4TWR5042G1
AHRI ref 5495901 C)il *AM7AOC48H41
A IRI ref 5495901 12.5 EER, 15.3 SEER
Efficiency 9 HSPF Eficiency
S Bnsible cooling 29050 Btuh
Heating input 12450 Btuh
Heating output 40000 Btuh@47-F L itent cooling 41500 Btuh
Temperature rise 26 OF T)tal cooling
1383 cfm A Aual air flow 1383 cfm
Actual air flow 0.047 cfm/Btuh
Air flow factor 0.045 cfm/Btuh A r flow factor 0 in H20
Static pressure 0 in H20 S:atic pressure 0.88
Space thermostat L Dad sensible heat ratio
Calculations approved by ACCA to meel all requirements of Manual J 8th Ed.
2012-Aug-20 14:19:59
wrightSOft Right-Suite&Universal 2012 12.0.12 RSU1 2605 Page 1
Ak C:\Users\Keith\nichoison.rup Calc=MJ8 Front Door faces: W
Job:
wrightsoft. AED Assessment Date: Aug 20,2012
Entire House By:
Energy Design Solutions, Inc.
4925 Alta Vista Ave,St.Augustine,FL 32080 Phone:904-669-6571 Email:kjmurray9eyahoo.com I
Project Information
For: Timothy Nicholson, Cool R Us Inc
1563 Linksie DR,Atlantic Beach, FL 32'233
Design Conditions
In3 or: Heating Cooling
Location: door temperature(*F) 68 75
Jacksonville Intl AR FL, US esign TD('F) 36 18
Elevation: 33 ft elative humidity 1(%) 50 50
Latitude: 30ON oisture difference(grAb) 29.4 51.2
Outdoor: Heating Cooling I
Dry bulb(*F) 33 93 Inf Itration:
Dailyrange(oF) - 18 ( M
Wetbulb(*F) - 77
Wind speed (mph) 15.0 7.5
Test for Adequate Exposure Diversity
Hourly Glazing L.oad
14,
1Z
1Q
4,
Zm-
0
8 9 10 11 12 13 14 15 16 17 18 19 23
Hourcl`My
.,e Hourly /Average AED limit
Maximum hourly glazing load exceeds average by 20.6%.
House has adequate exposure diversity (AED), bat ed on AED limit of 30%.
AED excursion: 0 Btuh
2012-Aug-20 14:19:59
Page 1
wrighftoft Rig ht-Su iteg U niv ersal 2012 12.0.12 RSU 12605
AUX CAUsersXKefth\nichoison.rup Calc MJ8 Front Door faces: W
01 1 01
1 61 c)AED excursion
1 Envelope loss/gain 210971 214681
1 210971 214681
4221 903 4221 903
12 a) Infiltration 0 0 0 0
b) Room ventilation 1
13 Internal gains: Occupants @ 230 6 1380 6 1380
Appliances/other 0 0
Subtotal(lines 6 to 13) 25318. 23751 25318 23751
L ss external load 0 0
0 0 0
L:ss transfer 0 0 0 0
0
Redistribution 25318 23751 25318 23751
4 Subtotal 5
115 Duct loads 21% 25% 5258 881 21% 25% 5258 5881
Total room load 305761 296321 1 _t 305761 296321
Air required(cfm) 13831 1383 1383 13L3J
Calculations awroved by ACCA to meet E 11 reauirements of Manual J 8th Ed,
2012-Aug-20 14:19:59
wrI161h"'Oft' Rig ht-Suite4D U niversal 2012 12.0.12 RSU1 2605 Page 1
C:\Users\Keith\nicholson.rup Calc=MJ8 Front Door faces: W