Permit 632 CU and AHU I-V
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00001220 Date 9/13/12
Property Address . . . . . . 632 CAMELIA ST
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------
Application desc
1 CU 1 AHU
--------------------------------------------------
Owner Contractor
-
------------------------
-----------------------
LONG EUGENE B & MARY F ONE HOUR AIR
632 CAMELIA ST 1015 ATLANTIC BLVD #249
ATLANTIC BEACH FL 322332522 ATLANTIC BEACH FL 32233
(904) 222-8482
----------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . . PKG UNIT
Permit Fee 79 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 3/12/13
---------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
-------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----
Permit Fee Total 79 . 00 79 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 83 . 00 83 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247-5826 Fax (904) 247-5845
JOB ADDRESS: 63 2 ivnd/rU S'--/- PERMIT#
PROJECT VALUE $ ql d 6 ARI# 1439 5-076
REQUIRED
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit .3
Heat: Unit Quantity�— BTU's Per Unit 7 Seer Rating__
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name_El 4�0fu 6 Phone Number SS-3--q l 1 7
Mechanical Company e f Office Phone 2y — lQ 7Fax 2 Lf7 SS2G
Co. Address: 1.1 cCity fj C State —L Zip X2`2
11
License Holder(Print): ifcatio .Registration �l7` nc
Notarized of License Holder
SHIRLEY L.GRgHgM SW and subscribed befo In t ' y of 20
` 0MM;3S10N k DD 957760
_+ •....B?, E:XNIfiES:February 14,20t@
Af,,h.•` Bonded 7Ijry Not a 1� ture of Notary Pu
87 ublic Undenvhtet3�
Job: 120058
Project Summary Date: 911212012
W���tSQ
Entire House By: CRAIG EDDY
ONE HOUR AIR
1196 MAYPORT RD tit,ATLANTIC BEACH,FL 32233 Phone:904-241-3107 Fax:904-247-5526 License:CAC1814420
For: EUGENE LONG
632 CAMELIA,ATLANTIC BEACH, FL 32233
Phone:904-553-4193
Notes:
Weather: Jacksonville/Craig, FL, US
Winter Design Conditions Summer Design Conditions
35 OF Outside db 91 OF
Outside db 70 OF Inside db 75 OF
Inside db35 OF Design TD 16 °F
Design TD Daily range M
50
Relative humidity
Moisture difference 53 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
31214 Btuh Structure 26124 Btuh
Structure 0 Btuh Ducts 0 Btuh
Ducts 0 Btuh Central vent(0 cfm) 0 Btuh
Central vent(0 Cfm) 0 Btuh Blower 0 Btuh
Humidification 0 Btuh
Piping 31214 Btuh Use manufacturer's data y
Equipment load Rate/swing multiplier 1.00
Infiltration
Equipment sensible load 26124 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average 2700 Btuh
Fireplaces 0 Structure 0 Btuh
Ducts 0 Btuh
Heating Cooling Central vent(0 cfm) 2700 Btuh
Area(ftp 1568 1568 Equipment latent load
Volume(ft") 12544 1 0.20 Equipment total load 28824 Stuh
Air changes/hour 79 42 Req.total capacity at 0.72 SHR 3.0 ton
Equiv.AVF(cfm)
Heating Equipment Summary Cooling Equipment Summary
Make GOODMAN Make GOODMAN
Trade ONE HOUR AIR
Trade ONE HOUR AIR
Cond GPC1336H41AC
Model GPC1336H41AC
AHRI ref 4385070 Coil
AHRI ref 4385070 13 SEER
Efficient 0 HSPF Efficiency 25992 Btuh
Heating input Sensible cooling 10008 Btuh
Heating output 0 Btuh @ 47°F Latent cooling 36000 Btuh
Temperature rise 0 OF Total cooling 1189 cfm
Actual air flow 1189 cfm Actual air flow 0.046 cfm/Btuh
Air flow factor 0.038 cfm/Btuh Air flow factor 0 in H2O
Static pressure 0 in H2O Load sensible heat ratio 0.91
Space thermostat
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2012-Sep-12 12:56:24
`
wrightlIlli Right-Suite®Universal 2012 12.0.13 Right J®Mobile
Page 1
C:\WINDOWS\TEMP\wstmp\ee9daa3e-8b4b-405e-8884-ac06d4f3905b.rup Calc=MJ8 Front Door faces: E