Permit HVAC 1615 Seminole Rd 2012 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00001395 Date 9/26/12
Property Address . . . . . . 1615 SEMINOLE RD
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
SANFORD, EDWARD J JR DONOVAN HEATING & AIR
LIFE ESTATE 315 SIXTH AVENUE SOUTH
4 SHENANDOAH CIR JAX BEACH FL 32250
CARTHAGE TN 37030 (904) 241-3785
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 99 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 3/25/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 99 . 00 99 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 103 . 00 103 . 00 . 00 . 00
PERMIT IS APPROVED ONLV IN ACCORDANCE WITH ALL CITV OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
AlEcHANICALpERMITAPp1jCATION
CITY OFATLANnC BEACH
'00 Sen"nole Rd Atlantic B=h,FL 32233
Ph(904)247-5826 Fax(9()4)247-5845
JOB ADDRm: 15 15,, I
(J
"AM-- #
PROJECT VALUE 3 BC70 of'o
NEW AIR CONDMONING&HEATING SYSTEM INSTALLATZON
Air Conditionw. Unit Quantity
Heat Tons PmUoit
Briusperu
Duct Systems: Total c'm nit Seer Ratiw
REPLACEMENT AIR CONDITIONING &HEATING SYSTEM INsTALLAT.1,
Air Conditi
oning: Unit Quanw*y I AM# 3
U
Heat Tons Per unit
BTU's Per Unit Vo
Duct Systems: Total CFM —0 Seer
FIRE PREVENTION
Fire Sprinkler System Quantity
Fire Standpipe, --------- (Requires 3 sets of pLim)
Underground Fire Main Value (Requh-es 3 sets of pis=)
(Req-uhw 3 sets of 11—A
Fire Hose Cabinets Quantity (Requires 3 sets of Faw)
Commercial Hoods Quantity 1011m)
Fire Suppression Systems Quantity Mequires 3 sets of plaw)
(Re4uims 3 seft of
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTWs—
ALL OTHER GAS p]pING Elevator:���
quantity of Outlets Heat Exchanger
Vented Wall Furnaces R igeratDr condenser
Water Heftrs Solar Collection Systems BTU'-s—
Tanks Wons) -------
Wells
OTHER:
P,ennft becomes void ifwork does not commence within a six month period or viork is ftVanded or abando-nedfor six monft, h
th wlication md IMOW ft Sam to be Mw and COMM All pmvWow of I &*Y certify the I have read
)r not 7be Permit dow not give auftdW to violft the providonsof lam and ora==90v`eMi08 Arb wwk will be CDMPhW wVh Whc1hff Vacified
any other state or local law reg"on construction or the perrummee ofoonstniction.
"z0pWy0wn=Name, C-dWAfcj Phone Number OILM -d3�9
dechanical.Company-Cbnovool —0face Phone S�t 1 T)
"'o.Address: ai'5- Llci� j?ax 9S-
d!atff- -S, City 1) t Uck State f
-kense,Holder(Print): I- Zip
State CertificationMegistcation.#_L!j�-j I�61
Woted S4vw&m ofLicense Holder
Swom and subscri-bed before me,this .26 day of
ig�re�ofNotaryftblic
Notary Pubk State of Florkla
rmn,:y H has
My C =Ul
FEE 186278
Expires 04/03/2016
wrightsoft- Project Summary Job:
Date: September 10,2012
Endiv House By: Aaron Thacker
Donovan Heat& Air
315 6th Pme S,Jacksonville Beach,FL 32250 Phone:904-241-3785 Fax 904-241-3745 Email:aaronCdonovanac.mm Web:www.[)onovanAC.cGm
Project Information
For: Edward Sanford
1615 Seminole Rd,Atlantic Beach, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 OF Outside db 99 OF
Inside db 70 OF Inside db 75 OF
Design TD 31 OF Design TD 24 OF
Daily range L
Relative humidity 50 %
Moisture difference 69 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 26705 Btuh Structure 23491 Btuh
Ducts 5610 Btuh Ducts 5837 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 32314 Btuh Use manufacturer's data n
Ratetswing multiplier 1.04
Infiltration Equipment sensible load 30501 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Aver
Fireplaces 0 Structure 1497 Btuh
Ducts 2972 Btuh
Heatin cool"n Central vent (0 cfm) 0 Btuh
Area(ft') 1040 12 Equipment latent load 4468 Btuh
Volume(ft') 8320 8320
Air changes/hour 0.45 0.23 Equipment total load 34970 Btuh
Equiv.AVF (cfm) 62 32 Req. total capacity at 0.70 SHR 3.6 ton
Heating Equipment Summary Cooling Equipment Summary
Make Carrier Make Carrier
Trade BASE 13 PURON HP Trade BASE 13 PURON HP
Model 25HBC342A**50 Cond 25HBC342A**50
AHRI ref no3701582 Coil FB4CNF048++TXV
AHRI ref no3701582
Efficiency 8 HSPF Efficiency 11.5 EER, 14 SEER
Heating input Sensible cooling 28700 Btuh
Heating output 39500 Btuh @ 47*17 Latent cooling 12300 Btuh
Temperature rise 26 OF Total cooling 41000 Btuh
Actual air flow 1367 cfm Actual air flow 1367 cfm
Air flow factor 0.042 cfm/Btuh Air flow factor 0.047 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
Space thermostat Load sensible heat ratio 0.87
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2012-Sep-26 14:03:20
wrlightSOft Right-SulteS Universal 8.0.24 RSU05995 Page I
C:\Users\Owner\Documents\Wrightsoft HVAC\Bogus 3 ton.rup Calc=MJ8 Front Door faces: W
0% "top
J%N Smal CERTIFIEDTM
L_ www.ahridirectory.org 'A
Certificate of Product Ratings
AHRI Certified Reference Number: 3701582 Date: 9/26/2012
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: 25HBC342A**50
Indoor Unit Model Number: FB4CNF048+TXV
Manufacturer: CARRIER AIR CONDITIONING
Trade/Brand name: BASE 13 PURON HP
Manufacturer responsible for the rating of this system combination is CARRIER AIR CONDITIONING
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 41000
EER Rating (Cooling): 11.50
SEER Rating (Cooling): 14.00
Heating Capacity(Btuh)@ 47 F: 39500
Region IV HSPF Rating (Heating): 8.00
Heating Capacity(Btuh)@ 17 F: 23600
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents ofthis Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, in "IMF, Air-Conditioning,Heating,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below. OWU an ILI and Refrigeration Institute
02012 Air-Conditioning, Heating,and Refrigeration Institute CERTIFICATE NO.: 129931610627205577