2044 Duna Vista Ct 2012 HVAC 2012 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
it
Application Number . . . . . 12-00001682 Date 11/13/12
Property Address . . . . . . 2044 DUNA VISTA CT
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 4082
----------------------------------------------------------------------------
Application desc
REPLACE 1 CU 1 AHU
-------------------------------------------------------------
Owner Contractor
------------------------
------------------------
ARMEL BRUCE E & JENNIFER S WAYCHOFFS AIR CONDITIONING
2044 DUNA VISTA CT 6929 PHILLIPS PARKWAY DR S
ATLANTIC BEACH FL 322334534 JACKSONVILLE FL 32256
(904) 838-9052
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . . REPLACE 1 CU 1 AHU . 00
Permit Fee . . . . 103 . 00 Plan Check Fee 0
Issue Date . . . . Valuation . . . .
Expiration Date . . S/12/13 ------
------------------------------------------------------------- --------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 103 . 00 103 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 107 . 00 107 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, Fl,32233
Ph(904)247-5826 Fax (904) 247-5845
JOB ADDRESS: aC)Lj(4 _�)LL(jCt \/jS+CL COLLr-� PERNHT# lo?- Ik f 2-
PROJECT VALUE $ L4081
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI# 370041-7
Air Conditioning: Unit Quantity Tons Per Unit -3.5 REQUIRED
Heat: Unit Quantity BTU's Per Unit 14 It OW Seer Ratil�g'__04(_
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity — (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity — (Requires 3 sets of plans)
TIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
�LL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
Vented Wall Furnaces Refrigerator Condenser BTU's
Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
)THER:
,rmit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
is application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the perforinance of construction.
-operty Owners Name 'Rr L,((!e Phone Number 00y�aLw-,)-7C3z
echanical CompanykA)aA42h RIC— —Office Phoneq&o ISSoN I>Slzg_�_l
SFax :02
Address:(gPOci !Ali I I IpS 'Pkwv City State FL Zip 3,)a5_&
.cense Holder (Print): State Certifi ati egistration 4 CACI-2 118-7
Varized Signature ofLicense Holder
S orn and subscribed before-me t s ay of NCN/CrYlbe r 2 0 1,-,L
JENNFER LyNm BOOKER Public, yX.1k
t
WCOWASsmMi" nature of Notary
EEXPM Dwmdm 01.2015, U
,I
NMI"
Job:
Right J@ Mobile Report Date: 11112/2012
+ wrightsoft Entire House By:
AL
Project Information
For: Bruce Armel
2044 Duna Vista Ct., Atlantic Beach,, FL 32256
Phone: 904-
Design Conditions
Location: Indoor: Heating Cooling
Jacksonville/Craig, FL, US Indoor temperature(oF) 70 75
Elevation: 43 ft Design TD (oF) 35 16
30'N Relative humidity(%) 30 50
Latitude: Moisture difference(gr/lb) 8.4 52.8
Outdoor: Heating Cooling
Dry bulb(*F) 35 91 Infiltration:
Dailyrange('F) - 17 ( M Method Simplified
Wet bulb('F) - 77 Construction quality Average
Wind speed(mph) 15.0 7.5 Fireplaces 0
N N 2
-Component Btu h/fF Btuh % of load
Walls 2.7 4237 12.8 MIS Dils
Glazing 19.7 4216 12.7
Doors 13.5 433 1.3 Claft
Ceilings 1.7 3603 10.9
Floors 4.4 9374 28.3
Infiltration 2.2 3876 11.7 ditaficn
Ducts 7381 22.3 CdIir9S__
Piping 0 0
Humidification 0 0
Ventilation 0 0
Adjustments 0
Total 33119 100.0
Component Btu h/f? Btuh %of load
Walls 1.1 1739 5.8 V�bls rtemal Gans
Glazing 45.0 9619 31.8
Doors 11.4 367 1.2
Ceilings 2.1 4457 14.7
Floors 0 0 0 Ga�ng
Infiltration 0.5 913 3.0 Duds
Ducts 10049 33.2
Ventilation 0 0
Internal gains 3090 10.2
Blower 0 0 aher
Adjustments 0 Ceilirgs Infift4on
Total 30233 100.0
Latent Cooling Load 4792 Btuh
Overall U-\ralue=0.105 Btih/ft2-'F
Data entries checked.
2012-Nov-1 2 OBA 3:49
wrightsoft Right-Suite(g)Universal 2012 12.1.00 Right J@ Mobile Page 1
ACCA C:\VnNDOWS\TEMP\w!;tmp\25662d8b-860e-4360-98f7-e8le3366efbb.rup Calc=MJ8 FrontDoorfaces: S
Job:
Project Summary Date: 11112/2012
+ wrightsoft Entire House By:
AL
Project Information ------
For: Bruce Armel
2044 Duna Vista Ct., Atlantic Beach,, FL 32256
Phone: 904-
Notes:
Des ig n Information
Weather: Jacksonville/Craig, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 35 *F Outside db 91 *F
Inside db 70 'F Inside db 75 -F
Design TD 35 'F Design TD 16 'F
Daily range M
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 25738 Btuh Structure 20184 Btuh
Ducts 7381 Btu h Ducts 10049 Btuh
Central vent(0 cfm) 0 Btu h Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 33119 Btu h Use manufacturer's data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 30233 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 2429 Btuh
Ducts 2363 Btuh
Heating Cooling Central vent(0 cfm) 0 Btu h
Area(ft') 2125 2125 Equipment latent load 4792 Btuh
Volume(ft) 19125 19125
Air changes/hour 0.32 0.16 Equipment total load 35025 Btuh
Equiv.AVF (cfm) 102 51 Req.total capacity at 0.70 SHR 3.6 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make
Trade Trade
Model Cond
AHRI ref Coil
AHRI ref
Efficiency 0 HSPF Efficiency 0 SEER
Heating input Sensible cooling 0 Btuh
Heating output 0 Btuh @ 47-F Latent cooling 0 Btuh
Temperature rise 0 'F Total cooling 0 Btu h
Actual air flow 1209 cfm Actual air flow 1209 cfm
Air flow factor 0.037 cfm/Btuh Air flow factor 0.040 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
Space thermostat Load sensible heat ratio 0.86
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2012-Nov-1 2 08:13:49
+ vv'rightsoft Right-SuiteG universal 2012 12.1.00 Right J0 Mobile Page 1
-*—'C�l C:\V\nNDOWS\TEMP\wstmp\25662d8b-860e-436G-98f7-e8le3366efbb.rtjp Calc=MJ8 Front Door faces: S
Job:
wrightsoft Right-JO Worksheet Date: 11112/2012
Entire House By:
AL
Entire House First Floor
1 Room name 199.5 ft 199.5 ft
2 Exposed wall 9.0 ft 9.0 ft heat/cool
3 Room height 1�0 x 2125.0 ft
4 Room dimensions 2125.0 ft' 2125.0 ft2
5 Room area I
- Ty I Consinj HTM Load Area (ft2) 0'ad
U-value Or Area (ft') (ICB h)
number (13tuh/ft'�-'IF) (Btuh/ft) or perimeter (ft) .Btu I h) or perimeter (ft)
1:111 -[:��Heat I or I
Gross
Heat Cc G=. r="PIS Heat
6 2B-3bw 0.079 n 2.73 1 12 360 318 868 356 360 318 868 356
11 D--2ow, 1972 2091 43 0 838 889 43 0 838 889
0570 n 64 57 155 63
2B-3bw 0.079 ne 2.73 1A2 64 57 1 55 63
t-G 1 0.570 ne 19.72 46.75 7 0 140 331 7 0 140 331
1 D-c2ow 2.73 1.12 450 396 1082 444 450 396 1082 444
12B-3bw 0.079 e 0 1068 3413
t-G I D-c2ow 0.570 e 19.72 63.01 54 0 1068 3413 54
2B-3bw 0.079 s 2.73 1.12 405 357 975 400 405 357 975 400
T--G 11 D-c2ow 0.570 s 19.72 25.16 48 0 953 1216 48 0 953 1216
1 2B-3bw 0.079 w 2.73 1.12 454 367 1003 412 454 367 1003 412
1D-,c2ow 0570 w 19.72 63.01 55 0 1076 3439 55 0 1076 3439
111130 0.390 w 13.49 11.43 32 32 433 367 32 32 433 367
2B-3bw 0.079 nw 2.73 1.12 64 57 155 63 64 57 155 63
t--G '1D-c2ow, 0570 nw 19.72 46.75 7 0 140 331 7 0 140 331
C 16G-19al 0.049 1.70 2.10 2125 2125 3603 4457 2125 2125 3603 4457
F 22Acph 1.358 46.99 0.00 2125 200 9374 0 2125 200 9374 0
0 0
21862 161 1 211862_. 16 18,1
Envelope loss/gain
3876 913 3876 913
12 a) Infiltration 0 0 0 0
b) Room ventilation
- 690 3 690
13 Internal gains: Occupants @ 230 3 2400 2400
Appliances/other --- -
- 25738 20184 25738, 20184,
Subtotal(lines 6 to 13) ----
0 0 0 0
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 25738 20184 25738 20184
14 Subtotal 29% 50% 7381 10049 29% 50% 7381 10049
15 Duct loads
- 331191 3023�3
331191 302331
Total room load 12091 12091 120 1209
Air required(cfm)
Calculations approved by ACCA to meet all reguirements of Manual J 8th Ed. 2012-Nov-12 08:13:49
%mriiO"'tsc)�ft Right-Suiteg Universal 2012 12.1.00 Right J@ While oorfaces: S Page 1
Ci\VVINDOWS\TEMP\wstrnp\25662dBb-86OeA360-98f7-e8le3366efbb.rup Calc=MJ8 Front D
Job:
Component Constructions Date: 11112/2012
wrightsoft Entire House By:
AL
Project Information
For: Bruce Armel
2044 Duna Vista Ct.,Atlantic Beach,, FL 32256
Phone-. 904-
Design Conditions
Location: Indoor: Heating Cooling
Jacksonville/Craig, FL, US Indoor temperature(T) 70 75
Elevation- 43 ft Design TD(T) 35 16
Relative humidity 30 50
Latitude, 30'N Moisture difference(gr/lb) 8.4 52.8
Outdoor: Heating Cooling
Dry bulb(T) 35 91 Infiltration:
Daily range(T) - 17 M Method Simplified
V\Ietbulb(*F) - 77 Construction quality Average
V\find speed(mph) 15.0 7.5 Fireplaces 0
Or Area 1.1-value Insul R Htg HTM Loss Cig HTM Gain
Construction descriptions ft2 BtuhW-0F W-0 F/Btuh Btuh/W Btuh l3tuh1W l3tuh
Walls 1.12 356
12B-3bw:Frm wall,brk 4"ext,r-1 1 cav ins,1/2"gypsum board int n 318 0.079 14.0 2.73 868
fnsh,r-3 ext bd ins,2"x4"wood frm ne 57 0.079 14.0 2.73 155 1.12 63
e 396 0.079 14.0 2.73 1082 1.12 444
S 357 0.079 14.0 2.73 975 1.12 400
w 367 0.079 14.0 2.73 1003 1.12 412
nw 57 0.079 14.0 2.73 155 1.12 63
all 1550 0.079 14.0 2.73 4237 1.12 1739
Partitions
(none)
Windows 889
1 D-c2ow:2 glazing,cir outr,air gas,wd frm mat,clr innr,1/4"gap, n 43 0.570 0 193 838 20.9
ne 7 0.570 0 19.7 140 46.8 331
1/8"thk e 54 0.570 0 19.7 1068 63.0 3413
s 48 0.570 0 19.7 953 25.2 1216
w 55 0.570 0 19.7 1076 63.0 3439
nw 7 0.570 0 19.7 140 46.8 331
all 214 0.570 0 19.7 4216 45.0 9619
Doors w 32 0.390 0 13.5 433 11.4 367
11 DO:Door,wd sc type
Ceilings 2.10 4457
16C-19al:Attic ceiling,asphalt shingles roof mat,r-19 ceil ins,1/2" 2125 0.049 19.0 1.70 3603
gypsum board int fnsh
Floors 0 0
22A-cph:Bg floor,heavy damp soil,on grade depth,carpet fir fnsh 200 1.358 0 47.0 9374
2012-Nov-12 08:13:50
wrightSCM Right-Suite@ Universal 2012 12.1.00 Right JO Mobile Page 1
ACC-l', C:\WiNDOWS\TEMP\wstmp\25662d8b-860e-4360-98f7-e81 e3366efbb.pip Cale=MJ8 Front Door fares S
Ulm
0%0 MEN CERTIFIEDT.
www.ahridirectory.org
Certificate of Product Ratings
AHRI Certified Reference Number: 3700417 Date: 11/13/2012
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: 213BN(A,W)042****A
Indoor Unit Model Number: FX4DN(B,F)043
Manufacturer: BRYANT HEATING AND COOLING SYSTEMS
Trade/Brand name: LEGACY LINE PURON HP
Manufacturer responsible for the rating of this system combination is BRYANT HEATING AND COOLING
SYSTEMS
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent, third
party testing:
Cooling Capacity (Btuh)-. 41000
EER Rating (Cooling): 11.50
SEER Rating (Cooling): 14.00
Heating Capacity(Btuh) @ 47 F 40000
Region IV HSPF Rating (Heating): 8.00
Heating Capacity(Btuh) @ 17 F 23800
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products ofAHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, "IMF, Air-Conditioning,Heating,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on &I " No ILI and Refrigeration Institute
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below.
(92012 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 129972946025883507