Fire Alarm System Inspection and Testing Report
This testing was performed in accordance with applicable N.F.P.A.standards.
Owner: VIA MARE CONDO ASSOCIATION ISC# J00736 Date: 29 NOVEMBER 21
Owner's Address: 1635 EAGLE HARBOR PRKWY E STE 4 FLEMING IS.,FL 32003
Property Being Evaluated: VIA MARE
Property Address: 331 AHERN STREET ATLANTIC BEACH,FL.32233
Monitoring Entity
Panel Manufacturer: SILENT KNIGHT Model No. 5700
Name: COPS
Circuit Styles: 4.0 Amt 1(SLC)
Telephone: 1-800-934-2527
Last Date System Had Service Performed: DECEMBER 2011 /WAFS
Account Ref.No. 3258128
Last Date Software or Configuration was Revised: V9.04 AUGUST 2006
Service
r,-Weekly AHJ DUVAL COUNTY FIRE MARSHAL
(1-Monthly AHJ phone# 904-630-0445
Quarterly
("-Semi-Annually (�` -Digital
(-` -R.F.
(i-Annually
Other(Specify) t Other Specify
Inspected by(print) MICHAEL TA Date: 29 NOVEMBER 2012 Time:
ELL 1300
Signature of Alarm Agent: (Agent Meets Requirements Per Florida Statute 489.518)
Name of Owner or representative
S gn tltlu e
vto have a copy of NFPA#72(d an extra charge of$50.00. QYes O No Date: 29 NOV:EMBER 2012 !!Owner or Owner rep.not on site.
Owner or rep.requests WAFS to release information from
inspections to the underwriters of my Insurance company. Oyes ONo System restored to normal operation:Time: 1500
Notifications are made Yes No Who Time
Monitoring Entity R 17 OPERATOR 3019 1307
Building Occupants r' F
Building Management (X: I- TONY GORIA 1200
Other(Specify) �" r
I. ALARM NOTIFICATION APPLIANCES TEST AND INSPECTION
Device - Circuit Style/Quantity - Operational Test Approved Location - Pass - Fail
Bells Quantity( 4 ) Size(6.00) Type(120VAC ) 15—' PK r 1X_'
Horns A( ) B( ) r; h r r
Speakers A( ) B( ) r r r r
Chimes A( ) B(
Strobes A( ) B( ) rr', F r
Other:(Specify) A( ) B( ) r r', r r'
No.of Alarm indicating circuits: Are Circuits supervised? {`,:Yes (—,No
Page 2
II.INITIATING AND SUPERVISORY DEVICE TEST AND INSPECTION
Device - Circuit Style/Quantity - Operational Test - Simulated Test - Pass - Fail
Manual Stations A( ) B( ) 17, r r' F
Ion Detectors A( ) B( ) rl F 17 r'',
Photo Detectors A( ) B(1 ) Fx-, r FX_
Duct Detectors A( ) B( ) �-- F F r,
Heat Detectors A( ) B( ) rr
Waterflow Detectors A( ) B(4 ) r, r
Supervisory Switches A( ) B(4 ) r' r (X F
Pressure Switches A( ) B( ) F
Low Air A( ) B( ) r,'
Other(Specify): A( ) B( ) F F, F r
III. SUPERVISORY SIGNAL INITIATING DEVICES&CIRCUIT INFORMATION
Site Water Temp. Yes (`No C N/A
Site Water Level ( Yes (`No r N/A
Fire Pump Power ( -Yes r No {i N/A
Fire Pump Running (`Yes (`No C N/A
Fire Pump Auto Position (`,,Yes (`No f%N/A
Fire Pump or Pump Control Trouble (-Yes ( No r!'N/A
Generator In Auto Position (`Yes r,,=No (q!)N/A
Generator or Controller Trouble 'Yes (`No (!`N/A
Switch Transfer (~Yes (' No r%N/A
Generator Engine Running (`Yes (`No ( N/A
Lock Box (`;Yes (`No lj* N/A
A.SIGNALING LINE CIRCUITS
Quantity and style(See NFPA 72,Table 3-6)of signaling line circuits connected to system
Quantity 1 Style(s): 4.0
IV.SYSTEM POWER SUPPLIES
A.Primary(Main):Normal Voltage 120VAC Amps 3
Overcurrent Protection:Type: CKT BRK Amps 20
Location(Panel#): HOUSE PANEL TO RIGHT OF FACP UNDER STAIRS
Disconnecting Means Location: CKT 9
B.Secondary(Standby): 24VDC(INSTALLED JUNE 2012)
Storage Battery:Amp-Hr.Rating 8Ah
Calculated capacity to operate system,in hours: r'' 24 60
NA Engine driven generator dedicated to fire alarm system:
C.Location of Fuel Storage: NA
D.TYPE BATTERY SECONDARY POWER
Dry Cell Type Visual Functional
Battery Condition [X—
Nickel Cadmium
[)W Sealed Lead-Acid Load Voltage 24.6
TX
Other(Specify): Discharge Test Min. F
Specific Gravity
E.Emergency or standby system used as a back-up to primary power supply,instead of using a secondary
power supply. NA Emergency system described in N.F.P.A.,.Article 700.
Page 3
V.SYSTEM TESTS&INSPECTIONS
A.Type Visual Functional D.Notification Appliances - Visual - Functional
Control Panel �, Audible F
Interface Equipment Visual r', r
L.E.D.s/Lampsr r' Speakers (— (—
Fuses/MicroBreakers rVoice Clarity �!
Primary Power Supply r r
Trouble Signals r
Disconnect Switches r' r
Ground Fault Monitoring r r' E.ON i OFF Premises Monitoring
Yes No N/A
B.Emergency Communication Equipment Alarm Signal (07 r r—
Type Visual Functional N/A
Alarm Restoril
Phone Set
r' Trouble Signal
Phone Jacks r' C '
r", � , r, Trouble Restaral
Off Hook Indicators
Supervisory Signal
Amplifier(s) F7 r, (�`
Tone Generator(s) �"'' r Supervisory Restoral
Call In Signal r, Remote Anuc�iator (` {` (`
System Performance (—', r r
C.Interface Equipment DEVICE SIMULATED
(SPECIFY) VISUAL OPERATION OPERATION
WAYNE NET r' F r'
r r r
r � r
Special Hazard System(Specify)
F—
VI.COMMENTS:
SIGNALS RECEIVED&RESTORED W/OPERATOR 2106 at 1525
VII.DEFICIENCIES: These items are the owner's responsibility to be repaired and will be quoted separate from inspection cost.
1)FLOW BELL ON BUILDING ONE DID NOT OPERATE WITH WATER FLOW
2)BUILDING TWO&THREE FLOW SWITCHES ACTIVATED FLOW BELLS,BUT DID NOT REPORT TO FACP;SPRINKLERS
PRESENTLY IMPAIRED DUE TO ALARM NOT REPORTING TO FACP OR MONITORING