Permit HVAC 2166 S Fairway Villas Ln 2013 CITY OF ATLANTIC BEACH
j 800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00001998 Date 1/15/13
Property Address . . . . . . 2166 S FAIRWAY VILLAS LN
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu add 3 returns
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
SEELY TROPIC HEATING & AIR
2166 FAIRWAY VILLAS LN E 750 MAYPORT RD
ATLANTIC BEACH FL 322334408 ATLANTIC BEACH FL 32233
(904) 241-1788
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 111 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 7/14/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 111 . 00 111 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 115 . 00 115 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE: WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH /�Q
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax(904) 247-5845 I
JOB ADDRESS: (� 1 6 N) - Y� u -c PERMIT#
PROJECT VALUE $ -j 35on"
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI# 5'35-817 0
Air Conditioning: Unit Quantity / Tons Per Unit Z REQUIRED
Heat: Unit Quantity i BTU's Per Unit Seer Rating /3 d
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks(gallons)
Wells
OTHER: !&(Z ,-e1w c � ti .'S .sice..a..a-i —.¢dg/....�
3 0 o cl:--Al s tp �v�•n
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name Lf)N CA E Phone Number q G`�q
Mechanical Company ra P,C. 1'4 4 h L Office Phone aq Fax
Co. Address: -750 City (- Ci, State E Zip 3 a a 33
License Holder(Print): \,�f)T- IF .� • �(���� State Certification/Registration# c6Cd 5'a,43 J
Notarized Signature of License Holder
KAREN E.PANTFOEDER Sworn and subscn ed before me this 5 day of C-k n uQ►'�! 2013
NOTARY PUBLIC Signature of NotaryPublic G y
STATE OF FLORIDA
Comm#EE064448
Expires 3/4/2016
i
CERTIFIED,.
,
9CertificateProduct Ratings
ce Number: 5358270 Date: 1/15/2013
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: GSZ130241B*
Indoor Unit Model Number: ARUF24B14A*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN, JANITROL,AMANA DISTINCTIONS, EVERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system combination is GOODMAN MANUFACTURING CO., LP.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent, third
party testing:
Cooling Capacity(Btuh): 22800'
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00
Heating Capacity(Btuh)@ 47 F: 21600*
Region IV HSPF Rating (Heating): 7.70
Heating Capacity(Btuh)@ 17 F: 13500
rerate of previously published data,unless accon__ a'NAS,which indicates an involuntary rerate-
�s®rc.
DIS*IMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory at
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information forthe modei cited on this certificate can be verified at Air-Conditioning,Heating,
click on" "link and errter the AHRI Certified Reference Number and the date on Also No ai and Refrigeration Institute
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below.
02012 Air-Conditioning,Heating, and Refrigeration Institute CERTIFICATE NO.: 130027346483342230
I
Pro ect Summa Job: Seeley
aw, t - � ry Date: 1/15/2013
Entire House By:
soft•C«d&#swru
AL
Project • f
For: Craig Seeley, Tropic Heating&Air Conditioning, Inc.
2166 Fairway Villas L.,Atlantic Beach, FL 32233
Phone: 904-241-1788 Fax: 904-241-2172
Email: Tropicac@msn.com
Notes:
Design • •
Weather: Jacksonville/Craig, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 35 'F Outside db 91 °F
Inside db 70 °F Inside db 75 °F
Design TD 35 'F Design TD 16 °F
Daily range M
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 16459 Btuh Structure 12549 Btuh
Ducts 3444 Btuh Ducts 3949 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 19904 Btuh Use manufacturer's data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 16497 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 1700 Btuh
Ducts 842 Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
,Area(f:2) 1000 1000 Equipment latent load 2542 Btuh
Volume(ft) 8000 8000
Air changes/hour 0.45 0.23 Equipment total load 19040 Btuh
Equiv.AVF(cfm) 60 31 Req. total capacity at 0.70 SHR 2.0 ton
Heating Equipment Summary Cooling Equipment Summary
Make n/a Make
Trade n/a Trade
Model n/a Cond
AHRI ref n/a Coil
AHRI ref
Efficiency n/a Efficiency 0 SEER
Heating input 0 MBtuh Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 °F Total cooling 0 Btuh
Actual air flow 701 cfm Actual air flow 701 cfm
Air flow factor 0.035 cfm/Btuh Air flow factor 0.042 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.87
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2013-Jan-15 06:21 40
WYigh't-soft Right-Su He®UnNersal 201212.1.05 Right J®Mobile Pagel
C:\WINDOWS\TEMP\w tmp\faa54ddl-2b70-470e-a901-0358bc32debg.rup Calc=MJ8 FrontDoorfaces. E
-- Job: Seeley
Right J® Mobile Report Date: Seeley
11AEntire House By:
ft"aoN%ftdm
AL
Project • •
For: Craig Seeley, Tropic Heating&Air Conditioning, Inc.
2166 Fairway Villas L.,Atlantic Beach, FL 32233
Phone: 904-241-1788 Fax: 904-241-2172
Email:Tropicac@msn.com
Design Conditions
Location: Indoor: Heating Cooling
Jacksonville/Craig, FL, US Indoor temperature (°F) 70 75
Elevation: 43 It Design TD(°F) 35 16
Latitude: 30°N Relative humidity(%) 30 50
Outdoor: Heating Cooling Moisture difference(gr/Ib) 8.4 52.8
Dry bul b(°F) 35 91 Infiltration:
Daily range(°F) - 17 ( M ) Method Simplified
Wetbulb(°F) - 77 Construction quality Average
Wind speed(mph) 15.0 7.5 Fireplaces 0
•
Component Btuh/ftz Btuh %of load
Walls 3.4 3278 16.5 Vd
Glazing 19.7 2202 11.1
Lur
Doors 13.5 425 2.1 g
Ceilings 1.7 1695 8.5 Gm __ Irfiltrm
Floors 6.6 6578 33.1
Infiltration 2.0 2280 11.5 Docs
Ducts 3444 17.3
Piping 0 0 cilirgs
Humidification 0 0 Rous
Ventilation 0 0
Adjustments 0
Total 19904 100.0
Component Btuh/ft2 Btuh %of load
Walls 2.6 2549 15.5 Intar�l C
Glazing 45.7 5104 30.9 WA Is
ans
Doors 11.4 360 2.2
Ceilings 2.1 2097 12.7
Floors 0 0 0 Ducts
Infiltration 0.5 549 3.3 -
Ducts 3949 23.9
Ventilation 0 0 Ga ng
Internal gains 1890 11.5
Blower 0 0 Infiltration
Adjustments 0
Total 16497 100.0 Deas Ceilings
Latent Cooling Load=2542 Btuh
Overall U-value=0.131 Btuh/ftz--°F
Data entries checked.
illwrigl•'itSoft Right-Su Re®Universal 201212.1.05 Right J®Mobile 2013-Jan-1
e01
9
C:1WINDOWS\TEMPlwstmp\faa54dd1-2b70-470e-a901-0358bc32debg.rup Calc=MJ8 FrontDoorfaces. E
Component Constructions Job: Seeley
n "'i"i'i 5I, p Date: 1/15/2013
Entire House By:
%Wh1 a Cub%srft-
AL
Project • !
For: Craig Seeley,Tropic Heating&Air Conditioning, Inc.
2166 Fairway Villas L.,Atlantic Beach, FL 32233
Phone: 904-241-1788 Fax: 904-241-2172
Email:Tropicac@msn.com
Design Conditions
Location: Indoor: Heating Cooling
Jacksonville/Craig, FL, US Indoor temperature(°F) 70 75
Elevation: 43 ft Design TD(°F) 35 16
Latitude: 30°N Relative humidity(%) 30 50
Outdoor: Heating Cooling Moisture difference(grab) 8.4 52.8
Dry bulb(°F) 35 91 Infiltration:
Daily range(°F) - 17 ( M ) Method Simplified
Wetbulb(°F) - 77 Construction quality Average
Wind speed(mph) 15.0 7.5 Fireplaces 0
Construction descriptions or Area U-value Insul R Htg HTM Loss Clg HTM Gain
1F Bhh/R--'F 1F-"FIBIh BMW Btuh BthM Btuh
Walls
1213-0sw:Frm wall,vnl ext,r-11 cav ins,1/2"gypsum board int n 184 0.097 11.0 3.36 619 2.61 481
fnsh,2"x4"wood frm a 288 0.097 11.0 3.36 968 2.61 752
s 216 0.097 11.0 3.36 724 2.61 563
W 288 0.097 11.0 3.36 968 2.61 752
all 977 0.097 11.0 3.36 3278 2.61 2549
Partitions
(none)
Windows
1 D-c2ow:2 glazing,Cir outr,air gas,wd frm mat,dr innr,l/4"gap, n 24 0.570 0 19.7 477 20.9 505
1/8"thk a 32 0.570 0 19.7 625 63.0 1995
S 24 0.570 0 19.7 477 25.2 608
W 32 0.570 0 19.7 625 63.0 1995
all 112 0.570 0 19.7 2202 45.7 5104
Doors
11 D0:Door,wd sc type n 32 0.390 0 13.5 425 11.4 360
Ceilings
16C-19al:Attic ceiling,asphalt shingles roof mat,r-19 ceil ins,1/2" 1000 0.049 19.0 1.70 1695 2.10 2097
gypsum board int fish
Floors
22A-cph:Bg floor,heavy damp soil,on grade depth,carpet fir fish 140 1.358 0 47.0 6578 0 0
Wrl htSOfC 2013Jan-1506:21:40
9 Right-Suite* 12.1.05 Right,1®M°bile Page 1
C:1w9NDOWMTEMP*,sMVVaa54dd1-2b70-470e-a901-035Bbc32deb9.rup Calc=MJB Front Door faces: E
IQ Right-J® Worksheet Job: Seeley
Entire House Date: 1/15/2013
By:
AL
1 Room name Entire House First Floor
2 Exposed wall 140.0 ft 140.0 ft
3 Room height 8.0 ft d 8.0 ft heaU000l
4 Room dimensions 1.0 x 1000.0 It
5 Room area 1000.0 ft' 1000.0 ft'
T Construction U-value Or HTM Area ft` Load Area If Load
Y ( ) ( )
number (Btuh/ftp-°F) I (Btuh/ftj I or perimeter (ft) (Btu h) or perimeter (ft) (Btuh)
Heat Cool Gross NIPIS Heat Cool Gross NIP/S Heat Cool
61213-0sw 0.097 n 3.36 2.61 240 184 619 481 240 184 619 481
1D-c2ow 0.570 n 19.72 2091. 24 0 477 505 24 0 477 505
11DO 0.390 n 13.49 11.43 32 32 425 360 32 32 425 360
Vy 12B-0sw 0.097 a 3.36 2.61 320 288 968 752 320 288 968 752
11 L—C 1D-clow 0.570 a 19.72 63.01 32 0 625 1995 32 0 625 1995
V►I 12B-Osw 0.097 s 3.36 2.61 240 216 724 563 240 216 724 563
I—G 1 D-c2ow 0.570 s 1972. 25.16 24 0 477 608 24 0 477 608
Vj/ 12B-0sw 0.097 w 3.36 2.61 320 288 968 752 320 288 968 752
G 1D-clow 0.570 w 1972 63.01 32 0 625 1995 32 0 625 1995
C 16C-19al 0.049 - 1.70 2.10 1000 1000 1695 2097 1000 1000 1695 2097
F 22A-cph 1.358 - 46.99 0.00 1000 140 6578 0 1000 140 6578 0
61 c)AED excursion 0 0
Envelope loss/gain 1 14179 10110 1 1 14179 10110
12 a) Infiltration 2280 549 2280 549
b) Room ventilation 0 0 0 0
13 Internal gains. Occupants 230 3 690 3 690
Appliances/other 1200 1200
Subtotal(lines 6 to 13) 16459 12549 16459 12549
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 16459 12549 16459 12549
15 Dud loads 21% 31% 3444 3949 21% 31% 3444 3949
Aotaequomdlom) I I I 199041 16701 I I I 19901 I 16701
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrigEiTsrrFY Right-Suited!)Universal 201212.1.05 Right JO Mobile 2013-Jan-1506:Page01
C.\WINDOWS\TEMP\wstmp\faa54dd1-2b70-470e-a901-0358bc32deb9.rup CaIc=MJ8 FrontDoorfaces: E 9
AED Assessment Job: Seeley
Date: 1/15/2013
Entire House By:
Ekr,:q A:asLty 5irit•na
AL
Project Information
For: Craig Seeley, Tropic Heating&Air Conditioning, Inc.
2166 Fairway Villas L.,Atlantic Beach, FL 32233
Phone: 904-241-1788 Fax: 904-241-2172
Email:Tropicac@msn.com
Design Conditions
Location: Indoor: Heating Cooling
Jacksonville/Craig, FL, US Indoor temperature(°F) 70 75
Elevation: 43 ft Design TD(°F) 35 16
Latitude: 30°N Relative humidity(%) 30 50
Outdoor: Heating Cooling Moisture difference(grAb) 8.4 52.8
Dry bul b(°F) 35 91 Infiltration:
Daily range(°F) - 17 ( M )
Wetbulb(°F) - 77
Wind speed(mph) 15.0 7.5
Test for Adequate ExposureDiversity
Hourly Glazing Load
7,00
6,00
5,00
4,00C
3,00G
2,00G
1 '00Q-
8 9 10 11 12 13 14 15 16 17 18 19 20
Hour of Day
Houty Average PEDlirrit
Maximum hourly glazing load exceeds average by 19.6%.
House has adequate exposure diversity (AED), based on AED limit of 30%.
AED excursion: 0 Btuh
.^� wrightsoft Right-Suite®Universa1201212.1.05 Right J®Mobile 2013-Jan-1506:21:40
I
Page 1
iCC�'IC3WINDOWSITEMRwstmplfaa54dd1-2b70-470e-a901-0358bc32debgrup Calc=MJ8 FrontDoorfaces. E