Permit HVAC 1345 Ocean Blvd 2013 CITY OF ATLANTIC BEACH
j 800 SEMINOLE ROAD
J ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number 12-00001728 Date 1/22/13
Property Address . . . I, . . . 1345 OCEAN BLVD
Application type description SINGLE FAMILY RESIDENCE
Property Zoning . . . . . RES SF DISTRICT
Application valuation . . 265000
Application desc
NEW SINGLE FAMILY DWELLING
----------------------------------------------------------------------------
Owner Contractor
LINDLEY TOLBERT DESIGN NC BOSCO BUILDING CONTRACTORS
465 BEACH AVE 2158 MAYPORT RD.
ATLANTIC BEACH FL ,32233 ATLANTIC BEACH FL 32233
(904) 241-0320
--- Structure Information 0 0 000 NEW SINGLE FAMILY DWELLING 2927 SF
Construction Type . . TYPE 5-B
Occupancy Type . . . . . . RESIDENTIAL
Flood Zone . . . . . . ZONE X
----------------------------------------------------------------------------
Permit MECHANICAL HVAC PERMIT
Additional desc .
Sub Contractor . . HAMMOND AIR CONDITIONING INC
Permit Fee . . . . 119 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date 7/21/13
---------------------------- -----------------------------------------------
Special Notes and Comments
SEE CORRECTION REPORT ATTACHED
Avoid damage to underground water/sewer utilities . Verify
vertical and horizontal. location of utilities . Hand dig if
necessary. If field coordination is needed, call 247-5834 .
Ensure all meter boxes, sewer cleanouts and valve covers
are set to grade and visible.
A sewer cleanout must be installed at the property line.
Cleanout must be covered with an RT1 concrete box with
metal lid. Cleanout to be set to grade and visible.
A reduced pressure zone backflow preventer must be
installed if irrigation will be provided or if there is a
private well on the prperty. Backflow preventer must be
tested by a certified ;ester and a copy of the results sent
to Public Utilities .
A Right-of-Way Permit must be obtained for use of pavers
in the right-of-way.
A Revocable Encroachme t Permit must be obtained.
Full right-of-way rest ration, including sod, is PPr��equired.
PERMIT I A' O fON S� f�C3( A WYIJM 4gT2 TWj"C# IQA
' VN( 17;h96E FLORIDA
BUILDING CODES.
X11
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Page 2
-----Application-Number--_-_ 'll _-_-_--12_00001728Date 1/22/13
-------------
Special Notes and Comments
and container cannot be placed on City Right-of-Way.
(Approved: Advanced Disposal, Realco, Shappelle ' s and Waste
Management . )
Full erosion control measures must be installed and
approved prior to beginning any earth disturbing
activities . Contact Public Works (247-5834) for Erosion
and Sediment Control Inspection prior to start of
construction.
2010 FLORIDA BUILDING CODE, 2008 NATIONAL ELECTRIC CODE
FOR AN APPROVED FINAL MECHANICAL A/C INSPECTION, A STICKER
SHALL BE INSTALLED ON THE AHU TO VERIFY THAT DUCTS HAVE
BEEN SEALED, A CERTIFICATION SHALL BE ON SIGHT FOR THE
INSPECTOR STATING THAT THE A/C SYSTEM PASSED THE "AIR BLAST
INSPECTION" FROM AND INDEPENDENT TESTING AGENCY.
*SUBMIT "CERTIFICATE OF COMPLIANCE" BY A LICENSED PEST
CONTROL COMPANY PRIOR TO C.O.
WINDOW AND DOOR INSPEC'T'ION:
*INSTALLATION INSTUCTI NS REQUIRED
*ALL STICKERS ARE TO REMAIN ON THE WINDOWS
*PROVIDE ACCESS TO ALL WINDOWS TO INSPECT FASTENERS
TREE REMOVAL FROM SUBJECT PROPERTY FOR CONSTRUCTION OF NEW
SFR IS COVERED BY TREEIPERMIT #12-00100040; TREE REMOVAL
FROM ADJACENT PROPERTIES FOR CONSTRUCTION ,OF NEW SFR ON
SUBJECT PROPERTY IS A CIVIL MATTER TO BE RESOLVED WITH
ADJACENT PROPERTY (TREE) OWNERS .
SOUTH SIDE OF HOUSE FACES THE REAR OF ADJACENT STRUCTURE;
THEREFORE SECTION 24-1�2 (c) (1) a DOES NOT APPLY; THIS
PROVISION ONLY APPLIESIIN THE CASE OF ADJACENT SIDE-TO-SIDE
POSITIONING.
---------------------------- -----------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------- -----------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ----------- ---------- ---------- ----------
Permit Fee Total 19 . 00 119 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 23 . 00 123 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE N ITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904)1247-5826 Fax (904) 247-5845 oz
JOB ADDRESS: Ce j V PERMIT#
PROJECT VALUE $ 19= 00
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity 2 Tons Per Unit &S
Heat: Unit Quantity 2 BTU's Per Unit 6&pm— Seer Rating
Duct Systems: Total CFM —SII REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI#
Air Conditioning: Unit Quantity Tons Per Unit REQUIRED
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
i
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES j MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks(gallons)
Wells
OTHER:
I
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name �., lleA". -761 1b ex k Phone Number 9o.1 -1Lj 1-0 32,0
Mechanical Company 9fiMft,,otip b;r Office Phonegay- -y.%kFax o4-391-6o5S
Co. Address: 3 l'L &AI lee. j. City 'a; tle. State�_]L Zip3Z�—
License Holder(Print): Pp. cy N.ww State Certification/Registration#c-gc,1%1 Co.-i.S-o
Notarized Signature of License Holder
" w GRAN M worn and subscribed be e me t 's d o 2013
iota ignature of otary Pub1 c
,; �j r'�f�i��Unrlerwri�ers
I
' I
Bimini 1345 cean Blvd Atlantic Beach 32233
H C Load Calculations
for
I
Bosco Custom Homes
2158 Mayport Road
Atlantic Beach, Fl-32233
ill '
70"
VAo"w**
RasiDeN''ntAL,
H HVAC LoAiDs
I,
ill I' i
Prepared By:
Jim Williams
Home Energy Services
2080 Davis Road
Jacksonville, Fl-32218
904-757-3569
Friday, November 02, 2012
Rhvac is an ACCA approved Manual J and Man jai D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
I
Rhvac-R"dentist&Light.Commercial HVAC Loads - — — Elite Software Devatopmentw Inc ;
�.Home;Energy Services Bimini 1345 ocean Blvd Atlantic Beach 32233'
Jalttsnvill _ .
Protect Report- _
Project Title: Bimini 1345 Ocean Blvd Atlantic Beach 32233
Project Date: Friday, November 02, 2012
Client Name: Bosco Custom Homes
Client Address: 2158 Mayport Ro d
Client City: Atlantic Beach, Fl.32233
Client Phone: 904.241.0320
Client Comment:
Company Name: Home Energy Services
Company Representative: Jim Williams
Company Address: 2080 Davis Road!
Company City: Jacksonville, FL 52218
Company Phone: 904-757-3569
Company Fax: 904-757-7104
Company E-Mail Address: jimWIliams@hom�buildingstore.com
Reference City: Jacksonville, Florida
Building Orientation: Front door faces East
Daily Temperature Range: Medium
Latitude: 30 Degrees
Elevation: 6 ft.
Altitude Factor: 0.9 9
Elevation Sensible Adj. Factor: 1.0b0
Elevation Total Adj. Factor: 1.Ob0
Elevation Heating Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.70
Outdoor Outdoor 1 Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb j Rel.Hum Rel.Hum Dry Bulb Difference
Winter: 32 29.92 80% n/a 70 n/a
Summer: 94 77 47% 50% 75 48
Total Building Supply CFM: 917 CFM Per Square._ .. ft.: 0.658
Square ft. of Room Area: 915 Square ft. Per Ton: 726
Volume(W)of Cond. Space: 21,712
Total Heating Required Including Ventilation Air: 39,513 Btuh 39.513 MBH
Total Sensible Gain: 42,132 Btuh 87 %
Total Latent Gain: 6,024 Btuh 13 %
Total Cooling Required Including Ventilation Air:ii 48,156 Btuh 4.01 Tons (Based On Sensible+ Latent)
77
Rhvac is an ACCA approved Manual J a4 Man 6 ak D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensiblE and latent loads according to the manufacturer's performance data at
your design conditions.
! IIII
i I III
j Friday, November 02, 2012, 2:37 PM
II
ltttivac-R idenda!&Light Commercial H1/AC Loads Elite Software Development,Inc,
(HM1HMal Ener y SiMik Bimini 1345 Ocean Blvd Atlantic E3e�ch 32233
JacksonyiNe,FL 32218 _ W . . . .- -- - Pam 3 11
- --- ---- --------- - -- - - -- --
Miscellaneous Report -- -
Syst it 1.Maln Qtutdoor Outdoor butdoot' 1 Indoo lndac r irl I
. 1V�3ulb _ _. V11 iub..._._. . Rei Huila Rel.Hurn t7r�Ful C�iffernce
Winter: 32 29.92 80% n/a 70 Na
Summer: 94 77 47% 50% 75 48.06
ystrri im YQdovr:,. iatSur & utdcr l -Indoor IIS dd ra
Wet R, 1 ! ( .__.` i+�)burn. . t7rSk „'Eirnc
Winter: 32 29.92 80% n/a 70 n/a
Summer: 94 77 47% 50% 75 48.06
71-77777,
Main Trunk Runouts
Calculate: Yes Yes
Use Schedule: Yes Yes
Roughness Factor: 0.00300 0.01000
Pressure Drop: 0.1000 in.wg./10 ft. 0.1000 in.wg./100 ft.
Minimum Velocity: 650 ft./min 450 ft./min
Maximum Velocity: 900 ft./min 750 ft./min
Minimum Height: 0 in. 0 in.
Maximum Height: 0 in 0 in.
Winter I Summer
Infiltration Specified: 0.250 AC/hr 0.250 AC/hr
115 ICFM 115 CFM
Infiltration Actual: 0.250 iIAC/hr 0.250 AC/hr
Above Grade Volume: X 27,712 ICu.ft. X 27,712 Cu.ft.
6,928 Cu.ft./hr 6,928 Cu.ft./hr
X 0.0167 X 0.0167
Total Building Infiltration: 115 CFM 115 CFM
Total Building Ventilation: 0 CFM 0 CFM
---System 1---
Infiltration&Ventilation Sensible Gain Multiplier 20.88 = (1.10 X 0.999 X 19.00 Summer Temp. Difference)
Infiltration&Ventilation Latent Gain Multiplier: 32.65 = (0.68 X 0.999 X 48.06 Grains Difference)
Infiltration &Ventilation Sensible Loss Multiplier 41.76 = (1.10 X 0.999 X 38.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.250 AC/hr(61 CFM)
Summer Infiltration Specified: 0.250 AC/hr(61 CFM)
---System 2---
Infiltration &Ventilation Sensible Gain Multiplier' 20.88 = (1.10 X 0.999 X 19.00 Summer Temp. Difference)
Infiltration &Ventilation Latent Gain Multiplier: 32.65 = (0.68 X 0.999 X 48.06 Grains Difference)
Infiltration&Ventilation Sensible Loss Multiplier 41.76 = (1.10 X 0.999 X 38.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.250 AC/hr(54 CFM)
Summer Infiltration Specified: 0.250 AC/hr(54 CFM)
,� � tti tau ;t3uct Surf m
, �
, n
bau L tl4'y�J 1��4i�
Ce� �
1 Supply Main Attic -� 16B 0.09 6 � 390 No
1 Return Main Attic 16B 0.15 6 144 No
i
Friday, November 02, 2012, 2:37 PM
I
FRwi--t
-Resiclerr iat pht +ommerclal HVAC Loyd -- - - Elite Software liv0jQpmelr�t,Inc.
HcsmBnery Sesrvs 8irnini 1345+Ocean Cf♦Ivd Attarttc3eact ,
.,%a tiu�lieFL11 _ LL_ ' .4
(Load-Preview Report - -- I - -- -- --
Net! Duct
Ss Ss' Ss
Net Rec� ft Sen Let: Net! Sen 1 Htg I Clg Act
Scope Ton Ton! /Ton, Area; Gain Gain Gaini Loss! Size
- _ CFM' CFMI CFM
Building 4.011 4.68 623 2,915 42,132 6,024 48,156 39,513 799 1,917 1,917
System 1 1.63; 1.82 809 1,472 16,384 3,203 19,587 21,123 427 745 745 10x15
Zone 1 1,472 16,384 3,203 19,587 21,123 427 745 745 10x15
1-Great Room/Dining 777 7,285 1,698 8,983 9,485 192 331 331 3--6
2-K trhen 440 4,614 719 5,333 6,350 128 210 210 2-6
3-Bath 1 48 0 0 0 0 0 0 0 0_0
4-Laundry 42 1,077 159 1,236 1,453 29 49 49 1-4
5-Study/Guest 165 3,408 627 4,035 3,835 78 155 155 1--7
System 2 2.3811 2.86 504 1,443 25,748 2,821 28,569 18,390 372 1,171 1,171 12x17
Duct Latent 854 854
Zone 1 1,443 25,748 17967 27,'715 18,390 372 1,171 1,171 12x17
6-Hal 1 204 2,278 138 2,416 1,747 35 104 104 0-0"
7-Master Bedroom 369 8,037 783 8,820 6,333 128 366 366 3--7
8-Master Bath 168 1,268 135 1,403 1,352 27 58 58 1-4
9-M W/C 19 47 0 47 32 1 2 2 1-4
10-M WIC 126 1,013 101 1,114 1,063 21 46 46 1-4
11-Bedroom 3 203 4,654 275 4,929 2,843 57 212 212 2-6
12-Bath 2 60 148 0 148 100 2 7 7 1-4
13-BR 2 WIC 39 1,438 120 1,558 1,044 21 65 65 1--5
14-Bedroom 2 210 5,457 280 5,737 2,756 56 248 248 2--7
15-Bath 3 45 1,410 135 1,545 1,121 23 64 64 1--5
�1 I
I I
II IIIA
I
Friday, November 02, 2012, 2:37 PM
ii
fthvac-t�esidentia(8�.1.ight 1Cgmmercial h{VAC Loads Elite Software Developmen#,Inc-'
Home Energy Serves ! Bimini 1345 Ocean 81vtl Atiantrc beache 5
JaCkpnviils� L1
Duct Size Preview _
Room or T Minimutyr Maximumi Rough.' Designs SP Duct _ Dguct Htg cig Act. Duct
Flow Flow Flo S
Duct Name I Valoci Valoci Factor L/100 Loss Val oci Length
System 1
Supply Runouts
Zone 1
1-Great Room/Dining 45011750 0 0.1 562.7 192 ' 331 3--6
2-Kitchen 4501 750 0 0.1 534.6 128 210 2-6
3-Bath 1 450 750 0 0.1 0 0 .; 0 0-0
4-Laundry 450 750 0 0.1 561.5 29 N49 1-4
5-Study/Guest 450, 750 0 0.1 580.1 78t , 155 1--7
Other Ducts
M ,a
Supply Main Trunk 6501 900 0 0.1 715.6 427 745 10x15
System 2
Supply Runouts
Zone 1
6-Hall 450 750 0 0.1 0 35 104 0--0
7-Master Bedroom 450 750 0 0.1 456.1 128 366 3-7
8-Master Bath 4501 750 0 0.1 660.8 27'j 58 1-4
9-M W/C 750 0 0.1 1
4501 24.4 r
2 1-tel
10-M WIC 45� 750 0 0.1 528.2 21 46 1--4
11-Bedroom 3 450 750 0 0.1 539.2 57 212 246
12-Bath 2 45r' 750 0 0.1 77 2 yk� 7 1-4
13-BR 2 WIC 45P 750 0 0.1 479.8 21 � 65 1-5
II �
14 Bedroom 2 45 750 0 0.1 464.5 56 248 2--7
15-Bath 3 450 750 0 0.1 470.4 23 =a ', 64 1-5
Other Ducts
Supply Main Trunk 65q 900 0 _0.1 826.9 372 _ 1,171 1207
_. ..._ . . Summary
I
System 1
Heating Flow: 427
Cooling Flow: 745
System 2
Heating Flow: 372
Cooling Flow: 1171
I, II
�I li
I
IIIA
i
I
I
Friday, November 02, 2012, 2:37 PM
1
Ft so-Residentfa#8�L,tght Commercial HVAC Loads Elite Software Development,Inc.i a
Home Energy$ervk�s Bimini 1345 Ocean Blvd Atla�ttic Beach 32233
JacksonwiHe, L21t
Total Building Summary Loads -
r
I , a , ra ri " Toa
E � Qu�nh .,Y» a Lq � GIrt' Vain
10D f: Glazing-French door, double pane low-eglass (e= 120 1,596 0 2,822 2,822
0.10), insulated fiberglass frame, u-value 0.3 5,
SHGC 0.35 j
4A-6-o: Glazing-Double pane low-e(e= 0.20 or I$ss), 343.8 4,575 0 8,127 8,127
high performance, operable window, a=0.05 on
surface 2, any frame, u-value 0.35, SHGC 0.35
10D-f: Glazing-French door, double pane low-e g ass (e= 141.6 2,259 0 3,124 3,124
0.10), insulated fiberglass frame, u-value 0.4 2.
SHGC 0.32
12E-Osw: Wall-Frame, R-19 insulation in 2 x 6 stud 1342.4 3,469 0 1,955 1,955
cavity, no board insulation, siding finish, woo studs
126-0sw: Part-Frame, R-11 insulation in 2 x 4 StL d cavity, 275 1,014 0 507 507
no board insulation, siding finish,wood studs
1213-0sw: Wall-Frame, R-11 insulation in 2 x 4 stud 1342.2 4,948 0 3,660 3,660
cavity, no board insulation, siding finish,wood studs
1613-30: Roof/Ceiling-Under Attic with Insulation on Attic 1485.5 1,805 0 2,568 2,568
Floor(also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-30 insulation
166-19: Roof/Ceiling-Under Attic with Insulation on Attic 72 134 0 191 191
Floor(also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, ark
Asphalt Shingles or Dark Metal, Tar and Gra el or
Membrane, R-19 insulation
22A-ph: Floor-Slab on grade, No edge insulationno 192 9,908 0 0 0
insulation below floor, any floor cover, passi heavy
moist soil
Subtotals for structure: 29,708 0 22,954 22,954
People: 7 1,400 1,610 3,010
Equipment: j 0 7,300 7,300
Lighting: 0 0 0
Ductwork: 4,982 854 5,337 6,191
Infiltration: Winter CFM: 115, Summer CFM: 11 4,823 3,770 2,411 6,181
Ventilation:Winter CFM: 0, Summer CFM: 0 1 0 0 0 0
AED Excursion: 0 0 2,520 2,520
Total Building Load Totals: 39,513 6,024 42,132 48,156
•'.'�� a��l�eufi'�iG,.��x�"i.� �-.r..a,. al ...._... _ ,.., .. °�T_ w.a .... .,... __ -�-j.>L N,srf 6d,.,e�-i ,
Total Building Supply CFM: i,917 CFM Per Square ft.: 0.658
Square ft. of Room Area: 2,915 Square ft. Per Ton: 726
Volume(ft')of Cond. Space 27,712
90 ....
Total Heating Required Including Ventilation Air: 39,513 Btuh 39.513 MBH
Total Sensible Gain: 42,132 Btuh 87 %
Total Latent Gain: 6,024 Btuh 13 %
Total Cooling Required Including Ventilation Air 48,156 Btuh 4.01 Tons (Based On Sensible+ Latent)
_.. ... a' = ..,
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensibl and latent loads according to the manufacturer's performance data at
your design conditions.
Friday, November 02, 2012, 2:37 PM
i
Rhvaa-f�esi�ntial&Light Commareial HVAC t Dads Elite Software Development,Inc.
Home Enemy Services Bimini 1345 Ocean Blvd Atlantic Reach 322331 j
Jacksi>r►ville�FL 3288 _ _..___ Page 7
Building Pie Chart
Infiltration 12%
Floor 25%
I
Ductwork 13%
Building
Loss
39,513 Roof 5%
Btuh
Glass 21%
Wall 4%
Roof 6%, AED Excursion 5%
Wall 13% Infiltration 13%
a
Building
Ductwork 13%
Gain
48,156
Btuh
Glass 29%
i
Equipment 15%
People 6%
Friday, November 02, 2012, 2:37 PM
I
I
ttwvi•FtestdentiaM ti<LiOht;C.orr�mercial HWAC Loads Elite Software Developmentlnc.
Home Energy Senric s Bimini 1345 Ocean Blvd Atlantic peach 32233
_mage 811
System 9 Room Load Summary
' N ,l Iltl T ,1 11. Run 4:ig Glg �- Acta
OW L errs N,
=# ! 3tuf .w. .. Mutt
. .
---Zone 1---
1 Great 777 9,485 192 3-6 563 7,285 1,698 331 331
Room/Dining
2 Kitchen 440 6,350 128 2-6 535 4,614 719 210 210
3 Bath 1 48 0 10 0-0 0 0 0 0 0
4 Laundry 42 1,4531 29 1-4 562 1,077 159 49 49
Study/Guest 165
35 78
3,408 627 155 155
5 System 1 total 1,47 8
2 21,123 427 1-7 580 16,384 3,203 745 745 I1
System 1 Main Trunk Size: 10x15 in.
Velocity: 716 ./min
Loss per 100 ft.: 0.091 in.wg
LYVi P�4� ! ".. ..... .. .. ,. _y..i,... ....,,.. >..,
L
4 iti�� bad 4i 5pilit �r1 Ibte/Latera# I-a
rr � 2a 1
`F �yyN j�Myy y J
"'tl
Net Required: 1.63 846X./ 16% 16,384 3,203 19,587
Actual: 1.95 75%/25% 17,550 5,850 23,400
77
..� j s_ .�.�:: ?,'h�`�">°s�k^�i:, �n'_a.�a.,^u.:.
.�_...,,_. v.,,�.y�nl,. -0��.;. s �._ _ i4m'S.eL�i1 �k.t..,.�'.m.......>
Heatina S stem Cooling System
Type: Air Source Heat Pump Air Source Heat Pump
Model: 25H6 324(A,W)**30 25HBC324(A,W)**30
Indoor Model: CNPV*2417A**
Brand: BASE113 PURON HP BASE 13 PURON HP
Description: Air SoOrce Heat Pump Air Source Heat Pump
Efficiency: 8 HSPF 13 SEER
Sound:
Capacity: 47°F: 2,600/ 17°F: 13,600 Btuh 23,400 Btuh
Sensible Capacity: n/a 17,550 Btuh
Latent Capacity: n/a 5,850 Btuh
AHRI Reference No.: n/a 4211040
li I II
II 'I
i
Friday, November 02, 2012, 2:37 PM
Ri i -Re id ntiai$�41 ht,Comore rrcial HVAC L-oat s r the Software Devetap6-int,Inc:,
Hcme I=nergy S rvI Bimini 1345 Ocean Blvd Atlantic Beach 32233 1
P
System 2 Room Load Summary
Dl
� - � � t Miran !9 Clg tr a Act
9
, � r
WA fdttt a - 3
---Zone 1---
6 Hall 204 1,747 35 0-0 0 2,278 138 104 104 li
7 Master Bedroom 369 6,333 128 3-7 456 8,037 783 366 366
8 Master Bath 168 1,352 27 1-4 661 1,268 135 58 58
9 M W/C 19 32 1 1 1-4 24 47 0 2 2 jl
10 M WIC 126 1,063 21 1-4 528 1,013 101 46 46
11 Bedroom 3 203 2,843 57 2-6 539 4,654 275 212 212
12 Bath 2 60 100 2 1-4 77 148 0 7 7
13 BR 2 WIC 39 1,044 21 1-5 480 1,438 120 65 65
14 Bedroom 2 210 2,756 56 2-7 464 5,457 280 248 248
15 Bath 3 45 1,121 23 1-5 470 1,410 135 64 64
Duct Latent 854
System 2 total 1,443 18,390 372 25,748 2,821 1,171 1,171
System 2 Main Trunk Size: 12x17 n.
Velocity: 827 ./min
Loss per 100 ft.: 0.099 n.wg
A-z""18ra
._.......2f"wr�1v���g�YEU U71, nG{yn{__.:..., Iasn
u25,748 2,821
`2.."
8pP,5t6(19M '
Net Required: 2.38 90%/ 10%
:
Actual: 2.50 75%/25% 22,500 7,500 30,000
,77
7 77
..._Heath System
....��a ...� .�. _... Cool g System
fir
Type: Air Source Heat Pump Air Source Heat Pump
Model: 25HB 330A**50 25HBC330A**50
Indoor Model: CSPH*3612A**
Brand: BASE 13 PURON HP BASE 13 PURON HP
Description: Air Source Heat Pump Air Source Heat Pump
Efficiency: 7.7 HISPF 13 SEER
Sound:
Capacity: 47*F: 10,000/ 17°F: 18,200 Btuh 30,000 Btuh
Sensible Capacity: n/a 22,500 Btuh
Latent Capacity: n/a 7,500 Btuh
AHRI Reference No.: n/a 4211207
II
I II
t
li
Friday, November 02, 2012, 2:37 PM
I
I