350 Garden Ln HVAC 2013 N C BEACH
CITY OF ATLANTI
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00002113 Date 2/06/13
Property Address . . . . . . 350 GARDEN LN
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 6300 --------------
-------------------------------------------------------------
Application desc
Replace 2 HVAC Systems -----------------------
-----------------------------------------------------
Owner Contractor
------------------------
------------------------
SAITTA, KENNETH OWNER
3SO GARDEN LANE
ATLANTIC BEACH FL 32233
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . . REPLACE 2 HVAC SYSTEMS
Permit Fee . . . . 135 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date 8/05/13 -----------------------
2 . 03
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE
STATE MECH DBPR SURCHARGE 2 . 03
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 13S . 00 13S . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
other Fee Total 4 . 06 4 . 06 . 00 . 00
Grand Total 139 . 06 139 . 06 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
M-ECHANICAL PERMIT APPLICATioN
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach,FL 32233
Ph(904)247-5826 Fax(904)247-5845
JoB ADDREss: y)C, PERMrr#
PROJECT VALUE$- LOU
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per.Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating—
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & BEATING SYSTEM IN QN
'r
'31P
It
A 6 S-3 0
STA
R1#�J�� 36,
Air Conditioning: Unit Quantity Tons Per Unit REQ
Heat Unit Quantity-:4— BTU's Per Unit je,�oo Seer Ratiniz /E
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Pipmg Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
Vented Wall Furnaces Refrigerator Condenser BTU's
Water Heaters Solar Collection Systems
Tanks(gallons)
Wells
OTHER:
?ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
his application and know the same to be true and correcL All provisions of laws and ordinances governing this work will be complied with whether specified
)r not The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
I C
roperty Owners Name --�4 1 40, PhoneNumber 90Y--2Y1-- 8-7R4
vfechanical Company fa-VLOV6 f, 14,fL Office Phone ��(-31 grFax -Z-H 1-3-)9Y-
.o.Address: 3 -S, City ..i)0,14 GeAck Statefi- Zip
Acense Holder(Print): State Certification/Registr�on#
iotarized Skmature of License HoLder
Sworn anlisubscribed before me this day of f--f 201
Notary Public State of Florida gnature of Notary Public...
T im L S 0
irnothy Lee Hughes
my Comm.s'on EE 1 86278
Exor , /0 01 6
OF My Commission EE 186278
f-Y' , -
Expires=04/03/2016
Job:
+ wrightsoft Project Summary Date: 2/5/13
Entire House By: Brandon Zaharie
Donovan Heat & Air
315 6th ave south,Jacksonville Beach,FL 32250 Phone:241-3785 Ernaill brandon@donovanae.com
I Del[gets lillfill]lil-litill 0 M�
For: Saitta
350 Garden Lane,Atlantic Beach, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 oF Outside db 95 'F
Inside db 68 'F Inside db 75 oF
Design TD 29 'F Design TD 20 '17
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 14414 Btuh Structure 14371 Btuh
Ducts 4124 Btuh Ducts 5926 Btuh
Central vent (13 cfm) 409 Btuh Central vent (13 cfm) 282 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 18948 Btuh Use manufacturer's data n
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 20579 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 1 (Average) Structure 1921 Btuh
Ducts 1295 Btuh
Heating Cooling Central vent (13 cfm) 465 Btuh
Area(ft') 121 121 Equipment latent load 3680 Btuh
Volume(ft') 10962 10962 24258 Btuh
Air changes/hour 0.56 0.23 Equipment total load
Equiv.AVF (cfm) 102 42 Req- total capacity at 0.70 SHR 2.4 ton
Heating Equipment Summary Cooling Equipment Summary
Make Tempstar Make Tempstar
Trade Trade
Model NXH530 Cond NXH530
ARI ref no. 3653116 Coil FVM4X30
ARI ref no. 3653116 15.8 SEER
Efficiency 8.7 HSPF Eff iciency
Heating input Sensible cooling 20906 Btuh
Heating output 29717 Btuh @ 47oF Latent cooling 8960 Btuh
Temperature rise 27 'F Total cooling 29866 Btuh
Actual air flow 996 cfm Actual air flow 996 cfm
Air flow factor 0.054 cfm/Btuh Air flow factor 0.049 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
Space thermostat Load sensible heat ratio 0.85
Printout certified by ACCA to meet all requirements of Manual J 8th Ed.
Right-SuiteO Universal 7.1.01 RSU05996 2013-Feb-05 11:20 31
c u.er.\S.jes\Docurnents\Wnght soft HVAC\2.5 TON Calc=MJ8 Orientation=N Page I
Job:
roject Summary Date: 215/13
wrightsoft P By: Brandon Zaharie
Entire House
Donovan Heat & Air
315 6th ave south,Jacksonville Beach,FL 32250 Phone:241-3785 Email: brandon@donovanac.corn
- Proiect Information
For: Saittla
350 Garden Lane, Jacksonville, FL 32233
Notes:
Desiqn Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 'F Outside db 95 'F
Inside db 68 'F Inside db 75 oF
Design TD 29 'F Design TD 20 'F
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 13919 Btuh Structure 11729 Btuh
Ducts 2799 Btuh Ducts 5690 Btuh
Central vent (12 cfm) 370 Btuh Central vent (12 cfm) 255 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh ufacturer's data n
Equipment load 17088 Btuh Use man
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 17674 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality 1 ( Average 1638 Btuh
Fireplaces Average) Structure 973 Btuh
Ducts
Heatin coolin Central vent (12 cfm) 420 Btuh
Area (ft') 1159 11'59 Equipment latent load 3031 Btuh
Volume(ft') 10368 10368
Air changes/hour 0.57 0.23 Equipment total load 20706 Btuh
Equiv.AVF (cfm) 98 40 Req. total capacity at 0.70 SHR 2.1 ton
Heating Equipment Summary Cooling Equipment Summary
Make Tempstar Make Tempstar
Trade
Trade Cond NXH524
Model NXH524 Coil FVM4X24
ARI ref no. 3653095 ARI ref no. 3653095 15.8 SEER
Eff iciency 8.5 HSPF Efficiency-
Sensible cooling 15747 Btuh
Heating input 6749 Btuh
Heating output 22384 Btuh @ 47'F Latent cooling 22496 Btuh
Temperature rise 27 'F Total cooling 750 cfm
Actual air flow 750 cfm Actual air flow 0.043 cfm/Btuh
Air flow factor 0.045 cfm/Btuh Air flow factor 0 in H20
0 in H20 Static pressure
Static pressure Load sensible heat ratio 0.85
Space thermostat
Printout certified by ACCA to meet all requirements of Manual J 8th Ed.
2013-Feb-05 11 22:46
-SuiteO Universal 7.1.01 RSU05996 Page I
Right
ACCK c:\users\Sates\Documents\Wrightsoft HVAC\2Ton.rup Calc=MJ8 orientation=N