456 Irex Rd HVAC 2013 CITY OF ATLANTIC BEACH
j 800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00002120 Date 2/06/13
Property Address . . . . . . 456 IREX RD
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
CORNERSTONE HOMES LLC B & G PLUMBING, HEATING &
8323 RAMONA BLVD W STE 6 AIR CONDITIONING LLC
JACKSONVILLE FL 32221 1729 DIBBLE CIR E
JACKSONVILLE FL 32246
(904) 370-4147
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 95 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 8/05/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 95 . 00 95 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 99 . 00 99 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (904) 247-5845
JOB ADDRESS: 4$6 T REx 0.- PERMIT# 'Q— 5�
PROJECT VALUE $ Z-900. !'
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
ARI# 3bgggob
Air Conditioning: Unit Quantity 1 Tons Per Unit 2.5 REQUIRED P
Heat: Unit Quantity BTU's Per Unit 3o,oocD Seer Rating 13,
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months. I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name G oQNirRSTON "o.r%Es Phone Number 545-H°%93
Mechanical Company 9 A, f-06%-4! , H}c •. A.cL , t_L e- Office Phone tz3-358 5 Fax 3 g y-Z o oto
Co. Address: 2 Z 32 c o **.a-vE wtiE BNvo. City 3A .0- State Ft Zip 327_%co
License Holder (Print): S co-c'c M A Rt%N State Certification/Registration# C Ae- 18 t ti 23
Notarized Signature of License Holder
LORI S.NORMEN orn and subscribed before ins r0 day of o4 20
-,
Notary Public-State of R"Ids
_• .r My Comm.Expbes Mu 10,201 gnature of Notary Public
'.� Commission M EE 170657
Bonded TAronh iwtiaui Natsry Assn.
Job:
Project Summary Date: 2/5/13
Entire House By: M.Ellis
Energy Design Systems, Inc.
12132 Weatherwood Estates Dr W,Jacksonville,FL 32223 Phone:904-268-3670 Fax:904-268-3670 Email:eds iax@grnail comi
Proiect Information
For: Residence, Changeout
456 Irex Dr, Atlantic Beach, FL
Notes: Front of house faces East.
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 °F Outside db 92 °F
Inside db 72 °F
Inside db 72 F 20 °F
Design TD 33 °F Design TD L
Daily range 50
Relative humidity 65 gr/Ib
Moisture difference
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 24436 Btuh Structure 19141 Btuh
2563 Btuh Ducts 4135 Btuh
Ducts 819 Btuh Central vent(23 cfm) 497 Btuh
Central vent(23 cfm) 0 Btuh
Humidification 0 Btuh Blower
Piping 0 Btuh n
Equipment load 27819 Btuh Use manufacturers data 0 97
Rate/swing multiplier 23060 Btuh
Infiltration Equipment sensible load
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average 2242 Btuh
Fireplaces 0 Structure Ducts 1117 Btuh
Heating Cooling Central vent(23 cfm) 991 Btuh
1220 1220 Equipment latent load 4350 Btuh
Area e ( 9760 9760
Volume (ft') 27410 Btuh
Air changes/hour 0 73 0 37 Req total capacity at 0.80 SHR 2.4 ton
Equiv. AVF(cfm)
Heating Equipment Summary Cooling Equipment Summary
Make Bryant Make Bryant
Trade LEGACY LINE PURON HP Trade LEGACY LINE PURON HP
Model 213BN(A,W)030...'A
Cond 213BN(A,W)030....A
AHRI ref 3699906 Coil FB4CNF030
AHRI ref 3699906 11.0 EER, 13 SEER
Efficiency 7.7 HSPF Efficiency 22500 Btuh
Heating input Sensible cooling 7500 Btuh
Heating output 30000 Btuh @ 47°F Latent cooling 30000 Btuh
Temperature rise 27 °F Total cooling 1000 cfm
Actual air flow 1000 cfm Actual air flow
0.037 cfm/Btuh Air flow factor 0.043 in H2 cfm/Btuh
Air flow factor 0 n H2O
Static pressure 0 in H2O Static pressure 0.85
Space thermostat Load sensible heat ratio
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2013-Feb-05 10:43:30
Wrl htSOft Page 1
9 Right-Suite®Universal 2012 12.1.03 RSU17457
ACCP. ...Manual J\BBG,Cornerstone Changeout,456 Irex or,Atl Bch.rup Calc=MJ8 Front Door faces: Page 1