MECH PERMIT 150 Sherry Dr CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00002442 Date 4/09/13
Property Address . . . . . . 150 SHERRY DR
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 5902
----------------------------------------------------------------------------
Application desc
Replace HVAC 5 tons 56, 000 btu' s
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
COMMUNITY PRESBYTERIAN OCEAN STATE HEAT & AIR, INC.
CHURCH 1476 ATLANTIC BLVD.
150 SHERRY DR NEPTUNE BEACH FL 32266
ATLANTIC BEACH FL 322335236 (904) 249-8251
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . . INSTALL NEW 5TON SYSTEM
Permit Fee . . . . 115 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 10/06/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 115 . 00 115 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 119 . 00 119 . 00 . 00 . 00
PERMIT,IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
-MECHANICAL PER-MIT APPLICATION
CITY OF ATLANTIC BEACH
8,30 Seminole Rd Atlantic Beach. FL -31-22131
Ph (904) 247-5926 Fa.), (904) 247-5845
JOB ADDRESS:
PERMfT
PROJECT f�4LUE S E-
NEW ,'UR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditionina: Unit Quant1tv Tons Per Unit
Heat: Unit Quantin" BTU's Per Unit
Duct Svstems: Total CFM Seer Ratinz j ff 0:�-U—IkED
REPLACEMENT AIR CONT-DITIONING & HEATING SYSTEM INSTALLA�TION
-Air Conditioning: Unit Quantity I Tons Per Unit ARI 4 .,3 19001 T
Heat: Unit Quantit"A" BTUs Per Unit KE-ULTIRED
Duct Systems: Total CFM --9�to 0 Seer Razing_ Q
RE-0 UIR-ED
FIRE PREVENTION
Fire Sprinkler System Quantit�, (Requires 3 sets of plans)
Fire S+andpipe Quantity (Requires31 sets of plans)
Under-around Fire Main Value (Requires sets of plans)
Fire 17rose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantil-�-- (Requires 3 sets of plans)
Fire Suppression Systems uantny
Q (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty— Automobile Lifts
Gas PiDine Outlets Boilers
Eievators,E�scalators s
-ALL OTHER GAS PIPING Heai Exchan-er
Quantitv of Outlets P
NT, umps
ented Wall Furnaces Refri�gerator Condenser BTU"s
4 V,'ater Heaters Solar Collection Systems
Tanks (gallons)
V7ejjS
OTHER:
N�
P
ermi-becomes void if work does not commence withir a six mo!7th period or work iss suspended 77,abapdoned for six m-onths.I hereby certif�'that,I have read
this application and know the same to be true and correct. All provisions of I?-,kks and ordinances gov--r-ning this work will be complied with whether specifi-,�
or not. The permit does not-orive authority to violate the provisions of any other stato or loccai law regulation construction or the performanec ofmnstruction.
Properft, 0-wners--Name PhoneNumber 7Dq- (,qLZ
I _Cn t4
Mechanical Company
0
d-Ne A,- Of-fice Phone 2V5-2;,j-1 Fax 2-vj- Zjy9
Co. Address: _1,1-7 U A4jjAe_ —8juj Citl
State Zjj) ?t 2-1,
License Holder(Print):
State Certificatio , -gistration
o
Notarized Sign.ature of License Ho
YVETTE P.MORALES S orn an d sub cf6re this da - of 20_a
NOTARY PLISUC
STATE OF FLORIDA Sig 1,re,of Not Public
Comn-A EE$79174 v
Expires 3/Ml 7
ACCA Manual "J" Heat Load Calculation Date 04/08/13
customers Name Community Presbyterian Church Location Atlantic Beach
OKI g-allga
I Gross Wall 77
1,503
2 W
,3 Windows
I
North Al, N, 2 29.0 16.0
15 435 240
East& West Al, E &W, 2 29.0 46.0 112 3,248 5,152
South— Al, S, 2 29.0 25,0 20 580 500
4 Doors
Front Solid Wood - Panel 27.0 15.8 30 810 474
Patio Solid Wood-Storm 16.4 97 0 0
Other___SIdg GI Dr, S, 2 32.6 25.0 0 0 0
5 Net Wall I
Area I R- 11, 1/2"Asp. l3rd. 3.2 t9 1,632 5,222 3,101
Area 2 R- 13, 1/2"Asp. Brd. 3.0 1.8 0 0
Area 3 R- 13, 1/2"Asp. Brd. 3.0 1.8 0 0
1
r6 Ceilings -- --E .8 —
1
Area I Attic, R-22 '1.9 -2q 0 0
Area 2 Attic, R- 19 2.1 2.3 0 0
Area 3 Attic, R- 19 2.1 2.3 1,503 3,156
3,457
7 Floors
Area I Slab 40.5 U 167 6,764 0
Area 2 None 0.0 0.0 ET 0 0
8 Infiltration Winter Summer Avg Cilng Ht
Poor 1500-2100 1.2 0.6 10 16,566 13,313
9 Sub Total BTUH Loss 36,781
10 Duct BTUH Loss 1 9,613
11 TOTAL HEATING LOAD 46, 94
12 People and Appliances Bedrooms — 7,200
13 Sub Total BTUH Gain (Structure)
14 Duct BTUH Gain gLocation Attic .........�33,437
15 TOTAL SENSIBLE 15% 6,321
39,758
16 Infiltraton Latent Gain Infit. CFM 151 12,321
17 People Latent Gain #People 8 4,800
19 TOTAL LATENT
17,121
19 Total Cooling Load 56,879
MWILd CERTIFIEDT.
L www.ahridiriectory.org
— 'A
Certificate of Product Ratings
AHRI Certified Reference Number: 3890017 Date: 4/8/2013
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: 2SHBC360(A,W)**30
Indoor Unit Model Number: FB4CNF060
Manufacturer: CARRIER AIR CONDITIONING
Trade/Brand name: COMFORT 13 PURON HP
Manufacturer responsible for the rating of this system combination is CARRIER AIR CONDITIONING
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 58000
EER Rating (Cooling): 10.80
SEER Rating(Cooling): 13.00
Heating Capacity(Btuh)@ 47 F: 56000*
Region IV HSPF Rating (Heating): 7.70
Heating Capacity(Btuh)@ 17 F: 36200
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no re resentations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for parnages of any kind arising out of the use or performance of the product(s),or the
unauthorized atteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory at wwvv.ahriclirectory�org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products ofAHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on it "IMF, Air-Conditioning,Heating,
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below. APOU 00 ILI and Refrigeration Institute
@2013 Air-Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 130099220955992966