336 10th St 2013 HVAC v
CITY OF ATLANTIC BEACH
s 800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00002573 Date 4/30/13
Property Address . . . . . . 336 10TH ST
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . RES SF DISTRICT
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 4ton unit, 48K btu' s
----------------------------------------------------------------------------
Owner Contractor
-
------------------------
-----------------------
BULL KATHLEEN & NIELS ONE HOUR AIR
336 10TH ST 1015 ATLANTIC BLVD #249
ATLANTIC BEACH FL 322335530 ATLANTIC BEACH FL 32233
(904) 222-8482
----------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . 83 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 10/27/13
------------------------------------------------------------------
Other Fees . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
-------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ------
Permit Fee Total 83 . 00 83 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 87 . 00 87 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(9044)-247-5826 Fax (904) 247-5845
JoB ADDRESS: `j� 6T J 1 ��� PERMIT#
PROJECT VALUE $
REQUIRED
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit e-
Heat: Unit Quantity BTU's Per Unit ( Seer Rating
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name &kL- A U L L Phone Number Z
I Mechanical Company ��t l Uv- n!r-�, Office Phon I- 16 Fax 2�l?-S� 2�
Co. Address: 1 �8 V►�l `�� '�PI-) City SIC 'l State =Zip 72237
License Holder (Print): Cgol L [o�� State Certification/Registration#C*C&4q-2o
Notarized Signature of License Holder
Before me this day of 20
Signature of Notary Public
Job: 122739
Project Summary Date: 4/3012013
wrightsoft Entire House By: CRAIG EDDY
ONE HOUR AIR
1198 MAYPORT RD#1,ATLANTIC BEACH,FL 32233 Phone:904-241-3107 Fax:904-247-5526 License:CAC1814420
UNT-TRINOMMM
For: NIELS &KATHY BULL
336 10TH STREET, ATLANTIC BEACH, FL 32233
Phone: 904-249-1345
Notes:
Weather: Jacksonville/Craig, FL, US
Winter Design Conditions Summer Design Conditions
35 °F Outside db 91 °F
Outside db 70 °F Inside db 75 °F
Inside db 16 °F
Design TD 35 °F Design TD M
Daily range 50
Relative humidity 53 gr/lb
Moisture difference g
Heating Summary Sensible Cooling Equipment Load Sizing
41571 Btuh Structure 37181 Btuh
Structure 0 Btuh Ducts 0 Btuh
Ducts 0 Btuh Central vent(0 cfm) 0 Btuh
Central vent(0 cfm) 0 Btuh Blower 0 Btuh
Humidification 0 Btuh
Piping
Equipment load 41571 Btuh Use manufacturer's data 1.00y
Rate/swing multiplier 37 .0 Btuh
Infiltration Equipment sensible load
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average 4781 Btuh
Fireplaces 0 Structure 0 Btuh
Ducts 0 Btuh
Heating Cooling Central vent(0 cfm)
Area(ftp
2112 2112 Equipment latent load 4781 Btuh
Volume(if) (cfm)hour 2534 0 44 2534
0.214
Equipment total load 41962 Btuh
Equiv.AVF (
Air changes173 89 Req. total capacity at 0.78 SHR 4.0 ton
Heating Equipment Summary Cooling Equipment Summary
Make GOODMAN Make GOODMAN
Trade AMANA Trade AMANA
Model ASZC180481 Cond ASZC180481
AHRI ref 4612963 Coil CHPF4960
AHRI ref 4612963 18 SEER
Efficiency 0 HSPF Efficiency 37392 Btuh
Heating input Sensible cooling 10608 Btuh
0
Heating output 0 'F @ 47°F Latent cooling 48000 Btuh
fm Actual air flow
Temperature rise cTotal cooling 1693 cfm
Actual air flow 1693 cf0.046 cfm/Btuh
Air flow factor 0.041 cfm/Btuh Air flow factor 0 in H2O
Static pressure 0 in H2O Static pressure 0 89
Space thermostat Load sensible heat ratio
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2013-Apr-30 08:53:02
wl-igfltsoftRight-SuiteO universal 2012 12.1.07 Right JOO Mobile
Page 1
ACOA. ...\wstmp\e735c284-1150-4096-be6e-bd78394acbfa.rup Calc=MJ8 Front Door faces: N