2077 Beach Ave 2013 HVAC CITY OF ATLANTIC BEACH
1 800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00002759 Date 5/29/13
Property Address . . . . . . 2077 BEACH AVE
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 CU 1 AHU 4 TONS
----------------------------------------------------------------------------
Owner Contractor
------------------------
------------------------
SHEPHERD ROBIN W & CHRISTINA DONOVAN HEATING & AIR
2077 BEACH AVE 315 SIXTH AVENUE SOUTH
ATLANTIC BEACH FL 322335934 JACKSONVILLE BEACH FL 32250
(904) 241-3785
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 107 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 11/25/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 107 . 00 107 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 111 . 00 111 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach,FL 32233
Ph(904)247-5826 Fax(904)247-5845
JOB ADDREss: 0 1] �, �� �/t� PERMIT#
PROJECT VALUE$ y p
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit _
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM
REQUIRED
REPLACEMENT AIR CONDITIONING & ]HEATING SYSTEM INSTALLATION
Air Conditioning; Unit Quantity Tons Per Unit ARI#
Heat: RE
Duct Systems: o��Mtr� i BTU's Per Unit Seer Rah n
REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
ALL OTHER GAS PIPING Elevators/EscalatorsHeat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Taniklss(gallons)
We
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months_I hereby certify that I haveread
this application and know the same to be true and correct All provisions of laws and ordinances governing this work will be complied with whether specified
)r not The permit does not give au to violate the provisions of any other state or local law regulation construction or the performance of construction
?roperty Owners Name kob;v-N f
Cs�l Phone Number
Mechanical Company l��t vvC n -t �- lei" Office Phone Zlt 1-3?KS-Fax ZH 1-31 9S
�o. Address: 3I S c. S
City owK t34U c 1. State C Zip 3 aaS�
:icense Holder(Print): -AU&w, �rtav/G n State Certification/Registration# G�Go3 b
Votarized Signature of License Holder
Sworn and subscribed before me this `� da of /a 20
YEE
tate of Florid S' of Notary Public A. # . Hughesn EE 186278
016
Project Summa Job.
+ wrightsoft Date: 5/29/13
Entire House By: Brandon Zaharie
Donovan Heat & Air
315 6th ave south, Jacksonville Beach, Fl-32250 Phone: 241-3785 Email brandon@donovanac.com
• • •
For: She hers
2077 Beach AVE, Atlantic Beach, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 °F Outside db 95 °F
Inside db 68 °F Inside db 75 °F
Design TD 29 °F Design TD 20 °F
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 21477 Btuh Structure 17679 Btuh
Ducts 7576 Btuh Ducts 15456 Btuh
Central vent (57 cfm) 1804 Btuh Central vent (57 cfm) 1244 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 30857 Btuh Use manufacturer's data n
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 34379 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 1 (Average) Structure 2029 Btuh
Ducts 2778 Btuh
Heating Cooling Central vent (57 cfm) 2047 Btuh
Area (ft' 2336 2336 Equipment latent load 6854 Btuh
Volume �ft3) 21024 21024
Air Changes/hour 0.38 0.16 Equipment total load 41233 Btuh
Equiv. AVF (cfm) 132 56 Req. total capacity at 0.70 SHR 4.1 ton
Heating Equipment Summary Cooling Equipment Summary
Make carrier Make carrier
Trade Trade
Model 25HNB648c Cond 25HNB648c
ARI ref no. 5480779 Coil FE4AN005
ARI ref no. 5480779
Efficiency 9 HSPF Efficiency 16 SEER
Heating input Sensible cooling 32292 Btuh
Heating output 45903 Btuh @ 47°F Latent cooling 13840 Btuh
Temperature rise 27 °F Total cooling 46132 Btuh
Actual air flow 1538 cfm Actual air flow 1538 cfm
Air flow factor 0.053 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.83
Printout certified by ACCA to meet all requirements of Manual J 8th Ed.
wrightsoft Right-Suite®Universal 7.1.01 RSU05996 2013-May-29 08:11:53
C:\Users\Sales\Documents\Wrightsoft HVAC\4 TON.rup Calc=MJ8 Orientation=N Page 1