84 Nicole Ln 2013 HVAC CITY OF ATLANTIC BEACH
f 800 SEMINOLE ROAD
s) ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00002900 Date 6/17/13
Property Address . . . . . . 84 NICOLE LN
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 CU 1 AHU
----------------------------------------------------------------------------
Owner Contractor
-
------------------------
-----------------------
FORTUNE, SCOTT THOMAS & JENNI DONOVAN HEATING & AIR
84 NICOLE LANE 315 SIXTH AVENUE SOUTH
ATLANTIC BEACH FL 322335978 JACKSONVILLE BEACH FL 32250
(904) 241-3785
--------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . 99 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 12/14/13
---------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- --------
Permit Fee Total 99 . 00 99 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 103 . 00 103 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
f Ph(904) 247-5826 Fax (904) 247-5845
fOB ADDRESS: 6 r\� t c,a 1, L a Y\P PERMIT#
PROJECT VALUE $ SZyt) ARI# 3�5 33 REQUIRED
_Air Handling Equipment Only '►Air Handling Unit & Condenser Condenser Only
JEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
ZEPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity ( Tons Per Unit 3
Heat: Unit Quantity I BTU's Per Unit 3 Seer Rating f -�
Duct Systems: Total CFM REQUIRED
TIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
IRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
)THER:
ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
its application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
ot. The permit does not give authSco-o
' to violate the provisions of any other state or local law regulation construction or the performance of construction.
'roperty Owners Name F02 rfiv+ti- Phone Number 525`55 2-Z--
nechanical Company 315 t� Ay€ S Office Phone )f/ 378rFax Zyt 37W_
:o. Address: 31 S �� AvE S City J AX 3�� State R Zip 37,Z i
,icense Holder(Print): �/V��ji a, yq, '�DON ovA.^/ State Certification/Registration# CAGO 3q7`
Notarized Signature of License Holder -,'2-. 4�2�
�,� Notary Punic state of i=bride efore me this
7 day of �U�-- 20 13
Timothy Lee Hughes
My commission EE 186278 gnature of Notary Public
4.5 Expires 04/03/2016
Job:
+ wrightsoft Project Summary Date: June 12,2013
Entire House By: Aaron Thacker
Donovan Heat & Air
315 6th Ave S,Jacksonville Beach, FL 32250 Phone:904-241-3785 Fax 904241-3745 Email:aaron@donovanac.com Web:www.DonovanAC.corn
Project Information
For: Scott Fortune
84 Nicole Ln,Atlantic Beach, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 OF Outside db 95 OF
Inside db 70 OF Inside db 75 OF
Design TD 31 OF Design TD 20 OF
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 26705 Btuh Structure 20836 Btuh
Ducts 4717 Btuh Ducts 4600 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 31422 Btuh Use manufacturer's data n
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 25436 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average 1154 Btuh
Fireplaces 0 Structure
Ducts 1961 Btuh
Heating Cooling Central vent (0 cfm) 0 Btuh
Area (ft') 1040 1040 Equipment latent load 3115 Btuh
Volume(ft') 8320 8320
Air changes/hour 0.45 0.23 Equipment total load 28551 Btuh
Equiv.AVF (cfm) 62 32 Req. total capacity at 0.70 SHR 3.0 ton
Heating Equipment Summary Cooling Equipment Summary
Make Tempstar Make Tempstar
Trade SMARTCOMFORT TX 5500 R41 OA HP Trade SMARTCOMFORT TX 5500 R41 OA HP
Model TXH536GKA* Cond TXH536GKA*
AHRI ref no3650133 Coil FVM4X36****
AHRI ref no3650133
Efficiency 8.5 HSPF Efficiency 12.5 EER, 15 SEER
Heating input Sensible cooling 23660 Btuh
Heating output 34400 Btuh @ 47'F Latent cooling 10140 Btuh
Temperature rise 28 OF Total cooling 33800 Btuh
Actual air flow 1127 cfm Actual air flow 1127 cfm
Air flow factor 0.036 cfm/Btuh Air flow factor 0.044 cfm/Btuh
Static pressure 0 in H2O Static Load se ssble heat ratio 0 89 in H2O
Space thermostat
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed-
2013-Jun-12 12:09:34
wrightSOft Right-Suite®Universal 8.0.24 RSU05995 Pagel
t1 C:\Users\Owner\Documants\Wrightsoft HVAC\Bogus 3 ton.rup Calc=MJ8 Front Door faces: W