2236 Barefoot Trac 2013 HVAC CITY OF ATLANTIC BEAf
800 SEMINOLE
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
SA
Application Number . . . . . 13-00002852 Date 6/13/13
Property Address . . . . . . 2236 BAREFOOT TRAC
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 CU 1 AHU
----------------------------------------------------------------------------
Owner Contractor
------------------------
------------------------
MONS NARAYAN C & JENNIFER LYNN DONOVAN HEATING & AIR
2236 BAREFOOT TRAC 315 SIXTH AVENUE SOUTH
ATLANTIC BEACH FL 322334564 JACKSONVILLE BEACH FL 32250
(904) 241-3785
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 95 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 12/10/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
--------- -------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 95 . 00 95 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 99 . 00 99 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (904) 247-5845
22 1(o —P)o-4-e -F
10B ADDRESS: �004 Col ct PERMIT#
PROJECT VALUE $ s,�-.00 ARI# REQUIRED
Air Handling Equipment Only )(�Air Handling Unit & Condenser Condenser Only
qEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
ZEPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit �15
Heat: Unit Quantity I BTU'sPerUnit 3o,000 SeerRating
Duct Systems: Total CFM REQUIRED
�IRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
TIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
�LL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
# Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
)THER:
ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
iis application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
ot. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Iroperty Owners Name -r-h y-i S mopis Phone Number 50 9 - 6?0 t4
/lechanical Company Dorl&vao 14es--�r � aw -Office Phone ZY1 3'765'Fax 2W17Yr
lo. Addres -3t 5 P zir)-32156
s: �, t6 AV<- City ��1 -g -8d, _State
icense Holder(Print): W, I I,a rv, Do f-i crvle� State Certification/Registration# CbCo 3 6-76
6,h* older L,
OP Notary Puwic state of Flohda
S.on EE 186278
Timothy Lee Hughes Before me this /2 day of 20 13
M :m
y ComlTission EE 186278
s r
14 2016
di Expires WOW" Signature of Notary Public
Job:
+ wrightsoft Project Summary Date: 6/4/13
Entire House By: Brandon Zaharie
Donovan Heat & Air
315 6th ave south,Jacksonville Beach, FL 32250 Phone: 241-3785 Email: brandon@donovanac.com
Proiect Information
For: Mons
2236 Barefoot Trace, Atlantic Beach, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 'F Outside db 95 'F
Inside db 68 'F Inside db 75 'F
Design TD 29 oF Design TID 20 'F
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 14414 Btuh Structure 14371 Btuh
Ducts 3195 Btuh Ducts 4674 Btuh
Central vent (13 cfm) 409 Btuh Central vent (13 cfm) 282 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 18019 Btuh Use manufacturer's data n
Rate/swing multi�lier 1.00
Infiltration Equipment sensi le load 19327 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 1 (Average) Structure 1921 Btuh
Ducts 1006 Btuh
Heati n Coolinp Central vent (13 cfm) 465 Btuh
Area (ft' 1219 121 Equipment latent load 3392 Btuh
Volume �ft-) 10962 10962
Air changes/hour 0.56 0.23 Equipment total load 22718 Btuh
Equiv.AVF (cfm) 102 42 Req. total capacity at 0.70 SHR 2.3 ton
Heating Equipment Summary Cooling Equipment Summary
Make Tempstar Make Tempstar
Trade Trade
Model TXH530 Cond TXH530
ARI ref no. 3650132 Coil FVM4X36
ARI ref no. 3650132
Eff iciency 8.5 HSPF Efficiency 15.5 EER
Heating input Sensible cooling 20906 Btuh
Heating output 29717 Btuh @ 47'F Latent cooling 8960 Btuh
Temperature rise 34 'F Total cooling 29866 Btuh
Actual air flow 801 cfm Actual air flow 801 cfm
Air flow factor 0.045 cfm/Btuh Air flow factor 0.042 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
I Load sensible h 0.85
Space thermostat eat ratio
Printout certified by ACCA to meet all requirements of Manual J 8th Ed.
Right-SuiteO Universal 7.1.01 RSU05996 2013-Jun-04 1T33:45
ACCK C:\U sers\Sales\D ocum ents\Wnght soft HVAC\2.5 TON Calc=MJ8 Orientation=N Page 1
This combination qualifies for a Federal Energy
"IMF Efficiency Tax Credit when placed in service
WNILI CERTIFIEDT. between Feb 17, 2009 and Dec 31, 2013.
www.ahi idirectory.a rg
L
Certificate of Product Ratings
AHRI Certified Reference Number: 3650132 Date: 6/12/2013
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: TXH530GKA*
Indoor Unit Model Number: FVM4X36****
Manufacturer: TEMPSTAR
Trade/Brand name: SMARTCOMFORT TX 5500 R410A HP
Manufacturer responsible for the rating of this system combination is TEMPSTAR
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity (13tuh): 28400
EER Rating (Cooling): 12.50
SEER Rating (Cooling)-. , 15.50
Heating Capacity(Btuh)@ 47 F: 27800*
Region IV HSPF Rating (Heating): 8.50
Heating Capacity(Btuh)@ 17 F: 16600
Ratings followed by an asterisk indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the products)listed on this Certificate.AHRI expressly di3claims all liability for damages of any kind arising out of the use or performance of the product(s),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory atwww.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION rectory.org, it "1201 -Conditioning,Heati,n
The information for the model cited on this certificate can be verified at www.ahridi Air
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on hou On ILI and Refrigeration Institute
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below.
@2013 Air-Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 130155281335288404