340 Garden Ln 2013 HVAC ff�
CITY OF ATLANTIC BEACH
1 j 800 SEMINOLE ROAD
"J t ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00003050 Date 7/15/13
Property Address . . . . . . 340 GARDEN LN
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
EMMANUEL, JOANN R DONOVAN HEATING & AIR
340 GARDEN LANE 315 SIXTH AVENUE SOUTH
ATLANTIC BEACH FL 32233 JACKSONVILLE BEACH FL 32250
(904) 241-3785
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 1/11/14
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 95 . 00 95 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
LI / Ph (90/4) 247-5826 Fax (904) 247-5845
1011 ADDRESS: ,3yo C30-1r-d-2411, LGrC-- PERMIT#
PROJECT VALUE $ SIUS ARI# 3C 1 Q�30 REQUIRED
_Air Handling Equipment Only >c,^ Air Handling Unit & Condenser Condenser Only
JEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
ZEPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit 2-
Heat: Unit Quantity I BTU's Per Unit 2 000 Seer Rating IS
Duct Systems: Total CFM REQUIRED
IRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
TIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
kLL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
)THER:
ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
►is application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
ot. The permit does not give authority to violate the p isi nLLs of any other state or local law regulation construction or the performance of construction.
'roperty Owners Name W, I ��nn., b�Ta Phone Number 0 —�I8'.�
✓Iechanical Company +,. otJ 0 4--li HEAT if A,g Office Phone 211 3-793" Fax Zyl 3"1VS-�
:o. Address: 31 (off- AVE s City J�'C � State Fl Zip 3Z2SZ�
,icense Holder(Print): 7r,,, t�OAley,4.✓ State Certification/Registration# Cora 34761
V ' �i, ense Holder
�'► Notary Public State of F c,;.:,,
Timothy Lee Hughes Before me tis day of
-1i rX4 20 3
My Commission EE 1962-/
Fr
VaV Expires 04/03/201Signature of Notary Public
.-
y ect Summa
Pro rJob:
+++ wrightsoft � 7 Date: 7/9/13
Entire House By: Brandon Zaharie
Donovan Heat&Air
315 6th ave south, Jacksonville Beach, FL 32250 Phone:241-3785 Email. brandon@donovanac com
Proiect Information
For: Bolton
340 Garden lane,Atlantic Beach, FL 32233
Notes:
D- • • •
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 °F Outside db 95 °F
Inside db 68 'F Inside db 75 °F
Design TD 29 °F Design TD 20 °F
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 13919 Btuh Structure 11729 Btuh
Ducts 2799 Btuh Ducts 5690 Btuh
Central vent (12 cfm) 370 Btuh Central vent (12 cfm) 255 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 17088 Btuh Use manufacturer's data n
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 17674 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 1 (Average) Structure 1638 Btuh
Ducts 973 Btuh
Heating Cooling Central vent (12 cfm) 420 Btuh
Area (ftz) 1152 1152 Equipment latent load 3031 Btuh
Volume (ft') 10368 10368
Air changes/hour 0.57 0.23 Equipment total load 20706 Btuh
Equiv.AVF (cfm) 98 40 Req. total capacity at 0.70 SHR 2.1 ton
Heating Equipment Summary Cooling Equipment Summary
Make �empstar Make Tempstar
Trade Trade
Model NXH524 Cond NXH524
ARI ref no. 3670830 Coil FXM4X24
ARI ref no. 3670830
Efficiency 8.7 HSPF Efficiency 15.2 SEER
Heating input Sensible cooling 15747 Btuh
Heating output 22384 Btuh @ 47°F Latent cooling 6749 Btuh
Temperature rise 27 °F Total cooling 22496 Btuh
Actual air flow 750 cfm Actual air flow 750 cfm
Air flow factor 0.045 cfm/Btuh Air flow factor 0.043 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.85
Printout certified byACCA to meet all requirements of Manual J 8th Ed.
444- wrigHtsoft Right-Suite®Universal 7-1 01 RSU05996 2013-Jul-09 12:32.17
C\Users\Sales\Documents\Wrightsoft HVAC\2Ton rup Calc=MJ8 Orientation=N Page 1