315 20th St 2013 HVAC CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00003042 Date 7/11/13
Property Address . . . . . . 315 20TH ST
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 CU 1 AHU 3 . 5 TONS
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
CLEARY ROGER L & KATHLEEN L TOTAL AIR CARE, INC.
315 20TH ST PO BOX 2004
ATLANTIC BEACH FL 32233 MIDDLEBURG FL 320SO
(904) 241-9921 (904) 282-5050
----------------------------------------------------------------------------
Permit W/W/O MECHANICAL PERMIT
Additional desc . .
Permit Fee . . . . 206 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 1/07/14
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 3 . 09
STATE MECH DBPR SURCHARGE 3 . 09
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 206 . 00 206 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 6 . 18 6 . 18 . 00 . 00
Grand Total 212 . 18 212 . 18 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (904) 247-5845
Wool
OB ADDRESS: f,- &AU 1:�i- —PERMIT #
PROJECT VALUE $ i&p ARI#- _REQUIRED
—Air Handling Equipment Only -.'�'Air Handling Unit & Condenser Condenser Only
iEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Ratinp-
Duct Systems: Total CFM REQUIREL-
?,EPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity i BTU's Per Unit Seer Ratina i,:5,.
Duct Systems: Total CFM REQUIREL
4RE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
4RE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
kLL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
)THER:
ermit becomes-void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify tha:I have read
iis application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with wheth,:r specified or
Dt. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of const uction.
Property Owners Name eaftAq Phone Number qoq- t4i -nt I
4echanical Company Aw- Office PhondQ 9Z-WFaxj9t-0L-�bi4-
IF - I
�,O laq d
,o. Address: City OAi-150-V State t-i- Zip. 5U�Z'
MECHANICAL PERMITAPPLICATION
CITY OFATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (904) 247-5845
OBADDRESS: PERMIT #
,icense Holder(Print):
/I ertifi�ation/Registration
Warized Signature of License Holder
Before me this day of 20
Signature of Notary Public
loor
JANET NICOLE PRINDLE
Notary Pubtic-state ot Fkxw&
My COMM.ExOrn Sep 23,2018
..... COMM8210n EE 837903
Residential System Sizing Calculation
Summary
Project Title-
315 20th st Roger Cleary
ATLANTIC BEACH, I'L 32233-
7/11/2013
Location for weather data: Jacksonville, FIL - Defaults� Latitude(30.5) Altitude(30 ft.) Temp Range(M)
Humidity data: InteriorRH (50%) Outdoor wet bulb (7 F) Humidity difference(53gr.)
Winter design teniperature(MJ8 99%) 32 F Summer design temperature(MJ8 99%) 93 F
Winter setpoint 70 F Summer setpoint 75 F
Winter temperature difference 38 F Summer temperature difference la F
Total heating load calculation 40569 Stuh Total cooling load calculation 38225 Btuh
Submitted heating capacity % of calc Btuh Submitted cooling capacity %of calc Btuh
Total (Electric Heat Pump) 103.5 42000 Sensible (SHR =: 075) 99.3 31500
Heat Pump +Auxiliary(0.0kW) 103.5 42000 Latent 1617 10500
Total (Electric Heat Pump) 109.9 42000
WINTER CALCULATIONS
Winter Heating Load (for 2 �5 sqft)
auvx-'-12%�
Load component Load
-��,nd,w total 360 sqft 13872 Btuh
Wall total 1020 sqh '3440 Btuh
Door total 60 sqft 1049 Btuh
Ceiling total 2025 sqft 2451 Btuh
Floor total 2025 sqft 8071 Btuh
infiltration 166 cfm 6946 Btuh
Duct loss 4741 Btuh
Subtotal 40569 Btuh
Ventilation G cfm 0 BtUh
TOTAL 14EAT LOSS 1 40569 Stuh
SUMMER CALCULATIONS
SUrnmer Coolinq Load(for 2025 sqft)
Load component Load
Window total 360 sqft 16473 Btuh
Wall total 1020 Sqft 2218 Btuh
Door total 60 sqft 800 ntuh
Ceiling total 2025 sqft 2773 Btuh
Floor total 0 BtUh
Infiltration 125 cfm 2468 Btuh
Internal gain 2120 Btuh
Duct gain 4880 Btuh 4W)
,9png.Ventilation 0 cfm 0 Btuh
Blower Load 0 Btuh
Total sensible gain 31731 Btuh
Latent gain(ducts) 1202 BtUh
Latent gain(infiltration) 449-1 Stuh
1-2tont qain(ventilation) 0 Btuh
Latent gain(internal/occupants/other) 800 Btuh
Total latent gain 6493 Btuh
TOTAL HEAT GAIN 38225 Dtuh
A991bk EnergyGaugeS S rn'S"i
PIREPARED BY-
Sth Edition DATF
IF EnergyGauge@ USRFZB v3.0
Residential Window Diversity
MidSummer
Project Title:
315 20th st Roger Cleary
ATLANTIC BEACH, FL 32233-
711112013
mom=
Summer design temperature 93 F Average window load for July 3695 Btuh
Cooling setpoint 75 F Peak window load for July 4926 Btuh
Summer temperature difference 18 IF Excusion limit(l 30%of Ave.) 4803 Btuh
1-8fitUde 30,5 North Window excursirm (.1111y) 123 Btuh
WINDOW Average and Peak Loads
7"
1,11,H.OLW Averal3e \4
M
"DOM
iO 12 2 P-M. 4 p.m. P rn
alfi-
Total July Window Load(Radiation and conduction)
Warning:This application has glass areB3 that produce relatively large heat gains for Part of the day, Variable
air volume devices may be required to overcome spikes in solar gain for one or more rooms.A zoned system
may be required or some rooms may require zone control.
EnergyGauget-5 So forflorida ra ices only
PREPARED BY-
DATE
44=11 1 -
EnergyGaugeV I USRFZB 0.0
Residential Window Diversity
October
Project Title:
315 20th st Roger Cleary
ATLANTIC BEACH, FIL 32233-
71111201-3
Summer design temperature 93 F Average window load for October 4618 Btuh
Cooling setpoint 75 F Peak window load for October 6383 Btuh
Summer temperature difference 18 F Excusion limit(l 30%of Ave.) 6003 Btuh
LatitUde 30.5 North Window excursion (Oct2����.
WINDOW Average and Peak Loads
LgM
11 2 Hoar A�traqe
Z'.M. 2:P'.:n 4!p.-m ep.ITI, a
Total October Window Load(Radiation and conduction)
Warning:This application has glass greaE,th.st produce relatively large heat gains for part of the day. Variable
air volume devices may be required to overcome spikes in solar-qain for one or more roams. A zoned system
may be required or some rooms may require zone control-
FnergyGauge�P�Syster2,41,
izing for��,Orida residlejic�—
PREPARED BY:
DATE: Z ��
EnergyGauge(D I USRFZB v3.0
System Sizing Calculations - Winter
Residential Load - Whole House Component Details
Project Title:
315 20th st Roger Cleary
ATLANTIC BFACH, FIL 32233- Building Type: User
7/11/2013
Reference City: Jacksonville, FIL (Defaults) Winter Temperature Difference: 38.0 F (MJ8 99%)
0,�1'
A
Window Panes/Type Frame U Orientation Area(sqftl, X HTM= Load
1 1, Clear Metal 113 N 108.0 42,9 4638 Btuh
2 1, Clear Metal 1.13 S 90.0 42.9 3865 Btuh
3 1, Clear Metal 1.13 S 90-0 42-9 3866 8tuh
4 1, NFRC 0.60 Metal 0.55 W 72.0 20.9 1505 Btuh
Window Total 360.D(sqft) 13872 Btuh
Walls Type Ornt- Ueff. R-Value Area X HTM= Load
(Cav/Sh)
1 Frame -Wood Ext (0.089) 13.0/0.0 232 3.37 782 Btuh
2 Frame -Wood Ext (0.089) 13.010-0 360 3.37 1214 Btuh
3 Frame-Wood Ext (0.089) 13.0/0-0 140 327 472 Btuh
4 Frame -Wood Ext (0.089) 13.010.0 288 3.37 071 Btuh
Wall Total 1020�§gjft 3440 Btuh
Doors Type Storm Ueff. Area X HTM= Load
1 Wood-Exterior, n (0-460) 20 17.5 350 Btuh
2 Wood - Exterior, n (0-460) 4Q 17.5 699 Btuh
Door Total 60(sqft) 104913tuh
Ceilings Type/Color/Surface Ueff- R-Value Area X HTM= Load
1 Vented Attic/L/Shing (0.032) 30.0/0-0 2025 1.2 2451 Btuh
Ceiling Total 2025(sqft) 2451 Btuh
Floors Type Ueff R-Value Size X HTM= Load
1 Slab On Grade (1.180) 0.0 180.0 ft(perim.) 44.8 8071 Btuh
Floor Total 2025 sqft 8071 Btuh
Envelope Subtotal. 28882 Btuh
Infiltration Type Wholehou-se ACH Volume(cuft) Wall R@tio CFM=
Natural 062 16200 1.00 166.3 6946 Btuh
Ductload Average sealed, R6.0, Supply(Aft), Return(Att) (DLM of 0.132) 4741 Btuh
All Zone5 Sensible Subtotal All Zones 40569 Btuh
EnergyGauge(l)I USRFZB v3.0 Page 1
Manual J Winter Calculations
Residential Load - Component Details (continued)
ProjeGt Title'
315 20th st Roger Cleary
ATLANTIC BEACH, FfL 32233- Building Type: User
7/11/2013
'EV
"man
Subtotal Sensible Heat Loss 40569 Btuh
Totals for Heating Ventilation Sensible Heat Loss 0 Btuh
Total Heat Loss 40569 13tuh
1. Dectric Heat Pump ICP#NXH5426KA 42000
Key�Window types-NFRG(Requires U-Factor and Shading coefficient(SHGC)of glass as nuinarical values)
or-Qla5s aY,'rle@i'uF'Tint'(U5e5 U-Fac-wr i�nd SHGC defaults)
U-(Window U-Factor)
HTM-(M2nuaIJ Heat Tran5fer MultiplieQ
VeF51011 8
EriergyGaugeSi/U!5RFZB v3.0 Page 2
0%
bystem Sizing Calculations - Summer
Residential Load - Whole House Component Details
Project Title:
315 20th st Roger Cleary
ATLANTIC BEACH, FL 32233- 7/1112013
Reference City: Jacksonville, FL Temperature Difference: 18.OF(MJ8 99Q/,3) Humidity difference: 53gr.
Type* QvGrhang Window Area(sqft) HTM Load
FWindow Panes SHGC U InSh is Ornt Len Hgt Gross Shaded Unshaded Shaded Unshaded
1 1 Clear 0.74,11.13 i�o N-oN O.Oft O-Ott 108.0 0.0 108.0 39-- 36 3867 Btuh
2 1 Clear 0.74,11.13 No No S O-Oft 0.0ft W-0 0.0 90.0 36 42 3807 Btuh
3 1 Clear 0.74,1.13 No N40 S 0-M O.Oft 90.0 0.0 90.0 36 42 3607 Stuh
4 1 NFRC 0.60,0.65 No No W 0.13ft O.Oft 72.0 0.0 72.0 22 68 4868 Btuh
Excursion 123 Btuh
Window Total 16473 Btuh
Type U-Value R-Value Area(sqft) HTM Load
Cav/Sheath
1 Frame-Wood-Fxt 0-09 13.010.0 232,0 2.2 505 Btuh
2 Frame-Wood-Ext 0.09 13,0/0.0 360.0 2.2 79S Btuh
3 Frame-Wood-Ext 0.09 13.0/0.0 140.0 2.2 304 Btuh
4 Frame-W000-EXt 0,09 13.0/0.0 288.0 2,2 F)26 BWh
Wall Total 1020(sqft) 2218 Btuh
Doom Type Area(sqft) HTM Load
I Wood-Exterior 20.0 13.3 267 Btuh
2 Wood-Exterior 40.0 13.3 534 l3tuh
Door Total 60(sqft) 800 Btuh
Ceilings Type/Color/Surtace U-Value R-Value Area(sqft) HTM Load
1 Vented Attic(Light/Shingle 0.032 30-0/0-0 2025.0 1.37 2773 Btuh
Ceiling Total 2025(sqft) 2773 Btuh
--�-,-Oors Type R-Value size HTM Load
I Slab On Grade 0,0 2025(ft-perimeter) 0.0 0 Btuh
Floor Total 2025.0(sqft) - 0 Btuh
Envelope Subtotal: 22264 Stuh
infiltration Type Average ACH Volume(Guft)Wall Ratio CFM= Load
Natural 0.46 16200 1 124.7 2468 BtUh
Internal Occupant$ Btuh/occuFant Appliance Load
gain 4 X 230 + 1200 2120 Btuh
Sensible Envelope Load: 26852 Btuh
Duct load Average seaM,Supply(R6,0-Attic),Retum(R&O-Attic) 4880 BtUh
Sensible Load All Zones 31731 Btuh
EnergyGaugeg I USRFZB v3.0 Page 1
Manual J Summer Calculations
Residential Load - Component Details (continued)
Project Title: Climate-FL—JACKSONVILLE-1 NTL—ARPT
315 20th st Roger Cleary
ATLANTIC BEACH, IFIL 32233- 7/1112013
Mail,
r
.99
Sensible Envelope Load All Zonea 26852 Btuh
Sensible Duct Load 4880 Btuh
Total SensIble Zone Loads 31731 Btuh
Sensible ventilation 0 Btuh
Blower 0 Btuh
Whole House Total sensible gain 31731 Btuh
Totals for Cooling Latent infiltration gain (for 53 gr. humidity difference) 4491 Btuh
Latent ventilation gain 0 l3tuh
Latent duct gain 1202 Btu h
Latent occupant gain (4.0 people @ 200 Btuh per person) 800 Stu h
Latent other gain 0 Btu h
Latent total gain 6493 Stuh
TOTAL GAIN 3821c la#..h
irk!Mj
42000=Btuh
1. Central Unit ICP#NXH5426KA 42000 Btuh
'Key: window types(Panes-Number and type of panes of glass)
(SHGC-Shadin�00effirient of glass as SHOC numerical value)
(U-Window LI-Factor)
(InSh-Interior shading device:none(NQ),Blind%(B),Drapenes(D)or Roller Shsdes(R))
- For Blindsi Assume medium color. half closed
Ffbr Oraperio-s Assume,medium weave,half closed
For Roller shades:Assurne translucent,half closed
(IS-Insect screen:none(N),Full(F-)or Half(1/z))
(Ornt-compass orientation)
Version 8
EnergyGauge(g)I USRFZB 0.0 Page 2