1662 E Park Ter 2013 HVAC N CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00003016 Date 7/11/13
Property Address . . . . . . 1662 E PARK TER
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
4 TONS 48K BTUS
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
BROWN DAVID J & JANET A DONOVAN HEATING & AIR
1662 PARK TERRACE WEST 315 SIXTH AVENUE SOUTH
ATLANTIC BEACH FL 32233 JACKSONVILLE BEACH FL 32250
(904) 241-3785
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 107 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 1/07/14
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 107 . 00 107 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 111 . 00 111 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247-5826 Fax (904) 247-5845
10B ADDRESS: (o 6,2 i1ric I f�(z PERMIT#
J5 I(Do 0-0
PROJECT VALUE $ ARI# crDO I Q'7_ —REQUIRED
Air Handling Equipment Only �(_Air Handling Unit & Condenser Condenser Only
4EW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
ZEPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit q
Heat: Unit Quantity BTU's Per Unit WFO-00 Seer Rating_ 15
Duct Systems: Total CFM REQUIRED
ZIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
ZIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
�LL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
)THER:
ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
iis application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
ot. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name "DA-v C- "BrVVVn Phone Number 2fq-gg-79
Aechanical Company T)q Pep, fE A4Z Office Phone 1-W-YUS- Fax
,o. Address: AVE S city T4X 6CI- State A zi,)UM
,icense Holder(Print): lionn �Dn Into ri State Certification/Registration# -3 9-76
Votarized Si a Ider— :�j
rida A5;r
Before me*ifq 9 day of -rL11
40 W N Notary Pubfic state of Rorwa N 20
TOWthy Lee Hughes
my convr"sion EE 186278
ExpiM 0"312016 Signature of Notary Public
OFV�
Job:
wrightsoft Project Summary Date: 6/28/13
Entire House By: Brandon Zaharie
Donovan Heat&Air
315 6th ave south, Jacksonville Beach, FL 32250 Phone 241-3785 Email brandon@donovanac.com
Project Information
For: BROWN
1662 PARK TERRACE EAST, ATLANTIC BEACH, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 OF Outside db 95 OF
Inside db 68 OF Inside db 75 OF
Design TD 29 OF Design TD 20 OF
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 21477 Btuh Structure 17679 Btuh
Ducts 7576 Btuh Ducts 15456 Btuh
Central vent(57 cfm) 1804 Btuh Central vent (57 cfm) 1244 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 30857 Btuh Use manufacturer's data n
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 34379 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 1 (Average) Structure 2029 Btuh
Ducts 2778 Btuh
Heating Coolin Central vent (57 cfm) 2047 Btuh
Area (ft') 2336 2339 Equipment latent load 6854 Btuh
Volume (ft') 21024 21024
Air changes/hour 0.38 0.16 Equipment total load 41233 Btuh
Equiv.AVF (cfm) 132 56 Req. total capacity at 0.70 SHR 4.1 ton
Heating Equipment Summary Cooling Equipment Summary
Make Tempstar Make Tempstar
Trade Trade
Model TXH548 Cond TXH 548
ARI ref no. 3650162 Coil FVM4X48
ARI ref no. 3650162
Efficiency 8.2 HSPF Efficiency 15 SEER
Heating input Sensible cooling 32292 Btuh
Heating output 45903 Btuh @ 47'F Latent cooling 13840 Btuh
Temperature rise 27 OF Total cooling 46132 Btuh
Actual air flow 1538 cfm Actual air flow 1538 cfm
Air flow factor 0.053 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
Space thermostat Load sensible heat ratio 0.83
Printout certified by ACCA to meet all requirements of Manual J 8th Ed.
41 Right-Suite@ Universal 7.1,01 RSU05996 2013-Jun-28 11�45 44
Page 1
C\Users\Sales\Documents\Wrightsoff HVAC\4 TON.rup Calc=MJ8 Orientation=N