1909 Mealy St HVAC 2013 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00002775 Date 7/25/13
Property Address . . . . . . 1909 MEALY ST
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu 2 tons
----------------------------------------------------------------------------
Owner Contractor
------------------------
------------------------
WILLIAMSON ANN MARIE TRUST DONOVAN HEATING & AIR
C/O ANN MARIE WILLIAMSON TSTEE 315 SIXTH AVENUE SOUTH
8483 BERESFORD LN JACKSONVILLE BEACH FL 32250
JACKSONVILLE FL 322417141 (904) 241-3785
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 1/21/14
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 9S . 00 95 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (904) 247-5845
foB Amuss: I q Oq_ jfV\C-:ALV PERMIT
PROJECTVALITE $ 'SODV — AIU# 3-754,q8.1- _REQUIRED
Air Handling Equipment Only Air Handling Unit & Condenser Condenser Only
iEW AIR CONDII ONING & HEATING SYSTEM INSTALLATION
Air Conditioning: nit Quantity Tons Per Unit
Heat-. Unit Quantity BTU's Per Unit Seer Rating
Duct Systems-, Total CFM RE,Q EFIRED
ZEPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity I Tons Per Unit
Heat: Unit Quantity I BTU's Per Unit vicoo — . Seer Rating
Duct Systems: Total CFM RE Q UIRED
TIRE PREVENTION
Fire Sprinkler Systero Quantity (Requires 3 sets of plans)
Fire Standpipc Quantity (Requires 3 sets of plans)
Underground Fire M�in Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
�IRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/F,scal.ators
kLL OTHER GAS PIPING Heat Fxchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Reftigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
)THER:
ermit becom"void if work does not commence within a six month period or work is suspcndcd or abmidoned for six inontlis.I hereby certify that I havc read
iis application and know the same to be t=and correct. All provisions of laws and ordfrianccs governing this work will be complied with'Mictlicr specified or
of, The permit does not give authority to violate the provisions of any otherstate or tocal law regulation ronstruction or the performance ofconstruction.
Iroperty Owners-Name 4.0 0 -- VJ I I I I A/V�163 Phone Number q0V 24 9 9 52-
Aechanical Company��o t�j 0�j ,,.p Coi�, �..Ciffice Phone Zj]-376<Fax 2 q1
p
,o. Address: City Stat I-Zip!77.
nX
Jeense Holder (Print): L7 0_,On State Certification/Registration# ach 3u�
Votarized Signafure ofLicensg- Ider
Z7�
Nowry pubjjr me thi of /17�4 20
,Skaw of Fi0fift efore day
*,�4INN T4"hy LOO Hugh0a
My Comm"jon E�186VE1 ignature ofNotary Public
0P Expires 003120ig
Job:
Pr 'ect Summary oate: $130113
wright!soft 01 lay; Brandon Zaharle
Entire House
Donovan Heat& Air
315 6111 eve south,Jacksonville Bonch, FL 32250 Pmow 241-3755 Email:brklmdongdomovAhlc.com
For: WILLIAMSON
1909 MEALY ST ATLANTIC BEACH, FL 32233
Notes,
Desiqn Informatiotl
Weather� Jacksonville Mayport Naval, FL, US
W, ter Design Conditions Summer Design Conditions
Outside db 39 OF Outside db 95 OF
Inside db 68 OF inside db 75 'IF
29 OF Design TD 20 OF
Design TO Daily range L
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 18919 Btuh Structure 11729 Stuh
Ducts 2799 13tuh Ducts 5690 Btuh
Central vent (12 cfm) 370 Btuh Central vent (12 cfm) 255 Btuh
HUMidifiGStion 0 Stuh Blowe.". 0 Stuh
Piping 0 Btuh
Equipment load 17088 13tuh Use manufacturer's data n
Rate/swin multiplier 1�00
Infiltration Equipmenesensible load 17674 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality 1 ( Average
Fireplaces Average) Structure 1638 EH0
D ucts 973 Btuh
Heati nF Coolin Central vent (12 cfm) 420 Stuh
Area(ft 115 1152 Equipment latent load 3031 Btuh
Volume ffl) 10368 10368 20706 Btuh
Air chanqes/hour 0.57 0.23 Equipment total load
Equiv.AVF (cfm) 98 40 Req, total capacity at 0,70 SHR 2.1 ton
Hea�lng Equipment Summary Cooling Equipment Summary
Make Tempstar Make Tempstar
Trade Trade NXH524
Model NXH524 Cond
ARI ref 54781 Coil FEM4P24
ARI ref no. 3754781 14 SEER
8.4 HSPF Efficiency
Efficien 37 Sensible cooling 15747 Btuh
Heating input
Heating output 22384 Btuh @ 47OF Latent cooling 6749 Btuh
Temperature rise 27 OF Total cooling 22496 Btuh
Actual air flow 750 cf m Actual air flow 750 cfm
Air flow factor 0,045 cfm/Stuh Air flow factor O.D43 cfm/13tuh
Static pressure 0 in H20 Static pressure 0 in H20
Space thermostat Load sensible heat ratio 0.85
Printout certified by ACCA to meet all requirements of Manual J 8th Ed,
Riqhi-WeO univortAl T1.01 RSUOSIY96 2013-May-30 12:46:00
C:,IU39ft\Sale,,%Noocumont�;\wrlghtsaft HVA(��Mnsup Offit=M43 Orientation=N Pogo 1
CERTIFIEDT"
www.ahridirectory.or g
L
Certificate of Product Ratings
AHRI Certified Reference Number: 3754781 Date: 5/31/2013
Product: Split S�stem: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number: NXH524GKA*
Indoor Unit Mod I Number: FEM4P24**A*
Manufacturer: T1-MPSTAR
Trade/Brand nar ie: 15 SEER N SERIES R41 OA HP
Manufacturer relponsible for the rating of this system combination is TEMPSTAR
Rated as follow� in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent, third
party testing:
Coolin Capacity(Btuh): 23600
Z
EER R ting (Cooling): 12.00
SEER Rating (Cooling): 14.00
Heating Capacity(Btuh) @ 47 F: 24000
Region IV HSPF Rating (Heating): 8.40
Heating Capacity(Btuh) @ 17 F: 14700
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for mociels and configurations listed in the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The infon-nation forthe model cited on this certificate can be verified atwww.ahridirectoTy.org, "IMP, Air-Conditioning,Heating,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on P%m an ILI and Refrigeration Institute
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below.
@2013 Air-Conditioning, Heating,and Refrigeration Institute CERTIFICATE NO.: 130144891547599178