82 W 8th St 2013 HVAC CITY OF ATLANTIC BEACH
111
j 800 SEMINOLE ROAD
J _ ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
'vJF !SA
Application Number . . . . . 13-00003101 Date 7/22/13
Property Address . . . . . . 82 W 8TH ST
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
ELO ANN MARIE TRUST DONOVAN HEATING & AIR
C/O ANN MARIE WILLIAMSON 315 SIXTH AVENUE SOUTH
8483 BERESFORD LANE JACKSONVILLE BEACH FL 32250
JACKSONVILLE FL 32244 (904) 241-3785
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . . 2 TON
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 1/18/14
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
---------------------
Fee summary Charged Paid Credited ----Due---
----------------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 95 . 00 95 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax(904)247-5845
IoB ADDRESS: g��- V��Sr 8 1�- sfi PERMrr#
PROJECT VALUE $ 31 q4 ARI# 5 7 Z5540 REQUIRED
Air Handling Equipment Only f Air Handling Unit & Condenser Condenser Only
STEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
tEPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity I Tons Per Unit 2-
Heat: Unit Quantity T— BTU's Per Unit ZY o0v Seer Rating i3
Duct Systems: Total CFM REQUIRED
IRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
+IRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
kLL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks(gallons)
Wells
)THER:
ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
lis application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
ot. The permit does not give authority to vio'l'ate/the provisions of any other state or local law regulation construction or the performance of construction.
'roperty Owners Name A rJ-) Wi I I, Phone Number 301~ '7137
Mechanical Company. _�1 )nrJ vyp►J W EAT e Arrz Office Phone ZV1370- Fax ZV/3_7X1
;o. Address: 315 G t� ryE 5 City ��+r 13 State F1 Zip 3Z2<t;'
,icense Holder(Print): vV.i bA,,- -H__ State Certification/Registration# (,A co 397 j
Notarized Signature of License Holder
IoW" Notary Public state or Florida efore me s 9 day of .l�-� 20 j3
Timothy Lee Hughes
x Commission 16 188278 1 ature of No Public
OF ti Expires 04/0312018
. 9 Project Summary Job:
wri htsoft � Summary Date: 7/19/13
Entire House By: Brandon Zaharie
Donovan Heat&Air
315 6th ave south, Jacksonville Beach, FL 32250 Phone. 241-3785 Email brandon@donovanac com
For: Williamson
82 West 8th St,Atlantic Beach, FL 32233
Notes:
Design Iriformati6if
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 °F Outside db 95 °F
Inside db 68 °F Inside db 75 °F
Design TD 29 °F Design TD 20 °F
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 13919 Btuh Structure 11729 Btuh
Ducts 2799 Btuh Ducts 5690 Btuh
Central vent (12 cfm) 370 Btuh Central vent(12 cfm) 255 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 17088 Btuh Use manufacturer's data n
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 17674 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 1 (Average) Structure 1638 Btuh
Ducts 973 Btuh
Heating Cooling Central vent (12 cfm) 420 Btuh
Area (ft') 1152 1152 Equipment latent load 3031 Btuh
Volume (ft') 10368 10368
Air changes/hour 0.57 0.23 Equipment total load 20706 Btuh
Equiv.AVF (cfm) 98 40 Req. total capacity at 0.70 SHR 2.1 ton
Heating Equipment Summary Cooling Equipment Summary
Makeennox Make Lennox
Trade Trade
Model 13HPX-024 Cond 13HPX-024
ARI ref no. 725540 Coil CBX25UH-024
ARI ref no. 5725540
Efficiency 8 HSPF Efficiency 13 SEER
Heating input Sensible cooling 15747 Btuh
Heating output 22384 Btuh @ 47°F Latent cooling 6749 Btuh
Temperature rise 27 °F Total cooling 22496 Btuh
Actual air flow 750 cfm Actual air flow 750 cfm
Air flow factor 0.045 cfm/Btuh Air flow factor 0.043 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.85
Printout certified by ACCA to meet all requirements of Manual J 8th Ed.
-+#-t- wvightsoft Right-Suite®Universal 7.1.01 RSU05996 2013-Jul-19 10 32:45
�' C:\Users\Sales\Documents\Wrightsoft HVAC\2Tonrup Calc=MJ8 Orientation=N Page 1