Loading...
1671 Francis Ave 2013 fire suppression CITY OF ATLANTIC BEACH 800 SEMINOLE ROAD r� ATLANTIC BEACH, FL 32233 INSPECTION PHONE LINE 247-5814 r nit � Application Number . . . . 13-00003282 Date 8/29/13 Property Address . . . . . . 1671 FRANCIS AVE Application type description MECHANICAL FIRE PERMIT Property Zoning . . . . . . . TO BE UPDATED Application valuation . . . . 0 ----------------------------------------------------------------- Application desc FIRE SUPPRESSION SYSTEM -------------------------------------------------------------- Owner Contractor - ------------------------ ----------------------- CITY OF ATLANTIC BEACH CINTAS FIRE PROTECTION 800 SEMINOLE RD 5863 W BEAVER STREET ATLANTIC BEACH FL 322335428 JACKSONVILLE FL 32254 (904) 695-4200 ------------------------------------------------------------ Permit . . . . . . FIRE SUPPRESSION SYSTEM Additional desc . Permit Fee 55 . 00 Plan Check Fee 00 Issue Date . . . . Valuation . . . . 0 Expiration Date . . 8/29/13 ---------------------------------------------------------- Special Notes and Comments 2010 FLORIDA BUILDING CODE, FLORIDA FIRE PREVENTION CODE 2008 NATIONAL ELECTRIC CODE --------------------------------------------------------- Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00 STATE MECH DBPR SURCHARGE 2 . 00 ------------------------------------------------------- Fee summary Charged Paid Credited Due ----------------- ---------- ---------- ---------- ---------- Permit Fee Total 55 . 00 55 . 00 . 00 . 00 Plan Check Total . 00 . 00 . 00 . 00 Other Fee Total 4 . 00 4 . 00 . 00 . 00 Grand Total 59 . 00 59 . 00 . 00 . 00 PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA BUILDING CODES. MECHANICAL PERMIT APPLICATION D CITY OF ATLANTIC BEACH 800 Seminole Rd Atlantic Beach, FL 32233 AUG 2 2 2013 Ph (904) 247-5826 Fax (904) 247-5845 B JOB ADDRESS: --�h �^^� PROJECT VALUE $ Q e V (A) ARI# REQUIRED Air Handling Equipment Only Air Handling Unit & Condenser Condenser Only NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION Air Conditioning: Unit Quantity Tons Per Unit Heat: Unit Quantity BTU's Per Unit Seer Rating Duct Systems: Total CFM REQUIRED REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION Air Conditioning: Unit Quantity Tons Per Unit Heat: Unit Quantity BTU's Per Unit ' Zating --�;y Duct Systems: Total CFM " kfREQUIRED Manual J documentation required on residential change out FIRE PREVENTION Fire Sprinkler System Quantity (Requires 3 sets of plans) Fire Standpipe Quantity (Requires 3 sets of plans) Underground Fire Main Value (Requires 3 sets of plans) Fire Hose Cabinets Quantity (Requires 3 sets of plans) Commercial Hoods Quantity (Requires 3 sets of plans) Fire Suppression Systems Quantity 1 (Requires 3 sets of plans) FIRE PLACES MISCELLANEOUS: Prefabricated Fireplace Qty Automobile Lifts Gas Piping Outlets Boilers BTU's Elevators/Escalators ALL OTHER GAS PIPING Heat Exchanger Quantity of Outlets Pumps # Vented Wall Furnaces Refrigerator Condenser BTU's # Water Heaters Solar Collection Systems lanks (gallons) FIL ECOPY ells FIL OTHER: Vrnppy Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or not. The permit does not give authority to violate the provisions any oth r state or local law regulation construction or the performance of construction. Property Owners Name - t. Phone Number Mechanical Company C�✓� � � '� Office Phone'5t'--1ON Fax d Co. Address: � �5 City State Zip i License Holder (Print): State Certification/Registration# q6 -300) id61 Notarized Signature of License Holder VA-day CYNTHIA K.G EENE Before me this Cj tk S� 20� Commission#EE 0832`x9 ' Signature of Notary Public Expires June 19,2015 •,'f ' is Bor4w Tft Troy Fain insurance gpp.38fr1�19 City of Atlantic Beach APPLICATION NUMBER Building Department (To be assigned y the Building Department.) 800 Seminole Road 3 Z Z. Atlantic Beach, Florida 32233-5445 Phone(904)247-5826 • Fax(904)247-5845 /� "-Wilt} E-mail: building-dept@coab.us Date routed: �'7 City web-site: http:/Amw.coab.us APPLICATION REVIEW AND TRACKING FORMA Property Address: � �l�n C/S D 7ent review required Yes No Buildin Applicant: Q S anning &Zoning Tree Administrator Project: Public Works Public Utilities Public Safety ire Services Review fee $ Dept Signature Other Agency Review or Permit Required Review or Receipt Dateof Permit Verified By Florida Dept. of Environmental Protection Florida Dept.of Transportation St.Johns River Water Management District Army Corps of Engineers Division of Hotels and Restaurants Division of Alcoholic Beverages and Tobacco Other: APP ATION STATUS Reviewing Department First Review: Approved. ❑Denied. (Circle one.) Comments: I I p BUILDING Al P S PLANNING &ZONINGReviewed by: TREE G. [ Date: � TREE ADMIN. Second Review: ❑Approved as revised. ❑Denied. PUBLIC WORKS Comments: PUBLIC UTILITIES PUBLIC SAFETY Reviewed by: Date: FIRE SERVICES Third Review: [Approved as revised. ❑Denied. Comments: Reviewed by: Date: Revised 05/14/09 City of Atlantic Beach APPLICATION NUMBER Building Department (To be assigned by the Building Department.) 800 Seminole Road /J — z f Z, Atlantic Beach, Florida 32233-5445 Phone(904)247-5826 - Fax(904)247-5845 E-mail: building-dept@coab.us Date routed: �'7Z13 City web-site: http://wm.coab.us APPLICATION REVIEW AND TRACKING FORM Property Address: �� �/�G{n C/S 14-✓E Dent review required Yes No Building Applicant: Z 7_4 'S Fanning &Zoning Tree Administrator Project: Public Works Public Utilities Public Safety ire Services Review fee $ Dept Signature Other Agency Review or Permit Required Review �Verie r Rceipt Date of Permit fied By Florida Dept.of Environmental Protection Florida Dept. of Transportation St.Johns River Water Management District Army Corps of Engineers Division of Hotels and Restaurants Division of Alcoholic Beverages and Tobacco Other: APPLICATION STATUS Reviewing Department First Review: ❑Approved. ❑Denied. (Circle one.) Comments: BUILDING PLANNING &ZONING Reviewed by: Date: TREE ADMIN. Second Review: []Approved as revised. ❑Denied. PUBLIC WORKS Comments: PUBLIC UTILITIES PUBLIC SAFETY Reviewed by: Date: FIRE SERVICES Third Review: ❑Approved as revised. ❑Denied. Comments: Reviewed by: Date: Revised 05/14/09 aNrAs. 97° �'fa"Y7CiYYy�fiiiYT�i; AN ANSUL R-102 RANGE HOOD SUPPRESSION SYSTEM FOR HABITAT BEACHES 1671 FRANCIS AVENUE ATLANTIC BEACH, FL 32233 REVIDWD FOR CODE COMPLUNCE CITY O ATJ`i.,A.NrrIC E,ACH }� � � • t, f pe crit does SEE PERMITS FOR ADDITIONAL 19ln p£V ,�v an. iSS1 _ pe-,mit- REQUIREMENTS AND CONDITIONS. i dot rE�l £E�3S1�_�I ,�r c�i canl�tying.vith X11 �/h, G. ,.,...t: RE��0$Y: !�N DATE: 3 - Stats Fac Codes w!tder x•.r.oi»x-+�.r,c..w..,:.w»+�.vr.,v...s�xr, REVIEWED ILE Jacksonville Fire Prevention Div C Uy AUG 2 1 2013 ❑ NO EXCEPTIONS ❑ EXCEPTIONS AS NOTED SHEET# ANSUL DESIGN R-102 RESTAURANT INSTALLATION FIRE SUPPRESSION RECHARGE AND SYSTEM MAINTENANCE (Standard UL 300 Listed) MANUAL .i ..R sm now om Now Now own Now r r.. oil' SECTION II—SYSTEM DESCRIPTION UL EX3470 ULC EX3470 Page 2-1 7-1-09 REV 4 TOTAL SYSTEM 'There are four types of R-102 Restaurant Fire Suppression Double-Tank System Systems: ►The R-102 double-tank system is available with stainless steel 1. Single-tank System ► enclosures and consists of: 2. Double-tank System 1. ANSUL AUTOMAN Regulated Release Assembly (Electrical ' 3. Three-tank System (1 Cartridge) or Mechanical) 4. Multiple Tank System (Three Tanks or More — Multiple 2. Nitrogen Cartridge and/or Carbon Dioxide Cartridge ► Cartridges) 3. ANSULEX Low pH Liquid Fire Suppressant The type of system required for the particular installation will be 4. Enclosure or Bracket Assembly determined through the guidelines covered in "System Design:' 5. Discharge Nozzles Additional equipment which may be required to complete the sys- tem design is explained in the "System Components" section. 6. Detection Components Additional devices covered are: remote manual pull stations, 7, Additional Devices(As Required) mechanical and electrical gas shut-off valves, electrical switches, and pressure switches. The regulated release assembly contains the regulated release mechanism,agent tank,expellant gas hose for agent tank hookup, Single-Tank System and enclosure knockouts to facilitate installing expellant piping, The R-102 single-tank system is available with a stainless steel detection system, and additional equipment. enclosure and consists of: The enclosure or bracket assembly is mounted separately but 1.ANSUL AUTOMAN Regulated Release Assembly (Electrical within the guidelines of the regulated release assembly expellant or Mechanical) gas piping requirements to ensure simultaneous actuation of the system.Refer to"System Components"section for individual com- 2.Nitrogen Cartridge and/or Carbon Dioxide Cartridge ponent descriptions. 3.ANSULEX Low pH Liquid Fire Suppressant ' 4.Discharge Nozzles 5.Detection Components 6.Additional Devices (As Required) The regulated release assembly contains the regulated release mechanism,agent tank,expellant gas hose for agent tank hookup, and enclosure knockouts to facilitate installing detection system O and additional equipment. Refer to"System Components"section O O O for individual component descriptions. o FIGURE 2 00932, � OO FIGURE 1 000133 • SECTION III—SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-1 7-1-09 REV.6 EXTINGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant(1.5 gallon—Part No. "ANSUL AUTOMAN"REGULATED RELEASE ASSEMBLY 79694 or 3.0 gallon—Part No.79372)is a potassium-based solu- (MECHANICAL) tion designed for fast knock-down and suppression of grease- related fires.The agent is shipped in plastic containers which pro- NOTE:AGENT TANK MUST BE complete tank Refer to Section ,Page - .1, oORDERED SEPARATELY m vide one com charge. iVP52for o p g ( g OR SEE PAGE 3-4 0� maximum agent fill capacity.) Agent storage life expectancy is o twelve years and can be stored at a temperature of—40 OF to 130 RELEASE ► OF(-40°C to 54°C).Note:When installing agent in R-102 sys- MECHANISM ►tem,temperature range is 32 OF (0 °C)to 130 OF (54°C).The distributor must record the batch numbers and date of shipment receipt to be filed with each installation record. ��e "ANSULEX"LOW pH LIQUID FIRE SUPPRESSANT 1 [�n REGULATOR SHIPPING WT 25 LB(11 kg) FIGURE 2 000136 3.0 GALLON 1.5 GALLON SHIPPING WT 35 LB(16 kg) SHIPPING WT.19 LB(9 kg) 000136 000137 REGULATED RELEASE ASSEMBLY(ELECTRICAL) FIGURE 1 The ANSUL AUTOMAN Regulated Electrical Release Assembly REGULATED RELEASE ASSEMBLY(MECHANICAL) (Part No.429856) is identical to the mechanical version except it also contains a factory installed 120 VAC solenoid and electrical The ANSUL AUTOMAN Regulated Mechanical Release Assembly switch. (Part No. 429853) contains the regulated release mechanism, The solenoid is used to provide electrical actuation of the release expellant gas hose for agent tank hookup, and enclosure knock- mechanism.The electric switch is used to protect the solenoid by outs to facilitate installing actuation piping;expellant piping;detec- opening the circuit to the solenoid once the system is fired. tion system; and additional equipment. This regulated release Additional electrical switches can be added as required for auto- assembly is used in single,double,and multiple-tank systems and matic equipment and gas shut-off accessories,as well as initiating must be mounted to a rigid surface.The release mechanism can audible and visual alarms. be used to interconnect both the actuation and expellant gas lines as required per system design.The regulator is designed to allow "ANSUL AUTOMAN"REGULATED RELEASE ASSEMBLY ►a constant flow of gas into the tank at 110 psi (7.6 bar)when the (ELECTRICAL)` system is actuated.The agent tank must be ordered separately. In single, double, and multiple-tank stems, the provided expel- NOTE:AGENT TANK MUST BE 9 P Y P P ORDERED ao c-a lant gas hose connects the agent tank to the bottom outlet of the SEPARATELY regulator. In double and multiple-tank system configurations, the OR SEE PAGE 3-4 a back outlet of the regulator is used as an expellant gas feed for one additional tank-enclosure or tank-bracket hookup.The enclo- REGULATOR SWITCH sure contains the required knockouts to facilitate this connection. If a pressure switch is to be attached to the regulator,additional fit- tings are required. The tank is mounted within the enclosure.The tank contains an ' SOLENOID adaptor/tube assembly with a burst disc union. The burst disc helps prevent siphoning of the agent up the pipe due to significant ° temperature fluctuations in the area where the tank is located.The ►tank is stainless steel and, under normal conditions, requires hydrostatic testing every twelve years. The detection and additional equipment required per system D design are connected to the release mechanism.The enclosure SHIPPING WT.34 LS(15 kg) contains knockouts to facilitate detection and additional hookups. The system can be actuated automatically or manually.Automatic actuation occurs when a fusible link within the detection system FIGURE 3 separates in a fire condition. Manual actuation of the system OW139 occurs when personnel pull on the remote manual pull station NOTE:ANSUL AUTOMAN Regulated Electrical Release,Part No.429856,is not pull ring. intended to be used with electric detection. SECTION III—SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-2 REV.6 7-1-09 REMOTE MECHANICAL RELEASE The tank bracket is constructed of mild steel and painted red. It is The Remote Mechanical Release, Part No. 433485, is used to designed for mounting the tank in a minimum amount of space. actuate up to five (5) R-102 regulated actuators. The remote The Bracket Assembly can only be utilized with 3.0 gallon tanks mechanical release utilizes a 101-10 carbon dioxide cartridge as (Part No.429862). the actuation pressure to operate the regulated actuators. The BRACKET ASSEMBLY release is housed in a stainless steel enclosure. MOUNTING m 0 /BRACKET 0 i RELEASE MECHANISM I I i 1 I 1 1 0 � I I I i SHIPPING WEIGHT: 20 LB(9.1 kg) 1 0 0 e FIGURE 4 SHIPPING WT 7 LB(3 kg) FIGURE 6 000141 SINGLE TANK ENCLOSURE ASSEMBLY The Single Tank Enclosure Assembly(Part No.429870)is used in REGULATED ACTUATOR ASSEMBLY double and multiple-tank systems and must be mounted to a rigid The Regulated Actuator Assembly (Part No. 429850) contains the surface near the regulated release or regulated actuator assembly regulator, pneumatic actuator, expellant gas hose for agent tank its expellent gas line will be connected to. hookup, and enclosure knockouts to facilitate installing expellant pip- The enclosure is designed for mounting either a 1.5 gallon (Part ing. This assembly is used in multiple-tank systems and must be No.429864)or a 3.0 gallon tank(Part No.429862) in a minimum mounted to a rigid surface. amount of space. The regulator contains two outlets 135° apart.One outlet is used to interconnect the expellant gas hose to the enclosed agent tank. ENCLOSURE ASSEMBLY The other outlet connects an expellant gas line to an additional enclosure or bracket assembly.The regulator is designed to allow a constant flow of nitrogen into each agent tank connected (two NOTE:AGENT TANK MUST BE ORDERED 0 ►tanks maximum)at 110 psi (7.6 bar). SEPARATELY 0 The pneumatic actuator is designed to uncture the expellant as OR SEE PAGE 3-4 P 9 P P 9 a cartridge seal upon receiving pressure from the regulated release assembly actuation piping.The enclosure contains a knockout to 0 facilitate distribution piping hookup. 0 REGULATED ACTUATOR ASSEMBLY MOUNTING -� ENCLOSURE NOTE:AGENT TANK MUST BE ORDERED PNEUMATIC SEPARATELY ACTUATOR h9�at! OR SEE PAGE 3-4 ASSEMBLY SHIPPING WT. 13 LB(6 kg) REGULATOR p SII I O I FIGURE 5 000,42 RED PAINTED BRACKET ASSEMBLY I SHIPPING WT. The Bracket Assembly (Part No. 429878) is used in double and 19 LB(9 kg) multiple-tank systems and must be mounted to a rigid surface near the regulated release assembly or regulated actuator assembly FIGURE 7 that its expellant gas line will be connected to. 000113 SECTION III—SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-5 7-1-09 REV.8 GAS CARTRIDGES NOZZLES The R-102 system uses gas cartridges to store nitrogen or carbon There are 11 types of discharge nozzles each designed to distrib- dioxide expellant gases under pressure until the system is actuat- ute the liquid agent in a uniform pattern throughout the hazard ed,at which time the cartridge seal is punctured and the released area: gas expels liquid agent from one or more tanks through the dis- 1. 1W Nozzle 7. 245 Nozzle charge piping and out the discharge nozzles. 2. 1N Nozzle 8. 260 Nozzle Four nitrogen gas cartridges and three carbon dioxide gas car- 3. 1/2N Nozzle 9. 290 Nozzle tridges are available as shown in Figure 13. 4. 3N Nozzle 10. 2120 Nozzle Cartridges noted as TC/DOT are both Transport Canada(TC)and 5. 2W Nozzle 11. 1 F Nozzle Department of Transportation (DOT) approved. Cartridges noted 6. 230 Nozzle as DOT are Department of Transportation approved only. Cartridge selection options are provided in Section IV under Tank Although these nozzles are similar in appearance and have 9 P P certain common parts, the tip of each nozzle is designed for a and Cartridge Requirements. specific application and must only be used in those areas. See NITROGEN GAS CARTRIDGES Nozzle Application Chart in Section IV — System Design, for individual nozzle usage. 3/8—18 NPT FEMALE THREAD 1 1 ► -lT 17114 IN, I 11 5/8 IN. (43.8 cm) I 7 7/8 IN. (29.5 cm) (3 114 m) INTERNAL CUP (31.1 cm) STRAINER ►(20cm) 1 INSIDE •�'I _I RECESS FORBLO > yyy��//��// yy 2 OFF 1/2 1N. 2 112 IN. 4 3/16 IN. 3 9/16 IN. CAP VLOOP XAAA_A VENDOR (6.4 cm) (6.4 cm) (10.6 cm) (9 cm) CODE LT-20-R LT-30-R DOUBLE-TANK LT-A-101-30 NOZZLE (IF PRESENT) CARTRIDGE CARTRIDGE CARTRIDGE CARTRIDGE STAMPING ► 000145 000146 000147 000148 FIGURE 14 CARBON DIOXIDE CARTRIDGES 00WW Nozzle Identification Chart ► Note:See Component Index for nozzle package shipping assem- } P. bly part numbers. 11 sre IN. Nozzle 9IN 7718 IN. (29.5 cm) Nozzle Nozzle Nozzle' Flow (22.9 cm) (20 cm) ►� Part No. Stamping NQL Nozzle Material �1 _ � 1W Nozzle 419336 1W" 1 Chrome-Plated Body �� _ ► 1N Nozzle 419335 1 N" 1 Chrome-Plated Body 21N. 21/21N. 21/2 IN. 1/2N Nozzle 419334 112N 1/2 Chrome-Plated Body (5.1 cm) (6.4 cm) (6.4 cm) ► 3N Nozzle 419338 3N 3 Chrome-Plated Body 101-10 CARTRIDGE 101-20 CARTRIDGE 101-30 CARTRIDGE ► 9W149 000150 000151 2W Nozzle 419337 2W 2 Chrome-Plated Body FIGURE 13 230 Nozzle 419339 230 2 Chrome-Plated Body Additional cartridge shipping assemblies are available for 245 Nozzle 419340 245 2 Chrome-Plated Body European and Australian requirements. 260 Nozzle 419341 260 2 Chrome-Plated Body ►Cartridge European Australian TC/DOT 290 Nozzle 419342 290 2 Chrome-Plated Body Description Part No. Part No. Part No. 2120 Nozzle 419343 2120 2 Chrome-Plated Body LT-20-R 428440 428948 423429 1 F Nozzle 419333 1F 1 Chrome-Plated Body LT-30-R 428441 426553 423435 Nozzle stamping may contain an additional letter indicating a vendor's code. Double Tank 428446 426563 423493 ►**Stainless steel versions are available in the 1 W nozzle(Part No.432527)and LT-A-101-30 428442 426555 423491 ► the 1N nozzle(Part No.435672). 101-10—CO2 428443 N/A 423439 SILICONE LUBRICANT 101-20—CO2 428445 N/A 423441 Dow Corning Compound 111, Part No. 78112, is available in a 101-30—CO2 428444 N/A 423443 5.3-ounce tube.Compound has excellent qualities for sealing and ►Note:For 101-10 cartridge, Part No.15850 is DOT only. lubricating system components. SECTION III—SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-6 REV.7 7-1-09 SWIVEL ADAPTOR CONDUIT OFFSET ASSEMBLY ►The Swivel Adaptor Assembly consists of a swivel nut,swivel body 'The conduit offset assembly, Part No.435961, is used to change and swivel ball.All are chrome-plated.The swivel adaptor allows direction of the wire rope on detection, mechanical gas valve,and any nozzle to be rotated approximately 30°in all directions.Swivel remote pull station lines.The conduit offset assembly can only be Adaptors must be ordered as a Swivel Adaptor Shipping used in the area where the conduit attaches to the regulated ►Assembly, Part No.423572,which contains 25 Swivel Adaptors or release assembly. When using the conduit offset assembly, the ►Part No.419385,which contains 9 Swivel Adaptors. maximum number of pulley elbows is still allowed.The Conduit ►Offset Shipping Assembly, Part No.436063,consists of 6 conduit 3/8-18 NPT offsets. FEMALETHREAD CONDUIT COUPLING \ JP3/8-18NPT CONDUIT THREAD I OFFSET 30 DEGREE ROTATION FIGURE 15 OODD03 CONDUIT RUBBER BLOW-OFF CAPS CONNECTOR ►The Rubber Blow-Off Cap helps keep the orifice of the nozzle free of grease or other substances that could interfere with agent dis- tribution.A retaining strap attaches the blow-off cap to the nozzle. FIGURE 18 Rubber Blow-Off Caps must be ordered as a Shipping Assembly, W0153 ►Part No. 77695, which contains 50 blow-off caps, or Part No. ►77411,which contains 12 blow-off caps. "QUIK-SEAL"ADAPTOR The"Quik-Seal"adaptor is a listed mechanical bulkhead fitting that produces a liquid-tight seal around both distribution piping and detection conduit which runs through restaurant hoods and ducts. The "Quik-Seal" adaptor accepts threaded pipe or conduit.The ►adaptor is available for 1/4 in. (Part No. 78196), 3/8 in. (Part No. ►77285), 1/2 in.(Part No.77287),or 3/4 in.(Part No.77289)pipe or conduit sizes.When using with EMT conduit, a conduit connector must be installed in each end of the adaptor. The "Quik-Seal" Adaptor Shipping Assembly must be ordered as stated below: 01 Shipping FIGURE 16 Assembly Hole Size 000M Size Part No. Qty. Required CB METAL BLOW-OFF CAP 1/4 in. 78196 24 3/4 in. The CB Metal Blow-off Cap Package, Part No.433208,is used for 3/8 in. 77285 24 1 1/8 in. all high temperature environments. The metal blow-off cap con- 1/2 in. 77287 24 1 1/8 in. tains a special O-ring placed inside the cap which integrates with 3/4 in. 77289 24 1 3/8 in. the nozzle to create a seal and to help hold the blow-off cap in ► ADAPTOR BODY position. GASKET The CB Metal Blow-Off Cap Package, Part No.433208, contains LOCKWASHER 10 blow-off caps. Also available is a 10 pack of CB Stainless Steel Blow-Off Caps, NUT Part No.434707. ►A 10 pack of Metal Blow-Off Cap O-rings, Part No.551530,is also FIGURE 19 OW1`4 .available. STAINLESS STEEL WIRE METAL CAP FIGURE 17 W7&13 SECTION III—SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-7 7-1-09 REV.6 "COMPRESSION-SEAL"ADAPTOR ►COCKING LEVER/LOCK BAR This adaptor is a mechanical bulkhead fitting that produces a The cocking lever is a component required to cock (arm) both the liquid-tight seal around pipe and conduit when installing distribu- mechanical/electrical ANSUL AUTOMAN release and the mech- tion piping and detection conduit through restaurant hoods and anical gas valve.After the ANSUL AUTOMAN is cocked (armed), ducts. The "Compression-Seal" adaptor is a straight-through the lock bar must be inserted to eliminate the accidental firing of design requiring no cutting or threading of conduit or pipe. The the release mechanism.These components are available as either ►adaptor is available for pipe sizes of 1/4 in.(Part No.79149),3/8 in. an individual shipping assembly or a shipping assembly containing (Part No.79151), 1/2 in.(Part No.79147),and EMT conduit size of both. Listed below are the various shipping assembly part num- 1/2 in. (Part No. 79153). Each "Compression-Seal" Adaptor bers. Shipping Assembly must be ordered as stated below: Part No. Description Shipping Assembly Hole Size 435603 Short Handle Cocking Lever only Size Part No. Qty. Required (Mechanical/Electrical ANSUL AUTOMAN) 1/4 in.Pipe/1/2 in.tube 79149 24 3/4 in. 435790 Short Handle Cocking Lever with Lock Bar 3/8 in. Pipe/5/8 in.tube 79151 24 1 1/8 in. (Mechanical/Electrical ANSUL AUTOMAN) 1/2 in.Pipe 79147 24 1 1/8 in. 14995 Long Handle Cocking Lever only 1/2 in. EMT Conduit 79153 24 1 1/8 in. (Mechanical/Electrical ANSUL AUTOMAN) 15618 Long Handle Cocking Lever with Lock Bar COMPRESSION NUT (Mechanical/Electrical ANSUL AUTOMAN) 26310 Cocking Lever only(ANSUL AUTOMAN II-C) ADAPTOR BODY GASKETA LOCKWASHER 416018 Cocking Lever only(Mechanical Gas Valve) NUT14985 Lock Bar ' FIGURE 20 Short Handle Cocking Lever 000155 "HOOD SEAL"ADAPTOR ASSEMBLY This adaptor is a mechanical bulkhead fitting that produces a liq- uid-tight seal around 112 in.EMT conduit when installing the detec- tion line through restaurant hoods and duct.The adaptor accepts a high temperature pulley elbow and, when used, correctly posi- tions the elbow or conduit in line with the conduit adaptor hole in the detector bracket.The"Hood Seal"eliminates the need for mul- tiple elbows when penetrating the top of a hood when installing the Requires a crescent wrench or open end/box wrench detection line."Hood Seal"Adaptors are available in quantities of 6 as Shipping Assembly Part No.423253. Long Handle Cocking Lever /SEAL NUT SEAL i WASHER ADAPTOR BODY—MGAS;KIT PULLEYELBOW (NOT PAOF ASSE ) Lock Bar USE ONLY PULLEY ELBOW,PART NO.423250 FIGURE 21 ooa155 ►REDUCING COUPLING The reducing coupling, Part No.436228,is made of stainless steel material with 3/8 in.x 1/2 in. NPT inlet threads. If necessary, the reducing coupling can be utilized when installing the Agent FIGURE 23 Distribution Hose Line Kit, Part No. 435982. Two couplings are 008.'125 required per Agent Distribution Hose. 114 IN. —► (3.3 cm) CEO 1 3116 IN. (3.0 cm) FIGURE 22 ► 008324 SECTION III—SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-8 REV.8 7-1-09 DETECTORS PULLEYTEE The detector consists of three basic components:the bracket,link- The Pulley Tee(Part No.427929) is used to change the direction age, and fusible link. (Fusible links are not included and must be of two wire ropes by 900.It must be used in areas where the tem- ordered separately.)The bracket holds the entire assembly to the peratures are within the range of 32 OF to 130 OF(0°C to 54°C). mounting surface.The linkage is used to support the fusible link. Pulley tees can be used in mechanical gas valve actuation lines The fusible link is designed to separate at a specific temperature and remote manual pull station lines. Pulley tees cannot be used and release the wire rope,thereby actuating the regulated release within a detection line. mechanism. ►The scissor style detector allows the wire rope to be strung com- pletely through the detection system conduit and brackets first and O O the detector linkage assemblies are then clipped on later. P.The detector consists of two types of assemblies: ►The Terminal Detector(Part No.435546)includes a test link and is placed last in a series of detectors.This detector is sometimes ► FIGURE 26 referred to as the end-of-line detector and is thus named because 000"7 it is at the point at which the wire rope"terminates,"or is anchored at the detector bracket.Only one terminal detector is required per STAINLESS STEEL CABLE detection system. The 1/16 in.stainless steel cable is run from the terminal detector, ►The Series Detector(Part No.435547)is any detector located in- through conduit, all series detectors and pulley elbows, and into line between the regulated release assembly and the terminal the regulated release mechanism trip lever.When any fusible link 0 detector. separates, the tension on the cable is relaxed, and the trip lever ►When using Part No.435546 and 435547 detectors, a total of 15 actuates the regulated release mechanism.The cable can also be detectors can be in one detection system:14 series detectors,Part used for mechanical gas valves and remote manual pull stations. ►No.435547 and 1 terminal detector, Part No.435546. The cable is available in 50 ft (15 m) (Part No. 15821) and 500 ft (152.4 m) (Part No.79653) lengths. ►Note:Series Detector, Part No.435547, is also available as Part ►No.435548,25/Pkg. SCISSOR STYLE-PART NO.435546 AND 435547 4 BRACKET LINKAGE QQ FUSIBLE LINK ► FIGURE 24 000159 PULLEY ELBOWS There are two types of pulley elbows used to change the direction of the wire rope by 90°.ANSUL recommends for temperatures not in excess of 700 OF (371 °C). Part No. 415670 has socket ends with set screws for 1/2 in.conduit, and Part No.423250 has com- pression ring ends also for 1/2 in.conduit.Pulley elbows must be ordered in quantities of 50 as Shipping Assembly Part No.415671 (socket end type)and Part No.423251 (compression end type). PART NO.415670 PART NO.423250 0 000160 000161 ► FIGURE 25 SECTION III-SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-9 7-1-09 REV.5 REMOTE MANUAL PULL STATION MECHANICAL GAS VALVES The remote manual pull station (Part No. 434618 or 435960) is The mechanical gas valves are designed to shut off the flow of gas made out of a molded red composite material. The red color to the appliances upon actuation of the regulated release assem- makes the pull station more readily identifiable as the manual bly.The valves are available in sizes of 3/4 in., 1 in., 1 1/4 in.,1 1/2 means for fire suppression system operation.The pull station is in.,and 2 in.ANSUL style;and 2 1/2 in.and 3 in.ASCO style.The compatible with the ANSUL Flexible Conduit.The molded manual valves are rated for natural and LP gas.Both styles are UL Listed pull station should be mounted at a point of egress and positioned 'and includes the air cylinder,tubing, and fittings, Part No. 15733, at a height determined by the authority having jurisdiction. Trim for connection to the release mechanism. Rings, Part No.427074(pack of 10),are available. Maximum Part No.434618(Without Wire Rope) Part Operating Part No.435960(With 50 ft(15.2 m)of Wire Rope) No. Description Pressure 55598 3/4 in.Gas Valve(ANSUL) 10 psi(0.69 bar) ca'"' 55601 1 in.Gas Valve(ANSUL) 10 psi (0.69 bar) QonO0 o 55604 1 1/4 in.Gas Valve(ANSUL) 10 psi(0.69 bar) W55607 1 1/2 in.Gas Valve(ANSUL) 10 psi (0.69 bar) 55610 2 in.Gas Valve(ANSUL) 10 psi(0.69 bar) x(16 25937 2 1/2 in.Gas Valve(ASCO) 5 psi(0.35 bar) 25938 3 in.Gas Valve(ASCO) 5 psi(0.35 bar) ' Flow Capacity BTU/HR,at 1 in.P.D. (CFH) 0.64 SP GR FIGURE 227 Pipe Size P.D.1 in.WC 1000 BTU/ft3 (inches) 0.64 SP GR Natural Gas FLEXIBLE CONDUIT 3/4 751 751,000 Flexible conduit allows for quicker installations and the conve- 1 1288 1,288,000 nience of being able to route the cable over, under and around 1 1/4 1718 1,718,000 obstacles. Flexible conduit can be used as a substitute for stan- 1 1/2 2630 2,630,000 dard EMT conduit or can be used with EMT conduit.Flexible con- 2 4616 4,616,000 duit can be used only with the Molded Manual Pull Station, Part 21/2 5700 5,800,000 No.434618, and mechanical gas valve installations.The Flexible 3 7100 7,300,000 Conduit comes in a 500 ft (152.4 m) length, Part No.434525, or To calculate gas flow for other than 1 inch p.d.: together with 500 ft(152.4 m)of wire rope, Part No.435959. Also available is a Flexible Conduit Strain Relief (50-pack), Part New cfh=(cfh at 1 inch)x new p. . No.435979. To calculate gas flow for other than 0.64 SP GR: A 50-pack of Flexible Conduit Inserts, Part No. 434347, is also New cfh=(cfh at 0.64)x0.64 available. New SP GR .Note:Flexible conduit cannot be used in detection systems. A B C Valve Size in. (mm) in. (mm) in. (mm) 3/4 in. 33/4 (95.3) 63/8 (161.9) 51/2 (139.7) 1 in. 33/4 (95.3) 63/8 (161.9) 51/2 (139.7) 1 1/4 in. 47/8 (123.8) 73/8 (187.3) 6318 (161.9) 1 1/2 in. 4 7/8 (123.8) 73/8 (187.3) 63/8 (161.9) 2 in. 57/8 (149.2) 77/8 (200.0) 611/16 (169.9) 2 1/2 in. 713/16 (198.4) ----- 91/16 (230.2) 3 in. 725/32 (197.6) ----- 91/16 (230.2) ► c c I --CJI + 8 I , A-d 3/4 IN.THRU 2 IN. 2 12 IN.THRU 3 IN. 004" 0042M ► FIGURE 28 SECTION III-SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-10 REV.4 7-1-09 ELECTRICAL GAS VALVES MANUAL RESET RELAY The electrical gas valves are designed to shut off the flow of either The Manual Reset Relay, Part No.426151,is required when using natural or LP gas to the appliances upon actuation of the regulat- an electrical gas valve shut-off system.After the electric gas valve ed release assembly.The valves are available in sizes of 3/4 in., has closed, either due to system actuation or power failure, the 1 in., 1 1/4 in., 1 112 in., 2 in.,2 1/2 in., and 3 in.The valve is held valve cannot be re-opened, allowing gas to flow, until the reset open by an energized solenoid and upon system actuation, the relay button is manually pressed, re-energizing the circuit. The switch contacts in the regulated release assembly open, thus de- reset relay is available 120 VAC.The manual reset relay is also energizing the circuit to the gas valve solenoid, causing the valve recommended for electrical shut down. to close.Valves are available in 120 VAC and are UL Listed. Part Max.Operating No. Description Pressure 13707 3/4 in.Solenoid Gas Valve (ASCO) 25 psi (1.7 bar) 13708 1 in.Solenoid Gas Valve (ASCO) 25 psi (1.7 bar) 550360 1 1/4 in.Solenoid Gas Valve(ASCO) 25 psi (1.7 bar) 13709 1 1/2 in.Solenoid Gas Valve(ASCO) 25 psi (1.7 bar) 13710 2 in.Solenoid Gas Valve (ASCO) 25 psi (1.7 bar) 550363 2 1/2 in.Solenoid Gas Valve(ASCO) 5 psi (0.35 bar) 17643 3 in.Solenoid Gas Valve(ASCO) 5 psi (0.35 bar) ► Flow Capacity BTU/HR, at 1 in.P.D. ► FIGURE 30 (CFH) 0.64 SP GR 000087 Pipe Size P.D. 1 in.WC 1000 BTU/ft3 (inches) 0.64 SP GR Natural Gas ELECTRICAL SWITCHES 3/4 264.96 247,500 The electrical switches are intended for use with electric gas 1 1091.01 1,119,000 valves, alarms, contactors, lights, contractor supplied electric 1 1/4 1662.49 1,730,000 power shut-off devices and other electrical devices that are 1 1/2 1818.35 1,900,000 designed to shut off or turn on when the system is actuated. 2 3117.18 3,251,000 Switches are available in kits: One Switch Kit, Part No. 423878, 21/2 6078.49 5,821,000 Two Switch Kit, Part No. 423879, Three Switch Kit, Part No. 3 7169.51 7,430,000 423880,and Four Switch Kit,Part No.423881.Mounting hardware To calculate gas flow for other than 1 inch p.d.: and 12 in. (305 mm) long wire leads are provided with each kit. Each switch has a set of single-pole, double-throw contacts rated New cfh =(cfh at 1 inch)x ✓new p.d. at: To calculate gas flow for other than 0.64 SP GR: UL/cUL/CSA Rating ENEC Rating New cfh =(cfh at 0.64)x V 0.64 250 VAC, 21 A Resistive IE4T105p Approved ► New SP GR 250 VAC, 2 HP 250V, 21A Resistive 125 VAC, 1 HP 8A Motor Load Valve A B Size in. (mm) in. (mm) ,/ N.C. COMMON � 3/4 in. 35/16 (81.0) 35/8 (92.1) 1 in. 5 (127.0) 627/32 (173.8) 1 1/4 in. 713/16 (198.4) 729/32 (200.8) 0 0 1 112 in. 5 (127.0) 5 19/32 (142.1) N C. 2 in. 63/32 (78.6) 5 15/16 (150.8) 2 112 in. 7 13/16 (198.4) 729/32 (200.8) 3 in. 7 13/16 (198.4) 729/32 (200.8) ► FIGURE 31 001612 B }. 4�1 ---+ A ' FIGURE 29 004210 SECTION III—SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-11 7-1-09 REV. 1 ALARM INITIATING SWITCH ML STYLE Fusible Link To Be Used The Alarm Initiating Switch Kit, Part No. 428311, can be field Fusible Shipping Where mounted within the ANSUL AUTOMAN release.This switch must Link Assembly Temperature Temperature be used to close a supervised alarm circuit to the building main fire parLND� pmt No. Rating Does Not Exceed alarm panel when the ANSUL AUTOMAN release actuates.This 550368(1) 551522(10) 165°F °C) 100 °F (38°C) (74 action will signal the fire alarm panel that there was a system actu- 550365(1) 551523(10) 212°F((74 °C) °C) 150 °F (66 ation in the kitchen area. The switch kit contains all necessary 550366(1) 551524(10) 280°F(138°C) 225 °F((66°C) mounting components along with a mounting instruction sheet. 550009(l) 551525(10) 360°F(182°C) 290 °F(143°C) The switch is rated 50 mA,28 VDC. 550367(l) 551526(10) 450°F(232°C) 360 °F(182°C) SPACER 56816(l) 551527(10) 500°F(260°C) 400°F(204°C) TOWARD ANSUL WHEN SPACER AND 56816(l) 73867 25 500°F 260°C 400°F 204°C AUTOMAN� / SWITCH ARE PROPERLY ( ) ( ) ( ) ( ) IJ MOUNTED,THIS DIVIDER MUST BE BETWEEN THE O O N.O.AND N.C.TERMINALS \• 0. /COM wsx. N.O. TEMPERATURE 7 RATING STAMPED ON �\ `\ �_'C9 FUSIBLE LINK BODY \ O `\ \ I\` N.C. ,\ \ K0TY00 ML STYLE171 ALARM INITIATING FIGURE 34 SWITCH ' FIGURE 32 MAXIMUM REGISTERING THERMOMETER W4880 ►The Maximum Registering Thermometer, Part No. 15240,may be used to indicate the highest normal temperature for the protected REGULATOR TEST KIT area.Once this is established,the correct rated fusible link can be �► The Test Kit Assembly(Shipping Part No.56972)is required to test -chosen. Other methods for determining maximum temperatures the regulator setting and nitrogen flow during 12-year maintenance ►may be used. examinations. This will ensure that the regulator is functioning properly. HOSE/GROMMET PACKAGE The Hose/Grommet Package,Part No.418511,consists of a 24 in. rubber hose and 2(two)grommets.This package is required when ►expellant gas hose is routed outside the ANSUL AUTOMAN Regulated Release, Regulated Actuator, and/or tank enclosure ►assemblies. ' FIGURE 33 OW169 FUSIBLE LINK Select correct UL Listed fusible link(s)for installation in detector(s) according to the temperature condition chart below: K STYLE Fusible Link To Be Used Fusible Shipping Where Link Assembly Temperature Temperature Part No. Part No. Rating Does Not Exceed 415739(l) 415739(l) 165°F (74°C) 100-F (38-C) 415740(l) 415740(l) 212°F(100°C) 150°F (66°C) 415741 (1) 415744(25) 280°F(138°C) 225°F(107°C) 415742(l) 415745(25) 360°F(182°C) 290°F(143°C) 415743(l) 415746(25) 450°F(232°C) 360°F(182°C) SECTION III—SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-12 REV.1 7-1-09 ►IN-LINE BURST DISC ASSEMBLY(MANIFOLDED SYSTEMS NOZZLE AIMING DEVICE ONLY) The Nozzle Aiming Device, Part No.431992, is available to prop- The in-line burst disc assembly is required to eliminate the siphon- erly aim each nozzle to the correct aiming point. The device ing of the agent up the pipe during extreme temperature variations. clamps to the nozzle and emits a small laser light that reflects on In addition to eliminating the siphoning effect, the common in-line the surface that it is aiming at.The nozzle can then be rotated to burst disc assembly eliminates the possibility of one or more indi- point at a predetermined aiming point and then tightened to hold vidual discs located in the tank adaptor from failing to burst.The that angle.The aiming device adaptor attaches to the nozzle.The assembly consists of a stainless steel body which houses the shipping assembly consists of the aiming device and the adaptor. burst disc.When utilizing this assembly in a manifolded system, it is necessary to modify(remove)the burst disc located in all of the R-102 tank adaptors in the system.The in-line burst disc assem- bly is to be mounted as close to the tank outlet as possible.After system discharge,the assembly must be disassembled and a new burst disc installed. • ADAPTOR Part No. Description NOZZLE 416970 In-Line Burst Disc Assembly AIMING 417911 Burst Disc(Pack of 10) DEVICE FIGURE 37 1.54 IN. 1 00 520 - -- (3.9 Cm) STAINLESS STEEL BRAIDED ACTUATION HOSE The Stainless Steel Actuation Hose is used to connect the actua- tion line compression tees between each pneumatic actuator.The hose has the same thread, 7/16-20, as the fittings.The actuation hose allows flexibility between the AUTOMAN and each regulated actuator. I Hose Part No. Length Couplings 31809 16 in.(41 cm) 7/16-20 x 7/16-20 Females I ; 32335 20 in.(51 cm) 7/16-20 x 7/16-20 Females 32336 24 in.(61 cm) 7/16-20 x 7/16-20 Females 430815 42 in. (107 cm) 7/16-20 Female x 1/4 in.NPT \ Fitting •. ��� Part No. Description RED SIDE OF BURST _ _ / 31810 Male Elbow(7/16-20 x 1/4 in.NPT) DISC TO - ! 31811 Male Tee(7/16-20 x 7/16-20 x 1/4 in.NPT) PART NO.NO. ADAPTOR,,PART 417707 415371 Tee(7/16-20 x 1/8 in.Male NPT x 1/8 in.Female NPT) FIGURE 35 32338 Male Straight Connector(7/16-20 x 1/4 in.NPT) 008383 25627 1/4 in.Check Valve 1/4 IN.CHECK VALVE The 1/4 in.check valve, Part No.25627, blocks the flow of actua- tion gas from the actuator that was actuated to the actuator(s)that was not actuated.This prevents actuation gas from escaping from 7/16-20 7/16-20 an open actuator which may have had the cartridge removed. , FIGURE 38 00N33 KIM CHECK VALVE PART NO.25627 ►AGENT DISTRIBUTION HOSE AND RESTRAINING CABLE KIT The Agent Distribution Hose and Restraining Cable Kit, Part No. 435982, consists of a 5 ft(1.5 m) long Agent Distribution Hose, a 3 ft (0.9 m) long Restraining Cable, and a Restraining Cable Hardware Package.The Agent Distribution Hose can be utilized with castered cooking appliances with castered supports found in commercial kitchens.The hose allows for movement of the appli- 1/4 IN.NPT ance for cleaning without having to disconnect any fire suppres- (0.6 cm) 2 IN. (5.1 cm) Sion system discharge piping. Note:The Agent Distribution Hose is authorized for use with only ► UL Listed ANSUL Wet Chemical Restaurant Fire Suppression FIGURE 36 ,.Systems. 000899 SMI SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-28 REV.6 7-1-09 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct,plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Minimum Nozzle Tip Maximum Hazard Nozzle Nozzle Nozzle Stamping— Hazard Dimensions Quantity Heights Part No. Flow No._ Duct or Transition Length—Unlimited 1 — 430912 1W (Single Nozzle) Perimeter—50 in.(127 cm) Diameter—16 in.(40.6 cm) Duct or Transition Length—Unlimited 1 — 419337 2W (Single Nozzle) Perimeter—100 in.(254 cm) Diameter—31 7/8 in.(81 cm) Duct or Transition Length—Unlimited 2 — 419337 2W (Dual Nozzle) Perimeter—150 in.(381 cm) Diameter—48 in.(122 cm) Electrostatic Precipitator Individual Cell 1 — 419334 1/2N (At Base of Duct) Plenum Length—10 ft(3.1 m) 1 — 419335 1N (Horizontal Protection) Plenum Length—6 ft(1.8 m) 1 — 430192 1W (Horizontal Protection) Width—4 ft(1.2 m) 1 — 419336 1W Plenum Length—4 ft(1.2 m) 1 — 419336 1W llliiiw (Vertical Protection) Width—4 ft(1.2 m) Fryer(Split or Maximum Size Non-Split Vat) (without drip board) 14 in.(36 cm)x 15 in.(38 cm) 1 13—16 in. 419342 290 Low Proximity (33—41 cm) Fryer(Split or Maximum Size Non-Split Vat) (without drip board) 14 1/2 in.(37 cm)x 14 in.(36 cm) 1 16—27 in. 419342 290 Medium Proximity (41 —69 cm) Fryer(Split or Maximum Size Non-Split Vat)* (without drip board) 15 in.(38 cm)x 14 in.(36 cm) High Proximity 1 27—47 in. 419339 230 Medium Proximity 1 20—27 in. 419340 245 Fryer(Non-Split Vat Only) Maximum Size (without drip board) 19 1/2 in.(49.5 cm)x 19 in.(48.2 cm) High Proximity 1 21 —34 in. 419338 3N Low Proximity 1 13—16 in. 419342 290 Maximum Size (without drip board) 18 in.(45.7 cm) x 18 in.(45.7 cm) High Proximity 1 25—35 in. 419338 3N (64-89 cm) For multiple nozzle protection of single fryers,see detailed information on Pages 4-10 and 4.11. SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-29 7-1-09 REV.6 '11111lW Nozzle Application Chart (Continued) Minimum Nozzle Tip Maximum Hazard Nozzle Nozzle Nozzle Stamping— Hazard Dimensions Quantity Heights Part No.- Flow No._ Fryer(Non-Split Maximum Size Vat Only)' (with drip board) 21 in.(53 cm)x 14 in.(36 cm) (Fry Pot must not exceed 15 in.x 14 in. (38 cm x 36 cm)) High Proximity 1 27—47 in. 419339 230 Medium Proximity 1 20—27 in. 419340 245 Maximum Size (with drip board) 25 3/8 in.(64.4 cm) x 19 1/2 in.(49.5 cm) (Fry pot side must not exceed 19 1/2 in. (49.5 cm)x 19 in. (48.2 cm) High Proximity 1 21 —34 in. 419338 3N Low Proximity 1 13—16 in. 419342 290 Maximum Size (with drip board) 18 in.(45.7 cm) x 27 3/4 in.(70.5 cm) High Proximity 1 25—35 in. 419338 3N (64-89 cm) Fryer(Split or Maximum Size Non-Split Vat) (with drip board) 14 in.(36 cm)x 21 in.(53 cm) 1 13—16 in. 419342 290 Low Proximity (33—41 cm) Fryer(Split or Maximum Size Non-Split Vat) (with drip board) 14 1/2 in.(37 cm)x 26 1/2 in.(67 cm) 1 16—27 in. 419342 290 Medium Proximity (41 —69 cm) ►Range Longest Side(High Proximity) 1 30—40 in. 419335 IN 32 in.(81 cm) (76—102 cm) Area—384 sq.in. (2477 sq cm) ► Longest Side(Low Proximity) 1 15—20 in. 419335 IN 24 in.(61 cm) (38—51 cm) Area—432 in.2 ► (2787 cm2) Longest Side 40—48 in. 419333 IF 28 in.(71 cm) (102—122 cm) Area—336 sq in. (With Backshelf) (2168 sq cm) Longest Side(High Proximity) 1 40—50 in. 419340 245 28 in.(71 cm) (102—127 cm) Area—672 sq in. (4335 sq cm) Longest Side (Medium Proximity) 1 30—40 in. 419341 260 32 in.(81 cm) (76—102 cm) Area—768 sq in. (4955 sq cm) D.' For multiple nozzle protection of single fryers,see detailed information on Pages 4-10 and 4-11. SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-30 REV.4 7-1-09 Nozzle Application Chart (Continued) Minimum Nozzle Tip Maximum Hazard Nozzle Nozzle Nozzle Stamping— Hazard Dimensions Ouant*X Heights FLrLN4. Flow No"_ Range(Continued) Longest Side(Low Proximity) 2 15—20 in. 419342 290 36 in.(91 cm) (38—51 cm) Area—1008 sq in. (6503 sq cm) Griddle Longest Side(High Proximity) 1 30—50 in. 419341 260 48 in.(122 cm) (76—127 cm) Area—1440 sq in. (perimeter (9290 sq cm) located) Longest Side(High Proximity) 1 30—50 in. 419342 290 30 in.(76 cm) (76—127 cm) Area—720 sq in. (center located) (4645 sq cm) ► Longest Side(High Proximity) 1 35 — 40 in. 419335/435672 1N/1 NSS 36 in.(91 cm) (89—102 cm) Area—1080 sq in. (perimeter located) (6968 sq cm) Longest Side 1 20—30 in. 419342 290 (Medium Proximity) (51 —76 cm) 48 in.(122 cm) (perimeter Area—1440 sq in. located) (9290 sq cm) ► Longest Side(Low Proximity) 1 15—20 in. 4193336 1W 26 in.(66 cm) (38—51 cm) Area—533 in.2 (center located) (3439 cm2) Longest Side(Low Proximity) 1 10—20 in. 419337 2W 36 in.(91 cm) (25—51 cm) Area—1080 in.2 (perimeter located) ► (6968 cm2) Longest Side(Low Proximity) 1 10—20 in. 419343 2120 48 in.(122 cm) (25—51 cm) Area—1440 sq in. (perimeter (9290 sq cm) located) ►Chain Broiler* Longest Side—34 in.(86 cm) 2 10—26 in. 419336/432527 1 W/1 WSS (Overhead Protection) Area—1088 sq in. (25—66 cm) (7019 sq cm) ►Chain Broiler Length—43 in.(109 cm) 2 1 —3 in. 419335/435672 1 N/1 NSS (Horizontal Protection) Width—31 in.(79 cm) (3—8 cm) ►Gas-Radiant Char-Broiler Longest Side—36 in.(91 cm) 1 15—40 in. 419335/435672 1 N/1 NSS Area—864 sq in. (38—102 cm) (5574 sq cm) ►Electric Char-Broiler Longest Side—34 in.(86 cm) 1 20—50 in. 419335/435672 1 N/1 NSS Area—680 sq in. (51 —127 cm) (4388 sq cm) ►Lava-Rock Broiler Longest Side—24 in.(61 cm) 1 18—35 in. 419335/435672 1 N/1 NSS Area—312 sq in. (46—89 cm) (2013 sq cm) ►Natural Charcoal Broiler Longest Side—24 in.(61 cm) 1 18—40 in. 419335/435672 1 N/1 NSS Area—288 sq in. (46—102 cm) (1858 sq cm) SECTION IV – SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-31 7-1-09 REV.7 ikw Nozzle Application Chart (Continued) Minimum Nozzle Tip Maximum Hazard Nozzle Nozzle Nozzle Stamping– Hazard Dimensions Quantity Heights Part No. Flow No.— Lava-Rock or Natural Longest Side–30 in.(76 cm) 1 14–40 in. 419338 3N Charcoal Char-Broiler Area–720 sq in. (36–102 cm) (4645 sq cm) Wood Fueled Char-Broiler Longest Side–30 in.(76 cm) 1 14–40 in. 419338 3N Area–720 sq in. (36–102 cm) (4645 sq cm) Upright Broiler Length–32.5 in.(82.5 cm) 2 – 419334 1/2N Width–30 in.(76 cm) ►Salamander Length–29 in.(74 cm) 1 – 419335 1N Broiler Width–16 in.(41 cm) Length–31 in.(79 cm) 1 – 419333 1F Width–15 in.(38 cm) Length–31 in.(79 cm) 1 – 419335 1N ' Width–15 in.(38 cm) Wok 14 in.–30 in.(36–76 cm) 1 35–45 in. 419341 260 Diameter (89–114 cm) 3.75–8.0 in.(9.5–20 cm) Deep ► 11 in.–24 in.(28–61 cm) 30–40 in. 419335/435672 1 N/1 NSS Diameter (76–102 cm) 3.0–6.0 in.(8–15.2 cm) Deep Minimum chain broiler exhaust opening—12 in.x 12 in.(31 cm x 31 cm),and not less than 60%of internal broiler size. SECTION IV - SYSTEM DESIGN • UL EX3470 ULC EX3470 Page 4-43 7-1-09 REV.6 OVERLAPPING NOZZLE COVERAGE ► • For appliance hazard surfaces with listed protection exceed- ing the standard hazard zone of 28 in. (71.1 cm) in depth, the ►Overlapping Coverage-Option 1 hazard surface(s) must be aligned with the back edge of the For each group of protected appliances under a common hood(s), hazard zone,with the front edge overhanging the front edge of the overlapping nozzles must be located from right to left so that the zone.See Appliance Chart,Table 1. each end nozzle is located a maximum of 6 in.(15.2 cm)inside the For appliance hazard surfaces that exceed the listed protec- outside edge of the cooking hazard of each end appliance,and the tion sizes, multiple zones must be utilized.Align entire hazard inside overlapping nozzles must be located between the two end surface area within the multiple zones. nozzles at a maximum spacing of 12 in.(30.5 cm). • All hood,duct,individual appliance,and piping limitations are as Hazard Zone specified in the R-102 Design, Installation, Recharge and The hazard zone is defined as a theoretical,flat and level, rectan- Maintenance Manual, Part No.418087. gular surface,that includes all of the cooking hazards of the pro- • All appliance protection currently listed in the R-102 Design tected appliances under a common hood(s).The purpose of the Manual,Part No.418087,is also approved protection.Zone pro- hazard zone is to provide a means of locating the appliances and tection can be considered optional protection. the overlapping nozzles, as well as aiming the overlapping noz- zles. The hazard zone measures 28 in. (71.1 cm) deep by the TABLE 1 length of the cooking hazard(s).The centerline of the hazard zone Overlapping Nozzle Coverage(Zone Protection) must bisect the 28 in.(71.1 cm)depth(from front to back)and run from right-to-left for the full width of the hazard zone. Appliance Type Maximum Cooking Hazard Overlapping Nozzle Appliance Protection Fryer 34 in.(86.4 cm) Deep x 5.8 ft2 (0.5 M2) Overlapping Nozzle Appliance Protection is defined as protection Griddle 30 in.(76.2 cm)Deep x Unlimited Length of cooking appliances by nozzles spaced uniformly at uniform ele- vations under a common hood(s).Overlapping protection of appli ances is continuous for the full length of the hood or divided when Wok, Maximum 30 in.(76.2 cm) Diameter x 8 in. group(s) of protected appliances are separated by counters or (20.3 cm) Deep appliances not requiring protection. Wok, Minimum 11 in.(27.9 cm) Diameter x 3 in. Full hood continuous protection is defined as overlapping noz- (7.6 cm) Deep zle appliance protection that covers the appliance line-up located Braising Pan/Tilt 34 in.(86.4 cm) Deep x Unlimited under the total hood length.All appliances requiring protection are Skillet` Length the appliances under the hood that can be an ignition source of Lava Rock 32 in.(81.3 cm)Deep x Unlimited grease in the hood,grease removal device or the duct. Char-Broiler Length Group protection is defined as overlapping nozzle appliance pro- Charcoal Broiler 32 in.(81.3 cm)Deep x Unlimited Length tection that protects individual hazard zones located under a com- (4 in.(10.2 cm) Maximum Fuel Depth) mon hood. These "groups" of appliances may be separated by appliances not requiring protection, such as steam equipment or Mesquite Wood 32 in.(81.3 cm) Deep x Unlimited Length work tables, or by dedicated appliance protection, such as sala- Broiler (12 in.(30.5 cm) Maximum Fuel Depth) mander broilers. Gas Radiant 36 in.(91.4 cm) Deep x Unlimited See Figure 91d (full hood continuous protection) and Figure 91e Char-Broiler Length (multiple group protection). Electric Char-Broiler 34 in.(86.4 cm) Deep x 20 in.(50.8 cm) Dedicated Nozzle Appliance Protection See Figure 91a for nozzle location Appliance protection using dedicated nozzle coverage is defined I t1 as protection of cooking appliances with enclosed cooking haz- ards, such as upright broilers, which cannot be protected withCOVER MUST NOT 0-61N.(0-15 cm) I 1 overlapping nozzles and therefore must be protected with nozzles INTERFERE WITH I f dedicated to the appliance. EDGE OF DISCHARGE 40.45 IN. I General Design Limitations PATTERN ! (1-1.1 m) ' t • Maximum depth of zone is 28 in.(71.1 cm). ! • The 245 nozzle,Part No.419340,is the only approved nozzle for ) overlapping(zone)protection. r ZONE • Nozzle must be located 0 in.to 6 in.(0 cm to 15.2 cm)forward I f of zone centerline,aimed back at the zone centerline. • Nozzles must be spaced a maximum of 6 in. (15.2 cm) from i each end of hazard and then a maximum of 12 in.(30.5 cm)on center for the remaining overlapping nozzles until the complete ► hazard Is covered. ZONE CENTER LINE ' FIGURE 91a 46PoDN27 SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-43.1 REV.0 7-1-09 OVERLAPPING NOZZLE COVERAGE(Continued) 4. The overlapping appliance nozzles must be located 0 in. to Overlapping Appliance Nozzle and Hazard Zone Locations 6 in.(0 cm to 15.2 cm)forward of the centerline or aimline of 1. All overlapping appliance nozzles must be the "245" nozzle, the selected hazard zone.See Figure 91c. Part No.419340, and must be located under a common hood ' 245 NOZZLE—NOZZLE MUST BE AIMED STRAIGHT at the same height above the hazard zone, in a straight line DOWN OR BACK AT CENTERLINE OF HAZARD ZONE from right to left and aimed at the centerline of the hazard — zone.The overlapping nozzle is used for both continuous over- lapping and multiple group overlapping protection. 2. The hazard zone must be positioned(located)so that all appli- ance hazard surfaces are within the zone.For appliance haz- ard surfaces with listed protection exceeding the standard 61N. 451N. hazard zone size of 28 in.(71 cm)in depth (see Table 1),the (15.2 Cm) (1.1 m) hazard surface(s) must be aligned with the back edge of the 40 IN. hazard zone,with the front edge overhanging the front of the (1 m) zone. 3. The overlapping appliance nozzles must be located 40 in.to 45 in. (1 m to 1.1 m) above the top surface of the protected appliances.See Figure 91c. Exception No. 1:Nozzle dimensions for wok protection are FRONT BACK OF ZONE measured to bottom of wok. Exception No. 2:When using OF ZONE CENTERLINE OF overlapping appliance nozzles in areas where there is a back 28 IN. HAZARD ZONE shelf,the nozzle cannot be positioned in the shaded area as (71.1 cm) shown in Figure 91b. ZONE FIGURE 91c Also, back shelf must not extend more than 11 in. (27.9 cm) OW915 over the hazard zone and cannot be less than 20 in.(50.8 cm) above the hazard zone.See Figure 91 b. OVERLAPPING NOZZLE(S) 45 CANNOT BE POSITIONED 44 IN THIS SHADED AREA 43 42 41 40 6 5 4 3 2 1 I �—CENTER LINE OF HAZARD ZONE BACK SHELF l 11 IN.(27.9 cm) MAXIMUM 20 IN. (50.8 cm) MINIMUM i (�—28 IN.(71.1 Cm)--►I FIGURE 91b DD6914 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-43.2 7-1-09 REV.0 OVERLAPPING NOZZLE COVERAGE(Continued) 2. When obstructions are located adjacent to appliance(s) pro- Overlapping Appliance Nozzle and Hazard Zone Locations- tected by overlapping nozzles,the overlapping appliance noz- Group Protection zle spacing must start with the appliance(s) adjacent to the obstruction.See Figure 91f. 1. For each group of protected appliances under a common hood(s),the overlapping nozzles must be located from right to 6 IN. 0.5 c 12 IN. 12 IN. 121N. (30.5 cm)I(30.5 cm)I(30.5 cm)I(30.5 cm) left so that each end nozzle is located a maximum of 6 in. (15.2 cm) _. .. . . . . 6 IN. MAX. + MAX. + MAX. + MAX. + MAX. + (15.2 cm) (15.2 cm) inside the outside edge of the cooking hazard of MAX. each end appliance,and the inside overlapping nozzles must be located between the two end nozzles at a maximum spac- ing of 12 in.(30.5 cm).See Figures 91d and 91e. OUTSIDE EDGE OF 12 IN.(30.5 cm)MAXIMUM COOKING SPACING(S)BETWEEN HAZARD OVERLAPPING NOZZLES 61N. (15.2 cm) / \ / 1 / \\ \\ -1L \\�- 6 IN. MAXIMUM / �\ / \ / 1 / MAXIMUM I_ FROM \,// \/ / \ HAZARD AREA FROM EDGE OF / /` /\ \ EDGE OF OBSTRUCTION COOKINGCOOKING HAZARD / / / �� HAZARD FIGURE 911' 001713 3. When an appliance requires dedicated protection with a pro- tected area intended for overlapping appliance nozzle protec- tion,the group protection option will be required for appliances on either side of the appliances using dedicated protection. FULL HOOD CONTINUOUS APPLIANCE PROTECTION Group protection using overlapping appliance nozzles must begin with the protected appliance(s) adjacent to the dedicat- FIGURE 91d ed appliance protected. An overlapping appliance nozzle(s) 001710 must be positioned within 6 in.(15.2 cm)of the edge(s)of the %W appliance hazard surface area(s) adjacent to the dedicated nozzle protection.See Figure 91g. 12 IN.(30.5 cm) 6 IN.(15.2 cm) MAXIMUM MAXIMUM 1 EDGE OF COOKING HAZARD 61N. --► II t I'�H 6IN. /r/ (15.2 cm) 12 IN. (15.2 cm) + 12 IN. + + 12 IN. 12 IN. + MAXIMUM (30.5 cm) MAXIMUM 6 IN. FROM R J� MAXIMUM FROM (15.2 cm) I(30��) (30.5 cm)(30.5 cm) 6 IN. EDGE OF \ / EDGE OF MAX. MAX. MAX. MAX. (15.2 cm) COOKING COOKING t MAX. HAZARD EDGE OF HAZARD EDGE y 6 IN.(15.2 cm) 6 IN.(15.2 cm) EDGE COOKING OF MAXII I MAXIMUM OF HAZARD COOKING COOKING HAZARD HAZARD GROUP APPLIANCE PROTECTION FIGURE 91e 001720 DEDICATED NOZZLE APPLIANCE FIGURE 91g 001756 4 SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-43.3 REV.0 7-1-09 OVERLAPPING NOZZLE COVERAGE(Continued) Overlapping Appliance Nozzle and Hazard Zone Locations— Group Protection(Continued) 4. On protected appliances, all hazard surfaces located in a group must be within 40-45 in. (102-114 cm) from the noz- zle(s).Once that dimension is exceeded,a new group must be started.See Figure 91 h. Note:The supply pipe feeding nozzle groups is to be at the same elevation.Adjust height for each group only by varying lengths of nozzle drops. 6 IN.(15.2 cm) I 6 IN.(15.2 cm) MAXIMUM I MAXIMUM I I NOZZLES I I � I NOZZLES 45 IN. I 40 IN. (114 cm)I(1(2 cm) ( 40 IN. (1 1 002 cm) 45 IN. 1(114 cm) 1 (� GROUP W GROUP.B. FIGURE 91h 006917 Detection Requirements For Overlapping Appliance Protection When utilizing overlapping appliance protection,fusible link detec- tors must be installed on a maximum of 2 ft (0.61 m) centers, starting with detectors located in (under)the duct opening(s). Starting from the detector under the duct opening, add detectors on 2 ft(0.61 m)maximum spacing until the complete length of the plenum area is covered,from one end to the other.The location of the last detector on each end of the plenum must not exceed 2 ft(0.61 m)from end of plenum. Note:Standard detector coverage, as specified in "Design Section,"is acceptable when utilizing dedicated nozzle cov- erages. SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-47 7-1-09 REV 5 TANK AND CARTRIDGE REQUIREMENTS For higher total flow numbers (23 to 110), multiple cartridges and Once the hazard analysis is completed and the total nozzle flow regulated actuators are required as shown in the System Selection numbers are established,the quantity and size of agent tanks and Guide in Section IX—Appendix. cartridges needed to supply the nozzles with the proper volumes ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS of agent at the proper flow rates can be determined.For cartridges used in the regulated release mechanism, flow capacities, tank This section contains the guidelines for installing the actuation and quantities and sizes, and regulated release cartridge options are expellant gas lines between the regulated release mechanism reg- given in the table below. ulator, each regulated actuator regulator, and each agent tank. These limitations should be considered when selecting the com- Total Quantity and Regulated Release ponent mounting locations. Flow Size of Cartridge Options Numbers` Tank(s) 'Nitrogen Carbon Dioxide The actuation gas line is the length of pipe and/or hose that is run from either the AUTOMAN Regulated Release Assembly or the 1 — 5 (1) 1.5 Gallon LT-20-R 101-10 ►Remote Release Assembly that directs high pressure from the 6-11 (1)3.0 Gallon LT-30-R 101-20 cartridge in the release to actuate one or more additional 11 —16 (1) 1.5 Gallon Double 101-30 Regulated Actuator Assemblies.The actuation gas line can consist (1)3.0 Gallon of 1/4 in.Schedule 40 black iron,chrome-plated,stainless steel,or 16-22 (2)3.0 Gallon Double 101 30" galvanized steel pipe and fittings,and/or factory supplied stainless steel braided actuation hose. 16—22 (2)3.0 Gallon Double — (Manifold) The expellant gas line is the length of pipe that is run from the ( 1-22-33 (M nif Gallon Double _ regulator in either the AUTOMAN Regulated Release Assembly or a Regulated Actuator Assembly that directs regulated pressure to When one or more regulated actuators are used, the following the agent storage tanks to pressurize the tank and discharge the tank and cartridge combinations apply for each regulated actuator: agent.The expellant gas line shall consist of 1/4 in. Schedule 40 Regulated Actuator Regulated Actuator black iron,chrome-plated, stainless steel,or galvanized steel pipe Tank(s) Cartridge and fittings. (1) 1.5 Gallon LT-20-R or 101-10 ►Actuation Gas Line—6 to 8*Tanks Maximum (1)3.0 Gallon LT-30-R or 101-20 8 Tank maximum reflects the utilization of 3 tank regulated actuators. (1) 1.5 Gallon and LT-A-101-30 or 101-30*`or 1. Use only 1/4 in. Schedule 40 black iron, hot-dipped galva- (1)3.0 Gallon double tank nized,chrome-plated, or stainless steel pipe and fittings. (2)3.0 Gallon LT-A-101-30 or 101-30**or double tank 2.The actuation gas line piping is installed from the regulated P- (2)3.0 Gallon (Manifold) LT-A-1 tan or Double release mechanism to each regulated actuator connected ►(3)3.0 Gallon LT-A-101-30 or Double within the system.The total length of the actuation gas line from the regulated release assembly to the regulated actuator ` For exceptions to maximum flow numbers,see Distribution Piping Requirements for 1.5 gallon assembly(ies) must not exceed 20 ft (6 m) when using an and 3.0 gallon systems in this Section. LT-20-R, an LT-30-R nitrogen cartridge, or a 101-10 or a The 101-30 cartridge can not be used when(2)two 3.0 gallon tanks are manifolded together. ► 101-20 carbon dioxide cartridge.See Figure 100. REGULATED ACTUATOR ASSEMBLY EXPELLANT GAS LINES NOT INCLUDED IN ACTUATION GAS LINE LENGTH TOTALS REGULATED ACTUATOR ASSEMBLY ACTUATION GAS LINE WITH AN LT-20-R, LT-30-R,101-10 OR 101-20 CARTRIDGE MAXIMUM LENGTH OF 20 FT.(6 m), MAXIMUM NO.OF FITTINGS 9 REGULATED ACTUATOR ASSEMBLY "ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY ► FIGURE 100 OC-01-115 SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-48 REV.6 7-1-09 ACTUATION AND EXPELLENT GAS LINE REQUIREMENTS 2.The actuation gas line piping is installed from the 101 remote (Continued) mechanical release to each R-102 regulated actuator assem- Actuation Gas Line—6 to 8'Tanks Maximum(Continued) bly.The total length of the actuation gas line from the remote mechanical release to the regulated actuator assemblies must 3.If an expellant gas line is connected to the regulated release not exceed 100 ft(30.5 m). assembly along with an actuation gas line,the total combined 3 length of the actuation and expellant gas line must not .A combined total of 20 elbows and 9 tees may be used exceed 30 It(9 m)when using a"double-tank"nitrogen car- in these lines. Two 45° elbows equal one 90° elbow. See tridge or a LT-A-101-30 nitrogen cartridge or a 101-30 carbon ' Figure 102. ► dioxide cartridge.See Figure 101. 4.Use only a 101-10 carbon dioxide cartridge in the 101 remote 4.A combined total of nine fittings may be used in these lines, mechanical release. eight 900 elbows and one tee.Two 450 elbows equal one 900 5.A safety vent relief valve (Part No. 15677) is required in the elbow. actuation gas line to relieve residual pressure after actuation. Actuation Gas Line—10 to 15'Tanks Maximum P. Actuation Gas Line—Using 1/4 in.Stainless Steel Hose '15 Tank maximum reflects the utilization of 3 tank regulated actuators. 15 Tank maximum reflects the utilization of 3 tank regulated actuators. 1.Use only 1/4 in. Schedule 40 black iron, hot-dipped galva- ► 1. Maximum total length of hose cannot exceed 17.5 ft(5.3 m). nized, chrome-plated, or stainless steel pipe and fittings. . Note: A combination of 1/4 in. stainless steel braided hose Note:Stainless steel hose and fittings can also be used.See and 1/4 in. NPT pipe can be used as long as the total com- Component Section for detailed information. bined actuation gas line length does not exceed 17.5 ft ACTUATOR AND EXPELLANT GAS LINES WITH A"DOUBLE TANK"CARTRIDGE (5.3 m). Stainless steel braided hose cannot be used for OR A 101-30 CARTRIDGE OR A LT-A-101-30 CARTRIDGE MAXIMUM COMBINED LENGTH-30 FT(9 m) ► expellant gas lines.See Figure 102 for additional details. MAXIMUM COMBINED FITTINGS-9 2. Maximum of 5 regulated actuators allowed 3. Actuated with remote release(Part No.433485)or Regulated Release Assembly(Part No.429853) REGULATED ACTUATOR ASSEMBLY REGULATED ACTUATOR REGULATED ACTUATOR ASSEMBLY ASSEMBLY EXPELLANT "ANSUL AUTOMAN' GAS LINES NOT INCLUDED REGULATED RELEASE ASSEMBLY IN COMBINED TOTALS ► FIGURE 101 000262 20 ELBOWS SAFETYEXPELLANT 1/4 IN.ACTUATION LINE- 9 TEES MAXIMUM MAXIMUM RELIEF VALVE GAS LINE 100 FT(30.5 m)MAXIMUM I I nl i hr"' I 1 I I I I I 1 I I nl 1 It I I I I I I I I I i I i i I I I EDI En I REGULATED ACTUATOR MAXIMUM OF 5 REMOTE RELEASE MECHANISMS WITH TANK AGENT TANK REGULATED (PART NO.433485)5 MAXIMUM ACTUATORS 1/41N.STAINLESS STEEL HOSE OPTIONS ► SAFETY 42 IN.(107 cm) 114 IN.STAINLESS RELIEF VALVE MAX.HOSE CH ECK VALVE LENGTH(T .) STEEL HOSEYP . � t t MAXIMUM OF ja- r r 5 REMOTE f RELEASE MECHANISMS (PART NO. 433485)OR ONE(1) i I i I I I I I i 1 REGULATED ► NO.42 853)SE ART It REGULATED ACTUATOR WITH TANK MAXIMUM OF 5 REGULATED ACTUATORS ► NOTE:WHEN MULTIPLE RELEASE ASSEMBLIES ARE UTILIZED,A 114 IN.CHECK VALVE, FIGURE 102 PART NO.25627,WILL BE REQUIRED AFTER EACH REGULATED RELEASE. 000301 SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-49 7-1-09 REV.5 ACTUATION AND EXPELLENT GAS LINE REQUIREMENTS (Continued) ► 4. If three 3.0 gallon tanks are connected to the regulator in Expellant Gas Line either a regulated release or regulated actuator assembly, ' 1. The expellant gas line is installed from the regulated release only factory supplied expellant gas hose assemblies will be I mechanism in double, three, and multiple-tank systems, and utilized. Refer to Distribution Piping Requirements — 9.0 from the regulated actuator assembly in multiple-tank sys- Gallon System,page 4-55 for additional design requirements. ► tems.The expellant gas line is the piping and/or hose between DISTRIBUTION PIPING REQUIREMENTS the regulator and the tank-enclosure/tank-bracket assembly. The total length of the expellant gas line from the regulated Once the nozzle placement and quantity of tanks has been deter- release mechanism or each regulated actuator assembly mined,it is then necessary to determine the piping configurations must not exceed 30 ft(9 m)when using a"double-tank'car- between the tank adaptor and each discharge nozzle.This section tridge, an LT-A-101-30 Cartridge, or a 101-30 Cartridge.See contains the guidelines and limitations for designing the distribu- ► Figures 103 and 104. tion piping so that the liquid agent will discharge from the nozzles at a proper flow rate.These limitations should also be referred to EXPELLANT GAS LINE when selecting the mounting location for the regulated release MAXIMUM LENGTH-30 FT(9 m), mechanism and agent tank. MAXIMUM NO.OF FITTINGS-9 General Piping Requirements 1. All R-102 system piping is straight line.Therefore,the need for critical lengths and balancing is minimized. 2. Two 45°elbows count as one 90°elbow. 3. Each branch line includes the tee or elbow leading to it, and all fittings within the branch line itself. 4. The minimum piping length of Schedule 40, 3/8 in.pipe from the tank outlet to any nozzle protecting a range,fryer,or wok must be 6 It(1.8 m). "ANSUL AUTOMAN" 5. Pipe lengths are measured from center of fitting to center of REGULATED RELEASE ► fitting.See Figure 105. ASSEMBLY CENTER TO CENTER ' FIGURE 103 000776 EXPELLANT GAS LINE MAXIMUM LENGTH-30 FT(9 m), MAXIMUM NO.OF FITTINGS-9 ► FIGURE 105 aoo77e 6. All distribution piping must be 3/8 in.Schedule 40 black iron, chrome-plated,or stainless steel.Do not use hot dipped gal- vanized pipe on the distribution piping. 7. All threaded connections located in and above the protected area must be sealed with pipe tape.Tape should be applied to male threads only.Make certain tape does not extend over the end of the thread,as this could cause possible blockage of the agent distribution. 8. Before installing blow-off caps on nozzles, apply a small amount of Dow Corning No. 111 silicone grease across the opening in the nozzle tip and also a small amount coating the exterior of the blow-off cap.This will help keep cooking grease from building up on the cap. REGULATED ACTUATOR 9. Tees used in the distribution piping can be used as thru tees, ASSEMBLY FIGURE 104 side outlet tees,or bull tees. ' 000m 2. A combined total of nine fittings may be used in these lines, eight 90°elbows and one tee.Two 450 elbows equal one 90° elbow. 3. If two tanks are connected to the regulated release assembly in a multiple-tank system arrangement, the total combined length of the actuation and expellant gas lines must not exceed 30 It (9 m) when using a"double-tank"nitrogen car- tridge,an LT-A-101-30 nitrogen cartridge,or a 101-30 carbon ► dioxide cartridge.See Figure 101. SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-50 REV.5 7-1-09 DISTRIBUTION PIPING REQUIREMENTS(Continued) Supply and Branch Line Identification SUPPLY LINE The R-102 distribution piping network is broken down into four The Supply Line is defined as the length of pipe which runs from specific pipe runs: the Supply Line, the Duct Branch Line, the agent tank outlet to the last branch line(whether a duct,appli- the Plenum Branch Line, and the Appliance Branch Line. See ance, or plenum branch line).This includes all supply line fittings ►Figure 106. except for the tees or elbows leading to the branch lines. See DUCT . o. Figures 106 and 107. BRANCH LINE !1 SUPPLY LINE PLENUM APPLIANCE BRANCH LINE BRANCH LINE NOTE:THIS IS A CONCEPTUAL DRAWING ONLY. THIS IS NOT AN ACTUAL INSTALLATION. ► FIGURE 106 000778 END OF SUPPLY LINE NOTE:THESE ARE EXAMPLES ONLY.OTHER CONFIGURATIONS CAN BE DESIGNED. f END OF SUPPLY LINE END OF SUPPLY LINE � END OF rLINETEE SUPPLY LINEZZLES FOR NUM TECTION) END OF rTEE SUPPLY LINE (NOZZLES FOR PLENUM PROTECTION) BRANCH LINE CANNOT BRANCH LINE CANNOT START AHEAD OF A START AHEAD OF A SUPPLY LINE TEE SUPPLY LINE TEE ► FIGURE 107 000780 SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-51 7-1-09 REV.5 DISTRIBUTION PIPING REQUIREMENTS(Continued) Supply and Branch Line Identification(Continued) PLENUM BRANCH LINE NOTICE The Plenum Branch Line is defined as the length of pipe which Branch lines cannot start ahead of a supply line runs from the supply line to the plenum nozzle(s).This includes all tee. branch line fittings as well as the tee or elbow used to start the DUCT BRANCH LINE ►branch line.See Figures 106 and 109. The Duct Branch Line is defined as the length of pipe which runs from the supply line to the duct nozzle(s).This includes all branch line fittings as well as the tee or elbow used to start the branch line. ►See Figures 107 and 108. 1 PLENUM BRANCH LINE I (TEE INCLUDED) DUCT BRANCH LINE 1 (ELBOW INCLUDED) 1 f- PLENUM BRANCH LINE -� (TEE INCLUDED) Q DUCT BRANCH LINE (TEE INCLUDED) ► FIGURE 109 000782 DUCT BRANCH LINE t• (TEES INCLUDED) • APPLIANCE BRANCH LINE The Appliance Branch Line is defined as the length of pipe which - runs from the supply line to the appliance nozzle(s).This includes all branch line fittings as well as the tee or elbow used to start the f- branch line.See Figures 107 and 110. i i 1 I 1 APPLIANCE BRANCH LINES (TEES INCLUDED) FIGURE 108 00079, ► FIGURE 110 0007M • SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-52 REV.4 7-1-09 DISTRIBUTION PIPING REQUIREMENTS(Continued) START OF LAST BRANCH LINE Distribution Piping Requirements—1.5 Gallon System START OF FIRST DUCT, PLENUM,AND APPLIANCE PROTECTION BRANCH LINE 1.This option allows for duct protection, plenum protection, 1 P. appliance protection, or any combination. However, only one SUPPLY ` ' (1)duct nozzle may be used,either a 1W or a 2W, nozzle. LINE TEE \ TOTAL LENGTH MUST NOT ► 2.All distribution piping, supply and branch, must be 3/8 in. EXCEED 8 FT Schedule 40 black iron,chrome-plated,or stainless steel. ( (2.a m) ► 3.Each 1.5 gallon tank allows a maximum of five flow numbers.` ► 4.The pipe length between the start of the first branch line and the start of the last branch line must not exceed 8 ft (2.4 m). When the supply line is split, the combined length of both START OF LAST legs of the supply line(start of first branch line to start of last BRANCH LINE ► branch line)must not exceed 8 It(2.4 m).See Figure 111. START OF FIRST BRANCH LINE 5.The combined length of all branch lines must not exceed 22 It ► FIGURE 111 o0078A (6.7 m).See Figure 112. ► 6.The requirements of the following table must not be exceeded: 1 W NOZZLE 1N NOZZLE O 1 N NOZZLE (BRANCH LINES IN BOLD) COMBINED LENGTH MUST NOT EXCEED 22 FT.(6.7 m) ► FIGURE 112 000785 Duct Plenum Appliance Requirements Supply Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft 6 ft 4 ft loft (12.2 m) (1.8 m) (1.2 m) (3 m) Maximum Rise 6 ft 4 It 2 ft 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 900 Elbow 9 4 4 6 Maximum Tees 1 1 2 3 Maximum Flow Numbers 5' 2 2 3 Exceptions: 1.Six(6)flow numbers are allowed when a duct branch line is the last branch line on the piping network and no IN nozzles are used to protect woks or griddles. 2.Six(6)Flow numbers are allowed when six(6)1 N nozzles are used and none of the nozzles are used to protect woks,griddles,ranges,and salamanders. NOTE:Only five(5)flow numbers are allowed if a IN nozzle is used for wok,griddle,range,or salamander protection. 3.Six(6)flow numbers are allowed when only two(2)3N nozzles are used. SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-53 7-1-09 REV.4 DISTRIBUTION PIPING REQUIREMENTS(Continued) Distribution Piping Requirements—3.0 Gallon System 1. The maximum length between the start of the first branch line SUPPLY�_� and the start of the last branch line must not exceed 24 ft ► TEE , (7.3 m).When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch ► line to the start of the last branch line) must not exceed 24 ft d �, ! (7.3 m).See Figure 113. ► U000266 COMBINED LENGTH OF 2. The total length of all branch lines must not exceed 36 It O BOTH LEGS OF SUPPLY ► (1 O.9 m).See Figure 113. LINE MUST NOT 3 BRANCH LINES EXCEED 24 FT(7.3 m) 3. Use a 3/8 in.union to connect the tank adaptor to the 3/8 in. supply line. 4. A maximum of two nozzles are allowed per duct branch line. 1N NOZZLE 5. The requirements of the following table must not be exceeded: 2W NOZZLE 1N NOZZLE f� 1 230 NOZZLE / O 245 NOZZLE 1/2N NOZZLE (BRANCH LINE IN BOLD) COMBINED LENGTH MUST adosaz NOT EXCEED 36 FT(10.9 m) ► FIGURE 113 Duct Plenum Appliance Requirements Supply Line Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft 8 ft 4 ft 12 ft (12.2 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise 6 ft 4 ft 2 ft 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 90° 9 4 4 6 Elbows Maximum Tees 1 2 2 4 Maximum Flow 11' 4 2 4 Numbers •Exceptions: ► 1.Twelve(12)flow numbers are allowed in any one tank for duct and plenum protection only. 2.Twelve(12)flow numbers are allowed with any one tank using only two-flow appliance nozzles. 3.Twelve(12)flow numbers are allowed with any one tank using only three-flow appliance nozzles. Special Instructions: ► 1.Twelve(12)flow numbers are allowed when four(4)Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 66 on Page 4-32.The discharge piping must ► be as shown in Figure 67 on Page 4-32. 2.For certain McDonald's applications,11.5 flow numbers are allowed when using a combination of one(1)2W dud nozzle,one(1)1/2N electrostatic precipitator nozzle, one(1)1N plenum nozzle,and four(4)two-flow appliance nozzles.Contact ANSUL Applications Engineering Department for additional information. SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-54 REV.5 7-1-09 DISTRIBUTION PIPING REQUIREMENTS(Continued) Distribution Piping Requirements — 6.0 Gallon Manifolded LENGTH OF PIPING MUST NOT EXCEED 24 FT. (7.3 m)FOM STAT OF FIRST System TO START OF LAST BRANCH LINEANCH LINE As an option to piping two(2)3.0 gallon tanks separately,two (2) 3.0 gallon tanks can be manifolded together to share a common agent distribution line.Only (2) 3.0 gallon tanks connected to the same regulator can be manifolded. The following requirements must be met when manifolding: 1. All piping must be 3/8 in.Schedule 40. START OF LAST BRANCH LINE 2. See Figure 115 for tank connections. 3. The length of supply line piping between the start of the first 0 branch line and the start of the last branch line must not 0 exceed 24 ft (7.3 m).See Figure 94.When the supply line is split,the combined total of both legs of the supply line(from the start of the first branch line to the start of the last branch line)must not exceed 24 ft(7.3 m). 2W NOZZLES IN 4. The combined length of all branch lines must not exceed 36 ft / NozzLE (10.9 m).See Figure 114. 1/ 5. A maximum of 22 flow numbers are allowed. 6. The requirements of the following table must not be exceeded. 1N NOZZLE 1N NOZZLE ® 1N t7 NOZZLE 2 FLOW APPLIANCE NOZZLE (BRANCH LINES IN BOLD) COMBINED LENGTH MUST NOT EXCEED 36 FT(10.9 m) FIGURE 114 000267 Duct Plenum Appliance Requirements Supply Line Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 32 ft 8 ft 4 ft 12 It (9.7 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise 6 ft 4 It 2 ft 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 90° 8 4 4 6 Elbows Maximum Tees 2 2 2 4 Maximum Flow 22 4 2 4 Numbers • SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-55 7-1-09 REV.4 DISTRIBUTION PIPING REQUIREMENTS(Continued) Distribution Piping Requirements—6.0 Gallon Manifolded ►Distribution Piping Requirements—With Independent Pipe System(Continued) Runs This configuration consists of two 3 gallon tanks. Both tanks are Independent pipe runs can also be used with the regulated connected to a common manifold tee and are pressurized from a ►release assembly and the tank/enclosure assembly or tank mount- single double tank(Part No.73022)nitrogen cartridge in the regu- ►ing brackets.See Figure 116.When manifolding is not used,each ►lated release assembly. See Figure 115. Note:A tank mounting of the two(2)3 gallon tanks utilize the piping limitations of a single bracket can be utilized instead of the tank/enclosure assembly. tank system. 'See Figure 117. 3/8 IN. 3/8 IN. 3/8 IN. BRANCH JJJJyyyy SUPPLY SUPPLY -(( USE HOSE! SEE GROMMET NOTE ► HOSE/ PACKAGE N0.1 GROMMET (PART NO. 3/8 IN BRANCH PACKAGE 418511) (PART NO. �—IN-LINE BURST DISC 418511) I ASSEMBLY—SEE NOTE NO.4 I REMOVE BURST DISC— SEE NOTE N0.3 ❑ 3.0 GALLON 3.0 GALLON 3.0 3.01� TANK TANK GALLON OR OR TANK 1.5 GALLON 1.5 GALLON DOUBLE TANK DOUBLE TANK TANK TANK NITROGEN NITROGEN CARTRIDGE OR CARTRIDGE OR 101-30 CO2 (LT-A-101-30 CARTRIDGE CARTRIDGE— (LT-A-101-30 3.0 GALLON REGULATED RELEASE 008127 REGULATED REGULATED RELEASE ASSEMBLY OR CARTRIDGE— 3.0 GAL LY OR 3.0 GALLON REGULATED ACTUATOR ONLY) REGULATED ACTUATOR ASSEMBLY REGULATED ACTUATOR ASSEMBLY TANK/ENCLOSURE ACTUATOR ONLY) ASSEMBLY TANKIENCLOSURE ASSEMBLY FIGURE 116 000786 NOTE 1:THE PIPE CONNECTION FROM TANK CENTER TO TANK CENTER CANNOT EXCEED 8.1/2 IN.(21.5 cm).ALSO,OEM ►Note: If an expellant gas hose is to be used for a second tank in RELEASE/BRACKET ASSEMBLY CAN BE UTILIZED WHEN MANIFOLDING 3.0 GALLON TANK. an adjacent tank enclosure or tank bracket assembly,the second NOTE 2: ONLY 3 GALLON TANKS CAN BE MANIFOLDED. tank will need to be installed On the left side of the ANSUL NOTE 3:THE BURST DISC THAT IS PART OF THE TANK AUTOMAN Regulated Release, with the outlets a maximum of 8 ADAPTOR/BURST DISC ASSEMBLY MUST BE REMOVED 1/2 in. (21.6 cm) from center to center, similar to the manifolded AND MODIFIED.SEPARATE THE ALUMINUM DISC system in Figure 115.Otherwise,the second tank will require 1/4 MATERIAL FROM THE PLASTIC GASKET.DISCARD THE ALUMINUM DISC MATERIAL AND REINSTALL THE in.NPT pipe instead of expellant gas hose. ► PLASTIC GASKET BACK INTO THE TANK ADAPTOR/BURST DISC ASSEMBLY. NOTE 4:THE IN-LINE BURST DISC ASSEMBLY,PART NO.416790. IS TO BE MOUNTED AS CLOSE TO THE TANK OUTLET AS POSSIBLE.AFTER SYSTEM DISCHARGE,THE ASSEMBLY MUST BE DISASSEMBLED AND A NEW BURST DISC INSTALLED. ► FIGURE 115 SECTION IV - SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-56 REV.4 7-1-09 DISTRIBUTION PIPING REQUIREMENTS(Continued) ' Distribution Piping Requirements-9.0 Gallon System This optional configuration consists only of three 3-gallon tanks,all pressurized from a single double-tank nitrogen cartridge with ►expellant gas hoses connected as shown in Figure 117.Tanks No. 1 and No.2 must be connected directly to the regulator with sepa- rate expellant gas hoses and Tank No. 3 must be connected to ►Tank No.2 with a third expellant gas hose as shown in Figure 117. Each tank must be connected to an independent distribution pip- ing network as shown in Figure 117. Distribution piping require- ments for each network must be as follows: 1. The maximum length between the start of the first branch line and the start of the last branch line must not exceed 24 It (7.3 m).When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft ► (7.3 m).See Figure 113. 2. The total length of all branch lines must not exceed 36 It ► 110.9 m .See Figure 113. 3.0 GA IGALLON � 1 ) g LLON GALLON 3. Use a 3/8 in.union to connect the tank adaptor to the 3/8 in. TANK TANK TANK p N0.3 N0.2 NO.1 supply line. 11_�\ 4. A maximum of two nozzles are allowed per duct branch line. 5. When using this 9.0 gallon system configuration, no mani- Two TANK ENCLOSURE 3 GALLON REGULATED DOUBLE TANK NITROGEN folding Of distribution piping is allowed. ASSEMBLY PART NO. RELEASE ASSEMBLY, CARTRIDGE OR 430324(INCLUDES(2) OR 3 GALLON LT-A-101-30 CARTRIDGE 6. When an ANSUL AUTOMAN Regulated Release is utilized in HOSES AND(2) REGULATED ACTUATOR (REGULATED ACTUATOR this configuration, additional regulator actuators cannot be GROMMETS) ASSEMBLY ONLY) Used. NOTE:WHEN THREE(3)3.0 GALLON TANKS ARE CONNECTED TO ONE(1) t gallon tanks can be utilized in this configuration. AUTOMAN REGULATED RELEASE ASSEMBLY,NO ADDITIONAL 7. Only 3 9 9 REGULATED ACTUATOR(S)ASSEMBLIES CAN BE USED. 8. The requirements of the following table must not be exceeded FIGURE 117 for each 3 gallon tank: W8126 Duct Plenum Appliance Requirements Supply Line Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft 8 It 4 ft 12 It (12.2 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise 6 ft 4 ft 2 ft 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 90° 9 4 4 6 Elbows Maximum Tees 1 2 2 4 Maximum Flow 11* 4 2 4 Numbers 'Exceptions: 1.Twelve(12)flow numbers are allowed in any one tank for duct and plenum protection ONLY. 2.Twelve(12)flow numbers are allowed with any one tank using only two-flow appliance nozzles. 3.Twelve(12)flow numbers are allowed with any one tank using only three-flow appliance nozzles. Special Instructions: ► t.When four(4)Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 66 on Page 4-32,the discharge piping must be as shown in Figure 67 on Page 4-32. 2.For certain McDonald's applications,11.5 flow numbers are allowed when using a combination of one(1)2W duct nozzle,one(1)1/2N electrostatic precipitator nozzle, one(1)IN plenum nozzle,and four(4)two-flow appliance nozzles.Contact Ansul Applications Engineering Department for additional information. SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-57 7-1-09 REV 2 DETECTION SYSTEM REQUIREMENTS Once the fire suppression system design has been determined, a Detector Placement Requirements detection system design must be completed.This section contains EXHAUST DUCTS guidelines and limitations for detection system installation. Each exhaust duct must have at least one detector installed in the Detector Identification duct entrance,located in the airstream of the cooking vapors,or at The two types of detectors are distinguished from each other by ' a maximum of 20 ft(6.1 m)into the duct opening.See Figure 118. their location in the detection system. 1.The Terminal Detector(Part No.417368)is the last in a series of detectors,or the only detector used in a single-detector sys- tem.This detector is thus named because it is at the point at -- which the wire rope ends, or"terminates" ► 2.A Series Detector(Part No.417369)is any detector located in- line between the regulated release mechanism and the termi- nal detector. zo Fr.(s m� MAXIMUM ►Detector/Pulley Elbow/Conduit Off-Set Design Limitations 1.Conduit runs,pulley elbows,and number of detectors per sys- tem must be within the approved system guidelines.The fol- lowing requirements must not be exceeded: Maximum Maximum Maximum Number of Number of Length of 1/2 Detectors Elbows in.Conduit per System per System per System FIGURE 118 ► Scissors Style 15 20 150 ft(45.7 m) 000271 Detector NOTICE (Without When gas appliances are used and the flue Off-Set Conduit gases from the burner are exhausted into the Scissors Style 15 16 150 ft(45.7 m) duct, the detector must be kept out of the air Detector(With stream of these exhaust gases. These gases Off-Set Conduit can be very hot and could actuate the system 2. If the hazard requires more than 15 detectors, up to five 101 unnecessarily. ► Remote Releases (Part No.433485) can be used for system Duct openings that are long and narrow or large actuation.Each 101 remote release allows the use of a maxi- enough to require multiple duct nozzles may mum of 15"scissor"style detectors(14 series and 1 terminal) require additional detectors. for a total of 75 detectors if needed. ELECTROSTATIC PRECIPITATOR If an electrostatic precipitator is located at or near the base of the exhaust duct, it is necessary to locate a detector below the pre- cipitator, at the base of the duct, and also locate one in the duct, ►just above the precipitator.See Figure 119. When installing the detector bracket and system conduit, make certain they do not interfere with the operation of the precipitator. Note: On secondary filtration units utilizing multiple filter stages/media,contact Ansul Technical Services for instructions. I i ► FIGURE 119 Oo 2z SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-58 REV.2 7-1-09 Detector Replacement Requirements(Continued) NOTICE COOKING APPLIANCES The conduit offset can be used at the top or bot- tom of the regulated release to change direction If the cooking appliance is located under an exhaust duct where a of the conduit. The conduit offset cannot be detector has been mounted, it is normally not necessary to utilize used with pulley tees.All other changes in direc- another detector for that cooking appliance, provided the detector tion must be made by using ANSUL approved ►is not more than 12 in.(30 cm)into the duct and the appliance has pulley elbows, Part No.423254 or 415670.See no larger cooking surface than 48 in.x 48 in. (121.9 cm x 129.1 ► Figure 121. cm).See Figure 120. Note: If two (2) appliances are located under a duct opening where a detector has been mounted and both appliances togeth- er do not exceed a cooking surface of 48 in.x 48 in. (121.9 cm x 121.9 cm) and the detector is located above both the protected appliances,it is not necessary to utilize an additional detector pro- / vided the duct detector is not more than 12 in. (30.5 cm) into the j duct opening. I � U I APPLIANCE APPLIANCE APPLIANCE FIGURE 121 REQUIRES COVERED BY REQUIRES 000270 SEPARATE DETECTOR SEPARATE DETECTOR UNDER DUCT DETECTOR Fusible Link Selection ' When possible, temperature readings should be taken at each ► FIGURE 120 detector location to determine correct fusible link temperature rat- 000269 ing.Temperature can be recorded using either a maximum regis- tering thermometer, Part No.15240,temperature tape or any other Each cooking appliance with a continuous cooking surface not accurate thermometer. exceeding 48 in.x 48 in.(122 x 122 cm)can be protected by a min- imum of one detector.Cooking appliances with a continuous cook- O 0 ing surface exceeding 48 in.x 48 in.must be protected by at least O one detector per 48 in.x 48 in.cooking area.Detectors used for cooking appliances must be located above the protected appli- ance toward the exhaust duct side of the appliance.The detector Ev=- should be located in the air stream of thea appliance to enhance .:, TEMPERATURE RATING pp STAMPED ON FUSIBLE system response time. [ LINK BODY ►Note: For overlapping detector coverage, see Page 4-45 for design requirements. ==�AL Detection Line Requirements 000170 000171 q K STYLE ML STYLE CONDUIT ' FIGURE 122 Rigid conduit or 1/2 inch EMT thin-wall conduit may be used. Select correct UL Listed fusible link(s)for installation in detector(s) Standard steel conduit fittings(compression type are recommend- according to the temperature condition.Two styles are available. ed) must be employed to properly install the detection system.All See Figure 122.See Component Section for detailed temperature conduit or pipe must be firmly supported.When using pipe, make ratings. certain that all ends are carefully reamed, deburred and blown clear of chips and scale before assembly. SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-59 7-1-09 REV 2 MANUAL PULL STATION REQUIREMENTS Metal Stamped Style—Part No.4835 or 54011 A remote manual pull station allows the R-102 system to be man- Parts that may be used for installation of a metal stamped remote ually operated at some point distant from the regulated release manual pull station are: assembly.The pull station should be installed at a height of 42-48 Description Balt NO. in. (107-122 cm), in accordance with the requirements of the Remote Manual Pull Station Assembly' 54011 American Disabilities Act(ADA) and the Authority having Jurisdic- Remote Manual Pull Station Assembly 4835 tion.and located in the path of egress.The pull station is the only Pulley Elbow 423250 source of manual actuation of the regulated release assembly. Pulley Elbow 415670 The total length of the cable used for each manual pull station with- Pulley Tee 427929 in a system must not exceed 150 ft(46 m). 'Assemby includes parts listed below: The maximum number of pulley elbows that may be used per pull 1/16 in.Stainless Steel Cable 50 ft.(15 m) 15821 station is 20. Oval Press-TO-Crimp Sleeves 4596 Glass Break Rod (1) 4834 ►One pulley tee, Part No.427929, is allowed per cable system. The maximum length of cable from the AUTOMAN to a pull station MECHANICAL GAS VALVE REQUIREMENTS is 150 ft (45.7 m) with a maximum of 20 pulley elbows used per An ANSUL or ANSUL approved mechanical gas shut-off valve side of the tee.As the tee is located farther from the AUTOMAN, system can be attached to the R-102 system.The system works the 150 ft (45.7 m) maximum must be observed but as pulley both mechanically and pneumatically by use of an air cylinder elbows are placed between the AUTOMAN and the tee,they must located inside the regulated release assembly. Upon actuation of be deducted from the available pulley elbows(20)allowed on each the fire suppression system, a pneumatically-operated air cylinder side. assembly will mechanically close the gas shut-off valve. Example: If 10 pulley elbows are placed between the AUTOMAN The total length of the cable for each mechanical gas valve must and the pulley tee, the maximum available pulley elbows left for not exceed 150 ft(46 m).The maximum number of pulley elbows ►use on each side of the tee is 10 per side.See Figure 123 for three that may be used is 20 for each valve. different examples. (Note: Both must be gas valves or both must ► One pulley tee(Part No.427929) is allowed per cable system. be pull stations.Mixing is not allowed.) The maximum length of cable from the AUTOMAN to a gas valve is TEE CLOSE TO AUTOMAN(EXAMPLE) 150 ft(45.7 m) with a maximum Of 20 pulley elbows used per side PULLEYTEE of the tee. As the tee is located farther from the AUTOMAN, the 150 ft(45.7 m)maximum must be observed but as pulley elbows are 12 IN. placed between the AUTOMAN and the tee,they must be deducted (305 mm) from the available pulley elbows(20)allowed on each side. Example: If 10 pulley elbows are placed between the AUTOMAN and the pulley tee, the maximum available pulley elbows left for ► use on each side of the tee is 10 per side.See Figure 123 for three GAS VALVE OR AUTOMAN GAS VALVE OR different examples. MANUAL PULL MANUAL PULL 149 FT(45.4 m)AND 20 PULLEY ELBOWS MAXIMUM Parts that may be used for installation of a Mechanical Gas Shut- PER EACH SIDE OF TEE off Valve are: TEE CLOSE TO GAS VALVES OR MANUAL PULL(EXAMPLE) Description PaIt No Gas Valve/Actuator 3/4 in.Assembly (ANSUL)` 55598 Gas Valve/Actuator 1 in.Assembly(ANSUL)' 55601 121N. 121N_ Gas Valve/Actuator 1 1/4 in.Assembly (ANSUL)` 55604 (305 mm) (305 mm) Gas Valve/Actuator 1 1/2 in.Assembly(ANSUL)" 55607 PULLEY TEE Gas Valve/Actuator 2 in.Assembly(ANSUL)' 55610 GAS VALVE OR GAS VALVE OR Gas Valve/Actuator 2 1/2 in.Assembly (ASCO)" 25937 MANUAL PULL MANUAL PULL Gas Valve/Actuator 3 in.Assembly(ASCO)" 25938 AUTOMAN Pulley Elbow 423250 149 FT(45.4 m)AND 20 PULLEY ELBOWS BETWEEN AUTOMAN AND TEE Pulley Elbow 415670 Pulley Tee 427929 1/16 in.Stainless Steel Cable 15821 or TEE HALFWAY BETWEEN AUTOMAN AND GAS VALVES OR MANUAL PULL(EXAMPLE) 50 ft(15 m)or 500 ft(152 m) roll 79653 75 FT(22.9 m)AND 10 PULLEY ELBOWS Oval Press-To-Crimp Sleeve 4596 Stop Sleeve(2) 26317 75 FT(22.9 m)AND 75 FT(22.9 m)AND 'Assembly includes parts listed below: 10 PULLEY ELBOWS 10 PULLEY ELBOWS Air Cylinder Assembly 15733 PULLEY TEE Air Cylinder 15521 6 Tubing Assembly 15529 AUTOMAN GAS VALVE OR GAS VALVE OR Copper Tubing, 1/8 in. 15525 MANUAL PULL MANUAL PULL Male Elbow 15523 Male Connector 15522 FIGURE 123 15421 006907 Machine Screw(2) Hex Nut(2) 15527 Lockwasher(2) 4141 Visual Inspection Seal (2) 197 SECTION IV — SYSTEM DESIGN ■ UL EX3470 ULC EX3470 Page 4-60 REV.2 7-1-09 MECHANICAL GAS VALVE REQUIREMENTS(Continued) Parts that may be used for installation of a 110 VAC Gas Shut-off All valves above are UL listed and approved.They may be mount- Valve are: ed in any position. Pipe threads are type NPT.Ambient operating Description Part N4 temperature range of all valves is 32°F to 120°F(0°C to 49°C). Electric Solenoid Valve,3/4 in.NPT* 13707 The valves are not weatherproof and must be located indoors in Electric Solenoid Valve, 1 in.NPT" 13708 areas approved by the"authority having jurisdiction" Electric Solenoid Valve, 1 1/2 in.NPT* 13709 ELECTRICAL GAS VALVE REQUIREMENTS Electric Solenoid Valve, 2 in.NPT' 13710 Electric Solenoid Valve,3 in.NPT` 17643 A UL Listed electrically-operated gas shut-off valve can be Manual Reset Relay(110 VAC) 14702 attached to the R-102 system to provide an electrical means of vanes are normally closed when de-energized. shutting off the gas line at a predetermined point.If an electric gas shut-off valve is used in the system it must be attached with both ALARM INITIATING SWITCH REQUIREMENTS an electric(snap-action)switch and a manual reset relay.For more The Alarm Initiating Switch can be field mounted within the information on the types of electric(snap-action)switches, refer to ANSUL AUTOMAN release.The switch must be used to close a the Electrical Switch, Field Installation section.The manual reset supervised alarm circuit to the building main fire alarm panel when relay is reviewed in this section. the ANSUL AUTOMAN release actuates.This action will signal the All electrical connections should be performed by a QUALIFIED fire alarm panel that there was a system actuation in the kitchen ELECTRICIAN and in accordance with authority having area.The switch kit contains all necessary mounting components jurisdiction. ► along with a mounting instruction sheet. See Page 5-19 for wiring information. The following is a brief explanation of how the R-102 system oper- The switch is rated 50 mA, 28VDC. ates with an Electric Gas Shut-off Valve attached: With the regulated release cocked in the ready condition,the nor- Fafi-Q- Description mally closed contacts in the snap-action switch allow current to 428311 Alarm Initiating Switch Kit flow to the manual reset relay.With the relay coil energized, nor- ELECTRICAL SWITCH REQUIREMENTS mally open contacts in the reset relay close, allowing the solenoid in the gas valve to be energized. ► Note: Electrical connections shall not be made in the ANSUL Once the R-102 system is activated,the normally closed contacts ► AUTOMAN. in the snap-action switch will open, de-energizing the reset relay. The electric(snap-action) switches for the R-102 system are spe- This will,in turn,open the contacts in the relay which will cause the cially designed to fit the regulated release assembly.The switches gas valve to become de-energized and close. are intended for use with electric gas valves, alarms, contactors, The system must be re armed and the "push to reset" button on lights, contractor supplied electric power shut-off devices, and the reset relay must be operated n reopen the gas valve. other electrical devices that are designed to shut off or turn on when the fire suppression system is actuated. (See Figures It is important to note that a power failure or an electrical power ► 110 through 112 in Installation Section for reference). interruption will cause the gas valve to close even though the sys- Contractors shall supply "UL listed, enclosed industrial control tem was not fired. equipment or magnetic switch having a rating matching that of the In either case,whether in a fired condition or when a power failure cooking appliance,coil 110 VAC/60 Hz or 24 VAC/60 Hz" has occurred, the manual reset relay and electric gas shut-off All electrical connections should be performed by a QUALIFIED valve must be reset to resume a normal operating condition. For ELECTRICIAN and in accordance with authority having resetting, refer to the"Recharge and Resetting Procedures" jurisdiction. section in this manual. Electric(Snap-Action) Switches that may be field installed are: Approvals Part No. Descri tp ion ANSUL gas valves listed in this section are UL listed and approved 423878 One Switch Kit for 110 VAC. If more information is required, refer to the Gas and 423879 Two Switch Kit Oil Equipment List of Underwriters Laboratories, Inc. under 423880 Three Switch Kit "Electrically Operated Valves Guide No.440 A5"or consult Ansul 423881 Four Switch Kit Incorporated, Marinette,Wisconsin 54143-2542. Each switch has a set of single-pole, double throw contacts rated If other gas valves are used, they shall be "UL listed electrically- at 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250,277 VAC. operated safety valves for natural or LP gas as required,of appro- priate pressure and temperature rating, 110 VAC/60 Hz:'The infor- exceeds the rated capacity of the switch. mation on temperature and type of gas that the valves are suitable for may be found in the Gas and Oil Equipment List of Electrical wiring and equipment shall be installed in accordance Underwriters Laboratories, Inc. under "Electrically Operated with NFPA 70(National Electrical Code)or the requirements of the Valves Guide No.440 A5: authority having jurisdiction. The electrically operated gas valve must be of the type that needs to be energized to remain open. ►Note: For electrical wiring diagrams, see Installation Section, •Pages 5-19.1 through 5-19.3. SECTION VI — TESTING AND PLACING IN SERVICE UL EX3470 ULC EX3470 Page 6-1 7-1-09 REV.3 After the system has been completely installed, and BEFORE 2. Manually push each air cylinder rod to full "DOWN"position. INSTALLING THE CARTRIDGE,the system must be tested at the The gas valve should close. If mechanical gas valve does not regulated release assembly.The testing information listed in this trip,remove each pulley elbow cover to make certain wire rope section deals with the limitations and parameters of this pre-engi- is resting on each pulley elbow sheave.If this does not correct neered system. Those individuals responsible for the testing of the the problem there may be too much slack in the line and it R-102 system must be trained and hold a current ANSUL certifi- should be retightened. cate in an R-102 training program. 3. Test for gas leaks by painting connections with a soap solu- Note:ANSUL AUTOMAN Release must be in the cocked position tion. Bubbles indicate a gas leak.Tighten connections where before testing manual pull station.Make certain to remove lock bar leaks appear and repeat test again to make certain no other before performing pull station testing. gas leaks exist. 4. If no gas leak is found,pull air cylinder rod to full"UP"position. TESTING MANUAL PULL STATION 5. Recock mechanical gas valve. To test each remote manual pull station, complete the following steps: 6. Check burners for gaseous odor. IF GASEOUS ODOR EXISTS, MANUALLY PUSH THE AIR CYLINDER ROD TO 1. With the expellant gas cartridge removed, remove lock bar THE FULL "DOWN" POSITION IMMEDIATELY. This will from regulated release assembly cable lever. cause the mechanical gas valve to shut the gas line off. 2. On pull station, remove break rod from the pull station by Open any doors and/or windows to clear the area of gaseous inserting a small screwdriver into slot at bottom of pull knob to fumes, then correct the gas leak before proceeding any facilitate turning the pull knob.Push slightly on the screwdriver further. and turn pull knob clockwise, then the pull knob can be removed without breaking the glass rod. 7. If no gaseous odor exists,pilot light may be ignited at this time. NOTICE 8. Reinstall side covers to gas valve housing. Make certain roll Take care in removing the break rod from the pin is positioned within both sides of the valve housing slot. pull station side shields while rotating the break Connect visual inspection seals(Part No.197)on ANSUL type rod/pull knob assembly. valves.See Figure 1. 3. Pull ring handle on pull station. If the regulated release assembly is tripped easily, the remote manual pull station is properly installed. If the regulated release assembly does not trip, remove pulley tee (if provided) and each pulley elbow cover to make certain wire rope is resting on the pulley tSEAL sheave.If this does not correct the problem,there is too much slack in the line and it must be retightened. 4. Recock regulated release assembly using cocking lever (Part No. 14995 or 435603)and reinstall lock bar(Part No. 14985). PECTION 5. On pull station, insert the break rod into the two holes toward NO.197) the top of the pull knob.Rotate the pull knob counterclockwise. NOTICE Take care in snapping in the ends of the break rod into the pull station side shields while rotat- ing the entire assembly. NOTICE FIGURE 1 If no other devices are being attached, proceed OW359 to Page 6-3, Step No. 1, and test the detection system. 9. Make certain the regulated release mechanism is cocked with lock bar in place. TESTING MECHANICAL GAS VALVES NOTICE To test each mechanical gas shut-off valve complete the following If no other devices are being attached, proceed steps: to Page 6-3, Step No. 1, and test the detection p system. 1. ZI CAUTION To reduce the risk of explosion due to leaking gas, before the gas line is turned on, make certain to extinguish any open flames and turn off all burners and any electrical or mechanical devices that are capable of igniting gas. Turn gas line on. SECTION VI — TESTING AND PLACING IN SERVICE UL EX3470 ULC EX3470 Page 6-2 REV.3 7-1-09 TESTING ELECTRICAL GAS VALVES TESTING ELECTRIC SWITCH To test each Electric Gas Shut-off Valve complete the following The procedure for testing a field installed Electric (Snap-Action) steps: Switch is as follows: 1. i i NOTICE CAUTIONZL If an electrical gas shut-off valve is attached to system, perform proper test procedure for the To reduce the risk of explosion due to leaking gas, before gas valve first, before completing the following the gas line is turned on, make certain to extinguish any steps. open flames and turn off all burners and any electrical or mechanical devices that are capable of igniting gas. 1• Turn power source on and if installed,depress reset button on manual reset relay (RED LIGHT ON). All electrical devices Turn gas line on. should be operating at this time. 2. Make certain electric(snap-action) switch is properly wired. 2. Remove lock bar. 3. Make certain all other devices connected to the manual resetI CAUTION relay are properly wired. Refer to typical wiring diagrams in ZL Figures 110, 111, 112, and 113 in"Installation"section. Do not install cartridge at this time or system may be 4. Test for gas leaks by painting connections with a soap solu- actuated. tion. Bubbles indicate a gas leak.Tighten connections where leaks appear.Repeat test again to make certain no other gas 3. Manually actuate the system by operating the remote pull leaks exist. station. It may be necessary to remove the glass break rod 5. If no gas leaks are found, turn power source on and depress prior to operating pull station. (If installed, the manual reset the reset button on the manual reset relay (RED LIGHT ON) relay will de-energize the electric gas valve, thus shutting off to energize(OPEN) electric gas valve. the gas line.) All electrically-operated devices predetermined to shut off or turn on should do so. If this does not occur,turn 6. Remove lock bar from regulated release mechanism. power source off and make sure all wiring is properly ► connected and retest.Refer to Figures 110, 111, 112,and 113 CAUTI• ► in"Installation"section for typical wiring diagrams. 4. If test is successful, recock regulated release mechanism Do not install cartridge at this time or system may be , using cocking lever (Part No. 14995 or 435603) and reinstall actuated. lock bar (Part No. 14985). If a manual reset relay is installed, depress the reset button (RED LIGHT ON). It will also be 7. Manually actuate the system by operating the remote pull necessary to re-light any pilot lights on the cooking appli- station. (It may be necessary to remove the glass break rod ances. prior to operating pull station.)Manual reset relay(RED LIGHT NOTICE OUT) will de-energize (CLOSE) the electric gas valve, thus If no other devices are being attached,proceed shutting off the gas line. If this does not happen, turn power to Page 6-3, Step No. 1, and test the detection source off.Then re-examine all wiring connections for proper system. ► hookup. Refer to Figures 110, 111, 112, and 113 in ► "Installation"section for typical wiring diagrams. 8. If test is successful, recock regulated release mechanism ► using cocking lever (Part No. 14995 or 435603) and reinstall lock bar (Part No. 14985). Depress reset button on manual reset relay(RED LIGHT ON). 9. Check burners for gaseous odor. IF GASEOUS ODOR EXISTS,TURN OFF POWER SOURCE IMMEDIATELY.This will cause the electric gas valve to shut the gas line off. Open any doors and/or windows to clear the area of gaseous fumes, then correct the gas leak before proceeding any further. 10. If no gaseous odor exists,pilot light may be ignited at this time. NOTICE If no other devices are being attached, proceed to Page 6-3, Step No. 1, and test the detection system. SECTION VI — TESTING AND PLACING IN SERVICE UL EX3470 ULC EX3470 Page 6-3 7-1-09 REV.4 TESTING DETECTION SYSTEM 1. Test detection system by completing the following steps: 4. Upon successful actuation of the system,complete the follow- a. Raise the regulated release mechanism tension lever to the ing steps: "UP"position. a. Raise tension lever to"UP"position and install a properly- b. Remove the fusible link from the terminal detector and rated fusible link in the terminal detector. install a test link(Part No.15751).See Figure 2. b. Cock regulated release mechanism using cocking lever ► (Part No. 14995 or 435603) and insert lock bar (Part No. 14985). O O c. Lower tension lever to"DOWN"position. ► d. For"scissor"style linkage, locate linkage in bracket all the way toward termination end of detection run. TEST LINK e. Make certain the 1/4 in. (6.4 mm) minimum to 3/8 in. FIGURE 2 (9.5 mm)maximum clearance was maintained between the "363 base of the trip hammer assembly and the cable lever c. Locate detector linkage and center in each bracket. assembly. For"clip on"style linkage, locate linkage in bracket slightly NOTICE toward termination end of detection run. Reset any electrical equipment that may have For"scissor"style linkage, locate linkage in bracket all the been affected by the system actuation. way toward termination end of detection run. f. Remove shipping cap and weigh each cartridge.Replace if d. Lower regulated release mechanism tension lever to weight is 1/2 ounce (14.2 g), or more, below weight ► "DOWN"position and remove lock bar. stamped on cartridge. e. Using a wire cutter,cut the test link at the terminal detector g. Install cartridge into the regulated release mechanism to simulate automatic actuation. receiver and each regulated actuator receiver.Hand tighten firmly. f. If system actuates successfully, go to Step 4. h. Remove the lock bar. 2. If the regulated release mechanism does not actuate, check i. Install cover on regulated release assembly and each regu- the following components and remedy any disorder as follows: lated actuator assembly and secure with appropriate a. Check the detector linkage for correct positioning. fasteners or visual inspection seal. Insert seal (Part No. " b. Check the wire rope for knotting or jamming. 197) in each upper and lower cover hole, if applicable. If system is install in an OEM enclosure, attach enclosure c. Check pulley elbows to see that wire rope is free and cover and secure with appropriate hardware or procedure. centered in pulley sheaves.If any evidence of pulley elbow deformation is found, replace the pulley elbow. ' CAUTIONZL d. Make certain that lock bar is removed. e. Make certain that regulated release mechanism is cocked. Before installing cover, make certain detection tension lever is secured in the"DOWN"position to enable auto- f. Make certain that tension lever is in"DOWN"position. matic detection and operation of the ANSUL 3. Re-test the system by completing the following steps: AUTOMAN Regulated Release. a. Make certain regulated release is cocked and lock bar is ' inserted. j. Record installation date on tag attached to unit and/or in a b. Raise the regulated release mechanism tension lever to the permanent file. "UP"position. c. Install a new test link (Part No. 15751) on the terminal detector. d. Lower the regulated release mechanism tension lever to the"DOWN"position. e. Check for 1/4 in. (6.4 mm) minimum 3/8 in. (9.5 mm) maximum clearance between the trip hammer assembly and the cable lever assembly. f. Remove the lock bar. g. Using a wire cutter,cut the test link at the terminal detector to simulate automatic actuation.