Application Number . . . . . 13-00003350 Date 9/04/13
Property Address . . . . . . 108 FLEET LANDING BLVD
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
-----------------------------------------------
Application desc
3 tons 36K BTU' s
----------------------------------------------
Owner Contractor
_ ------------------------
NAVAL CONTINUING CARE AIR PRO MECHANICAL OF N FL LLC
RETIREMENT FOUNDATION, INC 1008 COUNTY RD 217
1 FLEET LANDING BLVD JACKSONVILLE FL 32234
ATLANTIC BEACH FL 322334599 (904) 759-9019
-------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . . . 00
Permit Fee . . . . 83 . 00 Plan Check Fee
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 3/03/14
-----------------------------
Other Fees .
. STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----- ----------
Permit Fee Total 83 . 00 83 . 00 . 00
. 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 87 . 00 87 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax(904)247-5845
JOB ADDRESS: d� F� T L As N(> 1al`� PERMIT#
PROJECT VALUE $ `3 1cv ARI# -?JYYrSO REQUIRED
Air Handling Equipment Only Air Handling Unit & Condenser Condenser Only
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer RatingREQUIRED
Duct Systems: Total CFM
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity 1 Tons Per Unit 13 7
Heat: Unit Quantity / BTU's Per Unit AX Seer RatingREQUIRED
Duct Systems: Total CFM
Manual J documentation required on residential change out
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks(gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name T kk,-T LAu N W 6 Phone Number .2V&-f90 0
Mechanical Company IA;R- ffieL K11 Krq! LLQ- Office Phone;89-f9f V Fax
Co. Address: �A)> ' L,/2 .2/7 City RXyV%//E State�t Zip z 2
License Holder(Print): 5k;nt4 PictwW%1-1 St e Certification/Registration#Gjri�/2 ysl�d'E
Notarized Signature of License Holder
Before me this day of 20
Signature of Notary Public
Residential System Sizing Calculation
Summary
fleet landing Project Title: Code Only
108 FLEET LANDING BLVD 108 fleet landing Professional Version
ATLANTIC BEACH,FL Climate:North
8/29/2013
Location for weather data: Jacksonville -Defaults: Latitude(30) Altitude(26 ft.) Temp Range(M)
Humidity data: Interior RH 50% Outdoor wet bulb 77F Humidity difference 53 r.
Winter design temperature 32 F Summer design temperature 93 F
Winter setpoint 70 F Summer setpoint 75 F
Winter temperature difference 38 F Summer temperature difference 18 F
Total heating load calculation 38247 Btuh Total cooling load calculation 31928 Btuh
Submitted heating capacity %of calc Btuh Submitted cooling capacity %of calc Btuh
Total(Electric Heat Pump) 94.1 36000 Sensible(SHR=0.76) 115.9 27360
Heat Pump+Auxiliary(O.OkW) 94.1 36000 Latent 103.9 8640
Total Electric Heat Pum 112.8 36000
WINTER CALCULATIONS
Winter Heatin Load for 1732 s ft �„%�
Load comDonent Load ~dowxm%)
Window total 247 sqft 8166 Btuh
Wall total 1620 sqft 5840 Btuh N
Door total 38 sqft 502 Btuh
Ceiling total 1804 sqft 2382 Btuh
Floor total 180 sqft 8071 Btuh
Infiltration 221 cfm 9247 Btuh
Duct loss 4039 Btuh
Subtotal 38247 Btuh ,:� va.c,sz�
Ventilation 0 cfm 0 Btuh %
TOTAL HEAT LOSS 38247 Btuh
SUMMER CALCULATIONS
Summer Cooling Load for 1732 s t
Load com nent Load
Window total 247 sqft 6607 Btuh
Wall total 1620 sqft 4041 Btuh
Door total 38 sqft 383 Btuh
Ceiling total 1804 sqft 2068 Btuh r��M,ox) r. wao�cxx,
Floor total 0 Btuh
Infiltration 158 cfm 3118 Btuh
Internal gain 3840 Btuh
Duct gain 3554 Btuh wascux7 `"°'fig”
Sens.Ventilation 0 cfm 0 Btuh
Total sensible gain 23611 Btuh
Latent gain(ducts) 1041 Btuh rt _ w«sns+q
Latent gain(infiltration) 5676 Btuh
Latent gain(ventilation) 0 Btuh
Latent gain(intemaVoccupants/other) 1600 Btuh
Total latent gain 8316 Btuh
TOTAL HEAT GAIN 31928 Btuh
EnergyGauge®Syste
Version 8 PREPARED B
For Florida residences only DATE:
EnergyGaugeO FLRCPB v4.5.2
System Sizing Calculations - Summer
Residential Load - Whole House Component Details
fleet landing Project Title: Code Only
108 FLEET LANDING BLVD 108 fleet landing Professional Version
ATLANTIC BEACH,FL Climate:North
Reference City.Jacksonville (Defaults) Summer Temperature Difference:18.0 F 8/29/2013
Component Loads for Whole House.: . . ;: I; '-: . .� ..
Type' Overhang Window Area(sqft) HTM Load
Window PrdSHGCIU/InSh/ExSh/IS Olt Len H Gross Shaded Unshad Shaded Unshaded
1 2,Clear,0.87,None,N,H E 1.4ft 1ft. 60.0 60.0 0.0 27 72 1605 Btuh
2 2,Clear,0.87,None,N,H N 1.4ft 1ft. 30.0 0.0 30.0 27 27 802 Btuh
3 2,Clear,0.87,None,N,H W I.4ft 1ft. 60.0 60.0 0.0 27 72 1605 Btuh
4 2,Clear,0.87,None,N,H S 1.4ft 1ft. 6.0 6.0 0.0 27 32 160 Btuh
5 2,Clear,0.87,None,N,H S 1.4ft 11t. 15.0 15.0 0.0 27 32 401 Btuh
6 2,Clear,0.87,None,NA W 1.4ft 1ft. 40.0 40.0 0.0 27 72 1070 Btuh
7 2,Clear,0.67,None,N,H W 1 4ft 1ft. 36.0 36.0 0.0 27 72 963 Btuh
Window Total 247(sqft) 6607 Btuh
Walls TypeR-Value/U-Value Area(sqft) HTM Load
1 Frame-Wood-Ext 11.0/0.09 1154.0 2.6 2967 Stuh
2 Frame-Wood-Ext 11.010.09 322.0 2.6 828 Btuh
3 Frame-Wood-Adj 11.0/0.09 144.0 1.7 246 Btuh
Wall Total 1620(sqft) 4041 Btuh
Doors Type Area(sqft) HTM Load
1 Insulated-Exterior 20.0 10.1 203 Btuh
2 Insulated-Adjacent 17.8 10.1 180 Btuh
Door Total 38(sqft) 383 Btuh
Ceilings Type/Color/Surface R-Value Area(sqft) HTM Load
1 Vented Attic(DarkTile 30.0 1500.0 1.1 1576 Btuh
2 Vented AtGdDarkTile 19.0 232.0 1.6 375 Btuh
3 Vented AttidDarkTile 19.0 72.0 1.6 116 Btuh
Ceiling Total 1804(sqft) 2068 Btuh
Floors Type R-Value Size HTM Load
1 Slab On Grade 0.0 180 M(p)) 0.0 0 Stuh
Floor Total 180.0(sqft) 0 Btuh
Envelope Subtotal: 13099 Btuh
Infiltration Type ACH Volume(cuft)wall area(sqft) CFM= Load
SensibleNatural 0.42 22516 1620 221.4 3118 Btuh
Internal Occupants Btuh/oocupant Appliance Load
gain 8 X 230 + 2000 3840 Btuh
Sensible Envelope Load: 20057 Btuh
Duct load (DGM of 0.177) 3554 Btuh
Sensible Load All Zones 23611 Btuh
EnergyGauge®FLRCPB v4.5.2 Page 1
Manual J Summer Calculations
Residential Load - Component Details (continued)
Project Title: Code Only
fleet landing 108 fleet landing Protessional Version
108 FLEET LANDING BLVD g Climate:North
ATLANTIC BEACH,FL
8t2gl2013
WHOLE HOUSE TOTALS `"
Sensible Envelope Load All Zones 20057 Btuh
Sensible Duct Load 3554 Btuh
Total Sensible Zone Loads 23611 Btuh
Sensible ventilation 0 Btuh
Blower 0 Btuh
Whole House Total sensible gain 23611 Btuh
Totals for Cooling Latent infiltration gain(for 53 gr.humidity difference) 5676 Btuh
Latent ventilation gain 0 Btuh
Latent duct gain 1041 Btuh
Latent occupant gain(8 people @ 200 Btuh per person) 1600 Btuh
Latent other gain 0 Btuh
Latent total gain 8316 Btuh
TOTAL GAIN 31928 Btuh
EQUIPMENT
1.Central Unit # ----F 36000 Btuh
'Key: Window types(Pn-Number of panes of glass)
(SHGC-Shading coefficient of glass as SHGC numerical value or as clear or tint)
(U-Window U-Factor or'DEF'for default)
(InSh-Interior shading device:none(N),Blinds(B),Draperies(D)or Roller Shades(R))
(ExSh-Exterior shading device:none(N)or numerical value)
(BS-Insect screen'.none(N),Full(F)or Half(H))
10
(Ornt-compass orientation)
Version 8
For Florida residences only
EnergyGauge® FLRCPB v4.5.2 Page 2