169 Poinsettia St HVAC 2013 CITY OF ATLANTIC BEACH.
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
its)
Application Number . . . . . 13-00003411 Date 9/19/13
Property Address . . . . . . 169 POINSETTIA ST
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 CU 1 AHU
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
TAYLOR DAVID & ROWE DEBORAH S DONOVAN HEATING & AIR
169 POINSETTIA ST 315 SIXTH AVENUE SOUTH
ATLANTIC BEACH FL 32233 JACKSONVILLE BEACH FL 32250
(904) 241-3785
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 95 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 3/18/14
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 95 . 00 95 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 99 . 00 99 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904)247-5826 Fax(904) 247-5845
10B ADDRESS: A Y'\5e-k�l at, PERMrr#
PROJECTVALUE $ tlZoo ' ARI c5 0111- UIRED
Air Handling Equipment Only _��_Air Handling Unit & Condenser Condenser Only
4EW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit 2-5 Is
Heat: Unit Quantity I BTU's Per Unit m,&0o Seer Rating---
Duct Systems: Total CFM REQUIRED
tEPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Ratin REQUIRED
Duct Systems: Total CFM
?IRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
?IRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty— Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
�LL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks(gallons)
Wells
)THER:
ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
iis application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
ot. ne permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Iroperty Owners Name )P,-Vk Phone Number 15 3_Z3
Aechanical Company 1%Q1 —Office Phone7-qi 37S-�_ Fax__Z_�l—3-7t4r
city
I ;K 8 C", State Jn zip 32-2-5 0
.o. Address: Sk,�; VIE
V),dep,
.,icense Holder(Print) State Certification/Registration#LALD�9_2
Votarized Signature of License Hrolder fe le4 20 13
Al'.% Before me this day of
RICHARD TOMPKINS
commission#FIF 040399
0(-/
W;1 43� Expires July 29,2017 c
-a;kd B.,dd Th�T,.y F�i,Mnnof WIWO4 Signature of Notary Publi
Job:
Project Summary Date: September 16,2013
+ wrightsoft Entire House By: Aaron Thacker
Donovan Heat&Air
315 6th Ave S,Jacksonville Beach, FL32250 Phone:904-241-3785 Fax:904-241-3745 Email:aaron@donovanac.com Web:wwvv.DonovanAC.com
Project Information
F OT David Taylor
169 Poinsettia St,Atlantic Beach, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 OF Outside db 95 OF
Inside db 70 OF Inside db 75 OF
Design TD 31 OF Design TD 20 OF
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 11282 Btuh Structure 15262 Btuh
Ducts 3166 Btuh Ducts 4509 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
pipigg 0 Btuh Use manufacturer's data n
Equipment load 14448 Btuh Rate/swin multiplier 1.00
Infiltration Equipment'sensible load 19771 Btuh
Method Simphfied Latent Cooling Equipment Load Sizing
Construction quality Average
0 Structure 2253 Btuh
Fireplaces Ducts 959 Btuh
Heating Coolin Central vent(0 cfm) 0 Btuh
3212 Btuh
Area (ft2) 1324 13"N Equipment latent load
Volume (W) 11916 11916
0.45 0.23 Equipment total load 22983 Btuh
Air changes/hour 2.4 ton
Equiv.AVF (cfm) 89 46 Req. total capacity at 0,70 SHR
Heating Equipment Summary Cooling Equipment Summary
Make Tempstar Make Tempstar
Trade SMARTCOMFORT TX 5500 R41 OA H P Trade SMARTCOMFORT TX 5500 R41 OA H P
Model TXH530GKA* Cond TXH530GKA*
AHRI ref no3650112 Coil FVM4X24****
AHRI ref no3650112
Efficiency 8.5 HSPF Efficiency 12.5 EER, 15 SEER
Sensible cooling 19740 Btuh
Heating input 8460 Btuh
Heating output 28200 Btuh @ 47'F Latent cooling 28200 Btuh
27 OF Total coo1mg
Temperatuce 6-se 940 cfm
Actual air flow 940 cfm Actual air flow 0.048 cfm/Btuh
Air flow factor 0.065 cfm/Btuh Air flow factor 0 in H20
Static pressure 0 in H20 Static pressure
Space thermostat Load sensible heat ratio 0.86
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2013-Sep-16 08i25 32
+ wrightsoft Right-SuiteO Universal 8.0.24 RSUD5995 Page 1
C:\L)sers\Owner%Documents\Wrightsoff HVAC\Bogus 2.5 ton.rup Cate=MJ8 Front Door faces E