536 Vikings ln 2013 HVAC CITY OF ATLANTIC BEA01
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
. rfl
Application Number . . . . . 13-00003569 Date 10/23/13
Property Address . . . . . . S36 VIKINGS LN
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------
------------------------
DALLDORF, TRACY L ET AL TCI MECHANICAL INC
536 VIKINGS LANE 2331 SEMINOLE RD
ATLANTIC BEACH FL 322334151 ATLANTIC BEACH FL 32233
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . . Plan Check Fee . 00
Permit Fee . . . . 95 . 00 Valuation . . . . 0
Issue Date . . . .
Expiration Date . . 4/21/14
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---- ----- ----------
Permit Fee Total 95 . 00 95 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 99 . 00 99 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247-5826 Fax (904) 247-5845
JOB ADDREss: Cgfy vL.4,a;c &.1 Ft— -3 223 3 PERMIT
PROJECT VALUE $ 3675, 00 ARI# 36Y5731 REQUIRED
Air Handling Equipment Only X_Air Handling Unit & Condenser Condenser Only
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Ratin
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit 2. X"
Heat: Unit Quantity I BTU's Per Unit 29 Ji goo Seer Rating
Duct Systems: Total CFM /000 REQUIRED
Manual J documentation required on residential change out
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
�LL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
)THER:
-rmit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
is application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
it. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
roperty Owners Name �D4 La-10 ir Phone Number go q 5 001 6 10
[echanical Company k0m,4*d- -r Office Phone1010020 Fax
Address: WAMS-,' 6)44- 5�1`0044- City 414*nnk; B114 eL State 1�-LZip -37-7-3 3
icense Holder (Print):77i" L, &X State Certification/Registration 9 So 31;?—
AT
9tarized S Livase r
qHIRLEY L GRAHA4,
MMISSION#DD99WO me thisZ3' da
:,,,PIPES:February 14,20:14f
U
z3oridW Thru Nntpy Public UnLimift re of Notary Pub i
RUUD DesignStar Load Calculation
Results are intended for use w ith Ruud heating and cooling systems
................ .......................................................... .................... ...................... .........
Latitude, Longitude 30.3375�', -81�76860'
.......... .......................
House Square Footage: 1336 sq. ft.
-111.1--I -- --................................. ........... .......... .................................... ............. ........
Name: Tracy Balldorf
--I.-l-.............. ............ ............. ...........
Phone�
Email:
'House Information
SHR .75
Number of residents 4
-1.1-11.1 11- .......... ---.................-,-.......... ........... ....................... ............................... ........... ................
Ceiling height 9
................... .................. ........ ......................
Wall LI-value R-value 0.09111
.....................
Floor U-value R-value O�2 15
............ ----........... ............. .............. .............. ................. ............. -..................... .......... ..............
Ceiling U-value R-value 0,053 119
-1..1.1--...............1.11 -..........
Window Ll-value 0.5
.......... ................
Window SHGF 0,85
Moisture grains 53
Ductloss % 10
.........................
Duct gain % 10
............................ .............. ......................... ............. ...... ...........................
Cooling infiltraction (ACH) 0..6
...........
Heating infiltration (ACH) 0.8
Winter ventilation 0
...........
Summer ventilation 0
..........
'D Conditions
Outdoor Heating cooling
.............. ....................
Dry bulb ('F) 32 95
Daily range M
-1-1--.1................-1.1-.1.11............. ...........
Relative humidity 50%
Moisture difference 53
........... .............. ...............
Indoor Heating Cooling
................ ................
Indoor temperature (cF) 70 75
Design temperature differenceff) 38 20
.......... ..................
. . .
'Heating Load
Area Btuh % of load
' VVa|[ 3840 15.3
Floor 6399 25.5
Ceiling 2691 10,7
Windows � 3667 14,6
Infiltration 6232 6232 24.8
SvsL8rn Efficiency Loss 2283 91
-- - - - -- -- - - ...Total: 25112
251I2 '
- ...... --------------------... ... ... -
Heating Loads
25,112 BTU/hr
System Efficiency Loss
Floor
Ceiling
. �
Windows
Infiltration
all
'
�
�
�
Area Btuh % of load
6
Windows
Sensible
Latent Infiltration 4030 13.1
2428 7.9
Systern-,Eff Jenc
2"
'M-
AN-
A
'U"
g
2271
fce rin a I
T4
N-�
'-w
-�A
9
20'
pfel
..............
Latent People Load 920
............
Total: '71 0 816
Se ri i b i e I o a a 2 6,,-,,
Latent I oad 4956
--....................... .............
SHR 0,84
Capacity at .75 SHR 187 Tons
..........
Cooling Loads
30;,11.6 BRYN
Sensible People Load
Latent People Load
Internal
System Efficiency G
Windows
Sensible Infiltratio
Wall
Latent Infiltration
Ceiling
AED Graph
15000
..........
10000
5000
0 Bam loam liam 12pm 1pm 2 pm 3pm 4pm 5Pm 6pm 7pm 8PM
Hourly Loads Ave�age
ent selection
system equipment selection will be madeusing the following derived values.
Glass (E) 97 sq. ft.
Glass (S) 14 sq. ft.
........... .......... ................ ............. ............
Glass (N) 14 sq. ft.
-1-111-'-..........
Glass (W) 68 sq. ft.
..........
Summer outdoor 950F
.............. ...........
Surnmer Wet Bulb 7 TF
1-1-1--l-............ ............ ...........-- -'-............. ........... ...............
Summer Indoor 75"F
.............
....................... ......
Summer Design Grains 50%
1.11--............. .............. ................... ...........--- "'.1.1-1.11.1..........
Winter Outdoor 32`F
............
Winter lndoo� 70"17
Sensible Cooling 25,866 BtUh
-1-11....................--.- ............. ........... ............�--1.1-1 ...........
Latent Cool in g 4,950 Btuh
.............. ........ ..............I.-� ...........
Required Cooling Airflow 1,176 CFM
.......................1-11.1-1.1-- 1 -..' ........... ...........
Sensible Heating 25,112 Btuh
........... ..................
Required Heating Airflow 326 CFM
............................. ...........
................. ............... ........... ......................
c industry standards and procedures,and comply wi i all local,
All calculations are based upon approved hva
state and federal code requirements�All computed results are Estimates.Product provided by Energy Design
Systems and Idea Tree