1325 Beach Ave HVAC 2013 CITY OF ATLANTIC BEAQnor
800 SEMINOLE RO
ATLANTIC BEACH, FL 32233
F-`
Application Number . . . . . 13-00003890 Date 1/02/14
Property Address . . . . . . 1325 BEACH AVE
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
------------------------------------------
Application desc
1 cu 1 ahu
-----------------------------------------
Owner Contractor
---------------
------------------------
COOK WILLIAM F ET AL DONOVAN HEATING & AIR
1410 BEACH AVE 315 SIXTH AVENUE SOUTH
ATLANTIC BEACH FL 322335734 JACKSONVILLE BEACH FL 32250
(904) 241-3785
-- -------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . . . 00
0
Permit Fee . . . . 103 . 0Plan Check Fee
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 7/01/14
--------------------------------
Other Fees .
STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
Fee summar Charged Paid Credited Due
y ----------
----------------- ----------
---------- -
Permit Fee Total 103 . 00 103 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 107 . 00 107 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
.• MECHANICAL PERMIT APPLICATION
owlCITYOF ATLANTIC BEACH "
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904)247-5826 Fax(904) 247-5845
FOB ADDRESS: 15 ZrJ ��� � F PERMIT#
PROJECT VALUE$ 41ODDO ARI# S 1 REQUIRED
)(Air Handling Equipment Only Air Handling Unit & Condenser Condenser Only
JEW AIR CONDI'T'IONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit -
Heat: Unit Quantity BTU's Per Unit Seer Rating
UIRED
Duct Systems: Total CFM REQ
1EPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit —3.9- Jf
Heat: Unit Quantity BTU's Per Unit 39 � Seer Rating
REQUIRED
Duct Systems: Total CFM
IRE PREVENTION (Requires 3 sets of plans)
Fire Sprinkler System Quantity uires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity
Fire Suppression Systems Quantity (Requires 3 sets of plans)
?IREPLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
kLL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets PumRefrigerator Condenser BTU's
#Vented Wall Furnaces
#Water Heaters Solar Collection Systems
Tanks(gallons)
Wells
)THER: WAW f TD AIR-
ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I havefr�r
its application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether spec
ot. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
'roperty Owners Name wW COaK _ Phone Number ZV9- '/009
Mechanical Company Office Phone zyi 37tS—Fax :7 y/37y�
:o. Address: 31-r G A S _ City -14 RCA State r1 Zip 3Z Z S O
Acense Holder(Print): State Certification/Registration# CAGD 39761
Jotarized Signature of License Holder ''�/►� �'+►
.�•- 2 day of J A �� 20 (q
E4P
RICHARDTOMPKINS Before me thiscromission#FF 040399
E�rites July 29,2ot7Signature of Notary Public
9afd TNu Troy Fain lmws w�900.385-7019
w*� Job:
- wrightsofC Project Summary Dat•: 1014
Entine House By: Brandon Zahaft
Donovan Heat&Air
315 8th ave south,Jacksonville Beach,FL 32250 Phone:241-3785 Email:brandonadonovanac.com
Project • •
For: COOK
1325 BEACH AVE,ATLANTIC BEACH, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 OF Outside db 95 OF
Inside db 68 OF Inside db 20 of
Design TD 29 OF Design TD L
Daily range 50 %Relative humidity 53 r/Ib
Moisture difference 9
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 17933 Btuh Structure 15831 Btuh
Ducts 6151 Btuh Ducts 12221 Btuh
Central vent (33 cfm) 1054 Btuh Central vent(33 cfm) 727 Btuh
Humidification 0 Btuh Blower 0 Btuh
Eqm 0 Btuh n
uipent load 25139 Btuh Use manufacturer's data
Ratelswinngg multiplier 1.00
Infiltration Equipmerrfsensible load 28779 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average 1948 Btuh
Fireplaces 1 (Average) Structure
Ducts 2180 Btuh
Head co I* Central vent (33 cfm) 1196 Btuh
(ft
Area 2 179 179 Equipment latent load 5324 Btuh
Volume?ft') 16146 16146
Air cha /hour 0.45 0.20 Equipment total load 34103 on
on
Equiv.A (cfm) 122 54 Req. total capacity at 0.70 SHR 3.4 ton t
Heating Equipment Summary Cooling Equipment Summary
Make FHP Make FHP
Trade AQUARIUS SPLIT Trade AQUARIUS SPLIT
Model ECO41 Cond ECO41
ARI ref no. 567783 Coil
ARI ref no. 567783 1508 EER
Efficiency 3.89 COP Efficiency 28357 Btuh
Heating Input 33551 Btuh Sensible coding 12582 Btuh
Heating output 33551 Btuh Latent coding 41399 Btuh
Temperature rise 22 OF Total coding
cfm
Actual air flow 1398 cfm Actual air flow 0 050 cfm/Btuh
Air flow factor 0.058 cfm/Btuh Air flow factor 0 in H2O
Static pressure 0 in H2O Static pressure
Space thermostat Load sensible heat ratio 0.84
Printout certified by ACCA to meet all requirements of Manual J 8th Ed.
2014-Jan-02 10:24:28
C � wrighesofe- Right-Suite®Univeroal 7.1.01 RSU05996
AM C:\Users\Saba\Documents\wrightsoft HVAC13.5TON Cal:-MJ8 orientation.N Page 1