372 4th St 2014 HVAC CITY OF ATLANTIC BEACH
I�
1y 800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
J13It
Application Number . . . . . 14-00000137 Date 2/03/14
Property Address . . . . . . 372 4TH ST
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . RES SF DISTRICT
Application valuation . . . . 0
------------------------------------
Application desc
1 CU 1 AHU
-----------------------------------
Owner Contractor
-----------
------------------------
ALPERIN ALAN K DONOVAN HEATING & AIR
H
A4TH ST 315 SIXTH AVENUE SOUTH
372 ATLANTIC BEACH FL 322335344 �9CKSONV1L3EEACH FL 32250
gB
---------- -----------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . Plan Check Fee . 00
Permit Fee . . . . 99 . 00 0
Issue Date Valuation
Expiration Date 8/02/14
---------
-------------
__ ----------
Other Fees
STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
__ _ ________ ---------------
Fee summary Charged
Paid Credited Due
---- ---
Permit Fee Total 99 . 00 99 . 00
. 00
----------------- 00
Plan Check Total . 00 . 00 . 00
4 . 00 4 . 00 . 00 . 00
Other Fee Total
Grand Total 103 . 00 103 . 00 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904)247-5826 Fax(904) 247-5845
10B ADDREss: ��2 `7 sT PERMff#
PROJECT VALUE ARI# :Yo'-7 05 e 0 REQUIRED
_Air Handling Equipment Only !Air Handling Unit & Condenser Condenser Only
4EW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
tEPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity 1 Tons Per Unit 3
Heat: Unit Quantity I BTU's Per Unit 3j troy Seer Rating �_-,)
Duct Systems: Total CFM REQUIRED
IRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
IRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
kLL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks(gallons)
Wells
)THER:
ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
its application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
ot. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
'roperty Owners NameA41p� Phone Number Zyl s6 81
dechanical Company >`! f Office Phone Z`� 31 Fax
:o. Address: 3lS Ac City T� Z61 State Zip3QiQ
.icense Holder(Print): 1>»N 0 Y"1,4J q- State Certification/Registration#_c460,37 q
Jotarized Signature of License Holder61
RICHARD TOMPKINS Before me this 3� day of V a 20
L
_.r Commission#FF 040399
a•, o Expires July 29,2017 Signature of Notary Public
••F�„Y,f:r}��`' BmW Ttn Troy Fain Im nm-WO-M-7079
Job:
+'+ wrightsoft Project Summary Date: January 27,2014
Entire House By: Aaron Thacker
Donovan Heat&Air
315 6th Ave S,Jacksonville Beach, FL32250 Phone:904241-3785 Fax:904241-3745 Email:aaron@donovanac.com Web:www.DonovariAC.com
Project • •
For: Alan Halpperin
372 4th St,Atlantic Beach, FL 32233
Notes:
Design • •
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 OF Outside db 95 OF
Inside db 70 OF Inside db 75 OF
Design TD 31 OF Design TD 20 OF
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 26705 Btuh Structure 20836 Btuh
Ducts 4945 Btuh Ducts 4814 Btuh
Central vent (0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 31649 Btuh Use manufacturer's data n
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 25651 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average 1154 Btuh
Fireplaces 0 Structure
Ducts 2066 Btuh
Heating Cooling Central vent (0 cfm) 0 Btuh
Area (ft') 1040 1040 Equipment latent load 3220 Btuh
Volume (ft3) 8320 8320
Air changes/hour 0.45 0.23 Equipment total load 28871 Btuh
Equiv.AVF (cfm) 62 32 Req. total capacity at 0.70 SHR 3.1 ton
Heating Equipment Summary Cooling Equipment Summary
Make Tempstar Make Tempstar
Trade 15 SEER N SERIES R41 OA HP Trade 15
SEER N
GSERIES R41 OA HP
Model NXH536GKA" Cond Coil FXM4H536GK A'
AHRI ref no3670858 AHRI ref no3670858
Efficiency 8.7 HSPF Efficiency 12.5 EER, 15 SEER
Heating input Sensible cooling 24360 Btuh
Heating output 35400 Btuh @ 47°F Latent cooling 10440 Btuh
Temperature rise 28 OF Total cooling 34800 Btuh
Actual air flow 1160 cfm Actual air flow 1160 cfm
Air flow factor 0.037 cfm/Btuh Air flow factor 0.045 cfm/Btuh
0 in H2O Static pressure 0 in H2O
Static pressure
Space thermostat Load sensible heat ratio 0.89
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed,
2014-Jan-27 09:53:12
wrightsoft Right-Suite®Universal 8.0.24 RSUD5995 Page 1
ACC- C\Users\Owner\Documents\Wnghtsoft HVAC\Bogus 3 ton.rup Calc=MJB Front Door faces: S