2393 Mayport Road FIRE SPRINKLERS 2014 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
App n Number . . . . . 13-00003787 Date 2/20/14
D-V-f-NPQ --- "01 MLvP()PT PT)
RE number 169398-0100- -
NCR OLD ACCOUNT NUMBERS . . .
Application type description MECHANICAL FIRE PERMIT
Subdivision Name . . . . . .
Property Use . . . . . . . .
Property Zoning . . . . . . . COM GENERAL DISTRICT
Application valuation . . . . 18000
Owner Contractor
------------------------
------------------------
NAVAL CONTINUING CARE AMERICAN FIRE SERVICE INC
RETIREMENT FOUNDATION, INC 108 HALSEMA ROAD N
1 FLEET LANDING BLVD JACKSONVILLE FL 32220
ATLANTIC BEACH FL 322334599 (904) 759-0268
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL FIRE SPRINKLER
Additional desc . . Plan Check Fee . 00
Permit Fee . . . . 85 . 00 Valuation . . . . 0
Issue Date . . . .
Expiration Date . . 2/20/14
Qty Unit Charge Per Extension
BASE FEE 55 . 00
1 . 00 30 . 0000 EA M FIRE SPRKL 1ST 40 HEADS 30 . 00
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 85 . 00 85 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 89 . 00 89 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
BuILDING PERMIT APPLICATION
DEC 3 013 CITY OF ATLANTIC BEACH
800 Seminole Road, Atlantic Beach, FL 32233
1By_ Office (904)247-5826 Fax (904)247-5845 10 1
Job Address: mber: 43- 9119
AIA16- SIV6, Permit Nu
�W
Legal Description _�,,;boe-7- 0_ol�b Parcel# - Sq.Ft
F loor Area of S Ft.
Proposed Work h%ted/cooled non-heated/cooled
Valuation of Work z000 ,
Class of Work(circle one): ( N!�� Addition Alteration Repair Move Demolition pool/spa window/door
Use of existing/proposed structure(s)(circle one): Commercial Residenti
If an existing structure,is a fire sprinkler system installed? (Circle one): Yes
Florida Product Approval#
For multiple products use�_roduct approval form
Describe in detail the type of work to be performed: /A/57-,4// 4 MEW FJI—ZIC Z�9_4,j
Property Owner Information:
Name:r,/,=� —Address: 4A1Vb11'--C
city State—Zip IZ433 Phone ja*
E-Mail or Fax#(Optional
Contractor Information:
CompanyName: AlnjEg"Al 6g& gogyle.C._Qualifying Agent:,/j&4P- 9-96eAS
Citv -7-" State 024- Zip -3227--,
Address: )QPoqk Al,
Office Phone 170+ -151-24,4`4 Job Site/Contact Number %0-024CO Fax# 6)04- 7 e -449,1
State Certification/Registration#_�2 8 A 3 06-0 1 7-W5
Architect Name&Phone#
Engineer's Name&Phone#
Fee Simple Title Holder Name and Address
Bonding Company Name and Address
Mortgage Lender Name and Address
A ica h eb pade ba' a e in d he work and n talloa s i ndc or installation has commenced prior to the
a thisjurisdiction. This permit becomes null
fo f six(6)months at any time after
t
n f i s r io irk �s a period o
p I' 1 0 to, tt 'ta r
s y to I P be e ed
0
it a that a -0 k tr c
I c
'ce x _r-t , 0, c �or E e nc Wells, Pools, Furnaces, Boilers,Heaters,
(6
d hin s p
'v 0 c r
P ' Y' 'is Zese' ed
1 to
- 0 a P"_
'id work no C"_, e it t
is c , , , I, " t t s p s.,
w k .. nc d nd 7tand e a ate pe b
Tanks andAir Conifitioners,eta
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS
TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING.) CONSULT WITH
YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF
COMMENCEMENT.
I here certify that I have read and examined thisa lication and know the same to be true and correct. A 11 provisions of laws and ordinances governing this
p ty to violate or cancel the
g
type olVwork will be complhed with whether speci ied rein or not. The granting of a permit does not presume to g ve authori
provisions of any otherfire'deral,state, or local law re a * construction or the pe�formance ofconstruction.
le IF
Signature of Owne Signature of Con cto
PrintName ................... .................. Print Name ........ .... .. ........... ..........................................
.............I ................................................................................
Sworn t and subscribed before me
Swom,L(�and subscribed before me 1,
this I- Day of 420 f I__�ecf_j-n 202
I R
2d�,l
lslu' 35
017
MY C e
0 Public :S pres June 23,2017
OMmISSION*FF008247
Bonded Thru Troy Fain Insurance 8a3.85-7019
vised 0 1.26.10
EXPIRES November 4.2017
........ FlorldallotaryS�rW-e=m
City of Atlantic Beach APPLICATION NUMBER
Building Department (To be assigned by the Building Department.)
800 Seminole Road
Atlantic Beach, Florida 32233-5445 3 -7
Phone(904)247-5826 - Fax(904) 247-5845 12J,5
E-mail: building-dept@coab.us Date routed:
City web-site: http-://www.coab.us
APPLICATION REVIEW AND TRACKING FORM
Property Address:-Z-6q3 �A6,m,00-4eA eloartment review required Yes No
Building)
Applicant: k C —Pranning &Zoning
Tree Administrator
Project: VIC, Public Works
apl4y 'Public Utilities
Public Safety
Fire Services
Review fee $ Dept Signature
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified By
Florida Dept. of Environmental Protection
Florida Dept. of Transportation
St. Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPV6ATION STATUS
Reviewing Department First Review: [VfApproved. E]Denied.
(Circle one.) Comments:
BUILDING
PLANNING &ZONING Reviewed by: Date:.
TREE ADMIN. Second Review: F]Approved as revised. FIDenied.
PUBLIC WORKS Comments:
PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: FlApproved as revised. DIDenied.
Comments:
Reviewed by: Date:
Revised 05/14/09
Ti"! PROJECT CONSISTS OF THE ADDITION OF A NEW 6,854 SQUARE FOOT
�\Ai.-`,iNTENANCE BUILDING TO THE EXISTING FLEET LANDING RESIDENTIAL
MUNITY IN ATLANTIC BEACH, FLORIDA. THE BUILDING WILL BE FULLY
StF'RINKLERED AND WILL ALSO BE USED TO HOUSE GOLF CARTS.
'.)(�"IUPANCY AND CONSTRUCTION TYPE:
NEW BUILDING WILL BE TYPE V-13 COMBUSTIBLE WOOD FRAME
�,CASTRUCTION AND WILL CONTAIN BOTH A TYPE B BUSINESS OCCUPANCY
1-1%11'') A TYPE S-1 STORAGE OCCUPANCY.
,�_,_U,/ERNING STANDARDS:
TI-j.1- SYSTEM DESIGN AND INSTALLATION SHALL COMPLY WITH THE 2010
-1-D-11TION OF NFPA 13, THE 2010 EDITION OF NFPA 24, AS WELL AS THE 2010
BUILDING CODE AND THE 2010 FLORIDA FIRE PREVENTION CODE-
OF SERVICE:
IEW 6" FIRE SERVICE MAIN AND BACKFLOW PREVENTER WILL BE ADDED AS
3UPPLY FOR THE BUILDING'S FIRE SPRINKLER SYSTEM. THE POINT OF
\VICE WILL BE DOWNSTREAM OF THE BACKFILOW PREVENTER ON THE
-..'.'2 LDING SIDE.
--A CLASSIFICATIONS:
OFFICE AREAS SHALL BE CONSIDERED LIGHT HAZARD AREAS. ALL SHOP
STORAGE AREAS SHALL BE PROTECTED AS ORDINARY HAZARD GROUP 1 ,
FOR THE PAINT STORAGE ROOM WHICH SHALL BE CONSIDERED
HAZARD GROUP 2.
_'IGN APPROACH:
SYSTEM SHALL BE COMPRISED OF A SINGLE DRY RISER SERVING ALL
, ,-AS. INTERIOR LIGHT HAZARD AREAS SHALL BE DESIGNED FOR 0.10
/SOFT OVER THE MOST REMOTE 1,950 SOFT (30% PENALTY FOR DRY
-_'TEM DELAY) USING QUICK RESPONSE SPRINKLERS RATED FOR ORDINARY
__,.*PERATURES AND SPACED AT A MAXIMUM COVERAGE AREA 225 SQFT PER
D AND 15 FEET APART MAX. ORDINARY HAZARD GROUP I AREAS SH ALL
DESIGNED FOR 0.15 GPM/SOFT OVER THE MOST REMOTE 1,950 SOFT (30%
'ALTY FOR DRY SYSTEM DELAY) USING QUICK RESPONSE HEADS RATED
ORDINARY TEMPERATURES AND SPACED AT A MAXIMUM COVERAGE AREA
130 SOFT PER HEAD AND 15 FEET APART MAX. ORDINARY HAZARD
2 AREAS SHALL BE DESIGNED FOR 0.20 GPM SOFT OVER THE MOST
IOTE 1,950 SOFT (30% PENALTY FOR DRY SYSTEM DELAY) USING QUICK
'...'PONSE HEADS RATED FOR ORDINARY TEMPERATURES AND SPACED AT A
/l,' ;`JMUM COVERAGE AREA OF 130 SOFT PER HEAD AND 15 FEET APART
L- "
ATTIC AREAS SHALL BE DESIGNED FOR 0.10 GPM/SQFT OVER THE
.-T REMOTE 2,535 SOFT (30% PENALTY FOR DRY SYSTEM DELAY AND 30%
'ALTY FOR ROOF SLOPE) USING QUICK RESPONSE SPRINKLERS RATED FOR
_ _,INARY TEMPERATURES AND SPACED AT A MAXIMUM COVERAGE AREA 120
,:`_-T PER HEAD. EXTENDED COVERAGE SPRINKLERS AND SPECIAL ATTIC
INKLERS MAY BE USED AND SHALL BE DESIGNED ACCORDING TO THEIR
FTING.
WATER SUPPLY CHARACTERISTICS: �o L
f'HE NATER SUPPLY IS FROM AN 8" WATER MAIN RUNNING ALONG MAYPORT
BLVD. A NEW 6" BRANCH WILL BE RUN FROM THE MAIN TO THE RISER
LOCATION. THE DURATION OF THE SUPPLY WILL BE ADEQUATE FOR THIS
APPLICATION. THE FLEET LANDING FIRE PUMP WILL NOT PROVIDE SERVICE
FOR THIS BUILDING.
FLOW TEST INFORMATION:
A FLOW TEST WAS CONDUCTED ON 2/27/13 AT 11 - 35 AM BY CHRIS WALKER
OF ATLANTIC BEACH UTILITIES. THE TEST WAS CONDUCTED AT 2401
MAYPORT ROAD.
THE RESULTS OF THE TEST WERE AS FOLLOWS-
STATIC PRESSURE: 48 PSI
RESIDUAL PRESSURE: 35 PSI
FLOW: 1,000 GPM
VALVING AND ALARM REQUIREMENTS-
INSTALL A WATER FLOW PRESSURE SWITCH AT THE FIRE RISER, INSTALL AN
AIR PRESSURE MONITORING SWITCH, AND PUT TAMPER SWITCHES ON
CONTROL VALVES ON THE RISER WITH LOCAL AUDIBLE ALARM AND CENTRAL
STATION MONITORING - ISOLATION VALVES ON BACKFLOW PREVEN'TER SHALL
BE CHAINED AND LOCKED OPEN.
MIC RISK EVALUATION-
THERE IS A MINIMAL EXPECTED RISK OF MIC IN THE WATER SUPPLY FOR THIS
LOCATION ACCORDING TO ATLANTIC BEACH UTILITIES AND NO CORRECTIVE
MEASURES HAVE BEEN DESIGNED FOR THE SYSTEM.
3ACKFLOW PREVENTION DETAILS-
A NEW 6" DOUBLE CHECK BACKIFLOW PREVENTER DESIGNED FOR FIRE
PROTECTION APPLICATIONS WILL BE INSTALLED IN THE FIRE MAIN WITH A
MAXIMUM ALLOWABLE PRESSURE DROP OF 5 PSI.
,OMPONENT SPECIFICATIONS:
ALL PIPING, SPRINKLERS, AND OTHER COMPONENTS TO BE UL LISTED OR FM
APPROVED MATERIALS. SPRINKLER PIPING SHALL BE ALL BLACK IRON PIPING
.SCHEDULE 40 FOR SIZES 2" AND SMALLER AND SCHEDULE 10 FOR SIZES
:-ARGER THAN 2" THROUGHOUT ALL AREAS. NO LIGHT-WALL OR CPVC
'DIPING SHALL BE ALLOWED.
STRUCTURAL: 7 J"Ic
THE STRUCTURAL ENGINEER IS AWARE OF THE ADDITIONAL STRUCTURAL LOAD --------
OF THE FIRE SPRINKLER SYSTEM. AN ADDITIONAL DEAD LOAD OF 2-3
POUNDS PER SQUARE FOOT WILL BE ADDED TO THE STRUCTURAL DESIGN
CRITERIA. N,
Q T HE R
UNDERGROUND SERVICES SHOWN FOR COORDINATION PURPOSES ONLY. col
IF-OR ACTUAL SERVICE LOCATIONS SEE SITE CIVIL PLAN.
AMERICAN FIRE SERVICE INC.
108 HALSEMA ROAD NORTH
JACKSONVILLE FLORIDA 32220
HYDRAULIC CALCULATIONS FOR
NEW MAINTENCE FACILITY AT FLEET LANDING
1 FLEET LANDING BLVD.
ATLANTIC BEACH, FLORIDA 32233
DRAWING NUMBER:FP 1 OF 1 DATE: NOV 26, 2013
-DESIGN DATA-
REMOTE AREA NUMBER: 100 AREA REMOTE AREA LOCATION: ATTIC OVER OFFICES
OCCUPANCY CLASSIFICATION: LIGHT HAZARD
DENSITY: .10 gpm/sq. ft.
AREA OF APPLICATION: 2535 sq. ft.
COVERAGE PER SPRINKLER: 73.00 sq. ft.
TYPE OF SPRINKLERS CALCULATED: QUICK RESPONSE BRASS UPRIGHT K=5.6 TY3131
NUMBER OF SPRINKLERS CALCULATED: 36
HOSE-STREAM DEMAND: 100 gpm
TOTAL WATER REQUIRED (INCLUDING HOSE) : 684 .8 gpm
FLOW AND PRESSURE (AT BASE OF RISER) : 584 . 9 gpm @ 23.7 psi
TYPE OF SYSTEM:
*VOLUME OF DRY SYSTEM: 375.0
WATER SUPPLY 4 4r,
Source: ATLANTIC BEACH WATER DEPARTMENT
Location: MAYPORT ROAD (STATE ROAD AIA)
Static: 48.0 psi Residual: 35.0 psi Flow: 1000 gpm
CONTRACTOR Certification number: 55283300012005
NAME OF DESIGNER: MARK ROGERS
AUTHORITY HAVING JURISDICTION: BOB RATLIFF FIRE MARSHALL
Calculations performed by HASS under license # 50071123
granted by HRS SYSTEMS, INC.
(Notes continue after pipe calculations results. )
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
C)
(D
E
04
04 04 �4
(V u u
CD �4 co a) co
>, 71
m co 4) co 0, m
C) a) �D (a �o 0, F�
CD �4 (7 0 2, --1 Q
Q4 �4
04
u)
04 W 04 �4 4J
�4 �3 u)
0 -4 Ln -,q Qo 0 >1
1-4 -,1 Ln �j m u) m
44
�24
CD
CD
u-)
ry)
U)
U)
Co Q4
Cf) CD
C)
CO
CNJ
>1
�-q . 4
04 4-)
CL4 (0
ZD 4j
U) U) C)
fy.
�4
EA
5:�
n
< T
CD C) CD C) (D CD
C)
C) 1;
Ln (y) C�
04 C4 W M M D Q� W 04 U) -A
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 48.0 35.0 1000.0 41 .5 684.8 34 .9
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 684.8 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 584.8 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
101 13.7 K= 5.60 9.2 16.9
102 13.7 K= 5. 60 9.3 17.1
103 13.7 K= 5.60 9.7 17.5
104 13.7 K= 5. 60 10.6 18.2
105 16.7 K= 5. 60 8.0 15.8
106 16.7 K= 5. 60 8.1 15.9
107 16.7 K= 5.60 8.5 16.3
108 16.7 K= 5.60 9.2 17.0
109 13.7 K= 5. 60 9.2 17 .0
110 13.7 K= 5. 60 9.3 17.1
ill 13.7 K= 5. 60 9.8 17.5
112 13.7 K= 5.60 10.7 18.3
113 19.1 K= 5. 60 8.0 15.8
114 19.1 K= 5.60 8.1 15.9
115 19.1 K= 5.60 8.4 16.3
116 19.1 K= 5. 60 8.4 16.3
117 19.1 K= 5. 60 8.1 15.9
118 19.1 K= 5.60 8.0 15.8
119 22.1 K= 5. 60 7.0 14.8
120 22.1 K= 5. 60 7.1 14 .9
121 22.1 K= 5.60 7.4 15.2
122 22.1 K= 5. 60 7.4 15.2
123 22.1 K= 5. 60 7.1 14 .9
124 22.1 K= 5.60 7.0 14.8
125 21.5 K= 5. 60 7.5 15.3
126 21.5 K= 5. 60 7.6 15.4
127 21.5 K= 5.60 7 . 9 15.8
128 21.5 K= 5. 60 7.9 15.7
129 21.5 K= 5. 60 7.6 15.4
130 21.5 K= 5.60 7.5 15.3
131 19.1 K= 5. 60 8. 9 16.7
132 19.1 K= 5.60 9.0 16.8
133 19.1 K= 5. 60 9.4 17.2
134 19.1 K= 5. 60 9.4 17.2
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
135 19.1 K= 5. 60 9.0 16.8
136 19.1 K= 5.60 8. 9 16.7
1 11.7 - - - - 10.8 - - -
2 11.7 - - - - 10. 9 - - -
3 11.7 - - - - 11.4 - - -
4 11.7 - - - - 12.3 - - -
5 11.7 - - - - 11.2 - - -
6 11.7 - - - - 11 .3 - - -
7 11.7 - - - - 11 .7 - - -
8 11.7 - - - - 12.5 - - -
9 11.7 - - - - 10.8 - - -
10 11.7 - - - - 11.0 - - -
11 11.7 - - - - 11 .4 - - -
12 11.7 - - - - 12.4 - - -
13 11.7 - - - - 12.5 - - -
14 11 .7 - - - - 12.7 - - -
15 11.7 - - - - 13.1 - - -
16 11.7 - - - - 13.1 - - -
17 11.7 - - - - 12.6 - - -
18 11.7 - - - - 12.5 - - -
19 11 .7 - - - - 13.0 - - -
20 11.7 - - - - 13.1 - - -
21 11.7 - - - - 13.5 - - -
22 11.7 - - - - 13.5 - - -
23 11.7 - - - - 13.1 - - -
24 11.7 - - - - 13.0 - - -
25 11.7 - - - - 13.2 - - -
26 11.7 - - - - 13.3 - - -
27 11.7 - - - - 13. 7 - - -
28 11.7 - - - - 13.7 - - -
29 11.7 - - - - 13.3 - - -
30 11.7 - - - - 13.2 - - -
31 11.7 - - - - 13.5 - - -
32 11.7 - - - - 13.7 - - -
33 11.7 - - - - 14 .1 - - -
34 11.7 - - - - 14 .1 - - -
35 11.7 - - - - 13.7 - - -
36 11.7 - - - - 13.5 - - -
37 11.7 - - - - 13. 9 - - -
38 11.7 - - - - 13. 9 - - -
39 11.7 - - - - 13. 9 - - -
40 11.7 - - - - 14.2 - - -
41 11.7 - - - - 14 .5 - - -
42 11.7 - - - - 14 .8 - - -
43 11 .7 - - - - 15.4 - - -
44 11.7 - - - - 16.0 - - -
45 10.0 - - - - 17.4 - - -
46 10.0 - - - - 17.7 - - -
47 10.0 - - - - 17. 9 - - -
48 10.0 - - - - 18.2 - - -
TASR 10.0 - - - - 18.8 - - -
TDPV 5.0 - - - - 21.5 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
BASR 1.0 - - - - 23.7 - - -
Ul -3.0 - - - - 25. 6 - - -
U2 -3.0 - - - - 25. 9 - - -
BFD -3.0 - - - - 29.0 - - -
BFS -3.0 - - - - 34 .0 - - -
MD -3.0 - - - - 34 . 1 - - -
ms -3.0 - - - - 35. 1 - - -
SOURCE 0.0 SOURCE 34 . 9 584.8
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
NFPA PIPE DATA
Pipe Tag K-fac Add Fl F1 To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 1 5. 60 16. 9 Disch 6.3 2.00 100 1 . 6
1 11.7 10.8 0.0 1.000 T: 3.6 3.57 -0. 9
101 13.7 9.2 16. 9 1 .049 5.57 0.134 0.7
Pipe: 2 5. 60 17.1 Disch 6.3 2.00 100 1 . 6
2 11.7 10. 9 0.0 1.000 T: 3. 6 3.57 -0.9
102 13.7 9.3 17. 1 1 .049 5.57 0.136 0.8
Pipe: 3 5.60 17.5 Disch 6.5 2.00 100 1.7
3 11.7 11 .4 0.0 1.000 T: 3. 6 3.57 -0.9
103 13.7 9.7 17.5 1.049 5.57 0.142 0.8
Pipe: 4 5.60 18.2 Disch 6.8 2.00 100 1.7
4 11.7 12.3 0.0 1.000 T: 3. 6 3.57 -0.9
104 13.7 10.6 18.2 1.049 5.57 0.154 0. 9
Pipe: 5 5.60 15.8 Disch 5. 9 5.00 100 3.2
5 11.7 11.2 0.0 1.000 T: 3.6 3.57 -2.2
105 16.7 8.0 15.8 1 .049 8.57 0.118 1.0
Pipe: 6 5. 60 15.9 Disch 5. 9 5.00 100 3.2
6 11.7 11.3 0.0 1.000 T: 3. 6 3.57 -2.2
106 16.7 8.1 15.9 1.049 8.57 0.120 1.0
Pipe: 7 5. 60 16.3 Disch 6.0 5.00 100 3.2
7 11.7 11.7 0.0 1.000 T: 3.6 3.57 -2.2
107 16.7 8.5 16.3 1.049 8.57 0.125 1.1
Pipe: 8 5. 60 17.0 Disch 6.3 5.00 100 3.3
8 11.7 12.5 0.0 1.000 T: 3. 6 3.57 -2.2
108 16.7 9.2 17.0 1.049 8.57 0.135 1.2
Pipe: 9 5. 60 17.0 Disch 6.3 2.00 100 1. 6
9 11.7 10.8 0.0 1.000 T: 3.6 3.57 -0. 9
109 13.7 9.2 17.0 1.049 5.57 0.135 0.8
Pipe: 10 5.60 17 .1 Disch 6.4 2.00 100 1. 6
10 11.7 11.0 0.0 1.000 T: 3. 6 3.57 -0.9
110 13.7 9.3 17.1 1.049 5.57 0.137 0.8
Pipe: 11 5.60 17.5 Disch 6.5 2.00 100 1.7
11 11.7 11.4 0.0 1.000 T: 3. 6 3.57 -0.9
ill 13.7 9.8 17.5 1.049 5.57 0.143 0.8
Pipe: 12 5. 60 18.3 Disch 6.8 2.00 100 1.7
12 11 .7 12.4 0.0 1.000 T: 3. 6 3.57 -0.9
112 13.7 10.7 18.3 1.049 5.57 0.155 0.9
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 13 5. 60 15.8 Disch 5. 9 7. 92 100 4. 6
13 11.7 12.5 0.0 1. 000 T: 3.6 3.57 -3.2
113 19.1 8.0 15.8 1 .049 11 .49 0.118 1 .4
Pipe: 14 5. 60 15.9 Disch 5. 9 7. 92 100 4.6
14 11.7 12.7 0.0 1 .000 T: 3.6 3.57 -3.2
114 19.1 8.1 15. 9 1 .049 11 .49 0.119 1 .4
Pipe: 15 5. 60 16.3 Disch 6.0 7. 92 100 4.6
15 11.7 13.1 0.0 1 .000 T: 3.6 3.57 -3.2
115 19.1 8.4 16.3 1 .049 11 .49 0.124 1 .4
Pipe: 16 5. 60 16.3 Disch 6.0 7. 92 100 4.6
16 11.7 13.1 0.0 1.000 T: 3. 6 3.57 -3.2
116 19.1 8.4 16.3 1.049 11.49 0.124 1.4
Pipe: 17 5. 60 15. 9 Disch 5. 9 7. 92 100 4. 6
17 11.7 12. 6 0.0 1.000 T: 3. 6 3.57 -3.2
117 19.1 8.1 15. 9 1.049 11.49 0.119 1.4
Pipe: 18 5. 60 15.8 Disch 5., 9 7. 92 100 4. 6
18 11.7 12.5 0.0 1.000 T: 3. 6 3.57 -3.2
118 19.1 8.0 15.8 1.049 11.49 0.118 1.4
Pipe: 19 5. 60 14.8 Disch 5.5 10.42 100 6.0
19 11 .7 13.0 0.0 1.000 T: 3.6 3.57 -4.5
119 22.1 7.0 14.8 1 .049 13.99 0.105 1.5
Pipe: 20 5. 60 14 .9 Disch 5.5 10.42 100 6.0
20 11.7 13.1 0.0 1.000 T: 3. 6 3.57 -4.5
120 22.1 7.1 14 . 9 1.049 13. 99 0.106 1.5
Pipe: 21 5. 60 15.2 Disch 5.7 10.42 100 6.1
21 11.7 13.5 0.0 1.000 T: 3. 6 3.57 -4.5
121 22.1 7.4 15.2 1.049 13.99 0.110 1.5
Pipe: 22 5. 60 15.2 Disch 5.7 10.42 100 6.1
22 11 .7 13.5 0.0 1.000 T: 3. 6 3.57 -4.5
122 22.1 7.4 15.2 1.049 13.99 0.110 1.5
Pipe: 23 5. 60 14. 9 Disch 5.5 10.42 100 6.0
23 11.7 13.1 0.0 1.000 T: 3. 6 3.57 -4.5
123 22.1 7.1 14.9 1.049 13.99 0.106 1.5
Pipe: 24 5. 60 14 .8 Disch 5.5 10.42 100 6.0
24 11.7 13.0 0.0 1.000 T: 3. 6 3.57 -4.5
124 22.1 7.0 14 .8 1.049 13.99 0.105 1.5
Pipe: 25 5. 60 15.3 Disch 5.7 9.83 100 5.8
25 11.7 13.2 0.0 1 .000 T: 3. 6 3.57 -4.3
125 21.5 7.5 15.3 1 .049 13.40 0.111 1.5
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic . 10 2535 100 Hose
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 26 5. 60 15.4 Disch 5.7 9.83 100 5.8
26 11.7 13.3 0.0 1 .000 T: 3. 6 3.57 -4.3
126 21 .5 7. 6 15.4 1 .049 13.40 0.113 1.5
Pipe: 27 5. 60 15.8 Disch 5.8 9.83 100 5.8
27 11.7 13.7 0.0 1.000 T: 3. 6 3.57 -4 .3
127 21.5 7. 9 15.8 1.049 13.40 0.117 1. 6
Pipe: 28 5. 60 15.7 Disch 5.8 9.83 100 5.8
28 11.7 13.7 0.0 1 .000 T: 3. 6 3.57 -4.3
128 21.5 7. 9 15.7 1.049 13.40 0.117 1.6
Pipe: 29 5. 60 15.4 Disch 5.7 9.83 100 5.8
29 11.7 13.3 0.0 1.000 T: 3. 6 3.57 -4.3
129 21.5 7. 6 15.4 1.049 13.40 0.113 1.5
Pipe: 30 5.60 15.3 Disch 5.7 9.83 100 5.8
30 11.7 13.2 0.0 1.000 T: 3. 6 3.57 -4.3
130 21.5 7.5 15.3 1 .049 13.40 0.111 1.5
Pipe: 31 5.60 16.7 Disch 6.2 7.33 100 4.6
31 11.7 13.5 0.0 1 .000 T: 3. 6 3.57 -3.2
131 19.1 8. 9 16.7 1 .049 10. 90 0.131 1.4
Pipe: 32 5. 60 16.8 Disch 6.2 7 .33 100 4.7
32 11.7 13.7 0.0 1.000 T: 3. 6 3.57 -3.2
132 19.1 9.0 16.8 1.049 10. 90 0.132 1.4
Pipe: 33 5. 60 17 .2 Disch 6.4 7.33 100 4 .7
33 11.7 14 .1 0.0 1.000 T: 3.6 3.57 -3.2
133 19.1 9.4 17.2 1 .049 10.90 0.138 1.5
Pipe: 34 5. 60 17.2 Disch 6. 4 7.33 100 4.7
34 11.7 14 .1 0.0 1.000 T: 3. 6 3.57 -3.2
134 19.1 9.4 17.2 1.049 10. 90 0.138 1.5
Pipe: 35 5. 60 16.8 Disch 6.2 7.33 100 4.7
35 11.7 13.7 0.0 1.000 T: 3.6 3.57 -3.2
135 19.1 9.0 16.8 1.049 10. 90 0.132 1.4
Pipe: 36 5.60 16.7 Disch 6.2 7.33 100 4.6
36 11.7 13.5 0.0 1.000 T: 3.6 3.57 -3.2
136 19.1 8. 9 16.7 1.049 10.90 0.131 1 .4
Pipe: 37 0.0 0.0 2.7 8.00 100 0.1
2 11.7 10.9 16. 9 1.500 ---- 0.00 0.0
1 11.7 10.8 16.9 1. 610 8.00 0.017 0.1
Pipe: 38 0.0 16. 9 1 5.4 8.00 100 0.5
3 11.7 11.4 17.1 102 1.500 ---- 0.00 0.0
2 11.7 10. 9 34 .0 1. 610 8.00 0.060 0.5
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic . 10 2535 100 Hose
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 39 0.0 34 .0 2 8. 1 7.25 100 0.9
4 11 .7 12.3 17. 5 103 1 .500 ---- 0.00 0.0
3 11.7 11.4 51 .5 1 .610 7.25 0.130 0.9
Pipe: 40 0.0 51.5 3 11.0 1.04 100 1 .5
37 11.7 13.9 18.2 104 1.500 T: 5.7 5.71 0.0
4 11.7 12.3 69.7 1.610 6.75 0.228 1.5
Pipe: 41 0.0 0.0 2.5 8.00 100 0.1
6 11.7 11.3 15.8 1.500 ---- 0.00 0.0
5 11.7 11.2 15.8 1. 610 8. 00 0.015 0.1
Pipe: 42 0.0 15.8 5 5.0 8.00 100 0.4
7 11 .7 11.7 15. 9 106 1.500 ---- 0.00 0.0
6 11.7 11.3 31 .7 1. 610 8.00 0.053 0.4
Pipe: 43 0.0 31.7 6 7.6 7.25 100 0.8
8 11.7 12.5 16.3 107 1 .500 ---- 0.00 0.0
7 11.7 11.7 48.0 1 . 610 7.25 0.114 0.8
Pipe: 44 0.0 48.0 7 10.2 1 .04 100 1.4
38 11.7 13.9 17.0 108 1.500 T: 5.7 5.71 0.0
8 11.7 12.5 65.0 1.610 6.75 0.200 1.4
Pipe: 45 0.0 0.0 2.7 8.00 100 0. 1
10 11.7 11.0 17.0 1 .500 ---- 0.00 0.0
9 11.7 10.8 17.0 1. 610 8.00 0.017 0.1
Pipe: 46 0.0 17.0 9 5.4 8.00 100 0.5
11 11.7 11.4 17.1 110 1.500 ---- 0.00 0.0
10 11.7 11.0 34 .1 1. 610 8.00 0.061 0.5
Pipe: 47 0.0 34.1 10 8.1 7.25 100 0.9
12 11.7 12.4 17.5 111 1.500 ---- 0.00 0.0
11 11.7 11.4 51 . 6 1. 610 7.25 0.131 0.9
Pipe: 48 0.0 51.6 11 11.0 1.04 100 1.5
39 11.7 13.9 18.3 112 1.500 T: 5.7 5.71 0.0
12 11.7 12.4 69. 9 1.610 6.75 0.229 1.5
Pipe: 49 0.0 0.0 2.5 8.00 100 0.1
14 11.7 12.7 15.8 1.500 ---- 0.00 0.0
13 11.7 12.5 15.8 1.610 8.00 0.015 0.1
Pipe: 50 0.0 15.8 13 5.0 8.00 100 0.4
15 11.7 13.1 15. 9 114 1.500 ---- 0.00 0.0
14 11.7 12.7 31 .7 1.610 8.00 0.053 0.4
Pipe: 51 0.0 31.7 14 7.6 3.92 100 1.1
40 11.7 14.2 16.3 115 1.500 T: 5.7 5.71 0.0
15 11.7 13.1 48.0 1. 610 9.63 0.114 1.1
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 52 0.0 31.7 17 7.6 4.15 100 1.1
40 11.7 14.2 16.3 116 1.500 T: 5.7 5.71 0.0
16 11.7 13.1 47.9 1.610 9.86 0.114 1.1
Pipe: 53 0.0 15.8 18 5.0 8.00 100 0.4
16 11.7 13.1 15.9 117 1.500 ---- 0.00 0.0
17 11.7 12.6 31.7 1.610 8.00 0.053 0.4
Pipe: 54 0.0 0.0 2.5 8.00 100 0.1
17 11.7 12. 6 15.8 1.500 ---- 0.00 0.0
18 11.7 12.5 15.8 1.610 8.00 0.015 0.1
Pipe: 55 0.0 0.0 2.3 8.00 100 0.1
20 11.7 13. 1 14.8 1.500 ---- 0.00 0.0
19 11.7 13.0 14.8 1 . 610 8.00 0.013 0. 1
Pipe: 56 0.0 14.8 19 4 .7 8.00 100 0.4
21 11.7 13.5 14.9 120 1 .500 ---- 0.00 0.0
20 11.7 13.1 29.7 1.610 8.00 0.047 0.4
Pipe: 57 0.0 29.7 20 7.1 4.08 100 1.0
41 11.7 14.5 15.2 . 121 1.500 T: 5.7 5.71 0.0
21 11.7 13.5 45.0 1.610 9.79 0. 101 1.0
Pipe: 58 0.0 29.7 23 7.1 4.13 100 1.0
41 11.7 14.5 15.2 122 1.500 T: 5.7 5.71 0.0
22 11.7 13.5 45.0 1.610 9.83 0.101 1.0
Pipe: 59 0.0 14.8 24 4.7 8.00 100 0.4
22 ll.-/ 13.5 14. 9 123 1.500 ---- 0.00 0.0
23 11.7 13.1 29.7 1.610 8.00 0.047 0.4
Pipe: 60 0.0 0.0 2.3 8.00 100 0.1
23 11.7 13.1 14.8 1.500 ---- 0.00 0.0
24 11.7 13.0 14.8 1.610 8.00 0.013 0.1
Pipe: 61 0.0 0.0 2.4 8.00 100 0.1
26 11.7 13.3 15.3 1.500 ---- 0.00 0.0
25 11.7 13.2 15.3 1.610 8.00 0.014 0.1
Pipe: 62 0.0 15.3 25 4.8 8.00 100 0.4
27 11 .7 13.7 15.4 126 1.500 ---- 0.00 0.0
26 11.7 13.3 30.7 1.610 8.00 0.050 0.4
Pipe: 63 0.0 30.7 26 7.3 4 .08 100 1 .1
42 11.7 14.8 15.8 127 1.500 T: 5.7 5.71 0.0
27 11.7 13.7 46.5 1.610 9.79 0.108 1.1
Pipe: 64 0.0 30.7 29 7.3 4 .13 100 1.1
42 11.7 14.8 15.7 128 1 .500 T: 5.7 5.71 0.0
28 11.7 13.7 46.5 1 . 610 9.83 0.108 1.1
AMERICAN FIRE SERVICE INC.
Fire Protection Sprinkler Contractor
108 Halsema Road North
Jacksonville, Florida 32220
(904) 781-2460—Fax (904) 781-2483
MAINTENANCE FACILITY
FLEET LANDING
I FLEET LANDING BLVD
ATLANTIC BEACH
SUBMITTAL SHEETS
CITY O.F AILANMB�V
�UILDJNG OFF'C-E
Worldwide www.tyco-fire.corn
Contacts
Series DS-1 Dry-Type Sprinklers
5.6K Pendent, Upright, and Horizontal Sidewall
Quick Response, Standard Coverage
The owner is responsible for maintain-
General ing their fire protection system and de-
vices in proper operating condition. The
VT
Description installing contractor or sprinkler manu- LOWOW
TYCO Series DS-1 Dry-Type Sprinklers, facturer should be contacted with any 4U4
5.6K Pendent, Upright,and Horizontal questions.
Sidewall,Quick Response(3 mm Bulb) The Series DS-1 Dry-Type Sprinklers
and Standard Coverage, are decora- must only be installed in fittings that
tive glass bulb automatic sprinklers de- meet the requirements of the Design
signed for commercial use. Dry-Type Criteria section. q,
Sprinklers are typically used where: V
• pendent sprinklers are required on S rinkier
dry pipe systems that are exposed to p
freezing temperatures; for example, Identification
sprinkler drops from unheated por-
tions of buildings
Numbers (SiNs)
•sprinklers and/or a portion of the con- A
3/4 Inch NPT:
necting piping are exposed to freezing T 3935- Pendent
temperatures;for example, sprinkler
TY3735- Horizontal Sidewall
drops from wet systems into freezers,
sprinkler sprigs from wet systems into 1 Inch NPT:
unheated attics, or horizontal piping TY3235 - Pendent
extensions through a wall to protect an TY3135 - Upright
unheated areas such as loading docks, TY3335- Horizontal Sidewall
overhangs,and building exteriors Technical
• sprinklers are used on systems that are
seasonally drained to avoid freezing; Data
for example,vacation areas Approvals
MUM UL and C-UL Listed
The Series DS-1 Dry-Type Sprinklers FIVI Approved
described herein must be installed NYC Approved under MEA 352-01-E
and maintained in compliance with this Previous New York City Approval
document, as well as with the applica- and MEA certification numbers ap- Maximum Working Pressure
ble standards of the National Fire ply to product as shown in this data 175 psi(12,1 bar)
Protection Association, in addition to sheet. In accordance with Section
the standards of any authorities having
jurisdiction.Failure to do so may i.mpaj.r BC 3502 of the Construction Code, Inlet Thread Connections
the performance of these devices. current NYC Approvals for use in the 3/4 Inch NPT
City of New York apply to all products 1 Inch N PT or ISO 7-R1
that contain UL or FM Approvals and
Listings; therefore, not all products Discharge Coefficient
currently Approved for use in the City K=5.6 GpM/pSil/2
IMPORTANT of New York will carry an actual MEA (80,6 LPM/barl/2)
Always refer to Technical Data Certification number.
Sheet TFP700 for the "INSTALLER Refer to Tables A and B. Temperature Ratings
WARNING"that provides cautions Refer to Tables A and B.
with respect to handling and in- Finishes
stallation of sprinkler systems and Sprinkler: Natural Brass, Chrome
components.Improper handling and Plated,Signal White
installation can permanently dam-
age a sprinkler system or its compo- Escutcheon: Signal White, Chrome
nents and cause the sprinkler to fail Plated, Brass Plated
to operate in a fire situation or cause
it to operate prematurely.
Page I of 110 JUNE 2013 TFP510
TFP510
Page 2 of 10
Physical Characteristics
PLUG WITH INLET Inlet. . . . . . . . . . . . . . . . . . . . . Copper
SEALING Plug . . . . . . . . . . . . . . . . . . . . Copper
ASSEMBLY YOKE Yoke . . . . . . . . . . . . . . Stainless Steel
Casing. . . . .Galvanized Carbon Steel
Insert . . . . . . . . . . . . . . . . . . Bronze
PLUG INLET Bulb Seat. . . . . . . . . . .Stainless Steel
SPRING BAND Bulb. . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . .Bronze
SPRING Deflector . . . . . . . . . . . . . . . . Bronze
WATER Frame . . . . . . . . . . . . . . . . . . .Bronze
TUBE
CASING
Guide Tube . . . . . . . . .Stainless Steel
Water Tube . . . . . . . . .Stainless Steel
GUIDE INSERT Spring . . . . . . . . . .Stainless Steel
TUBE Plug Spring*. . . . . . . . .Stainless Steel
BULB Sealing Assembly . . . . . . . . Beryllium
Nickel w/TEFLON
SEAT
FRAME
Escutcheon . . . . . . . . . .Carbon Steel
*For 3/4 Inch NPT only
3 mm BULB
VENT HOLE Operation
COMPRESSION When the TYCO Series DS-1 Dry-Type
DEFLECTOR SCREW Sprinkler is in service,water is prevent-
ed from entering the assembly by the
FIGURE I Plug with Sealing Assembly in the Inlet
SERIES DS-1,314-INCH NPT, DRY-TYPE SPRINKLER of the Sprinkler.See Figures 1 and 2.
ASSEMBLY The glass Bulb contains a fluid that ex-
pands when exposed to heat.When the
rated temperature is reached,the fluid
PLUG WITH INLET expands sufficiently to shatter the glass
SEALING Bulb,and the Bulb Seat is released.
ASSEMBLY YOKE The compressed Spring is then able
to expand and push the Water Tube as
SPRING well as the Guide Tube outward.This
INLET action simultaneously pulls inward on
BAND the Yoke, withdrawing the Plug with
Sealing Assembly from the Inlet and
WATER allowing the sprinkler to activate and
TUBE CASING flow water.
Design
GUIDE INSERT
TUBE
riteria
BULB The TYCO Series DS-1 Sprinklers are
S EAT
FRAME intended for use in fire sprinkler sys
tems designed in accordance with the
standard installation rules recognized
VENT HOLE 3 mm BULB by the applicable Listing or Approval
agency; for example, LIL Listing is
COMPRESSION based on NFPA 13 requirements.
DEFLECTOR SCREW Sprinkler Fittings
Install the 3/4 or 1 Inch NPT Series
FIGURE 2 DS-1 Dry-Type Sprinklers in the 3/4 or
SERIES DS-1, I-INCH NPT AND ISO 7-R I DRY-TYPE SPRINKLER 1 Inch NIPT outlet or run of the follow-
ASSEMBLY ing fittings:
• malleable or ductile iron threaded tee
fittings that meet the dimensional re-
quirements of ANSI B16.3(Class 150)
• cast iron threaded tee fittings that
meet the dimensional requirements
of ANSI B16.4(Class 125).
TFP510
Page 3 of 10
3/4-Inch NPT
TY3935 Pendent TY3935 Pendent TY3735 Horizontal Sidewall
with Top of Deflector-to-Ceiling
with Standard with Standard Escutcheon Distance of 4 to 12 inches
Recessed Escutcheon (Figure 3) (100 to 300 mm)
(Figure 4) with Deep Escutcheon with Standard Escutcheon
(Figure 5) (Figure 8)
without Escutcheon with Deep Escutcheon
(Figure 6) (Figure 9)
without Escutcheon
(Figure 10)
Finish
Temperature Bulb
Rating Color Code Natural Chrom White Natural Chrome White Natural Ch
Brass Plated Polyester Brass Plated Polyester Brass P1 r
135'F(57-C) Orange
155'F(68-C) Red
175-F(79-C) Yellow 1,2 1,2 1-,2*
200'F(93-C) Green
286oF(141-C) Blue N/A
Notes
1. Listed by Underwriters Laboratories,Inc.(maximum order!ength of 48 inches)
2. Listed by Underwriters Laboratories for use in Canada(maximum order length of 48 inches)
. Light and Ordinary Hazard Occupancies Only
N/A-Not Available
TABLE A
SERIES DS-I QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
�w I Inch NPT
TY3235 Pe dent TY3235 Pendent TY3335 Horizontal Sidewail
with Top of Deflector-to-Ceiling
with Standard with Standard Escutcheon Distance of 4 to 12 inches
Recessed Escutcheon (Figure 3) (100 to 300 mm)
(Figure 4) with Deep Escutcheon with Standard Escutcheon
(Figure 5) (Figure 8)
without Escutcheon
(Figure 6) with Deep Escutcheon
(Figure 9)
TY3135 Upn ht
Aeon without Escutcheon
without Escutc
(Figure 7) (Figure 10)
Finish
Rating Color Code N a :atural Chrome White
Temperature Bulb Brass Plated Polyester Brass Plated Polyest Brass I Plated Polyester
atural Chrome White Natural F Chrom White., N;.7tur.1
135-F(57-C) Orange
155-F(68-C) Red 1,2,3,4 1,2,4
175'F(79-C) Yellow 1,2,3,4 1,2,4 1',2-,3'*,4 1*,2*,4
200-F(93-C) Green
N/A
286'F(141*C) Blue
Notes: 4. Approved by the City of New York under MEA 352-01-E
1. Listed by Underwriters Laboratories,Inc.(maximum order length 5. The Upright Sprinkler without an Escutcheon(TY3135)is avail-
of 48 inches) able in 1 Inch NPT only
2. Listed by Underwriters Laboratories for use in Canada(maxi- ;-;ght and Ordinary Hazard Occupancies Only
mum order length of 48 inches) L ight Hazard Occupancies Only
3. Approved by Factory Mutual Research Corporation(maximum N/A-Not Available
order length of 48 inches)
TABLE B
I INCH NPTAND ISO 7-171, SERIES DS-I QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS
I(Iiiw LABORATORY LISTINGS AND APPROVALS
TFP510
Page 4 of 10
SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING
(REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN
CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION)
FACE OF FACE OF FACE OF
SPRINKLER SPRINKLER SPRINKLER
FITTING FITTING. FITTING
ORDERLENGTHS: ORDERLENGTHS: ORDER LENGTHS: 3-1/2"DIA
3-3/4"to 48" 1/2"to 46" (883,9 mm)
2-3/4"to 48" 1-3/4" DIA. (12,7 to 1168,4 mm)
(69,9 to 1219,2 mm) (44,5 mm) (95,3 to 1219,2 mm)
IN 1/4"(6,4 mm) 2-1/4"DIA. IN 1/4"(6,4 mm r2-1/2"DIA
IN 1/4"(6,4 mm) (63,5 mm)
INCREMENTS INCREMENTS (57,2 mm) INCRE ENTS
FACE OF 7F� I ;P"
CEILING FACE OF
FACE OF CEILING
CEILING --I ii I
4-1/4"+1/8"
(108,0 t 3,2 mm)
3"DIA. 1-3/8" 1/8" 2-7/8"DIA.
2-3/16"±1/8" (76,2 mm (34,9±3,2 mm) (73,0 mm)
(55,6±3,2 mm) ) I I
FIGURE 4
FIGURE 3 PENDENT TY3235 AND TY3935 FIGURE 5
PENDENT TY3235 AND TY3935 WITH STANDARD RECESSED PENDENT TY3235 AND TY3935
WITH STANDARD ESCUTCHEON ESCUTCHEON WITH DEEP ESCUTCHEON
SPRINKLER FI-MNG
(REFER TO DESIGN TOP OF
CRITERIA SECTION) DEFLECTOR
FACE OF
SPRINKLER
�w FITTING
ORDER LENGTHS:
5"to 48"
(127,0 to 1219,2 mm)
ORDER LENGTHS: IN 1/4"(6,4 mm)
5"to 48" INCREMENTS
(127,0 to 1219,2 mm)
IN 1/4"(6,4 mm) I
INCREMENTS FACE OF
ACE OF
SPRINKLER
FITTING
MINIMUM
1-3/4'(44,5 mm)j
DEFLECTOR
TO CEILING SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FIGURE 7
FIGURE 6 UPRIGHT TY3135
PENDENT TY3235 AND TY3935 WITHOUT ESCUTCHEON
WITHOUT ESCUTCHEON I INCH NPT ONLY
TFP510
Page 5 of 10
Do not install the DS-1 Sprinklers into
ORDERLENGTHS: an elbow fittings.The Inlet of the sprin-
(W 2-3/4"to 48"(69,9 to 1219,2 mm) kler can contact the interior of the el-
IN 1/4"(6,4 mm.)INCREMENTS 2-3/8"±1/8" bow, potentially damaging the Inlet
(60,3±3,2 mm) seal.
FACE OF FACIE OF The unused outlet of the threaded tee is
SPRINKLER MOUNTING plugged as shown in Figure 13.
F FITTING SURFACE You can also install the Series DS-1
'TTING SURFACE
Dry-Type Sprinklers in the 3/4 or 1 Inch
I NELL Figure 730
3" DIA. NPT outlet of a GRIN
(76,2 mm) Mechanical Tee. However,the use of
3.5' the Figure 730 Tee for this arrangement
is limited to wet pipe systems.
I L
1-3/4" DIA.
SPRINKLER FITTING , _ The configuration shown in Figure 12
(REFER TO DESIGN (44,5 mm) CENTE LINE 5/16" is only applicable for wet pipe systems
CRITERIA SECTION) OF WATERWAY (7,9 mm) where the sprinkler fitting and water-
FIGURE 8 filled pipe above the sprinkler fitting are
TY3335 AND TY3735 HORIZONAL SIDEINALL not subject to freezing and where the
WITH STANDARD ESCUTCHEON length of the Dry-Type Sprinkler has the
minimum exposure length depicted in
Figure 11. Refer to the Exposure Length
ORDER LENGTHS: section.
1/2"to 45-3/4"(12,7 toll 62,1 mm) For wet pipe system installations of
IN 1/4"(6,4 mm INCREMENTS 4-1/4,,±1/8,, the 1 Inch NPT Series DS-1 Dry-Type
�FACE OF (108,0 3,2 mm) Sprinklers connected to CPVC piping,
U �
2-1/2" DIA. T use only the following TYCO CPVC
FACE OF MOUNTING
S SPRINKLER (63,5 mm) SURFACE fittings:
FITTING 1 x 1"NPT Female Adapter(P/N 80145)
P
F
R
IT
IN
TK
I N
LE
G
R
x 1 x 1 NPT Sprinkler Head Adapter
3 1/2" DIA Tee(P/N 80249).
(88,9 mm) For wet pipe system installations of the
3. the 3/4 Inch NPT Series DS-1 Sprinklers
connected to CPVC piping, use in the
I(iIiW SPRINKLER FIT�TTING 3/4" x 3/4" NPT Female Adapter(P/N
(REFER TO DESIGN CENTERLINE 5/16" 80142).
CRITERIA SECTION) FIGURE 9 OF WATERWAY (7,9 mm) For dry pipe system installations, use
TY3335 AND TY3735 HORIZONAL SIDEWALL only the side outlet of maximum 2-1/2-
inch reducing tee when locating the
WITH DEEP ESCUTCHEON Series DS-1 Sprinklers directly below
the branch line.Otherwise,use the con-
ORDER LENGTHS: figuration shown in Figure 13 to assure
5-1/2"to 48"(139,7 to 1219,2 mm)- complete water drainage from above
IN 1/4"(6,4 mm)INCREMENTS MINIMUM the Series DS-1 Dry-Type Sprinklers
2-1/4"(57,2 mm) and the branch line. Failure to do so
DEFLECTOR TO may result in pipe freezing and water
FACE OF MOUNTING damage.
SPRINKLER SURFACE
FITTING
Do not install the Series DS-1 Dry-Type
Sprinkler into any other type fitting
fwithout first consulting the Technical
3.5' 5/16" Services.Department. Failure to use the
(7,9 ry1m) appropriate fitting may result in one of
SPRINKLER FITTING the following:
(REFER TO DESIGN CENTERLINE 9 Failure of the sprinkler to operate prop-
CRITERIA SECTION) OF WATERWAY erly due to formation of ice over the
FIGURE 10 inlet Plug or binding of the Inlet Plug.
TY3335 AND TY3735 HORIZONAL SIDEWALL * Insufficient engagement of the Inlet
WITHOUT ESCUTCHEON pipe threads with consequent leakage.
Drainage
In accordance with the minimum
requirements of the National Fire
Protection Association for dry pipe
�w sprinkler systems, branch,cross, and
TFP510
Page 6 of 10
RUN
FACE OF TO WET SIDE OUTLET
SPRINKLER SYSTEM OUTLET PLUGGED
FITTING PLUGGED SPRINKLER
TO DRY FITTING
EXPOSURE Icon SYSTEM (SEE DESIGN
Mom LENGTH CRITERIA
(SEE DESIGN SPRINKLER SECTION)
DSB-2 CRITERIA DSB-2
INTENDED SECTION) INTENDED FITTING 00ml DSB-2
FOR FREEZER FOR FREEZER (SEE DESIGN INTENDED
CRITERIA FOR FREEZER
P
C
L
I
ST
F
�R(SEE
Sp
F
(SEE
-R Cl
STRUCTURES STRUCTURES SE
SECTION) ST RUCTURES
FIGURE 12 FIGURE 13
FIGURE I I SPRINKLER FITTING SPRINKLER FITTING
EXPOSURELENGTH HEATED AREA UNHEATED AREA
STRAP TIES 1-3/4"DIA.
(ENDS ON (44,5 mm)
OPPOSING CLEARANCE INSULATED WRENCH
SIDES OF HOLE FREEZER RECESS
BOOT) ADHESIVE STRUCTURE
DSB-2 BOOT
DSB-2
ADHESIVE BOOT
1-3/4" DIA. WRENCH
(44,5 mm) FLAT
CLEARANCE 20
INSULATED PUSH WRENCH
FREEZER IN TO ENSURE
HOLE '00
STRUCTURE STRAP TIES ENGAGEMENT
DS-1 (ENDS ON DS-1 WITH SPRINKLER
SHOWN WITH OPPOSING SHOWN WITH WRENCHING AREA
SIDES OF STANDARD FIGURE 16
STANDARD ESCUTCHEON W-TYPE 7
ESCUTCHEON BOOT) SPRINKLER WRENCH
FIGURE 14 FIGURE 15
MODEL DSB-2 SPRINKLER MODEL DSB-2 SPRINKLER
BOOT WITH PENDENT SERIES BOOT WITH SIDEWALL SERIES
DS-I DRY SPRINKLER DS-I DRY SPRINKLER
-------------
TFP51 0
Page 7 of 10
(iw Ambient Temperature Temperatures for Heated Area(a)
Exposed to Discharge End of 40-F(4-C) I 50-F(10-C) I - 60-F(16-C)
Sprinkler Minimum Exposed Barrel Length, Inches(Mrn)(b)
40-F(4-C) 0 0 0
30-F(-1-C) 0 0 0
20-F(-7-C) 4(100) 0 0
10-F(-12-C) 8(200) 1 (25) 0
0-F(-18-C) 12(305) 3(75) 0
-10-F(-23-C) 14(355) 4(100) 1 (25)
-20-F(-29-C) 14(355) 6(150) 3(75)
-30-F(-34-C) 16(405), 8(200) 4(100)
40-F(40-13) 18(455) 8(200) 4(100)
-50-F(46-C) + 20(510) 10(255) 6(150)
0
-60-F(-51-C) 20(510) 10(255) 6(150)
Notes:
(a) For protected area temperatures that occur between values listed above, use the next cooler temperature.
(b)These lengths are inclusive of wind velocities up to 30 mph(18,6 kph).
TABLE C
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS
MINIMUM RECOMMENDED LENGTHS
feed-main piping connected to Dry Use of the Model DSB-2 Dry Sprinkler minimum-to-maximum torque of 20
Sprinklers and subject to freezing tem- Boot,described in technical data sheet to 30 ft.-lbs.(26,8 to 40,2 Nm).
peratures must be pitched for proper TFP591 and shown in Figures 14 and Higher levels of torque can distort the
drainage. 15,can Drovide the,recommended seal. sprinkler Inlet with consequent leakage
or impairment of the sprinkler.
Exposure Length compensate for
When using Dry Sprinklers in wet pipe Installation Do not attempt to
sprinkler systems to protect areas sub- The TYCO Series DS-1 Dry-Type insufficient adjustment in an
ject to freezing temperatures,use Table Sprinklers must be installed in accor- Escutcheon Plate by under or over-
tightening the Sprinkler. Re-adjust the
C to determine a sprinkler's appropriate dance with this section. position of the sprinkler fitting to suit.
exposed barrel length to prevent water
from freezing in the connecting pipes General Instructions Step 1. Install pendent sprinklers only
due to conduction.The exposed bar- The Series DS-1 Dry-Type Sprinkler in the pendent position,and install up-
rel length measurement must be taken must only be installed in fittings that right sprinklers only in the upright posi-
from the face of the sprinkler fitting to meet the requirements of the Design tion.The deflector of a pendent or up-
the surface of the structure or insula- Criteria section. Refer to the Design right sprinkler must be parallel to the
tion that is exposed to the heate area. Criteria section for other important re- ceiling.
Refer to Figure 11 for an example. quirements regarding piping design and Install horizontal sidewall sprinklers in
sealing of the clearance space around the horizontal position with their cen-
Clearance Space the Sprinkler Casing. terline of waterway perpendicular to
In accordance with Section 8.4.9.2 of inkler the back wall and parallel to the ceil-
the 2010 edition of NFPA 13,when con- Do not install any bulb type spr
necting an area subject to freezing and if the bulb is cracked or there is a loss ing. Ensure the word "TOP"on the De-
an area containing a wet pipe sprinkler of liquid from the bulb.With the sprin- flector faces the ceiling.
system,the clearance space around the kler held horizontally,a small air bubble Step 2. With a non-hardening pipe-
sprinkler barrel of Dry-Type Sprinklers should be present.The diameter of the thread sealant such as TEFLON tape
must be sealed.Due to temperature dif- air bubble is approximately 1/16 inch applied to the Inlet threads,hand-tight-
ferences between two areas,the poten- (1,6 mm)for the 135'F (57'C)rating to en the sprinkler into the sprinkler fitting.
tial for the formation of condensation in 1/8 inch(3,2 mni)for the 266�1`(141'C) Step 3.Wrench-tighten the sprinkler
the sprinkler and subsequent ice build- rating. using either:
up is increased. If this condensation is 9 A leak-tight 3/4 Inch NPT sprinkler
not controlled, ice build-up can occur joint should be obtained by applying e a pipe wrench on the Inlet Band or
that might damage the dry-type sprin- a minimum-to-maximum torque of 10 the Casing(Figures 1 and 2)
kler and/or prevent proper operation in to 20 ft.-lbs. (13,4 to 26,8 Nm). * the W-Type 7 Sprinkler Wrench on
a fire situation. 0 A leak-tight 1 Inch NPT sprinkler joint the Wrench Flat(Figure 16).
should be obtained by applying a
TFP510
Page 8 of 10
Apply the Wrench Recess of the Replace sprinklers that: Ordering
W-Type 7 Sprinkler Wrench to the were damaged by dropping,striking,
Wrench Flat. wrench twisting,wrench slippage,or Procedure
Note: If sprinkler removal becomes the like.. Contact your local distributor for avail-
necessary, remove the sprinkler us- *Were modified or over-heated.
ing the same wrenching method not- ability.When placing an order,indicate
ed above. Sprinkler removal is easier e have cracked bulbs or have lost liquid the full product name and Part Number
when a non-hardening sealant was from the bulbs. Refer to the Installation (P/N).
used and torque guidelines were fol- Section in this data sheet. Dry-Type Sprinklers
lowed.After removal,inspect the sprin- * are leaking or exhibiting visible signs Specify this dry-type sprinkler as
kler for damage. of corrosion. follows:
Step 4. After installing the ceiling or The owner is responsible for the in- * SIN
wall and applying a ceiling finish, slide spection,testing, and maintenance of Pendent TY3935 or TY3235,Sidewall
on the outer piece of the Escutcheon their fire protection system and devices
until it comes in contact with the ceil- in compliance with this document, as TY3735 or TY3335, or Upright TY3135
ing or wall. Do not lift the ceiling panel well as with the applicable standards of & Quick Response,Standard Coverage,
out of its normal position. the National Fire Protection Association Dry-Type Sprinkler
When using the Deep Escutcheon, (e.g., NFPA 25), in addition to the stan- * Deflector Style
hold the outer piece in contact with dards of any other authorities having Upright, Pendent,and Horizontal
the mounting surface(ceiling or wall). jurisdiction.The installing contractor or Sidewall
Then rotate the inner piece approxi- sprinkler manufacturer should be con-
mately 1/4 turn with respect to the out- tacted relative to any questions. * 5.6 K-Factor
er piece,to hold the Deep Escutcheon Automatic sprinkler systems are recom- * Order Length
firmly together. mended to be inspected,tested, and Dry-Type Sprinklers are furnished based
maintained by a qualified Inspection upon Order Length as measured per
Care and Service in accordance with local re- Figures 3 through 10.After taking the
quirements and/or national codes. measurement,round it to the nearest
Maintenance 1/4 inch increment.
e Inlet Connections
The TYCO, Series DS-1 Dry-Type 3/4 Inch NPT 1 Inch NPT or ISO 7-R1
Sprinklers must be maintained and ser-
viced in accordance with this section. *Temperature Rating
Before closing a fire protection system e Sprinkler Finish
main control valve for maintenance * Escutcheon Style and Finish, as
work on the fire protection system that applicable
it controls, obtain permission to shut 9 Part Number(P/N) from Table D
down the affected fire protection sys-
tems from the proper authorities and The Upright Sprinkler without an
notify all personnel who may be affect- Escutcheon (TY3135) is available in
ed by this action. 1 Inch NPT only.
Absence of the outer piece of an es- Part Numbers are for 3/4 Inch and
cutcheon, which is used to cover a 1 Inch NPT standard order sprin-
clearance hole, can delay the time to klers. Orders for all other sprinkler
sprinkler operation in a fire situation. assemblies must be accompanied
A Vent Hole is provided in the Bulb Seat by a complete description. Refer to
the Price List for a complete listing of
(Figures 1 and 2)to indicate if the Dry- Part Numbers.
Type Sprinkler is remaining dry. Evi-
dence of leakage from the Vent Hole in- Sprinkler Wrench
dicates potential leakage past the Inlet Specify: W-Type 7 Sprinkler Wrench,
seal and the need to remove the sprin- P/N 56-850-4-001.
kler to determine the cause of leakage;
for example, an improper installation Sprinkler Boot
or an ice plug. Close the fire protec- Specify: Model DSB-2 Dry Sprinkler
tion system control valve and drain the Boot, P/N 63-000-0-002.
system before removing the sprinkler. This Part Number includes one Boot,
Exercise care to avoid damage before, two Strap Ties,and 1/3 oz.of Adhesive.
during, and after installation. Never The quantity of adhesive is sufficient for
paint, plate, coat, or otherwise alter installing one Boot.
automatic sprinklers after they leave
the factory.
Never repaint factory-painted Cover
Plates.When necessary,replace cover
plates with factory-painted units. Non-
factory applied paint can adversely de-
lay or prevent sprinkler operation in the
event of afire.
TFP51 0
Page 9 of 10
CW P/N* 60 - XXX - X - XXX
II
FSIN SPRINKLER ESCUTCHEON(l)
01 Pendent with Standard TY3935 SIGNAL WHITE
Escutcheon(3/4"NPT) (Figure 3) 0 CHROME PLATED (RAL9003)
02 Pendent with Deep TY3935 1 NATURAL BRASS SIGNAL WHITE
Escutcheon(3/4"NPT) (Figure 5) (RAL9003)
03 Pendent with Standard Recessed TY3935 2 NATURAL BRASS BRASS PLATED
Escutcheon(3/4"NPT) (Figure 4)
4 SIGNAL WHITE SIGNAL WHITE
04 Pendent without TY3935 (RAL9003) (RAL9003)
Escutcheon(3/4"NPT) (Figure 6) #_
9 CHROME PLATED CHROME
05 Sidewall with Standard TY3735
Escutcheon(3/4"NPT) (Figure 8)
06 Sidewall with Deep TY3735 TEMPERATURE SAMPLE
Escutcheon(3/4'NPT) (Figure 9) RATINGS(2) ORDER
I LENGTHS(3)
07 Sidewall without TY3735 0 135'F(57-C)
Escutcheon(3/4"NPT) (Figure 10) 1 155'F(68oC) E55 5.50"
082 8.25"
36 Pendent with Standard TY3235 2 175'F(79-C) 180 18.00"
Escutcheon(1"NPT) (Figure 3)
3 20e'F(93'C) 187 18.75"
Pendent with Deep TY3235 C)
33 Escutcheon(1"NPT) (Figure 5) 372 37.25"
37 Pendent with Standard Recessed TY3235 �480 48.00"
Escutcheon(1"NPT) (Figure 4)
32 Pendent without TY3235
Escutcheon(1"NPT)
Notes
Use Prefix "I" for ISO 7-R1 Connection; for example,
Sidewall with Standard TY392F !-00,-3 10-4-0 5 5.
34 Escutcheon(1"NPT) (Figure 8) 1. Escutcheon applies to sprinklers provided with
escutcheons.
43 Sidewall with Deep TY3335 2. 286'F(141'C)temperature rating applies to non-recessed
Escutcheon(1"NPT) (Figure 9) sprinkler assemblies.
3. Dry-Type Sprinklers are furnished based upon "Order
44 Sidewall without TY3335 Length"as measured per Figures 3 through 10,as appli-
Escutcheon(1"NPT) (Figure 10) cable, and for each individual sprinkler where it is to be
installed.After the measurement is taken, round it to the
nearest 1/4 inch increment.
Upright without TY3;135
38 Escutcheon(1"NPT) (Figure 7)
T4BLE D
SERIES DS-I DR Y-TYPE SPRINKLERS
PART NUMBER SELECTION
TFP510
Page 10 of 10
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700
Copyright @ 2013 Tyco Fire Products,LP. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
Worldwide www.tyco-fire.com
tq tection Contacts
Products
Series TY-FRB — 2.8y 4.2,y 5.6. and 8.0 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response,, Standard Coverage
General spheres.Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the appli- Z;_Z_ /41111,1111-�,P�?,*�
Description cable approval agencies,the testing is
The TYCO Series TY-FR13, 2.8, 4.2, not,representative of all possible cor-
5.6, and 8.0 K-factor, Upright, Pen- rosive atmospheres. Consequently, 1:
I! ,i
it is recommended that the end user I
dent, and Recessed Pendent Sprin-
klers described in this data sheet are be consulted with respect to the suit-
ability of these coatings for any given
quick response, standard coverage,
decorative 3 mm glass bulb-type spray corrosive environment.The effects of
sprinklers designed for use in light or ambient temperature,concentration of
ordinary hazard,commercial occ�pan- chemicals,and gas/chemical velocity,
cies such as banks, hotels, and shop- should be considered, as a minimu,it,
ping malls. along with the corrosive nature of the
chemical to which the sprinklers will be
The recessed version of the Series TY- exposed.
FRB Pendent Sprinkler,where applica-
ble, is intended for use in areas with a An intermediate level of the Series TY- vow-
finished ceiling.This recessed pendent FRB Pendent Sprinklers is detailed
sprinkler uses one of the following: in Technical Data Sheet TFP356, and
Sprinkler Guards are detailed in Tech-
A
• A two-piece Style 10 (1/2 inch NPT) nical Data Sheet 11 FP780.
or Style 40(3/4 inch NPT) Recessed
Escutcheon with 1/2 inch(12,7 mm)of AV:
recessed adjustment or up to 3/4 inch
(19,11 mm)of total adjustment from the The Series TY-FRB, 2.8, 4.2, 5.6,
flush pendent position,or a and 8.0 K-factor, Upright, Pendent,
and Recessed Pendent Sprinklers
• A two-piece Style 20 (1/2 inch NPT described herein must be installed
or Style 30(3/4 inch NPT) Recessed and maintained in compliance with Sprinkler
Escutcheon with 1/4 inch(6,4 mm)of this document and with the applica-
recessed adjustment or up to 1/2 inch We standards of the National Fire Pro-
(12,7 mm)of total adjustment from the tection Association, in addition to the Iden fication
flush pendent position. sta.ndards of any authorities having Number (SIN)
The adjustment provided by the I.unsdiction.Failure to do so may impair
Recessed Escutcheon reduces the the performance of these devices. TY1131: Upright 2.81K, 1/2-NPT
accuracy to which the fixed pipe drops The owner is responsible for maintain- TY1 231: Pendent 2.81K, 1/2-NPT
to the sprinklers must be cut. ing their fire protection system and TY2131: Upright 4.21K, 1/2-NPT
Cc rrosi on-resistant coatings, where devices in proper operating condition. TY2231: Pendent 4.2 K, 1/2-N PT
applicable, are utilized to extend the The installing contractor or sprinkler TY3131: Upright 5.6 K, 1/2-N PT
life of copper alloy sprinklers beyond manufacturer should be contacted with TY3231: Pendent 5.61K,1/2-NPT
that which would otherwise be obtained any questions. TY4131: Upright 8.OK,3/4-NPT
when exposed to corrosive atmo- TY4231: Pendent 8.01K,3/4-NPT
TY4831: Upright 8.01K, 1/2-NPT
TY4931: Pendent 8.01K, 1/2-NPT
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING"that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page I of 10 OCTOBER 2013 TFP171
TFP171
Page 2 of 10
Temperature rating Pipe thread connections per 1 Frame 3 Sealing 5 Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 Button Assembly Screw
(IIiw Deflector. special request. PLATE SEATING 4 Bulb 6 Deflector*
SURFACE 7 Bushing
7
1
7/16"
(11,1 mm) 3
NOMINAL 2-1/4"
MAKE-IN (57,2 mm)
2-3/16" __4
(55,6 mm) 1-9116"
(39,7 mm) 5
6*
1/2"' PT** WRENCH STYLE 10 or 20
FLATS RECESSED 2-7/8"(73,0 mm)DIA.
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE I
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1 131)AND PENDENT(TY1231)SPRINKLERS
2.8 K-FACTOR, 112 INCH NPT
Temperature rating Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
1
7/16"
(11,1 mm)
2
NOMINAL 6"
1 /1
MAKE-IN 55,6 mm) 4
�w 2-3/16"
(55,6 mm)
5
6*
1/2" NPT** WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS
4.2 K-FACTOR, 112 INCH NPT
TFP171
Page 3 of 10
Temperature rating Pipe thread connections per 1 Frame 3 - Sealing 5 Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 Deflector
SURFACE
7/16" 3
(11,1 mm)
7,/1 6"m)
1 1 m
NOMI NAL
MAKE_l N
2 3
6
556
W STYLE 10 or 20
NOMINAL
MAKE-IN 2-3/16" 2
1 (55,6 mm)
2-3/16" 1-1 1 12" 4
(55,6 mm) (38,1 mm) .5
1/2"N RENCH �_2-7/8"(73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS
5.6 K-FACTOR, 112 INCH NPT
Temperature rating Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
1
1/2"
(12,7 mm) 3
7F NOMINAL 51�/16
MAKE-IN FY ' T
(5 mm)
kw 4
(57,2 mm)
/2, 5
3/4" NPT** WRENCH STYLE 30 or 40 Y6*
FLATS RECESSED 2-718"(73,0 mm)DIA.
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS
8.0 K-FACTOR,314 INCH NPT
TFP171
Page 4 of 10
CEILING PLATE 1 - Frame 5 Compression
�4w SEATING SURFACE 2 - Button Screw
1 3 - Sealing 6 Deflector
Assembly
7/16" 3 4 - Bulb
(11,1 mm) 2-1/4"
1 7,/1' (57,2 mm) 2
NOMINAL
I y
MAKE-IN Temperature rating is
2-3/16" 1-9/16" 4 indicated on Deflector.
(55,6 mm) 1 (39,7 mm)
5 Pipe thread connections
per ISO 7-1 can be
6 provided on special
1/2"NPT** WRENCH request.
FLATS
UPRIGHT PENDENT CROSS SECTION
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS
8.0 K-FACTOR, 112 INCH NPT
torque can distort the sprinkler Inlet
Technical Design with consequent leakage or impairment
Data Criteria of the sprinkler.
Do not attempt to compensate for
Approvals The TYCO Series TYFRB, 2.8, 4.2, insufficient adjustment in the Escutch-
UL and C-UL Listed 5.6, and 8.0 K-factor, Upright, Pen- eon Plate by under- or over-tightening
FM, LPCB, and NYC Approved dent,and Recessed Pendent Sprinklers the sprinkler. Re-adjust the position of
Refer to Table A and B for complete are intended for fire protection sys- the sprinkler fitting to suit.
approval information including tems designed in accordance with the
corrosion-resistant status, standard installation rules recognized Series TY-FRB Upright and Pendent
by the applicable Listing or Approval Sprinklers
Maximum Working Pressure agency (such as, UL Listing is based The Series TY-FRB Pendent and
Refer to Table C. on the requirements of NFPA 13, and Upright Sprinklers must be installed
FM Approval is based on the require- in accordance with the following
Discharge Coefficient ments of FM's Loss Prevention Data instructions.
K=2.8 GPM/pSil/2 (40,3 LPM/barl/2) Sheets). Only the Style 10, 20, 30' or
K=4.2 GPM/pSil/2 (60,5 LPM/barl/2) 40 Recessed Escutcheon,as applica- Step 1.Install Pendent sprinklers in the
K=5.6 GpM/pSil/2 (80,6 LPM/barl/2) ble,is to be used for recessed pendent pendent position. Install upright sprin-
K=8.0 GPM/pSil/2 (115,2 LPM/barl/2) installations. klers in the upright position.
Step 2. With pipe-thread sealant
Temperature Rating Installation applied to the pipe threads, hand-
Refer to Table A and B. tighten the sprinkler into the sprinkler
The TYCO Series TY-FRB, 2.8, 4.2, fitting.
Finishes 5.6,and 8.0 K-factor,Upright,Pendent,
Sprinkler: Refer to Table D. Recessed and Recessed Pendent Sprinklersmust Step 3. Tighten the sprinkler into the
Escutcheon:White Coated,Chrome be installed in accordance with this sprinkler fitting using only the W-Type 6
Plated, or Brass Plated. section. Sprinkler Wrench(Figure 14).With refer-
ence to Figures 1 through 5,apply the
Physical Characteristics General Instructions W-Type 6 Sprinkler Wrench to the sprin-
Frame. . . . . . . . . . . . . . . . . . . Bronze Do riot instail any bulb-type sprinkler if kler wrench flats.
Button. . . . . . . . . . . .. .Brass/Copper the bulb is cracked or there is a loss
Sealing Assembly. . . . . . . . .Beryllium of liquid from the bulb.With the sprin- Series TY-FRB Recessed Pendent
Nickel w/TEFLON kler held horizontally, a small air bub- Sprinklers
Bulb . . . . . . . . . . . . . . . . . . . . . .Glass ble should be present. The diameter The Series TY-FRB Recessed Pendent
Compression Screw. . . . . . . . Bronze of the air bubble is approximately 1/16 Sprinklers must be installed in accor-
Deflector. . . . . . . . . . .Copper/Bronze inch(1,6 mm)for the 135'F(57*C)and dance with the following instructions.
Bushing(K=2.8) . . . . . . . . . . . Bronze 3/32 inch(2,4 mm)for the 286'F(141'C) Step A.After installing the Style 10,20,
temperature ratings. 30, or 40 Mounting Plate, as applica-
Operation A leak-tight 1/2 inch NPT sprinkler joint ble,over the sprinkler threads and with
The glass bulb contains a fluid that shold be obtained by applying a min- pipe-thread sealant applied to the pipe
e.xpands when exposed to heat.When imum to maximum torque of 7 to 14 threads,hand-tighten the sprinkler into
the rated temperature is reached, the ft.-Ibs. (9,5 to 19,0 �Im), A leak tight the sprinkler fitting.
fluid expands sufficiently to shatter the 3/4 inch N PT sprinkler joint should be Step B.Tighten the sprinkler into the
glass bulb, allowing the sprinkler to obtained with a torque of 10 to 20 ft, sprinkler fitting using only the W-Type
4Iiiw activate and water to flow. lbs. (13,4 to 26,8 Nm). Higher levels of 7 Recessed Sprinkler Wrench (Figure
TFP1 71
Page 5 of 10
SPRINKLER FINISH (See Note 5)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME S11 NAL***
FACTOR COLOR BRASS PLATED WHITE
135�1`(57-C) Orange
PENDENT 155-F(68-C) Red
(TY1231)
and 175oF(79-C)_ Yellow 1,2,3,4
UPRIGHT
(TY1131) 200-F(93-C) Green
286-F(141-C) Blue
2.8 RECESSED 135'F(57-C) Orange
1/2"NPT PENDENT 155-F(68-C)_ Red
(TY112311)� 175'F(79-C) Yellow
Figure 6
200-F(93-C) Green
RECESSED 135-F(57-C) Orange 1,2,4
PENDENT 155'F(68-C) Red
(TY1231) 175'F(79-C) Yellow
Figure 7 1
200cF(003-C) Fe,�n
135'F(57-C) Orange
PENDENT 155'F(68-C) Red
(TY2231)
and 175-F(79-C) Yellow
UPRIGHT
(TY2131) 200'F(93-C) Green
286-F(141'C) Blue
4.2 RECESSED 135'1`(57�C) Orange
1/2"NPT PENDENT 155'F(68-C) Red 1,2
(TY2231)' 175'1`(79�C) Yellow
Figure 8
200oF(93c,C) Green
RECESSED 135'F(57-C) Orange
PENDENT 155-F(68-C) Red
(TY2231)-* 175-F(79-C) Yellow
Figure 9 i
1 200oF(93oC) Green
NOTES:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. Where Polyester Coated Sprinklers are noted to be i);..aod 0-ULListed,the sprinKlers are UL and C-UL Listed
as Corrosion-Resistant Sprinklers.
Installed with Style 10(112"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable.
Installed with Style 20(1/2"NPT)or Style 30(3/4"NPTj 1,2"Total Adjustment Recessed Escutcheon,as applicable.
Frame and Deflector only. Listings and approvals apply to color(Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
2.8 AND 4.2 K-FA C TOR SPRINKLERS
15). With reference to Figures 1 to 4,
apply the W-Type 7 Recessed Sprinkler
Wrench to the sprinkler wrench flats.
Step C. After ceiling installation and
finishing, slide on the Style 10, 20, 30,
or 40 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFP171
Page 6 of 10
SPRINKLER FINISH(See Note 8)
K BULB LIQUID NATURAL CHROME I SIGNAV-- LEAD
FACTOR TYPE TEMPERATURE COLOR BRASS PLATED WHITE COATED
PENDENT — 135-F(57-C) Orange
(TY3231) 155'F(68-C) Red
and 175'F(79-C) Yellow 1,2,3,4,5,6,7 1,2,3,5
UPRIGHT —200-F(93-C) Green
(TY3131)
286-F(141-C) Blue
135-F(57-C) Orange
RECESSED 155-F(68-C) Red
5.6 PENDENT —
1/2"NPT (TY3231)' -175-F(79-C) Yellow 1,2,4,5 N/A
Figure 10 200'F(93-C) Green
286-F(141-C) Blue
135-F(57-C) Orange
RECESSED 155-F(68-C) Red
PENDENT —
(TY3231)-- 175-F(79-C) Yellow 1,2,3,4,5 N/A
Figure 11 200-F(93-C) Green
286-F(141-C) Blue
PENDENT 135-F(57-C) Orange
(TY4231) 155-F(68-C) Red
and 175-F(79-C) Yellow 1,2,3,4,5,6,7 1,2,5
UPRIGHT 200'F(93-C) Green
(TY4131)
286-F(141'C) Blue
135-F(57-C) Orange
RECESSED 155-F(68-C) Red
8.0 PENDENT
3/4"NPT (TY4231)- 175-F(79-C) Yellow 1,2,5 N/A
Figure 12 200'F(93-C) Green
286-F(141'C) Blue
(W 135-F(57-C) Orange
RECESSED 155-F(68-C) Red
PENDENT —
(TY4231).. —175-F(79-C) Yellow 1,2,3,5 N/A
Figure 13 200-F(93-C) Green
286-F(141-C) Blue
PENDEN I 135-F(57-C) Orange
8.0 (TY4931) 155-F(68-C) Red
1/2"NPT and 175-F(79-C) Yellow 1,2,4,5,6 1,2,5
UPRIGHT r2OO-F(93-C) Green
(TY4831) __i "
I 286'F(141*C) 131,a�
NOTES:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate
the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax
31-53-428-3377.)
7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed
as Corrosion-Resistant Sprinklers.Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved
as a Corrosion-Resistant Sprinklers.
Installed with Style 10(1/2"NP-0 or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable.
Installed with Style 20(1/2"NPT)or Style 30(3/4"NPI)1/2"Total Adjustment Recessed Escutcheon,as applicable.
Frame and Deflector only.Listings and approvals apply to color(Special Order).
N/A:Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFP171
Page 7 of 10
�w K NATURAL [! SPRINKLER FINISH
FACTOR TYPE (P:HROME77SIGNAL LEAD
ROM L
L W IT
BRASS P L:AT:ED WHITE COATED
PENDENT(TY1231)
and
2.8 UPRIGHT(TY1131)
1/2"NPT RECESSED 175 PSI(12,1 BAR) N/A
PENDENT(TY1231)
PENDENT(TY2231)
and
4.2 UPRIGHT(TY2131)
1/2"NIPT RECESSED 175 PSI(12,1 BAR) N/A
PENDENT(TY2231)
PENDENT(TY3231)
and 175 PSI
5.6 UPRIGHT(TY3131) 250 PSI(17,2 BAR) (12,1 BAR)
1/2"NPT — OR 175 PSI(12,1 BAR)
RECESSED (SEE NOTE 1)
PENDENT(TY3231) N/A
PENDENT(TY4231)
and 175 PSI
8.0 UPRIGHT(TY4131) (112,11 BAR)
3/4"NPT — 175 PSI(12,1 BAR)
RECESSED
PENDENT(TY4231) N/A
8.0 PENDENT(TY4931)
1/2"NPT and 175 PSI(12,1 BAR) 175 PSI
UPRIGHT(TY4831) (12,1 BAR)
NOTES:
1. The maximum working pressure of 250 psi(17,2 bar).only applies to the Listing by Underwriters Laboratories Inc.(UL);the
Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York.
TABLE C
MAXIMUM WORKING PRESSURE
Care and corrosive products of combustion, but tion Service in accordance with local
have not operated,should be replaced requirements and/or national codes.
if they cannot be completely cleaned
Maintenance by wiping the sprinkler with a cloth or Care must be exercised to avoid dam-
The TYCO Series TY-FRB must be by brushing it with a soft bristle brush. age to the sprinklers -before, during,
and after installation. Sprinklers dam-
maintained and serviced in accordance Care must be exercised to avoid dam- aged by dropping, striking, wrench
with this section. age to the sprinklers- before, during, tWiSt/slippage, or the like, must be
Before closing a fire protection system and after installation.Sprinklers dam- replaced. Also, replace any sprinkler
main control valve for maintenance aged by dropping, striking, wrench that has a cracked bulb or that has lost
work on the fire protection system tWiSt/slippage, or the like, must be liquid from its bulb. (Ref. Installation
that it controls, obtain permission to replaced. Also, replace any sprinkler Section).
shut down the affected fire protection that has a cracked bulb or that has lost
systems from the proper authorities liquid from its bulb. (Ref. Installation Initial and frequent visual inspections of
and notify all personnel who may be Section.) random samples are recommended for
affected by this action. The- own.pr is responsibloc for the corrosion-resistant sprinklers to verify
inspection,testing,and maintenance the integrity of the corrosion-resistant
Absence of the outer piece of an of material of construction. Thereafter,
escutcheon, which is used to cover their fire protection system and devices annual inspections per NFPA 25 should
a clearance hole, can delay sprinkler in compliance with this document, as suffice.
operation in a fire situation. well as with the applicable standards
of the National Fire Protection Associa- Inspections of corrosion-resistant
Sprinklers which are found to be leak- tion (e.g., NFPA 25), in addition to the sprinklers are recommended at close
ing or exhibiting visible signs of corro- standards of any other authorities hav- range, instead of from the floor level
sion must be replaced.
Ing jurisdiction. Contact the installing per NFPA. Inspection at close range
Automatic sprinklers must never be contractor or sprinkler manufacturer can better determine the exact sprin-
painted, plated, coated, or other- regarding any questions. kler condition and the long-term integ-
rity of the corrosion-resistant material,
wise altered after leaving the factory. Automatic sprinkler systems are rec- which can be affected by the corrosive
`(Iiiiiw Modified sprinklers must be replaced. ommended to be inspected, tested, conditions present.
Sprinklers that have been exposed to and maintained by a qualified Inspec-
TFP171
Page 8 of 10
2-7/8" DIA. 2-7/8"DIA.
�w 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/9±1/8" (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) 2,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
MOL
P
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)
-,,rc� �
/7_ F77 7/
MOUNTING
MOUNTING SURFACE
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm)l
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 6 FIGURE 7
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 112 INCH NPT 2.8 K-FACTOR, 112 INCH A/PT
2-7/8" DIA. 2-7/8"DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm)
(1 5,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) 2,7±3,2 mm) 2-1/4"DiA. 1/4"(6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 min) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
(3,2 mm) - (3,2 mm)
F/7
/7,
MOUNTING
MOUNTING SURFACE
SURFAC/E
CLOSURE SERIES 1-1/4"(31,8 mm) SERIES 1-1/4"(31,8 mm)
TY-FRB 3/4"(19,1 mm) CLOSURE TY-FRB 1"(25,4 mm)
FIGURE 8 FIGURE 9
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 112 INCH NPT 4.2 K-FACTOR, 112 INCH NPT
TFP171
Page 9 of 10
2-7/8"DIA. 2-7/8"DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm)
- 1/2±1/8" 1/2"(12,7 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4"(6,4 mm) 2,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8"
(3,2 mm) (3,2 mm)
L -a r� l
- P77 71
Z,
MOUNTING
MOUNTING SURFACE
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm)
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 10 FIGURE I I
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 112 INCH NPT 5.6 K-FACTOR, 112 INCH NPT
2-7/8" DIA. 2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE qPRINKLER PLATE
FITTING FITTING
1/8"
(3,2 mm) 1 P77 (3,2 mm)
MOUNTING
MOUNTING SURFACE
SURFACE
7
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm)
TY-FRB 13/16""(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 12 FIGURE 13
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR,314 INCH NPT 8.0 K-FACTOR,314 INCH NPT
WRENCH
RECESS
WRENCH RECESS
^(END"A" USED FOR
1 J/
/2"NPT MODELS)
WRENCH RECESS
(END"B" USED FOR
3/4"NPT MODELS) PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14 FIGURE 15
W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED
WRENCH SPRINKLER WRENCH
TFP171
Page 10 of 10
P/N 57 - XXX - X XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
330 1 2.8K UPRIGHT(1/2"NPT) TY1 131 1 NATURAL BRASS 135 135'F(57-C)
331 2.8K PENDENT(1/2"NPT) TY1231 3 PUREWHITE
(RAL9010)' 155 155-F(68-C)
340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE
I (RAL9003) 175 175-F(79-C)
341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK
I I (RAL9005)-- 200 200-F(93-C)
370 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286-F(141-C)
371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED
390 8.OK UPRIGHT(3/4"NPT) TY4131 Eastern Hemisphere sales only.
Available in only 2.8K,4.2K,and
391 8.OK PENDENT(3/4"NPT) TY4231 8.OK,155-F(68-C)and 200'F(93*C);
requires lead time to manufacture.
360 8.OK UPRIGHT(1/2"NPT) TY4831*
PENDENT(1/2"NPT) TY4931-
TABLE D
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB(Specify SIN),
(specify K-factor), (specify Pendent or
Upright) Sprinkler (specify) tempera-
ture rating, (specify)finish or coating,
P/N (specify from Table D)
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify*)
finish, P/N (specify*)
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Refer to Technical Data Sheet TFP770
GLOBAL HEADQUARTERS 1400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700
Copyright 0 2013 Tyco Fire Products,LP. All rights reserved. tflem
TEFLON is trademark of The DuPont Corporation. Fire Protection Products
maw
___A1K_
Worldwide www.tyco-fire.com
Contacts
Model DPV-1 Dry Pipe Valve., External Resetting
2-1/2 thru 6 Inch (DN65 thru DN150)
250 psi (17
..2 bar)
General
Description
The TYCO Model DPV-1 Dry Pipe
Valves are differential valves used to
automatically control the flow of water
into dry pipe fire protection sprinkler
systems upon operation of one or more
automatic sprinklers. The DPV-1 also
provides for actuation of fire alarms
upon system operation. The Model
DPV-1 features are as follows:
External reset.
250 psi(17,2 bar)pressure rating.
Unique offset single clapper design
enabling a simple compact valve to
minimize installation labor.
Ductile iron construction to ensure a
lightweight valve to minimize shipping
cost.
A variety of inlet and outlet
connections. Available End Connections and Sizes
Compact, Pre-Trimmed, and Semi- Norninal Valve Size
Assembled, easy to operate valve End Connection 2-1/2 Inch 3 Inch 4 Inch 6 Inch
trim.
Simple reset procedure through the (DN65) (DN80) (DN100) (DN150)
elimination of priming water. Flange x Flange N/A N/A
Dry pipe sprinkler systems are used Flange x Groove N/A N/A
in unheated warehouses, parking Groove x Groove
garages, store windows, attic
spaces, loading docks, and other
areas exposed to freezing tempera- Available
tures, where water filled pipe cannot N/A Not Available
be utilized. When set for service, the _J
dry pipe sprinkler system is pressur-
ized with air (or nitrogen). The loss The owner is responsible for main-
of pressure through an operated The Model DPV-1 Dry Pipe 'Valves taining their fire protection system and
automatic sprinkler in response to described herein must be installed devices in proper operating condition.
heat from a fire permits the DPV-1 Dry and maintained in compliance with this The installing contractor or manufac-
Pipe Valve to open and allow a flow of document, as well as with the appli- turer should be contacted with any
water into the sprinkler system piping. cable standards of the National Fire questions
Table B establishes the minimum Protection Association, in addition to
required system air pressure that the standards of any other authorities
includes a safety factor to help prevent having jurisdiction. Failure to do so
false operations that might occur due to may impair the performance of these
water supply fluctuations. devices.
(Iiiw
Page I of 20 MARCH 2013 TFP1020
TFP1020
Page 2 of 20
NO. DESCRIPTION CITY REF
I Valve Body...... . 1 NR
2 Air and Water
Seat ... ....... . 1 NR
3 Handhole Cover. 1 NR
4 Handhole Cover
0—11 Gasket ......... . 1 See(b)
5 1/2-13 UNC x 1"Hex
12 Head Cap Screw:
6 2-1/2&3 Inch
Valves. ........ . .5 CH
13 4 Inch Valve ..... .6 CH
7 CLAPPER RESET 6 Clapper......... . 1 See(a)
ASSEMBLY 14 PLUNGER 7 Clapper Facing. 1 See(a)or(b)
PARTS 8 Clapper Facing
Retaining Plate... . 1 See(a)
15,18 9 2-1/2 and 3 Inch Valves:
1/4"x 3/8"Long
#10-32 Shoulder
16 Screw... ...._ .5 See(a)
4 Inch Valve:
17 1/4-20 UNC x 112"
Socket Head Cap
Screw... ....... .7 See(a)
10 Clapper Hinge
Pin . ........... . 1 See(a)
11 Reset Knob ..... . 1 See(c)
12 Reset Spring 1 See(c)
13 Reset Bushing Se�-,(c)
14 Reset Bushing
O-Ring... ... .... . 1 See(b)or(c)
15 Reset Plunger
O-Ring .. .... .. . . 1 See(b)or(c)
16 Reset Plunger.. I See(c)
17 Reset Latch
Subassembly . 1 See(c)
18 Dow Corning FS3452
Flourosilicone
4 Grease, 1.5 g 1 See(b)cr(c)
NR:Not Replaceable
3
2
CH:Common Hardware
0
REPLACEMENT PARTS
0 NO. DESCRIPTION P/N
(a) Clapper Assembly
0 Includes Items 6-10:
2-1/2&3 Inch Valves.. 92-309-2-203
4 Inch Valve ..... . ... 92-309-2-403
10 (b) Repair Parts Kit
5 Includes Items
4,7,14,15,&18:
2-1/2&3 Inch Valves. . 92-309-1-204
4 Inch Valve ..... . ... 92-309-1-404
(c) Reset Plunger Parts Kit
Includes Items 11-18. . 92-310-1-405
FIGURE I -PART I OF 2
(lIiiiw MODEL DPV-1 DRY PIPE VALVE
2-112,3,AND 4 INCH(DN65,DN80, DN100)ASSEMBLIES
TFP1020
Page 3 of 20
NO. DESCRIPTION QTY REP.PART NO. DESCRIPTION QTY. FIER PART NO.DESCRIPTION QTY. REP.PART
1 Valve Body.......1 NR 5 Socket Head Cap 8 Hex Head Cap Screw
2 Air and Water Screw 5/8-11 UNC x 1"�.- 6 CH
Seat ...... ......1 NR 3/8-16UNCxl"...8 NR 9 Clapper... ...... 1 See(a)
3 Water Seal 6 Handhole Cover... 1 NR 10 Clapper Facing.... 1 See(a)or(b)
O-Ring ......... .1 NR 7 Handhole Cover 11 Clapper Facing
4 Air Seal O-Ring....1 NR Gasket . .........1 See(b) Retaining Plate.... 1 See(a)
12 Socket Head Cap
Screw
1/4-20 UNC x 1/2' . 9 See(a)
0-14 13 Clapper Hinge Pin.. 1 See(a)
14 Reset Knob ... ... 1 See(c)
15 15 Reset Spring ... 1 See(c)
16 Reset Bushing 1 See(c)
17 Reset Bushing
16 O-Ring........ ... 1 See(b)or(c)
1 18 Reset Plunger
CLAPPER F�—
RESET O-Ring.... ...... 1 See(b)or(c)
ASSEMBLY 17 PLUNGER 19 Reset Plunger...— 1 See(c)
Cl`—� PARTS 20 Reset Latch
18,21 Subassembly ..... 1 See(c)
21 Dow Corning FS3452
Flourosilicone
19 Grease,1.5 g 1 See(b)or(c)
NR:Not Replaceable
20
CH:Common Hardware
REPLACEMENT PARTS
NO. DESCRIPTION P/N
(a) Clapper Assembly
Includes Items 9-13 . . . 92-309-2-603
(b) Repair Parts Kit
(W Includes Items
7,10,17,18,21 . .. . . . 92-309-1-604
(c) Reset Plunger Parts Kit
2 includes Items 14-21 92-310-1-405
-----------
C)
4 1
n 7
6
5
3
13
0
8
FIGURE 1 -PART 2 OF 2
MODEL DPV-I DRY PIPE VALVE
6 INCH(DN150)ASSEMBLY
TFP1020
Page 4 of 20
Handhole Cover are ductile iron. The o PS10-2 waterflow alarm switch
Technical Data Handhole Cover Gasket is neoprene, * PS40-2 low air pressure alarm switch
Approvals and the Clapper Facing is EPDM.
UL and C-UL Listed. FM Approved The Air/Water Seat Ring is brass, the Note: When the system pressure is
NYC under MEA 172-02-E (4 and 6 Clapper is bronze or aluminum bronze, greater than 175 psi(12,1 bar),provision
inch). and both the Clapper Retaining Plate is to be made to replace the standard
and Latch are bronze.The Hinge Pin is order 300 psi(20,7 bar)Water Pressure
Dry Pipe Valve aluminum bronze,and the fasteners for gauge with a separately ordered 600
The TYCO Model DPV-1 Dry Pipe the Handhole Cover are carbon steel. psi(41,4 bar)Water Pressure Gauge.
Valves are for vertical installations(flow
going up), and they are rated for use Valve Trim Air Supply
at a maximum service pressure of 250 Installation dimensions are given Table B shows the system air pressure
psi(17,2 bar).The Valve dimensions are in Figure 7, and the Valve Trim and requirements as a function of the
shown in Figure 7. Pre-Trimmed Valve Assemblies are water supply pressure. The air (or
illustrated in Figures 4, 5, and 6. The nitrogen) pressure in the sprinkler
Flanged connections are available and Valve Trim and Pre-Trimmed Valve system is recommended to be auto-
drilled per ANSI,ISO,AS,and JIS spec- forms a part of the laboratory listings matically maintained by using one of
ifications (Ref. Table A). The grooved and approval of the DPV-1 Valve and is the following pressure maintenance
outlet connections, as applicable, necessary for the proper operation of devices,as appropriate:
are cut in accordance with standard the DPV-1 Valve. Each package of trim
groove specifications for steel pipe. o Model AMD-1 Air Maintenance
and pre-trimmed includes the following Device(pressure reducing type).
They are suitable for use with grooved items:
end pipe couplings that are listed or & Model AMD-2 Air Maintenance
approved for fire protection system * Water Supply Pressure Gauge Device(compressor control type).
service.Available combinations of inlet * System Air Pressure Gauge
and outlet connections are detailed in o Model AMD-3 Nitrogen Maintenance
the Ordering Procedure section.They 9 Air Supply Connections Device(high pressure reducing type).
are also noted in the "Available End * Main Drain Valve The Pressure Relief Valve provided with
Connection and Sizes" table located * Low Body Drain Valve the valve trim is factory set to relieve
on Page 1. at a pressure of approximately 45 psi
Threaded port connections of valves * Alarm Test Valve (3,1 bar). If the normal system air
having flanges drilled to ANSI, AS, or 9 Automatic Drain Valve pressure is less than or exceeds 40 psi
JIS specifications are NPT threaded per (2,8 bar),then the pressure Relief Valve
ANSI Standard B1.20.1.Threaded port 9 Drip Funnel must be reset to relieve at a pressure
connections of valves having flanges * Connections For Optional Quick that is in accordance with the authority
drilled to ISO are available either Opening Device(Accelerator) having jurisdiction.
threaded per ISO 7-1 or NPT threaded Also included in the Pre-Trimmed Valve Quick Opening Device
per ANSI Standard B1.20.1.Valves with Assembly,which can be ordered sepa- As an option,the Model DPV-1 Dry Pipe
NPT threaded ports will readily accept rately for the Valve Trim, includes the Valve may be equipped with the VIZOR
the trim arrangements detailed in Parts following items: Electronic Dry Pipe Valve Accelerator
2 and 3 of Figures 4,5,and 6. (4 and 6 inch sizes) as detailed in
Components of the DPV-1 Valves 9 Model BFV-N butterfly vlave Technical Data Sheet TFP1105 or the
are shown in Figure 1. The Body and o Figure 577 grooved coupling Model ACC-1 Mechanical Dry Pipe
Flange Drilling Specification
Nominal Dimensions in Inches and(mm)
Nominal ANSI B16.1 1 IS07005-2 JIS B 2210 AS 2129
Valve Size (Class 125) (PN16)2 (10K) (Table E)
Dim. Dim. aty. Dim' Dim. aty. Dim. Dim. Oty. Dim. Dim. City.
A B N A B N A B N A B N
4 Inch 7.50 0.75 8 7.09 0.75 8 6.89 0.71 8
0.59 8 7.00
(DN100) (190,5) (19,0) (180,0) (19,0) (175,0 (15,0) (178,0) (18,0)
6 Inch 9.50 0.88 8 9.45 0.91 8 9.45 0.75 8 9.25 0.87 8
(DN150) 1 (241,3) 1 (22,2) (240,0) (23,0) (240,0) (19,0) (235,0) (22,0)
'Same drilling as for ANSI B16.5(Class 150)and ANSI 1316.42(Class 150). Dim.A Qty.N
2 Same drilling as for BS 4504 Section 3.2(PN 16)and DIN 2532(PN 16). Bolt Circle Number of
Diameter (D—. Bolt Holes
Dim B
Bolt Hole
TABLE A Diameter
DIMENSIONAL SPECIFICATIONS
FOR SELECTION OF FLANGE DRILLING
TFP1020
Page 5 of 20
Valve Accelerator (2-1/2, 3, 4, and 6 When one or more automatic sprin-
inch sizes)as detailed in Technical Data klers operate in response to a fire,
Sheet TFP1 112. air pressure within the system piping Maximum System Air
is relieved through the open sprin- Water Supply Pressure Range,
The VIZOR or the ACC-1 is used to klers. When the air pressure is suffi- Pressure, psi
reduce the time to valve actuation ciently reduced, the water pressure psi
following the operation of one or more overcomes the differential holding 20 10
automatic sprinklers. In some cases the Clapper Assembly closed and the 60 15-23
the use of a quick opening device such Clapper Assembly swings clear of the
as the VIZOR or the ACC-1 may be water seat, as shown in Figure 3C, 80 20-28
required to meet the requirements of
the National Fire Protection Association This action permits water flow into the 100 25-33
to meet water delivery times. system piping and subsequently to be 120 30-38
discharged from any open sprinklers.
Also,with the Clapper Assembly open, 145 35-43
Operation the intermediate chamber is pres- 165 40-48
surized and water flows through the
The TYCO Model DPV-1 Dry Pipe Valve alarm port(Ref. Figure 313) at the rear 185 45-53
is a differential type valve that utilizes of the DPV-1 Valve to actuate system 205 50-58
a substantially lower system (air or water flow alarms, The flow from the
nitrogen) pressure than the supply alarm port is also sufficient to close the 225 55-63
(water) pressure, to maintain the set otherwise normally open Automatic 250 60-68
position shown in Figure 3A.The differ- Drain Valve in the valve trim.
ential nature of the DPV-1 is based on After a valve actuation and upon sub-
the area difference between the air seat TABLE B
and the water seat in combination with sequent closing of a system main SYSTEM AIR PRESSURE
the ratio of the radial difference from control valve to stop water flow, the REQUIREMENTS
the Hinge Pin to the center of the Water Clapper Assembly will latch open as
Seat and the Hinge Pin to the center of shown in Figure 3D. Latching open of
the Air Seat.The difference is such that Continued on page 16
1 psi (0,07 bar)of system air pressure FLOW RATE IN LITRES PER MINUTE(LPM)
can hold approximately 5.5 psi (0,38 (1 GPM=3.785 LPM)
bar)of water supply pressure. 500 700 1000 2000 3000 5000 10000
Table B establishes the minimum —9.0
0,60
required system air pressure that
a-- 7.0 0,50
includes a safety factor to help prevent
... ... ......
false operations that occur due to water . ..... .... 0,40
Z 5.0 .... ... ...
supply fluctuations.
—0,30
1uJ 4.0
The Intermediate Chamber of the DPV-1
is formed by the area between the Z) 3.0 =0,20 cc
C3 <
Air Seat and Water Seat as shown in co
Z
Figure 313.The Intermediate Chamber cc 2.0
Lu 7 o-
normally remains at atmospheric CID
0
010 ir in
pressure through the Alarm Port y
connection and the valve trim to the Z ---- ------
D - 0,08 (Lru COO)
normally open Automatic Drain Valve (D
0 1.0 --------- 0
(Fig.4,5,or 6). Having the Intermediate 0,06 (n 6
Chamber, Figure 313, open to atmo- Z _-:7 C/)
IL 0.7 --0,05 Lu 11
sphere is critical to the DPV-1 Valve 0 = -- - 0�
-=0,04
remaining set, otherwise the full o 0.5 _j
___z- z <
resulting pressure of the system air Lu —0,03
cc 0.4
pressure on top of the Clapper Z)
0
Assembly cannot be realized. 0.3
(n —0,02 Z
uj
For example, and assuming a water
supply pressure of 100 psi(6,9 bar), if 0.2
<
the system air pressure is 25 psi (1,7 K
bar) and there was 15 psi (1,0 bar) 2
pressure trapped in the Intermediate 0
Chamber, the resulting pressure Z 0.1
across the top of the Clapper would 100 200 300 500 700 1000 2000 3000
only be 10 psi (0,7 bar).This pressure FLOW RATE IN GALLONS PER MINUTE(GPM)
would be insufficient to hold the The approximate friction losses,based on the Hazen and Williams formula and ex-
Clapper Assembly closed against pressed in equivalent length of Schedule 40 pipe with C=100 are as follows:
a water supply pressure of 100 psi 2.2 feet for the 2-1/2 inch valve at a typical flow rate of 250 GPM
(6,9 bar). It is for this reason that the 4.9 feet for the 3 inch valve at atypical flow rate of 350 GPM
plunger of the Automatic Drain Valve 8.9 feet for the 4 inch valve at a typical flow rate of 600 GPM
must be depressed during several of 22 feet for the 6 inch valve at a typical flow rate of 1500 GPM
the resetting steps, as well as during FIGURE 2
illlIw inspections, making certain that the MODEL DPV-1 DRY PIPE VALVES
Automatic Drain Valve is open. NOMINAL PRESSURE LOSS VS.FLOW
TFP1020
Page 6 of 20
AIR PRESSURE WATERFLOW
TO SYSTEM TO SYSTEM
It CLAPPER CLAPPER
1"NPT ASSEMBLY ASSEMBLY
AIR SUPPLY IN SET FULLY OPEN
PORT POSITION
CLAPPER LATCH
1/2"NPT PIVOTS TO ALLOW
WATER CLAPPER ASSEMBLY
SUPPLY TO FULLY OPEN
PRESSURE
3/4"NPT ALARM
&ALARM
PORT OPEN TO
TEST PORT
ATMOSPHERE
ALARM PORT
WATERFLOW
CLAPPER TO ALARM
ASSEMBLY
FROM FROM
WATER SUPP AIR WATER SUPPLY
SEAT
FIGURE 3A FIGURE 3C
SET POSITION WATER
OPERATED POSITION
SEAT ALARM
PORT
DRAIN FROM
DRAIN FROM SYSTEM
SYSTEM VALVE
COMPLETE
WATERWAY INTERMEDIATE
CHAMBER PUSH HERE
FIGURE 3B TO RESET
SET POSITION VALVE
�w INTERMEDIATE
RESET
CLAPPER CHAMBER KNOB
ASSEMBLY
LATCHED
OPEN RESET
ASSEMBLY CLAPPER
LATCH
PIVOTS TO —
CLAPPER UNLATCH
LATCH CLAPPER
ASSEMBLY
MAIN DRAIN PORT.
3/4"NPT 1-1/4"NPT'(2-1/2 INCH CLAPPER
LOW BODY &3 INCH VALVES) ASSEMBLY
2"NPT(4 INCH VALVE)
DRAIN
RESEATED
PORT
WATER SUPPLY DN40 FOR VALVES WITH WATER SUPPLY
SHUT OFF ISO THREADED PORTS SHUT OFF
FIGURE 3D FIGURE 3E
DRAIN POSITION RESET POSITION
FIGURE 3-PART 1 OF 2
MODEL DPV-I DRY PIPE VALVES
2-112, 3,AND 4 INCH(DN65, DN80,AND DN100)
SET AND OPEN POSITIONS
TFP1020
Page 7 of 20
AIR PRESSURE WATERFLOW
TO SYSTEM TO SYSTEM
CLAPPER
ASSEMBLY
FULLY OPEN
1 NPT CLAPPER LATCH
AIR SUPPLY PIVOTS TO ALLOW
PORT
CLAPPER ASSEMBLY
TO FULLY OPEN
3/4"NPT ALARM
PORT OPEN TO
CLAPPER ATMOSPHERE
ASSEMBLY
IN SET
POSITION
1/2"NPT
WATER SUPPLY
PRESSURE
&ALARM
TEST PORT ALARM PORT
WATERFLOW
CLAPPER TO ALARM
ASSEMBLY AIR
FROM SEAT FROM
WATER SUPPLY WATER SUPPLY
FIGURE 3A ALARM FIGURE 3C
SET POSITION VVAI ER OPERATED POSITION
SEAT PORT
. ............ DRAIN FROM
DRAIN FROM SYSTEM
SYSTEM INTERMEDIATE VALVE COMPLETE
tw CHAMBER FIGURE 313 WATERWAY PUSH HERE
F
TO RESE
SET POSITION
INTERMEDIATE VALVE
CLAPPER CHAMBER
ASSEMBLY RESET
LATCHED KNOB
OPEN RESET
ASSEMBLY
3/4"NPT
LOW BODY CLAPPER
DRAIN LATCH
PORT PIVOTS TO
UNLATCH
CLAPPER
ASSEMBLY
2"NPT
MAIN DRAIN CLAPPER
LATCH
PORT CLAPPER
ASSEMBLY
RESEATED
WATER SUPPLY WATER SUPPLY
SHUT OFF SHUT OFF
FIGURE 3D FIGURE 3E
DRAIN POSITION RESET POSITION
FIGURE 3-PART 2 OF 2
MODEL DPV-1 DRY PIPE VALVES
6 INCH(DN1.rO,)
SET AND OPEN POSITIONS
TFP1020
Page 8 of 20
NOTES:
1. SEE FIGURE 4 PART 3 FOR TRIM ARRANGEMENT WITH BILL OF MATERIALS LOW AIR
AND COMPONENT PART NUMBERS. PRESSURE
2. TRIM SHOWN FULLY ASSEMBLED;COMPONENTS SUCH AS GAUGES AND ALARM
SWITCHES MAY REQUIRE ASSEMBLY IN TRIM AT INSTALLATION. SWITCH SYSTEM
AIR SUPPLY
1 INCH NPT SYSTEM CONTROL VALVE
CONNECTION AIR SUPPLY (NORMALLY
FOR LOCAL PRESSURE OPEN)
SPRINKLER GAUGE
2-1/2 INCH(DN65) WATERFLOW
1/2 INCH NPT or 3 INCH(DN80) PRESSURE
CONNECTION - MODEL DPV-1 ALARM
FOR SYSTEM DRY PIPE VALVE SWITCH
AIR SUPPLY (GxG ONLY)
GROOVED
ALARM M IN COUPLING
TEST VALVE DRAIN VALVE
(NORMALLY (NORMALLY 1/2 INCH NPT
CLOSED) S TE CLOSED) CONNECTION
3/4 INCH NPT SYSTEM FOR OPTIONAL
ER CONNECTION SHUT-OFF 1-1/4 INCH NPT ACCELERATOR
S PPLY TO DRAIN VALVE CONNECTION
PR RE (NORMALLY TO DRAIN AUTOMATIC
GAUGE LOW BODY OPEN) DRAIN VALVE
DRAIN VALVE
(NORMALLY 1-1/4 INCH NPT
CLOSED) CONNECTION DRIP
TO DRAIN FUNNEL
FIGURE 4-PART I OF 3
2-112 AND 3 INCH(DN65 AND DN80)MODEL DPV-1 DRY PIPE VALVE
PRE-TRIMMED ASSEMBLY
AIR SUPPLY 1/2 INCH NPT 1/2 INCH NPT NOTES:
4w CONTROL VALVE CONNECTION CONNECTION 1. INSTALL TRIM ASSEMBLIES IN
(NORMALLY OPEN) FOR OPTIONAL FOR OPTIONAL ALPHABETICAL ORDER.
ACCELERATOR AUTOMATIC AIR PRESSURE 2. SEE FIGURE 3 FOR VALVE PORT
SWITCH
1/2 INCH NPT DRAIN VALVE IDENTIFICATION.
CONNECTION 3. ROUTE 1/4"TUBING TO DRIP
FOR SYSTEM
AIR SUPPLY H SYSTEM FUNNEL.
AIR SUPPLY MAIN
PRESSURE DRAIN VALVE
1/2 INCH NPT D GAUGE (NORMALLY
CONNECTION G A
FOR WATERFLOW E CLOSED)
PRESSURE ALARM
SWITCH
1-1/4 INCH NPT DRIP
CONNECTION FUNNE
TO DRAIN 1-1/4 INCH NPT
CONNECTION
2-1/2 INCH(DN65) TO DRAIN
1 INCH NPT c or 3 INCH(DN80)
CONNECTION MODEL DPV-1
FOR LOCAL DRY PIPE VALVE
SPRINKLER (GxG ONLY)
ALARM F B LOW BODY
DRAIN VALVE
TEST VALVE SYSTEM (NORMALLY
(NORMALLY WATER SUPPLY 3/4 INCH NPT CLOSED)
CLOSED) PRESSURE CONNECTION
GAUGE TO DRAIN
FIGURE 4-PART 2 OF 3
�w 2-112 AND 3 INCH(DN65 AND DN80)MODEL DPV-1 DRY PIPE VALVE
EXPLODED ARRANGEMENT OF SEMI-ASSEMBLED TRIM
46 Schedule 10/ Schedule 40 M-COATO
Submittal Data Sheet
Fully Listed and FM Approved Sprinkler Pipe Sch-40 ASTMA135/A795
rVI-c0AT Specifications
When you specify Schedule-1 O/Schedule-40-M-COAT@ sprinkler pipe from 0 rn na I Nominamil.D.-N-om-in=a wt. Wt.(H20 Filled) CRR
In;mm 0 0.In;mrn ,M Wall in;.mm Lbs/Ft;kq/m Lbs/Ft;kqlm
Allied Tube&Conduit,you get UL listed and FM approved products.Although 1" 1,315 1.049 0.133 1.680 2.05 1
these productsdo not require separate approvals,Schedule-1 O/Schedule-40- 25 33.4 26.6 3.38 2.5 3.OS -
M-COATgivesyou theextra quality assurance you demand,Our Sch-10(1-1A" I V�- 1.660 1.380 0.140 2.270 2.93 1
32 42.1 35.1 3.56 3.39 4.36 -
-8")pipe and Sch-40(1 2-1/2")pipe have passed the same thorough lab -Fle- 1.900 1.610 0.145 2.720 3.61 1
testing as our other listed pipe products,and receive periodic mill inspections .3 40.9 3.68 4.0 5.37 -
from both UL and FM agents to ensure consistent quality, 2- 2.375 2.067 0.154 3.656 5.13 1
50 60.3 1 52.5 3.91 5.4 7.63 -
2�h 2.875 1 2.469 0.203 5.80 7.86 1
(i) Superior Coating 6S 62.7 5.16 1 8.6 11.73 -
Our advanced formula mill coating offers a clean,durable surface that is also Sch-10 ASTIVI A135/A795
paintready for custom color applications without special preparation. M-COAT Specifications
NPS Norninall -N-om-I`=aI.D.1-7o-m-ina7---Tt-. Wt.(H20 Filled) CRR
I I U W
o'. ..
In;mm In,Pm In;mm Wall in:mm Lbs/Ft,k/m Lbs/Ft;kq/m -
t
The internal surface of all black Fire Sprinkler pipe up to 4.5000" in diameter I 1A 1.660 1,442 0.109 1.810 2 525 7.0955
shall be coated with Allied Tube&Conduit Antibacterial Formula "M-COAT". 32 42.2 36.6 2.77 2.7 3.75 -
1112" 1.900 1.682 0.109 2.09 3.04 5.6570
40 483 42 7 2 77 3.1 4.52 -
American Made 2 2.375 2.157 0.109 2.640 4.22 4,5827
9
50 60.3 54�8 2.77 3.9 1 6.28 1
Manufactured at one of 3 U.S.Facilities and is available through distributors in Th" 2.875 2.635 0,120 3,530 5.89 3.5196
he USA,Canada,Mexico,and Latin America, 65 73 66.9 3.05 5.26 8.77 -
3" 3.500 3.260 0,120 4.34 7.94 2,5550
75 88.9 82.8 3.05 6.4 11 M -
Specifications & Approvals 4" 4.500 4.260 0.120 5.62 11.78 1.6020
100 114.3 108.20 3.05 8.3 17.53
5 5.563 5.295 0.134 7.78 17.33 1.4874
SchedUle-1 O/Schedule-40 M-COAT pipe are in compliance with the following: 1 141.3 134.5 3.40 11.58 25.80 -
ASTM Al 35,Type E,Grade A,and NFPA 13.Both pipe products have a working 6- 6.625 6.357 0.134 9.3 23.03 1.0251
150 168.3 161.5 3.40 118
pressure rating of 300 psi maximum and also meet the stringent requirement 8.* 8.625 8.249 0.188 16.96 s
for the following tests:Welded Outlets,Hydrostatic Pressure,Side Wall Rupture, 200 219 209.50 4.78 1 25.2 1
Vibration Test. 'Not available with kl-(-.oai
4PPROVED
Project: Sprinkler Contractor: Date:
Engineer: Specification Reference: System Type:
Locations: Comments:
Customer Service: (800)882-5543 Fax: (800)659-7730 www.alliedtube-sprinkler.com
a I h e d 16100 S Lathrop Ave 11350 Norcorn Rd. 2525 N 27th Ave.
TUBE& CONDUIT* Harvey,IL 60426 Philadelphia, PA 19154 Phoenix,AZ 85009
atkore
02013 Atkore International,Inc.All Rights Reserved.STP-S3-4M-1301
Check Valve 803d April 13, 2012
CR
A A SWING CHECK VALVE
N41KJNG* MODEL D-1 & G-1
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
SIZE A B_ C D E
15 2-1/2" 9 4-1/2" 2-5/8" 2" 2' Fig—Fig
Not Available
(65mm) (228,6 (114,3) (66,7) (50,B) (50,8)
31, 10-1/8"4-13/16"2-11/16" 2-9/32"2-9/32" FIg—FIg
(80mm) (257) (122.2) (68,3) (58.1) (58.1) Not Available
7 4" 10-5/8" 5-3/16" 3-1/8" 2-1/4" 2-1/4" 9" 15/16"
Pr (1 00mm) (269,9).1 (131,8) (79.4) (57.2) (57,2) (228,6) (23,81)
8 1.
S..Iingp;;..,,.r 13-3/8' —13/115" 4-1/16" 2-1/4" 2-1/4" 11-
locctlon A (340) (173,3) (103.2) (57,2) (57,2) (279.4) (25,4)
.11 volv. 9
17" 8-13/16" 5" 2 2; 2-7/8" 3-1/2" 1-1/8-
Pr r
1.,.Iln-p�
.o..tlon
12 (431,8) (223.4) (127) C63 4 (73,0) 1(342.9) 28,58)
10 15 Dimensions shown in parentheses are millimeters.
3
4", 6", and 8" valves are manufactured with sculptured flanges.
a-4 Dimension Indicates thickness of flange at bolt holes.
2 6 D
Figure 1
PART NUMBER
ITEM D-1 G-1 G-1 G-1 G-1 NO.REQ'D
NO. 2-1/2" 3" 4" 6" 8" DESCRIPTION MATERIAL
(131,166) (DN80) (DN100l (IDN1160) (DN200) 2-112" 3" 4" 6" 8"
I Body Ductile Iron,ASTM A536
(65-45-12) 1 1 1 1 1
2 Cover Assembly,300 PSI WWP E-Coated HSLA Steel,A71 5 and 1 1 1
Stainless Steel,UNS-S30400
3 107576 107576 07576 07576 None Bushing Lubricomp 189 Ryton 2 2 0
4 05355A 05355A 04900A 04991A 05334A Clapper Hinge Pin Stainless Steel,UNS-S30400 1 1 1 1 1
5 05445A 05445A 05445A 05445A 05369A Hinge Pin Retaining Ring Stainless Steel,UNS-S15700 2 2 2 2 2
6 01755A Clapper Hex Jam Nut#10-24 UNC Stainless Steel,UNS-S30400 1 0 0 0 0
08159 08159 Clapper Hex Jam Nut 3/8"-24 UNIF Stainless Steel,UNS-S30400 0 1 1 0-
08144 08144 Clapper Hex Jam Nut%"-20 UNC Stainless Steel,UNS-S30400 0 0 0 1 1
1
2
0
0
7 06595A 08158 , 08158 08143 , 08143 Sealincl Washer EPDM and Stainless Steel 1 1 1 11 1,
8 Clapper Teflon�Coat R Steel UNS-
G101190 1 1 1 1
9 Clapper Rubber EPDM,ASTM D2000 1 1 1 1
10 Clapper Rubber Retainer Stainless Steel,UNS-S30400 1 1 1 1 1
06595A' H.H.C.Screw#10-24 LINC x 1/2"(12.7 mm)1g. Stainless Steel,UNS-S30400 1 0 0 0 0
10194 10194 Screw, Button Head,Socket,3/8"-24 UNIF x 1/2" Stainless Steel,UNS-S30400 0 1 1 0 0
Screw, Button Head,Socket, 1/2"-20 UNIF x 3/4"
10308 Stainless Steel,UNS-S30400 0 0 0 1 1
(19.1 mm)Ig.
10686 Screw, Button Head,Socket, 1/2"-20 UNF x 7/8" Stainless Steel,UNS-S30400 0 0 0 0 1
12 Seat Brass, UNS-C84400 1 1 1 1 1
13 05354B 05354B 04649B 04992B 05339C Cover Gasket EPDM,ASTM D2000 1 1 1 1 1
-16 UNC x 3/4"(119,1 mm)Ig. Steel,Zinc Plated 4 4 6 0 0
0 1 517A 0 1 517A 0 1 517A H.H.C.Screw 3/8"
14 �04993A
H.H.C.Screw '/2"-13 UNC x 7/8"(22.2 mm)Ig. Steel,Zinc Plated 0 0 0 6 0
-11 UNC x 1-1/4"(31.8 mm)Ig. Steel,Zinc Plated 0 0 0 0, 6
01922A H.H.C.Screw 5/8"
15 1/2"(115 mm)NPT Pipe Plug Steel 2 2 1 21 01 0
3/4"(20 mm)NPT Pipe Plug Steel 0 1 01 01 21 2
Indicates replacement part is not available
Indicates replacement part only available in a Sub-Assembly listed below.
Sub-Assemblies
3.6-11 05499B 08518 08519 08520 08521 ClapperA sembly
9,10 -- 14864 1 14865 14866 -- Replacement Clapper Rubber Kit*
I Clapper rubbers are different on 3",4",&6"G-1 valve than original manufacture.If clapper rubber requires replacement order replacement rubber kit.
Form No. F 102688 Replaces page 803a-d, dated July 1, 2011.
(Revised Figure 1)
April 13, 2012 Check Valve 803c
®R
SWING CHECK VALVE
N41KJM* MODEL D-1 & G-1
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-6464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
6-13. Valve Maintenance
(Refer to Figure 1)
1. Perform steps 1 through 5 of paragraph 6.A- FIVE-YEAR INTERNAL INSPECTION.
2. To remove clapper rubber(9):
a. Use the appropriate wrenches to loosen and remove the button-head socket screw(11), hex nut(6),sealing washer(7),
and rubber retainer(10).
b. Remove the clapper rubber(9) for inspection. If the clapper rubber shows signs of wear, such as cracking, cuts, or
excessively deep grooves where the rubber contacts the water seat, replace the rubber.
3. To re-install clapper rubber(9):
a. Place the clapper rubber(9)over the center hub of the rubber retainer(10).
b. Position the retainer(10) (with rubber in place)against the clapper(8) as shown in Figure 1.
c. Replace and tighten the button-head socket screw(11), sealing washer(7), and hex nut(6). The sealing washer(7)
and hex nut(6) must be located on the top side of the clapper as shown in Figure 1. Do not over-tighten.
4. To remove clapper(8), and/or hinge pin (4):
a. Remove the hinge pin retaining rings (5)to free the hinge pin (4) for removal.After the hinge pin (4) is removed, the
clapper(8)can be removed.
5. To re-install clapper(8), and/or hinge pin (4):
a. Verify that the clapper rubber(9) is in good condition and that it is properly installed.
b. Position the clapper(8)with the elongated hinge holes aligned between the holes of the hinge bracket welded inside
the cover (2). The system (top) side of the clapper (8) must face the direction indicated by the flow arrow stamped
inside the cover(2).
c. Insert the hinge pin(4)through the holes at one end of the hinge assembly. Continue to push the hinge pin(4)through
the holes at the remaining end of the hinge assembly.
d. Re-install the hinge pin retaining rings (5).
6. To re-install cover/clapper assembly (2-11):
`IIIIIIiiw a. Verify that cover gasket(13) is in position and in good condition.
b. Slide the cover/clapper assembly(2-11)into the Swing Check Valve so that the clapper rubber(9)contacts the water
seat(12).
c. Replace the cover screws (14). Use the appropriate wrench to cross-tighten all screws to the torque value shown in
Table 2 for the valve used. DO NOT over-tighten.
7. AVAILABILITY
The Viking Swing Check Valve is available through a network of domestic and international distributors. See the Viking Corp.Web
site for closest distributor or contact The Viking Corporation.
& GUARANTEES
For details of warranty, refer to Viking's current list price schedule or contact The Viking Corporation directly.
Table 2: Torque Values for Viking Swing
Check Valve Cover Screws
Valve Size Screw S je Values
2-1/2" (DN65) 3/8"-16 HHC 19 ft-lbs 2.63 kg-m
3" (DN80) 3/8"-16 HHC 19 ft-lbs 2.63 kg-rn
4" (DN100) 3/8"-16 HHC 19 ft-lbs 2.63 kg-m
6" (D N 150) 1/2"-13 HHC 45 ft-lbs 6.23 kg-m
8" (DN200) 5/8"-11 HHC 93 ft-Ibs 12.9 kg-nn
Check Valve 803b ApriI13 2012
®R,
SWING CHECK VALVE
N41KJNG* MODEL D-1 & G-1
The Viking Corporation, 210 N Industrial Park Drive, Hastings M1 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
4. INSTALLATION
The Swing Check Valve must be installed in an area not subject to physical damage.When corrosive atmospheres and/or contami-
nated water supplies are present, it is the owner's responsibility to verify compatibility with the Swing Check Valve and associated
equipment. Prior to installing the valve, thoroughly flush the water supply piping to verify that no foreign matter is present. The
Swing Check Valve may be installed in the vertical position with direction of flow up, or in the horizontal position with the access
cover up.
Systems with water working pressures above 175 psi (12 bar) may require extra-heavy pattern fittings.Viking Swing Check Valve
flanges are Ductile Iron ANSI B16.42, Class 150, with a maximum water working pressure of 300 psi (20.7 bar). ANSI B16.42,
Class 150 flanges are not compatible with ANSI Class 250 or Class 300 flanges.To mate the Viking Swing Check Valve with ANSI
Class 250 or Class 300 flanges, use the grooved-inlet/grooved-outlet style installed with listed grooved/flanged adapters of the
appropriate pressure rating. For piping with grooved connections, the grooved-inlet/grooved-outlet style Swing Check Valve may
be installed with listed grooved couplings of the appropriate pressure rating.
5. OPERATION (Refer to Figure 1)
Flow through the Viking Swing Check Valve lifts the rubber-gasketed clapper(8, and 9)off the seat(12)to enter the sprinkler pip-
ing. When flow through the valve stops, the clapper(8) closes quickly. The rubber gasket(9)forms a tight seal against the brass
water seat(12), trapping pressure above the clapper and preventing reverse flow from sprinkler piping.
Hydrostatic Test:
The Swing Check Valve is manufactured and listed for use at a maximum water working pressure of 300 psi (20.7 bar). The valve
is factory tested 6t 600 psi (41.4 bar). Check Valves may be hydrostatically tested (in accordance with NFPA 13) at 350 psi(24.1
bar)and/or 50 psi (3.4 bar)above the normal water working pressure for limited periods of time(two hours)for the purpose of ac-
ceptance by the Authority Having Jurisdiction. If air testing is required, do not exceed 40 psi (2.8 bar)air pressure.
6. INSPECTIONS, TESTS AND MAINTENANCE
NOTICE: The owner is responsible for maintaining the fire-protection system and devices in proper operating
condition.
The Viking Swing Check Valve must be kept free of foreign matter, freezing conditions (when used on wet systems), corrosive
atmospheres, contaminated water supplies, and any condition that could impair its operation or damage the device.
It is imperative that the system be inspected and tested on a regular basis. The frequency of the inspections may vary due to
contaminated water supplies, corrosive water supplies, and corrosive atmospheres. For minimum maintenance and inspection
requirements, refer to NFPA 25. In addition, the Authority Having Jurisdiction may have additional maintenance, testing, and in-
spection requirements that must be followed.
WARNING: Any system maintenance which involves placing a control valve or detection system out of serv-
ice may eliminate the fire-protection capabilities of that system. Prior to proceeding, notify all the Authority
Having Jurisdiction. Consideration should be given to employment of a fire patrol in the affected areas.
6-A. Five-Year Internal Inspection
Internal inspection of Swing Check Valves is recommended every five years unless inspections and tests indicate more fre-
quent inspections are required.
(Refer to Figure 1)
1. Notify the Authority Having Jurisdiction, remote station alarm monitors, and those in the area affected that the system will
be taken out of service. Consideration should be given to employment of a fire patrol in the affected areas.
2. Close the water supply main control valve, placing the system out of service.
3. Open the main drain. If necessary, open the system test valve to vent and completely drain the system.
4. Use the appropriate wrench to loosen and remove the cover screws(114), and remove the cover/clapper assembly(2-11).
5. Inspect the water seat(12). Wipe away all contaminants, dirt, and mineral deposits. DO NOT use solvents or abrasives,
6. Inspect the cover/clapper assembly (2-11) and the cover gasket(13). Test the hinged clapper(8)for freedom of move-
ment. Renew or replace damaged or worn parts as required.
CAUTION: Never apply any lubricant to seats, gaskets, or any internal operating parts of the valve. Petroleum-
based grease or oil will damage rubber components and may prevent proper operation.
7. When Internal inspection of the Check Valve is complete, perform step 6 of paragraph 11. VALVE MAINTENANCE to re-
install the cover/clapper assembly (2-11).
April 13, 2012 Check Valve 803a
CR,
SWING CHECK VALVE
N4 I KJ W*j MODEL D-1 & G-1
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9601 Technical Services: 877-384-6464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
The Viking Swing Check Valve is a general purpose rubber-faced check valve ap-
proved for use in fire protection systems. The Swing Check Valve is manufactured
with a ductile iron body, brass seat, and a'rubber-faced clapper assembly, hinged to
a removable access cover for easy inspection and maintenance.
The valve may be installed vertically or horizontally with access cover facing up. For
availability of flanged-flanged and grooved-grooved options, refer to Table 1.Tapped
openings (with plugs) and gauge connections are provided on both the inlet and
outlet chambers of the valve.
FEATURES
A. Ductile iron body for less weight and extra strength.
B. Rated to 300 psi (20.7 bar)water working pressure.
C. Rubber-faced clapper hinged to access cover for quick removal and easy servic-
ing.All moving parts can be serviced without removing the valve from the installed
position.
D. With the cover/clapper assembly removed, the clapper rubber replacement re-
quires removal of only one screw.
E. Can be installed vertically or horizontally with access cover facing up.
2. LISTINGS AND APPROVALS
cULus Listed: Guide No. HIVIER
FM Approved: Single Check Valves
NYC Department of Buildings: MEA 89-92-E, Vol. XI
3. TECHNICAL DATA
Specifications:
Rated to 300 psi (20.7 bar)water working pressure.
Factory tested hydrostatically to 600 psi(41.4 bar). Viking Technical Data may be found on
Standard Flanged Connections:ANSI B1 6.42 Class 150 (mates with ANSI Class The Viking Corporation's Web site at
125 and Class 150 flanges). http://www.vikinggroupinc.com.
Standard Grooved Connections:ANSI/AWWA C606 The Web site may include a more recent
Tapped Bosses: 2-1/2" (DN65), 3" (DN80)and 4" (DN100): Two 1/2" (15 mm) NPT edition of this Technical Data Page.
6" (DN150)and 8" (DN200):Two 3/4" (20 mm) NPT
Material Standards: Refer to Figure 1.
Ordering Information: Refer to Table 1 for part numbers and shipping weight.
Table I Systems with water working pressures above
Size Valve Inlet Type Outlet Friction Shipping Part No. 175 psi (12 bar) may require extra-heavy pat-
Nominal Type Loss* Weight tern fittings. Viking Swing Check Valve flanges
2-1/2"(DN65) Groove Groove 6 ft.(1.8 m) 16 lbs.(7 kg) 05497C are Ductile Iron ANSI 1316.42, Class 150, with a
maximum water working pressure of 300 psi(20.7
3"(DN80) Goove Groove 10 ft.(3.1 m) 20 lbs.(9 kg) 08536 bar). ANSI B16.42, Class 150 flanges are NOT
4"(DN100) Flange Flange 13 ft.(4.0 m) 47 ibs.(21 kg) 08538 compatible with ANSI Class 250 or Class 300
4"(D N 100) Groove Groove 13 ft.(4.0 m) 27 lbs.(12 kg) 08539 flanges. To mate the Viking Swing Check Valve
with ANSI Class 250 or Class 300 flanges,use the
6"(D N 150) Flange Flang e 20 ft.(6.0 m) 75 lbs.(34 kg) 08542 grooved-inlet/grooved-outlet style installed with
6"(DN 150) Groove Groove 20 ft.(6.0 m) 51 lbs.(23 kg) 08543 listed grooved/flanged adapters of the appropriate
8"(DN200) Flange Flange 23 ft.(7.0 m) 135 lbs.(61 kg) 08546 pressure rating. For piping with grooved connec-
tions,the grooved-inlet/grooved-outlet style Swing
8"(DN200) T��� Groove 123 ft.(7.0 m)P 06 lbs.(48 kg) 08547 Check Valve may be installed with listed grooved
�.Expressed in equivalent length of Schedule 40 pipe based on Hazen&Williams formula:C=120 couplings of the appropriate pressure rating.
Form No. F102688 Replaces page 803a-d, dated July 1, 2011.
(Revised Figure 1)
2
��W'111411,11 1111= IN$me E
C(@- <�> FE P_C__Bj
LISTED 0026
MEA:276-99-E CSFM:7770-0531:113
SERIES 705W
46W WITH WEATHERPROOF ACTUATOR
The Series 705W butterfly valve features an approved weatherproof actuator housing
approved for indoor or outdoor use. It has a ductile iron body and disc with EPDM disc
coating.The body is coated with a heat fused polyphenylene sulfide blend to meet FM
requirements.Designed for fire protection services only.Series 705W valve is UL Listed
and FM Approved for 300 psi/2065 kPa service.The Series 705W is also LPCB approved
for 20 Bar and VdS approved for 16 Bar service. Contact Victaulic for details of agency
approvals.
WEATHERPROOF ACTUATOR
Pre-wired supervisory switches that monitor the valve in the fully open position for all
sizes.
OPTIONAL SUPPLY-SIDE TAP
Series 705W valves are available with a;6"NPT supply side tap designed to allow
direct water supply connection to Victaulic FireLock actuated fire protection valves.See
separate drawings below.This is an optional feature and must be clearly noted on all
orders.
MATERIAL SPECIFICATIONS Body:Ductile iron conforming to ASTM A-536,coated with polyphenylene sulfide blend.
Disc: Ductile iron conforming to ASTM A-536,various grades, EPDM coated
Disc Coating:
Grade"E"EPDM
EPDM(Green color code).Temperature range—30OF to+230OF/-340C to+1100C.
Recommended for cold and hot water service within the specified temperature range plus a
variety of dilute acids,oil-free air and many chemical services. UL classified in accordance
with ANSUNSF 61 for cold+86*F/+30'C and hot+180*F/+82*C potable water service, NOT
RECOMMENDED FOR PETROLEUM SERVICES.
Stem Bearings:Teflon impregnated fiberglass with stainless steel backing.
Stem Bearing Nuts:Type 416 Stainless Steel.
Tap Plug:Carbon steel, plated.
O-Ring: EPDM
Bracket:Carbon steel, painted.
Actuator:
* 21h—8765—200 mm: Bronze traveling nut on a steel lead screw,in a ductile iron housing.
* 10—127250—300 mm:Steel worm and cast iron quadrant gear,in a cast iron housing.
JOB/OWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para—
Location Date Approved
Date
www.victaulic.com
VICTALLIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2008 VICTAUL;C COMPANY.ALL RIGHTS REEERVED. X/Ctauhc�
I�EV 9
1PS CARBON STEEL PIPE -FIRE f"ROTECTION VALVES 10.18
.. ..............
aive
SERIES 705W
WITH WEATHERPROOF ACTUATOR
DIMENSIONS- Its <&>
USTEI)
sill _,_P.v_Aprx,Wgt,7
Dim""'i,
Nomi-I A�t_li oot'j-
E'd rl Fn�
I'm 'A"
N"
29$ 2.875 377 8.76
4.21 6.08 3.00 0.00 0.75 8 j
65 73.0 9S.6 222.5 106.9 154.4
76.2 0.0 19.1 3.8
76.1 mm 3.000 3.77 8.76 4.21 6.08 3.00 0.00 0.75
8.3
76.1 95.6 222.5 106.9 76.2 0.0
154.4 19.1 3.8
3 3.500 3,77 9AO 0.08 4.21 6.08 3.00 0.00 0.75 8.9
80
88.9 95.6 238.8 2.0 106.9 154.4 76.2 0.0 19.1 4.0
4 4.500 4.63 10.84 0.07 6.01 6.98 3.00 0.73 1.13 14.9
__IOO 114.3 117.6 275.3 1.8 152.7 T7Z3 76.2 18.5 28.7 6.8
139.7 mm 5.500 5.88 12.38 0.43 6.01 8.57 4.50 21.0
139.7 149.4 314.5 10.9 152.7 217.7 114.3 9.5
5 5.563 5.88 12.38 0.43 6.01 8.57 4.50
21.0
125 141.3 149.4 314.5 10.9
152.7 217.7 114.3
9.5
165.1 mm 6.500 5.88 13.41 1.00 7.51 9.32 4.50 1.60 1.88 26.5
149.4 340.6 25.4 190.8 236.7 114.3 40.6 47.8 12.0
6
6.625 5.88 13.41 1.00 7.51 9.32 4.50 1.60 1.88 26.5
ISO
168.3 149.4 340,6 25.4 190.8 236.7 114.3 40.6 47.8 12.0
8 8625 5.33 16.50 '.27 9.65 10.98 6.30 0.00 0.68 43.0
219.1 135.4 419.1 32.3 245.1 278.9 160.0 0.0 17.3 19.5
10 10,750 6.40 19.14 1.72 12.20 16.19 9.00 80-0
250 273.0 162.6 486.2 43.7 309.9 411.2 228.6 36.3
12 12.750 6.50 21.54 2.66 14.25 17.22 9.00 102.0
300 323.9 165.1 5471 6-7.6 362.0 437.4 228.6 46.3
On Centerline
t These dimensions apply only to a Series 705W Butterfly Valve with a 1/2-inch NPT supply-side tap
1,To prevent rotation of valves,it is recommended That Series 701W be installed with Viclaulic Style 07 Ze,o-Fle.t Style 005 FireLock,Style 009/009V FireLock
EZ,or Style HP-70 Rigid Couplings.IfVictaulic flexible couplings are used.additional support may be required.
2-Valve must not be installed with disc in full open position.Disc must be partly closed so that no part is protruding beyond end ofvalve body.
3.Victaulic grooved end butterfly valves are permitted for use with grooved end pipe(IPS)only.Not permitted for use with plain end(IPS)pipe-
4.Series 705W valves are designed for ambient weather conditions as opposed to submersible service.
0 0
W NPT
B W NPT B Supply Tap
Supply Tap
L
N
N
F
1-j- L _��j E IP I- L I' E PE
2-h-4-INCH/65-100-MM SIZES 5-12-INCH/125-300-MM SIZES
www.victaulic.com
viCTAULIC IS A REGISTERED TRADEMARK OF VICTALILIC COMPANY.0 2008 VICTALILIC COMPANY.ALL RIGHTS RESERVED.
10.18 2 ��E'4 H
STEEL Flf'� FiRF. PROTECTION VAUff.-�, 10. 18
-1 Plittlrerfly Vallvc,
LA
SERIES 705W
WITH WEATHERPROOF ACTUATOR
DIMENSIONS-
0026
LISTED
Si, Dimensions-inchesimillimeters
A,tual Q�tsid
N,rninal e
Diarne(er
i nch�, End IQ End Hgt,
W
Mn) N'
0.00 0.75 83
76.1-- 3.000 3,77 8.76 4.21 6.08 4.50
95.6 222.5 106.9 154.4 114.3 0.0 19.1 3.8
3.500 377 SIAO 0.08 4.21 6.08 4.50 0.00 0.75 8.9
3 88.9 9,5.6 238.8 2.0 106.9 154.4 114.3 0.0 19.1 4.0
4 i 4.500 4.63 10'a4 0.07 6.01 6.98 4.50 0.73 1.13 14.9
100 114.3 117.6 275.3 1.8 152.7 177.3 114.3 18.5 28.7 6.8
139.7mm 5.500 5.88 12.38 0.43 6.01 8.57 7.87 - - 21.0
139.7 149A 314.5 10.9 152.7 217.7 200 9.5
6.625 5.88 13AI 1.00 7.51 9.32 7.87 1.60 1.88 26.5
6
150 168.3 149.4 340.6 25.4 190.8 236.7 200 40.6 47.8 12.0
8 8.625 5.33 16.50 1.27 9.65 10.98 7.87 0.00 0.68 43.0
200 219.1 135.4 419.1 32.3 245.1 278.9 200 0.0 IZ3 19.5
10 1 10.750 6AO 19.14 1.72 12.20 16.19 9.84 80.0
___150 1 273.0 162.6 486.2 43.7 309.9 411.2 250 36.3
2 12.750 6.50 21.54 2,66 14.25 17.22 9.84 102.0
1 300 323.9 165.1 547.1 67.6 362.0 437A 250 463
*On Centerline
t These dimensions apply only to a Series 705W Butterfly Valve with a 1/2-inch NPT,supply-side tap
1.To prevent rotation ofvalves.it is recommended that Series 705W be installed with Victaulic Style 07 Zero-Flex'.Style 005 Firel-ock,Style 009/009V FireLock
EZ,or Style HP-70 Rigid Couplings.IfV!ctaulic flexible couplings are used.additional support may be required.
2.Valve must not be installed with disc in full open position.Disc must be partly closed so that no part is protruding beyond end ofvalve body.
3.Victaulic grooved end butterfly valves are permitted for use with grooved end pipe(IPS)only.Not permitted for use with plain end(IPS)pipe.
4.Series 705W valves are designed for ambient weather conditions as opposed to submersible service.
0
f VVINIPT
LL SupplyTap
B 'A'NPT
-pplyTap
i , - N N
_F_
j-__4 A ;P
76.IMM-4-INCH165-100-MM NOMINAL SIZES 139.7MM-12-INCH/125-300-MM NOMINAL SIZES
www.victaulic.com -I./c taul lc�
VICTALILIC IS A REGISTERED TRADEMARK OF VICTALILIC COMPANY.C 2008 VICTALILIC COMPANY.ALL RIGHTS RESERVED.
REV H
IrS CARBON �TFEL PIPE--FIRE PROTELl,ION VALVES 10. 18
............
Fiypl ,llv-W�' Wittertly Vaive
SERIES 705W
WITH WEATHERPROOF ACTUATOR
PERFORMANCE Cv values for flow of water at+60*F/+16*C with a fully open valve are shown in the table below.For
additional details,contact Victaulic.
Formulas for Cv Values:
AP Q, Where.
C Q=Flow(GPM)
AP Pressure Drop(psi)
Q C,x�/A—P C, Flow Coefficient
C, C S-,
C
i Actual
Nominal ),.,Side Nominal 0 t5ide N outside
si�� t.", I Sie Di arnet" 'is., 1 �Di,',.eZt
Inche� tnche� 5., 'ches
MM e'll �Mai -MM '90PRW.] M-M- Tom tFult openij;
216 2.875 325 1397 rn m 5500 8 8.625
65 73.0 1,39.7 1150 200 219.1 400
10.750
76.1 mm 3.000 325 5 5.563 1150 10 5750
125
76.1 141.3 250 273.0
3 3.500 6.500 1850 750 8300
80 88.9 482 165.1 MM 12 12.
165.1 300 323.9
4 4- 00 6 6.625
1.0 ,5,,.3 600 1 50 168.3 1850
Formulas for Kv Values:
AP Q, Where:
K Q=Flow
v
Q I�- JAT AP Pressure(bar)
I� Flow Factor
K� si, K, Size K,
I I----777
Actual 1
. Actual
Nmi�ial utside Nomw.l Nominal Outside
Size' zz" Size Di;imvtpl
Inches In 1.11,112.5 1 Incnes Indla5
.nM MM lFull Opep) 'Tim "IM (Full Opeq),_
2 li 2.875 5500 8 8.625
65 73.0 2 8, 139.7 rnm 1' 995 2940
39.7 200 219.1
76.1 mm 3.000 280 5 5.563 10 10.750
76.1 125 141.3 995 250 273.0 4975
3 3.500 415 165.1 mm 6,500 12 12.750 7180
80 88.9 165.1 1600 300 323.9
4 4"0' 6 6.625
100 ,4.3 520 1 50 168.3 1600
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTALILIC COMPANY.0 2008 VICTAULIC COMPANY.ALL RIGHTS RESERVED. c tauhc�
REV �-1
IRS UIRRQN STEEL PIPE- FIRE PROTECTION VALVFS 10. 18
......---------
ock" 8tifterfly Valve
SERIES 705W
WITH WEATHERPROOF ACTUATOR
SWITCH AND WIRING 1.The supervisory switch contains two,single pole,double throw,pre-wired switches.
2.Switches are rated:
10 amps 0 125 or 250 VAC/60 Hz
0.50 amps @ 125 VDC
0.25 amps @ 250 VDIC
3.Switches supervise the valve in the"open"position.
4.One switch has two#18 IVITW wires per terminal,which permit complete supervision of leads
(refer to diagrams and notes below).The second switch has one#18 IVITW wire per terminal.
This double circuit provides flexibility to operate two electrical devices at separate locations,
such as an indicating light and an audible alarm,in the area that the valve is installed.
5.A#14 IVITW ground lead(green)is provided.
Switch#1=S1 For connection to the supervisory circuit of a UL
Listed alarm control panel
Switch#2=S2 Auxiliary switch that may be connected to auxiliary
devices,per the authority having jurisdiction
S, Normally Closed:(2)Blue
Common:(2)Yellow
Normally Closed:Blue with Orange Stripe
S2 Normally Open:Brown with Orange Stripe
Common:Yellow with Orange Stripe
LL L6nD
ILEKm—7 fm_ meN�ELWEK%�
o,:
_L Wr,_A=D'
E�:
c�"E
suPERw1m
co.
WT-CH
CWKT
C—C—ECTORS sL
2�K.
t0,5AA25VDr
T
025AT25OVDC
WILI BELL
�J.�KE
NOTE:The above diagram shows a connection between the common terminal(yellow–S1 and
yellow-with-orange stripe–S2)and the normally closed terminal(blue–S1 and blue-with-orange
stripe–S2).In this example,the indicator light and alarm will stay on until the valve is fully open.
When the valve is fully open,the indicator light and alarm will go out.Cap off any unused wires
(e.g.brown with orange stripe).
Only S1(two leads per terminal)may be connected to the fire alarm control panel.
The connection of the alarm switch wiring shall be in accordance with NFPA 72 and the auxiliary
switch per NFPA 70(NEC).
...........
wwwmictaulic.com
VICTAULIC ISA REGISTERED TRADEMARK OF VICTALILIC COMPANY.0 2008 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
10J8-6 EV h
p] 16114 4 4;11;1 vIIIII a IN 2§;J:00:00 to]0 STIA RIMS
SERIES 705W
%Mw WITH WEATHERPROOF ACTUATOR
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
..........-
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be
installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the
right to change product specifications.designs and standard equipment without notice and without
incurring obligations.
..........
INSTALLATION Reference should always be made to the installation sheet included with the valve.Verify you have
the latest revision by visiting our website at www.victaulic.com.Further reference can be found in the
1-100 Victaulic Field Installation Handbook.
WCAS-7HFF85
-------------- . .. ...... .......
For complete contact information,visit www.victaulic.com
10.18 2466 REV H UPDATED 812008 X/c tauhc�
VICTAULIC IS A REGISTERED TRADEMARK OF VICTALILIC COMPANY.0 2008 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
10J8
M
lox$]
hreLockli�' Fittings
See Victaulic publication 10.01 for details V..P0
-----------
FireLock4l products comprise a unique system specifically designed for fire protection
services.FireLock full-flow elbows and tees feature CAD-developed,hydrodynamic
design,affording a shorter center-to-end dimension than standard fittings.A noticeable
bulge allows the water to make a smoother turn to maintain similar flow characteristics as
standard full flow fittings.
FireLock fittings are designed for use exclusively with Victaulic IPS-sized couplings that
have been Listed or Approved for Fire Protection Services.Use of other couplings or
flange adapters may result in bolt pad interference.
Victaulic FireLock fittings pressure ratings conform to the ratings of Victaulic FireLock Eze
Style 009N/Style 009H couplings.
MATERIAL SPECIFICATIONS Fitting: DUCtIle ron contorming to ASTIVI A-536,grade 65-45-12.
Fitting Coating:
• Orange enamel.
• Red Enamel in EMEA-1.
• Optional:Hot dipped galvanized.
JOBIOWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para-----
Location Date Approved
Date
www.victaulic.com io/c ta U C�
VICTALILIC IS A REGISTERED TRADEMARK OF VICTALLIC COMPANY 0 2012 VICTALILIC COMPANY.ALL RIGHTS RESERVED.
REV K
IPS CARBON SfEEL PIPE -FIR�' PROTECTION PRODUCT�� 10.03
FireLocVl Fittings
DIMENSIONS
c
'�CtoEl to E
T Cj T
-r- c 'b
to
E
1?120 w-,
1.E L
L-4�:-
NO.001 NO.002 NO.006
No,001 N 003 No.002
si- 90'Elb- 45'Elb-
N.Im-1
Aduai i
Aprmx
si- 0.!-Jd� cloE Weight E� h c to E Weight
11101
MIn mlil kg mnl kg
1 Y4 1,660 0.8 0 3
32 42A 21 01
I lh 1.900 0.82 04
40 48.3 - - - - - - 21 0.2
2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 06
50 60.3 70 0.8 51 0.8 70 1.1 22 03
21/2 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.83 1 0
65 73.0 76 1.4 57 1.0 76 1.6 22
76.1 mm 3.000 3.00 3.30 2.25 2.4 - - -
76.1 76 1.5 57 1.1
3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88
80 88.9 86 1.8 64 1.4 86 2.4 22 0.5
108mm 4,250 4.00 5.7 3.00 5.1 4.00 7.5 -- -
108.0 102 2.6 76 2.3 102 3.4
4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1,00 2.4
]Do 114.3 102 3.0 76 2.5 102 3.9 25 1 1
5 5.563 488 12.6 3.25 8.3 4.88 15.7 1.00 4.1
125 141.3 1'24 5.7 83 3.8 124 7.1 25 1.9
159mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 - -
158.8 140 5.7 89 4.2 140 8.0
6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 100 5.9
150 168.3 140 8.3 89 5.3 140 10.3 25 2.7
8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7
200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 1
(Iiiiw
www.victauliC.CDM
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. X/ctaulle
10,03 2
IPS CARSON SIFFEL PIPE -HRE PROTECTION PRODUIiS 10.03
FireLock(',` Fittings,
FLOW DATA Frictional Resistance
Equivalent Feet/motors of Straight Pipef,�
1.660
42.4
1.900 -
40 48.3 -
2 2.375 3.5 1.8 8.5 3.5
50 60.3 1.1 0.5 2.6 1.1
21/2 2.875 4.3 2.2 10.8 4.3
65 73.0 1.3 0.7 3.3 1.3
76.1 rnm 3.000 4.5 2.3 11.0 4.5
76.1 L4 0.7 3.4 1.4
3 3.500 5.0 2.6 13.0 5.0
80 88.9 1.5 0.8 4.0 1.5
108mm 4.250 6.4 3.2 15.3 6A
108.0 2.0 0.9 4.7 2.0
4 4.500 6.8 3.4 16.0 6.8
100 114.3 2.1 1.0 4.9 2.1
5 5.563 8.5 4,2 21.0 8.5
125 141.3 2.6 1.3 6.4 2.6
159mm 6.250 9.4 4.9 25.0 9'6
158.8 2.9 1.5 7.6 29
6 6.625 10.0 5.0 25.0 10.0
150 168.3 3.0 1.5 76 3.0
8 8.625 13.0 5.0 33.0 13.0
1 200 219.1 4.0 L5 10.1 4.0 -1
t The flow data listed is based upon the pressure drop of Schedu!e 40 pipe.
www.victaulic.com 1,i.c ta U ic�
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY,0 2012 VICTAULIC COMPANY.ALL RICHTS RESERVED.
REV K
GENERAL NOTES NOTE:When assembling Firel-ock EZ couplings onto end caps,take additional care to make certain
the end cap is fully seated against the gasket end stop.For Firel-ock EZ Style 009N/009H
couplings,use Firel-ock No.006 end caps containing the"EZ"marking on the inside face or No.60
end caps containing the"QV EZ"marking on the inside face.Non-Victaulic end cap products shall
not be used with Style 009/009WO09H couplings.
................. .................-------------- .......
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be
installed in accordance with current Victaulic installationlassembly instructions.Victaulic reserves the
right to change product specifications,designs and standard equipment without notice and without
incurring obligations.
For complete contact information,visit www.victaulic.com
10.03 1539 REV K UPDATED 09/2012
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
10,03
Malleable Iron
Threaded FI* tti' ngs
150# 300#
............
4,1�
1-1,11, 0
...........
M-0
SMITH - COOPERO
I N T E R N A T 1 0 N A L
�ftw SMITF1 , C00PER7
I N T E R N A T 1 0 N A L
Malleable Iron Threaded Fittings
150# & 300#
Specificatio!
• Class 150 branded fittings are UL Listed and FM Approved at 300 psi
• Class 300 branded fittings are UL Listed
• Hot-dipped galvanized fittings are certified to; NSF/ANSI 614 and
California AB1953 Lead Free
LISTED
• Canadian Registration Numbers available at www.smithcooper.com
FM
• Malleable castings conform to ASTM A197 < >
APPROVED
• Hot-dipped galvanized fittings conform to ASTM A153
* Malleable fitting dimensions conform to ASME B16.3
• Malleable bushings, plugs and locknuts conform to ASME B16.14
• Malleable unions conform to ASME B16.39
• NPT threads on all fittings conform to ASME 131.20.1
• Independent lab verification that fittings meet applicable chemical &physical properties
• Manufacturing facilities are ISO 9001:2000 and ISO 14001
• The '*> trademarked fittings are 100% air tested
�J Makable Iron Fitfings- 150# UL/FM
Fig. 33E I & 34E I -90- Elbow LISTED APPROVED
Size art umber A Packing
Weight
IN Black GaIv IN Inner Master LB
1/8 33E 1001C 34E 1001C 0.69 50 -----do-o -- 0.1
1J4 33E 1002C 34E 1002C 0.81 35 560 0.1
3J8 33E 1003C 34E 1003C 0.95 45 360 0.2
112 33E 1004C 34E1004C 1.12 50 20U 0.2
3/4 33E 1006C 34E 1006C 1.31 35 140 0.3
A 1 33E 1010C 34E 1010C 1.50 20 80 0.6
1-1/4 33E 1012C 34E 1D12C 1.75 20 40 0.9
1-112 33E 1014C 34E 1014C 1.94 15 30 1.2
2 33E 1020C 34E 1020C 2.25 8 16 1.8
2-112 33E 1024C 34E 1024C 2.70 6 12 3.1
3 33E 1030C 34E 1030C 3.08 - 7 3.9
A 3-1/2 33E 1034C 34E 1034C 3.42 4 6.6
4 33E 1040C 34E 1040C 3.79 3 7.5
5 33E 1050C 34E 1050C 4.50 2 13.2
6 33E 1060C 34E 1060C 5.13 19.8
8 33E 1080C 34E 1080C 6.3B 32.0
Fig. 33REI & 34REI - 90' Reducing Elbow
Size A B Pac ing Weight-
Part Number
IN
Black Ga1v IN IN Inner Master LB
114 x 1/8 33RE1002001C I 34RE1002001C 0.76 0.74 40 640 0.2
3/8 x 1/8 33RE1003001C 34RE1003001C 0.85 0.81 70 560 0.2
3/8 x 1/4 33RE1003002C 34RE1003002C 0.90 0.88 60 480 0.2
112 x 1/8 33RE1004001C 34RE1004001C 0.96 0.96 50 400
0.2
112 x 1/4 33RE1004002C 34RE1004002C 0.98 o.97 40 320 0.2
1/2 x 3/8 33RE1004003C 34RE1004003C 1.04 1,03 50 200 0.2
3/4 x 1/8 33RE1006001C 34RE1006001C 1.06 1.02 40 160 0.3
3 x 1 4 33RE1006002C 34RE1006002C 1.08 1.05 160 0.3
3/4 x 3/8 33RE1006003C 34RE1006003C 1.13 1.12 40 160 0.3
A 3/4 x 112 33RE1006004C 34RE1006004C 1.22 1.20 40 160 0.3
1 x 1/4 33RE1010002C 34RE1010002C 1.22 1.10 25 300 0.3
1 x 3/B 33RE1010003C 34RE1 01 0003C 1.27 1.18 25 100 0.5
1 x 112 33RE1 01 0004C 34RE!010004C 1.36
1.26 25 100 0.4
1 x 3/4 33RE1010006C 34RE1010006C 1.45 1.37 25 100 0.5
B 1-1/4 x 1/2 33RE1012004C 34RE 101 2004C 1.53 1.34 20 80 0.6
1-1/4 x 3/4 33RE1012006C 34RE1012006C 1.62 1.45 15 60 0.7
1-1/4 x 1 33RE101 2010C 34RE1012010C 1.67 1.58 10 40 0.8
1-112 x 1/2 33RE1014004C 34RE1014004C 1.75 1.52 15 60 0.8
1-112 x 3/4 33RE1014006C 34RE1014006C, 1.75 1.52 10 40 0.8
1-1/2 x 1 33RE1014010C 34RE1014010C 1.60 1.65 16 40 0.9
1-112 x 1-1/4 33RE1014012C 34RE1014012C 1.88 1.82 8 32 1.1
2 x 1/2 33RE1020004C 34RE1020004C 1,97 1.60 10 40 1.2
2 x 3/4 33RE1020006C 34RE1020006C 1.97 1.60 10 40 1.2
2 x 1 33RE1020010C 34RE1020010C 2.02 1.73 14 28 1.5
2 x 1-1/4 33RE1020012C 34RF1020012r- 2.10 1.90 10 20 1.5
2 x 1-112 33RE1020014C 34RE1020014C 2.16 2.02 10 20 1.6
2-112 x 3/4 33RE1024006C 34RE1024006C 2,30 10 20 1,9
2-112 x I 33RE1024010C 34RE1024010C 2.36 1.87 8 16 2.1
2-112 x 1-114 33RE1024012C 34RE1024012C 2.44 2.03 8 16 2.2
2-112 x 1-112 33RE1024014C 34RE1024014C 2.51 2.16 8 16 2,3
2-112 x 2 33RE1024020C 34RE1024020C 2,60 2.39 8 16 2,6
3 x 112 33RE1030004C 34RE1030004C 2.56 1.69 10 20 6.0
3 x 3/4 33RE1030006C 34RE1030006C 2.60 1,87 8 16 6.6
3 x I 33RE1030010C 34RE1030010C 2.66 1.99 8 16 2.4
3 x 1-1/4 33RE1030012C 34RE1030012C 2.74 2.16 5 10 6.0
3 x 1-1/2 33REi030014C 34RE1030014C 2.80 2.28 - 8 2.5
3 x 2 33RE1030020C 34RE1030020C 2.89 2.52 a 2.7
3 x 2-112 33RE1030024C 34RE1030024C 2.99 2,83 8 4.0
4 x 1-112 33RE1040014C 34RE1040014C 2.31 2.50 5 4.7
4 x 2 33RE1040020C 34RE1040020C 3.41 2.74 5 5.1
4 x 2-112 33RE1040024C 34RE1040024C 3�50 3.05 5 6.3
4 x 3 33RE1040030C 34RE1040030C 3.60 3.30 5 6.6
SMITH-COOPFR INTFRNATIONAI,l TOIA. FREF 1-800-766-0076 - FAX(323)890-4456 www.smithcooper.com
Malleable Iron Fittings- 150#UL/FM
IGUI <S>
Fig. 33SEI & 34SE1 - 90'Street Elbow LISTED APPROVED
Size Part Number A B, Packing weight
IN Black GaIv IN IN Inner Master LB
1/8 33SE1001C 34SE1001C 0.69 1.00 60 960 0.05
1/4 33SE1002C 34SE1002C 0.81 1.19 35 560 01
3/8 33SE1003C 34SE1003C 0.95 1.44 40 320 0.2
112 33SE1004C 34SE1004C 1.12 1.61 60 240 0.2
3/4 33SE1006C 34SE1006C 1.30 I.B9 35 140 0.3
1 33SE1010C 34SE1010C 1.50 2.13 40 so 0.6
A 1-114 33SE1012C 34SE1012C 1.75 2.44 25 50 0.8
1-1/2 33SE1014C 34SE1014C 1.94 2.67 8 32 1.2
------- 2 33SE1020C 34SE1020C 2.25 3.27 8 16 2.0
2-112 33SE1024C 34SE1024C 2.70 3.B6 - 10 3.6
3 33SE1030C 34SE1030C 3.08 4.51 7 4.2
4 33SE1040C 34SE1040C 3.79 5.69 3 9.1
B 6 33SE1060C 34SE1060C 5.13 8.03 1 23.1
Fig. 330EI & 340EI - 90' Side Outlet Elbow
Size Part Number A Packing Weight
I N Black GaIv IN Inner Master LB
1/8 330E1001C 340E1001C 0.69 45 720 01
114 330E1002C 34CE1002C 0.81 50 400 0.2
3/8
330E1003C 340E1003C 0.95 50 200 0.2
112 330E1004C 340E1004C 1.12 45 180 0.2
3/4 330E1006C 340E1006C 1.31 20 80 0.4
1 330E1010C 340E1010C 1.50 20 40 0.7
A 1-114 3-'OE1012C 340E1012C 1.75 15 30 1.1
1-112 330E1014C 340E1014C 1.94 12 24 1.3
2 330E1020C 340E1020C 2.25
12 2.5
A
Fig. 33F I & 34F I -45' Elbow
Size Part Number A Pac ing Weight
I N Black GaIv I N Inner M aster LB
1/8 33F 1001C 34F 1001C 0.60 50 800 0.1
1/4 33F1002C 34F 1002C 0.73 30 480 0.1
3/8 33F1003C 34F 1003C 1 0.80 50 400 0.1
112 33F1004C 34F 1004C 0.8B 50 200 0.2
3/4 33FIC06C 34F 1006C 0.9B 40 160 0.3
1 33FI010C 34F 101CC 1.12 20 80 0.5
1-1/4 33F 1012C 34F 1012C 1.29 20 40 0.7
1-1/2 33F1014C 34F 101 4C 1.43 8 32 1.1
2 33F1020C 34F 1020C 1.68 12 24 1.7
2-1/2 33F1024C 34F 1024C 1.95 - 15 2.9
3 33F 1030C 34F 1030C 2,17 10 3.4
4 33F1040C 34F 1040C 2.61 3 6.4
A 5 33F1050C 34F 1050C 3.05 i 2 12.1
6 33F1060C 34F 1060C 3.46 1 15.4
8 33FIOBOC 34F 1080C 4.00 -1 26.0
Fig. 33SFI & 34SFI -45' Street Elbow A-7 B Weight
Size Part Number Packi
1-nner Master LB
I N Black GaIv I N I N
1/8 33SF1001C 34SF1001C 0.65 0.85 70 1120 0.1
1/4 33SF1002C 34SF1002C 0.73 0.94 40 640 01
3/8 33SF1003C 34SF1003C 0.80 1.03 50 600 0.1
112 33SF1004C 34SF1004C 0,88 115 65 260 0.2
3/4 33SF1006C 34SF1006C 0.98 1.29 40 160 O�3
1 33SF1010C 34SF1010C 1.12 1.47 25 100 0.5
1-1/4 33SF1012C 34SF1012C 1.29 1.71 10 40 0.8
1-1/2 33SF1014C 34SF1014C 1.43 1.88 10 40 0.9
2 33SF1020C 34SF1020C 1.68 2.22 12 24 1.5
2-112 33,�F1024C 34SF102�C 1.95 2.57 5 10 2.7
'A 3 33SF1030C 34SF1030C 2.17 3.00 - 6 3.6
B 4 33SF1040C 34SF1040C Z61 3.70 4 9.2
SN/IfTH-COOPER TNTERNATIONAT,l TOIA, FREE 1-800-766-0076 - FAX(323)890-4456 - wwwsmichcooper.com
V Malleable Iron Fittings- 150# UL/FM
Cell
Fig. 33T 1 & 34T I - Tee LISTED APPROVED
Size I Part Number A Packing --Wei�ght
IN I Black GaIv IN Inner Master LB
1/8 33T 1001C 34T 1001C 0.69 so 640 0.1
1/4 33TIO02C 34T 4002C 0.81 45 360 0.1
3J8 33T 1003C 34T 1003C 0.95 25 200 0.2
112 33T 1004C 34T 1004C 1.12 35 140 0.3
3/4 33T 1006C 3471006C 1.31 20 80 0.5
A 1 33T 1010C 34T 101 OC 1.50 25 50 0.8
1-1/4 33T 10 1 2C 34T 1012C 1.75 14 26 1.2
1-112 33T 1014C 34T 1014C 1.94 12 24 1.6
2 33T 1020C 341 1020C 2.25 - is 2.5
2-1/2 33T 1024C I 34T 1024C 2.70 10 4.2
A A 3 33T 1030C 34T 1030C 3.08 6 6.1
3-1/2 33T1034C 34T 1034C 3.42 2 9.4
4 33T 1040C 34T 1040C 3.79 2 9.7
5 33T1050C 34T 1050C 4.50 2 15.4
6 33T 1060C 34T 1060C 5.13 1 26.4
8 33T 1080C 34T 1080C 6.50 1 50.7
Fig. 33BTI & 34BTI -Bull Read Tee
Size Part Number A B Packing Weight
I N Black GaIv I N I N I N Inner Master L B
1/4 x 3/8 33BT1002003C 34BT1002003C 0.90 0.90 0.88 20 240 0.3
1/2 3/4 33BT1004006C 34BT1004006C 1.22 1.22 1.20 25 100 0.3
112 x 1 33BT1004010C 34BT1004010C 1.36 1.36 1.26 40 so 0.5
3/4 x 1 338T1 00601 OC 34BT1006010C 1.45 1.45 1.37 15 60 0.5
3/4 x 1-1/4 33BT1006012C 34BT1006012C 1.62 1.62 1.45 20 40 0.7
1 x 1-1/4 33BT1010012C 34BT1010012C 1.67 1.67 1.58 8 32 0.9
C 1 x 1-1/2 33BT1010014C 34BT1010014C 1.80 1.80 1.65 15 30 1.1
1 x 2 33BT1010020C 34BT1010020C 2.02 2.02 1.73 12 24 1.2
1 1-1/4 x 1-112 33BT1012014C 34BT1012014C 1.88 1.88 1.82 10 20 1.3
i-1/4 x 2 33BT1012020C 34BT1012020C 2.10 2.10 1.90 8 16 1.8
1-112 x 2 33BT1014020C 34BT1014020C 2.16 2.16 2.02 9 16 1.7
B A 2 x 2-112 33BT10200240 34BT1020024C 2.60 2.60 2.39 6 12 3.0
2 x 3 33BT1020030C 34BT1020030C 2.88 2.86 2.55 - 6 4.0
2-1/2 x 3 33BT1024030C 34BT1024030C 3.00 3.00 2.83 6 5.8
3 x 4 33BT1030040C 34BT1030040C 1 3.60 1 3.60 1 3.30 2 8.6
Fig. 33STI & 34STI -Service Tee
Size Part Number A B Pac ing Weight
IN Black GaIv IN IN inner Master LB
112 33ST1004C 34ST1004C 1.12 1.63 40 160 0.3
3/4 33ST1006C 34ST1006C 1.31 1.89 25 100 0.5
1 33ST1010C 34ST1010C 1.50 2.14 30 60 0.8
A 1-1/4 33ST1012C 34ST1012C 1.75 2.45 15 30 1.2
1-112 33ST1014C 34ST1014C 1,94 2.69 10 20 1.7
2 33ST1020C 34ST1020C 2.25 3.26 6 12 2.0
A B
Fig. 330TI & 340TI -Side Outlet Tee
Size Part Number A Packing Weight
IN Black Galv IN Inner Master LB
112 330T1004C
340T1004C 1.12 20 80 0.2
3/4 330T 006C 34oT1006C 1.31 15 60 0.4
1 330T1010C 340T1010C 1.50 25 50 0.7
A 1-1/4 330T1012C 340T1012C 1.75 12 24 1.1
1-112 330TJ 014C 340T1014C 1.94 8 16 1.4
2 330T1020C 340T1020C 2.25 - 10 2.7
A A
SMITH-COOPFR INTFRNATIONAI�' - TOIJ.FRRF 1-800-766-0076 FAX(323)890-4456 - www.smichcooper.com
1M, ?J
Fig. 33X I & 34X I - Cross LISTED APPROVED
Size
Part Number
A Pac ing Weight
IN Black Ga1v IN
Imier Master LB
33X 1001C 34X 1001C 0.69 20 320
1/8
0.2
1/4 33X 1002C 34X 1002C 0.81 40
320 0.2
/8 33X 1003C 34X 1003C 0.95 40 160
0.3
112 33X 1004C 34X 1004C 1.12 30 120 0.3
3/4 33X 1006C 34X 1006C 1.31 20 80 0.6
A A 1 33X 10100 34X 101 OC 1.50 20 40 1.1
1-1/4 33X 1012C 34X 1012C 1.75 - 20 1.4
A 1-112 33X 101 4C 34X 1014C 1.94 18 1.9
2 33X 1020C 34X 1020C 2.25 10 Z8
2-112 33X 1024C 34X 1024C 2.70 6 5.0
3 33X 1030C 34X 1030C 3.08 4 7.3
A 4 33X 1040C 34X 1040C 3.79 2 12.6
Fig. 33C I & 34C I - Cap
Size Partk-umher--A ing
IN Black Ga1v Pac Weight
IN Inner Master LB
1/8 33C 1001C 34C 1�01C 0.53 120 1920 0.05
1/4 33C 1002C 34C 1002C 0.63 80 1280 0.05
8 33C 10030 34C 1003C 0.74 60 720 0.1
3/
112 33C 1004C 34C 1 OU4C 0.87
75 600 0.1
3/4 33C 1006C 34C 1006C 0.97 40 320 0.2
33C 1010C 34C 1010C 1.16 25
200 0.�
1-1/4 33C 101 2C
34C 1012C 1.28 25 100 0.5
A 1-112 33C 1014C 34C 1014C 1.33 25 100 0.6
2 33C 1020C 34C 1 020C 1.45 15 60 1.1
2-112 33C 1024C 34C 1024C 1.70
20 40 1.6
3 33C 1030C 34C 1030C 1.80 12 24 2.2
3-1/2 33C 1034C 34C 1034C 1.90 6 12 3.5
4 33C 1040C 34C 1040C 2.08 - 12 3.9
5 33C 1050C 34C 1050C 2.32 10 5.6
6 33C 1060C 34C 1060C 2.55 5 8.8
8 33C 1080C 34C 1060C 3.20 _j 4 7 0
Fig. 33EPI & 34EPI -Extension Piece
Size Part Number A Pac ing Weight
IN-_ Black GaIv IN _--inrier Master LB
1 T2 33EP1004C 34EP1004C 1.72 50 400 0.2
3/4 33EP1006C 34EP1006C 1,B2 40 160
1 33EP1010C 0.2
1-1/4 33EP1012C 34EP1010C 2.20 30 120 0.3
34EP1012C 2.60 30 60 0.6
1-112 33EP1014C 34EP1014C 2.65 20 40 0.8
- 2 33EP1020C 34EP1020C 2.85 15 30 1.2
A
Fig. 33LT1 & 341,T." -Lateral
Size Part Number A B Packing- Weight
IN Black GaIv IN IN Inner Master LB
112 33LT1004C 34J1 004C 2.32 1.71 30 120 0.3
3/4 33LT1006C
34LT1006C 2.77 2.05 40 80 0.6
33LT1010C 34LT1010C 3.28 2.43 20 40 0.9
1-114 33LT1012C 34LT1 01 2C 3.94 2.92 12 24 1A
1-112 33LT1014C 34LT1 01 4C 4.38 3.28 10 20 2.0
2 33LT1020C 34LT1 020C 5.17 3.93 5 10 3.1
2-112 33LT1024C 34LT1024C 6.25 4.73 - 4 8.2
3 33LT1030C 34LT1030C 7.26 5.55 2 16.1
- ------ 1 4 33LT1040C 34LT1040C 1 8.98 6.97 2 20.0
B
A
SMITH-COOPER INTERNATIONAL' TOLL FREE 1-800-766-0076 * FAX(323)890-4456 - www.smithcooper.com
maneable Iron Fittings-,150#:UL/FM
Fig. 33RTI & 34RT1 -Reducing Tee LISTED APPROVED
Size Part Number A B c Pac Ing Weight
IN Black GaIv IN IN IN Inner Master LB
3/8 x 1/8 33RT1003001C 34RT1003001C 0.81 0.81 0.86 60 240 0.2
160 0.2
3/8 x 1/4 33RT1003002C 34RT1003002C 0.81 0.81 0.86 40
0.97 20 480 0,3
112 x 1/8 33RT1004001C 34RT1004001C 0.91 0.91
0.97 0.98 20 160 0.2
1/2 x 1/4 33RT1004002C 34RT1004002C 0.97
112 x 1/4 x 1/2 33RT1004002004C 34RT1004002004C 1.12 0.97 1.12 20 160 0.2
112 x 3/8 33RT1004003C 34RT1004003C 1.04 U4 1.03 20 160 0.2
112 x 3/8 x 112 33RT1004003004C 34RT1004003004C 1.12 1.03 1.12 20 160 0.2
3/4 x 1/4 33RT1006002C 34RT1006002C 1,12 1.12 1.12 25 100 0.3
c 3/4 x 3/8 33RT1006003C 34RT1006003C 1.12 1,12 1.13 25 100 0.4
3/4 x 3/8 x 3/4 33RT1006003006C 34RT1006003006C 1.31 1.13 1.31 25 100 0.4
3/4 x 112 33RT1006004C 34RT1006004C 1.20 1.20 1.22 20 80 0.4
A 3/4 x 1/2 x 112 33RT1006004004C 34RT1006004004C 1.20 1.12 1,22 25 100 0.3
3/4 x 112 x 3/4 33RT1006004006C 34RT1006004006C 1.31 1.22 1.31 20 80 0.4
3/4 x 112 x 1 33RT1006004010C 34RT10060040100 1.45 1.36 1.37 18 72 0.5
B 1 x 1/4 33RT1010002C 34RT1010002C 1.12 1.12 1.25 20 80 0.5
1 x 3/8 33RT1010003C 34RT1010003C 1.18 1.1B 1.27 is 60 0.5
1 x 112 33RT1010004C 34RT1010004C 1.26 1.26 1.36 15 60 0.6
j, 1 x 112 x 112 33RT1010004004C 34RT1010004004C 1.26 1.12 1,36 20 80 0.6
1 x 112 x 3/4 33RT1010004006C 34RT1010004006C 1.37 1.22 1.45 20 80 0.6
lid;
t',�
1 x lJ2 x 1 33RT1010004010C 34RT1010004010C 1.50 1.36 1.50 15 60 0.7
,-:5� 1 x 3/4 33RT1010006C 34RI1010006C 1.38 1.31 1.45 12 48 0,7
1 x 3/4 x 112 33RT1010006004C 34RT1010006004C 1.26 1.20 1.36 20 80 0.6
I x 3/4 x 314 33RT1010006006C 34RT1010006006C 1.38 1.31 1.45 15 60 0.6
I x3/4xl 33RT-1010006010C 34RT1010006010C 1.50 1.45 1.50 is 60 0.7
1-114 x 3/8 33RT1012003C 34RT1012003C 1.26 1.26 1.44 20 40 0.8
1-1/4 x 112 33RT1012004C 34RT1012004C 1.34 1.34 1.53 20 40 0.8
1-1/4 x 112 x 112 33RT1012004004C 34RT1012004004C 1.36 1.12 1.53 25 50 0.6
1-1/4 x 112 x 3/4 33RT1012004006C 34RT1012004006C 1.45 1.26 1.53 25 50 0.7
1-1/4 x 112 x 1 33RT1012004010C 34RT1012004010C 1.58 1.36 1.67 20 40 0.8
1-1/4 x 112 x 1-1/4 33RT1012004012C 34RT1012004012C 1.75 1.53 1.75 20 40 1.1
1-1/4 x 3/4 33RT1012006C 34RT1012006C 1.45 1.45 1.62 20 40 0.9
1-1/4 x 3/4 x 112 33RT10-12006004C 34RT1012006004C 1.34 1,12 1.53 10 40 0.7
1-1/4 x 3/4 x 3/4 33RT1012006006C 34RT1012006006C 1.45 1.31 1.62 10 40 0.9
1-114 x 3/4 x 1 33RT1012006010C 34RT1012006010C 1.58 1.45 1.67 10 40 0.9
1-1/4 x 3/4 x 1-1/4 33RT10i2006012C 34RT10120060120 1.75 1.62 1.75 10 40 i'l
1-1/4 x I 33RT1012010C 34RT1012010C 1.58 i.SB 1.67 20 40 l'o
1-1/4 x 1 x 112 33RT1012010004C 34RT1012010004C 1.34 1.26 1.53 20 40 0.8
1-1/4 x 1 x 3/4 33RT1012010006C 34RT1012010006C 1.45 1.38 1.63 20 40 1.0
1-1/4 x 1 x 1 33RT1012010010C 34RT10120100-10C 1.58 1.50 1.69 20 40 0�9
1-1/4 x 1 x 1-1/4 33R"',012010012C 34RT1012010012C 1.75 1.69 1.75 20 40 I'l
1-112 x 3/8 33RT1014003C 34RT1014003C 1.36 1.36 1�66 18 36 1.0
1-112 x 112 33RT1014004C 34RT1014004C 1.41 1.41 1.66 is 36 U
1-112 x 112 x 1/2 33RT1014004C)04C 34RT1014004004C 1.35 1.08 1.67 12 48 0.7
1-112 x 1/2 x 314 33RT'1014004006C 34RTIO!4004006C 1.56 1.18 1.80 12 4B 1.1
1-112 x 112 x 1 33RT1014004010C 34RT1014004010C 1.65 1.35 1.80 18 36 1.0
1-112 x 112 x 1-1/4 33RT1014004012C 34RT1014004012C 1.81 1.56 1,88 15 30 i'l
1-112 x 112 x 1-1/2 33RT1014004014C 34RT1014004014C 1-94 1,66 1.94 12 24 1.1
1-1/2 x 3/4 33RT1014006C 34RT1014006C 1.52 1,52 1.75 is 30 1.0
1-112 x 3/4 x 1/2 33RT1014006004C 34RT1014006004C 1.35 1.12 1.77 is 30 1.1
1-1/2 x 3/4 x 3/4 33RT1014006006C 34RT1014006006C 1.55 1.35 1.77 15 30 1.1
1-1/2 x 3/4 x 1 33RT1014006010C 34RTI()14006010C 1.82 1.35 1.B8 15 30 1.0
1-112 x 3/4 x 1-1/4 33RT1014006012C 34RT1014006012C 1.94 1.66 1.88 1 2 24 11
1-112 x 3/4 x 1-1/2 33RT1014006014C 34RT1014006014C, 1.94 1.75 1.94 12 24 1.3
1-112 x I 33RT1014010C 34RT1014010C 1.65 1.65 1.80 is 30 1.2
1-112 x 1 x 112 33RT1014010004C 34RT1014010004C 1.44 1.25 1.69 15 30 0.8
1-112 x 1 x 3/4 33RT1014010006C 34RT1014010006C 1.50 1.44 1.75 is 30 1.2
1-112 x 1 x 1 33RT1014010010C 34RT1014010010C 1.65 1.50 1.80 15 30 1.1
1-112 x 1 x 1-1/4 33RT1014010012C 34RT1014010012C 1.82 1.67 1.88 12 24 1.2
ST\/llTH-000PF,RlNTFRNATl0NAL6 - TOLLFRFEI-800-766-0076 - FAX(323)890-4456 * www.sinchcooper.com
Malleable Iron Fitfings- 150#UL/FM
Fig. 33RC1 & 34RCI -Reducing Coupling LISTED APPROVED
Size Part Number A Packing Weight
ig't
01
0.1
01
IN Black Ga1v IN Inner Master LB
1/4 x 1/8 33RC1002001C 34RC 1002001 C 1.00 50 600
3/8 x 1/8 33RC1003001C 34RC10030011C 1.13 35 420 0.1
3/B x 1/4 33RC1003002C 34RC1003002C 1.13 30 360 0.1
112 x 1/8 33RC1 004001 C 34RC1004001C 1.25 50 400 0.1
1/2 x 1/4 33RC1004002C 34RC1004002C 1.25 50 400 0.1
112 x 3/8 33RC1004003C 34RC1004003C 1.25 40 320 0.1
3/4 x 1/8 33RC1006001C 34RC1006001C 1.44 35 280 0.2
3/4 x 1/4 33RC1006002C 34RC1006002C 1.44 30 240 0.2
x 3/4 x 3/8 33RC1006003C 34RC1006003C 1,44 60 240 0.2
3/4 x 1/2 33RC1006004C 34RC1006004C 1.44 60 240 0.2
A I x 1/4 33RC1010002C 34RC1010002C 1.69 45 180 0.3
1 x 3/B 33RC1010003C 34RC1010003C 1.69 30 120 0.3
1 x 112 33RC1010004C 34R"1010004C 1.69 30 120 0.3
1 x 3/4 33RC1010006C 34RC1010006C 1.69 25 100 0.4
1-1/4 x 3/8 33RC1012003C 34RC1012003C 2.06 25 100 0.5
1-1/4 x 112 33RC1012004C 34RC1012004C 2.06 25 100 0.5
1-1/4 x 3/4 33RC1012006C 34RC1012006C 2.06 25 100 0.5
1-1/4 x 1 33RC1012010C 34RC1012010C 2,06 15 60 0.5
1-112 x 3/8 33RC1014003C 34RC1014003C 2.31 15
60 0.6
1-112 x 1/2 33RC1014004C 34RC1014004C 2.31 15 60 0.6
1-112 x 3/4 33RC1014006C 34RC1014006C 2.31 15 60 0.6
1-112 x 1 33RC1014010C 34RC1014010C 2.31 15 60
0.7
1-112 x 1-1/4 33RC1014012C 34RC1014012C 2.31 12 48 0.7
2 x 3/8 33RC1020003C 34RC1020003C 2.81 14 56 0.9
2 x 112 33RC10?0004C 34PC1020004C 2.81 12 4B 0.9
2 x 3/4 33RC1020006C 34RC1020006C 2.81 12 48 1.0
2 x 1 33RC 102001 OC 34RC1020010C 2.81 12 48 1.0
2 x 1-1/4 33RC1020012C 34RC1020012C 2.81 14 28 1.0
2 x 1-112 33RC1020014C 34RC1020014C 2.81 12 24 1.0
'wow 2-1/2 x 1/2 33RC1024004C 34RC1024004C 3.25 - 25 1.5
2-112 x 3/4 33RC1024006C 34RC1024006C 3.25 25 1.5
2-112 x 1 33RC1024010C 34RC1024010C 3.25 25 1.6
2-1/2 x 1-1/4 33RC1 024012C 34RC1024012C 3.25 25 1.7
2-112 x 1-1/2 33RC1024014C 34RC1024014C 3.25 25 1.7
2-112 x 2 33RC1024020C 34RC1024020C 3.25 25 1.8
3 x 112 33RC1030004C 34RC1030004C 3.69 20 2.0
3 x 3/4 33RC1 030006C 34RC 1030006C 3.69 20 2.2
3xl 33RCl 03001 OC 34RC1030010C 3.69 20 2.2
3 x 1-1/4 33RC1030012C 34RC1030012C 3.69 20 2.0
3 x 1-112 33RC1030014C 34RC1030014C 3.69 20 2.2
3 x 2 33RC1030020C 34RC1030020C 3.69 16 2.4
3 x 2-112 33RC1030024,C 34RC11030024C 3.69 12 2.5
4 x 112 33RC1040004C 34RC1040004C 4.38 10 4.0
4 x 3/4 33RC1040006C 34RC1040006C 4,38 10 4.0
4 x 1 33RC1040010C 34RC1040010C 4.38 1 0 3.7
4 x 1-1/4 33RCI 040012C 34RC1040012C 4.36 10 3.7
4 x 1-112 33RC I 040014C 34RC1040014C 4.38 10 4.4
4 x 2 33RC1040020C 34RC1040020C 4.38 10 4.4
4 x 2-112 33RC1040024C 34RCI,-,40024C 4.38 10 4.0
4 x 3 33RC1040030C 34RC104003CC 4.38 a 4.2
5 x 2 33RC1050020C 34RC1050020C 4.56 4 5.5
5 x 2-112 33RC1050024C 34RC1050024C 4.56 4 5.5
5,,3 33RC1050030C 34RC1050030C 4.56 4 5.2
5 x 4 33RC1050040C 34RC1050040C 4.56 4 9.8
6 x 2 33RC1060020C 34RC 1 060020C 4.25 4 7.5
6 x 2-112 33RC1060024C 34RC1060024C 4.25 4 7.5
6 x 3 33RC1060030C 34RC1060030C 4.25 4 7.9
6 x 4 33RC1060040C 34RC1060040C 4.81 3 9.9
6 x 5 33RC1060050C 34RC1060050C 4.25 3 8.7
6 x 6 33RC1080060C 34RC1080060C 5.20 2 17.1
SMITH-COOPER INTF.RNATIONAL,I" - TOLI, FREF. 1-800-766-0076 - FAN(323)890-4456 www.smithcoopmcom
AMERICAN FIRE SERVICE INC.
108 HALSEMA ROAD NORTH
JACKSONVILLE FLORIDA 32220
HYDRAULIC CALCULATIONS FOR
NEW MAINTENCE FACILITY AT FLEET LANDING
4W 1 FLEET LANDING BLVD.
ATLANTIC BEACH, FLORIDA 32233
DRAWING NUMBER:FP 1 OF 1 DATE: NOV 26, 2013
-DESIGN DATA-
REMOTE AREA NUMBER: 100 AREA REMOTE AREA LOCATION: ATTIC OVER OFFICES
OCCUPANCY CLASSIFICATION: LIGHT HAZARD
DENSITY: .10 gpm/sq. ft.
AREA OF APPLICATION: 2535 sq. ft.
COVERAGE PER SPRINKLER: 73.00 sq. ft.
TYPE OF SPRINKLERS CALCULATED: QUICK RESPONSE BRASS UPRIGHT K=5. 6 TY3131
NUMBER OF SPRINKLERS CALCULATED: 36
HOSE-STREAM DEMAND: 100 gpm
TOTAL WATER REQUIRED (INCLUDING HOSE) : 684.8 gpm
(W FLOW AND PRESSURE (AT BASE OF RISER) : 584.9 gpm @ 23.7 psi
TYPE OF SYSTEM:
*VOLUME OF DRY SYSTEM: 375.0
WATER SUPPLY
Source: ATLANTIC BEACH WATER DEPARTMENT
Location: MAYPORT ROAD (STATE ROAD AIA)
Static: 48.0 psi Residual: 35.0 psi Flow: 1000 gpm
CONTRACTOR Certification number: 55283300012005
NAME OF DESIGNER: MARK ROGERS
AUTHORITY HAVING JURISDICTION: BOB RATLIFF FIRE MARSHALL
Calculations performed by HASS under license # 50071123
granted by HRS SYSTEMS, INC.
(Notes continue after pipe calculations results. )
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
CD
m
rz > >
04 $4
01 �3
CD �4 co a) oD
::I - �4
C� co 'r �J 'r 9-:
w co U) OD 04
CD 04
04 �4 (2)
04
-H Q) E!
co co
�Q 04 04
(0 �4 �j En
0 Ln -,, �-Q 0 >,
u-) �1 oo u) u)
r-4
�a4
CD
CD
10
U) 01 1
" C)
rf) C)
>A
�-1 , I
0D
a4 4-)
(A4
(un)
(Z) C) (D CD
(y) cD
�mw) 04 O� W CO M 04 04
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic . 10 2535 100 Hose
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQID
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 48.0 35.0 1000.0 41.5 684.8 34. 9
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 684.8 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 584.8 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
101 13.7 K= 5.60 9.2 16. 9
102 13.7 K= 5.60 9.3 17.1
103 13.7 K= 5.60 9.7 17.5
104 13.7 K= 5. 60 10.6 18.2
105 16.7 K= 5. 60 8.0 15.8
106 16.7 K= 5. 60 8.1 15. 9
(W 107 16.7 K= 5. 60 8.5 16.3
108 16.7 K= 5. 60 9.2 17.0
109 13.7 K= 5. 60 9.2 17.0
110 13.7 K= 5. 60 9.3 17.1
ill 13.7 K= 5. 60 9.8 17.5
112 13.7 K= 5.60 10.7 18.3
113 19.1 K= 5.60 8.0 15.8
114 19.1 K= 5. 60 8.1 15. 9
115 19.1 K= 5. 60 8.4 16.3
116 19.1 K= 5.60 8.4 16.3
117 19.1 K= 5.60 8.1 15.9
118 19.1 K= 5.60 8.0 15.8
119 22.1 K= 5. 60 7.0 14.8
120 22.1 K= 5. 60 7.1 14 . 9
121 22.1 K= 5. 60 7.4 15.2
122 22.1 K= 5.60 7.4 15.2
123 22.1 K= 5. 60 7.1 14.9
124 22.1 K= 5. 60 7.0 14.8
125 21.5 K= 5. 60 7.5 15.3
126 21.5 K= 5.60 7. 6 15.4
127 21.5 K= 5.60 7.9 15.8
128 21.5 K= 5. 60 7.9 15.7
129 21.5 K= 5. 60 7. 6 15.4
130 21.5 K= 5. 60 7.5 15.3
131 19.1 K= 5. 60 8.9 16.7
132 19.1 K= 5. 60 9.0 16.8
133 19.1 K= 5. 60 9.4 17.2
134 19.1 K= 5. 60 9.4 17.2
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
4w (FT) (PSI) (GPM)
135 19.1 K= 5.60 9.0 16.8
136 19.1 K= 5.60 8. 9 16.7
1 11.7 - - - - 10.8 - - -
2 11.7 - - - - 10.9 - - -
3 11 .7 - - - - 11.4 - - -
4 11 .7 - - - - 12.3 - - -
5 11 .7 - - - - 11.2 - - -
6 11.7 - - - - 11 .3 - - -
7 11.7 - - - - 11 .7 - - -
8 11 .7 - - - - 12.5 - - -
9 11 .7 - - - - 10.8 - - -
10 11.7 - - - - 11.0 - - -
11 11 .7 - - - - 11.4 - - -
12 11.7 - - - - 12.4 - - -
13 11.7 - - - - 12.5 - - -
14 11 .7 - - - - 12.7 - - -
15 11.7 - - - - 13.1 - - -
16 11.7 - - - - 13.1 - - -
17 11.7 - - - - 12. 6 - - -
18 11.7 - - - - 12.5 - - -
19 11 .7 - - - - 13.0 - - -
20 11.7 - - - - 13.1 - - -
21 11.7 - - - - 13.5 - - -
22 11.7 - - - - 13.5 - - -
23 11.7 - - - - 13.1 - - -
24 11.7 - - - - 13.0 - - -
25 11.7 - - - - 13.2 - - -
26 11.7 - - - - 13.3 - - -
27 11.7 13.7 - - -
28 11.7 - - - - 13.7 - - -
29 11.7 - - - - 13.3 - - -
30 11.7 - - - - 13.2 - - -
31 11.7 - - - - 13.5 - - -
32 11.7 - - - - 13.7 - - -
33 11.7 - - - - 14 .1 - - -
34 11.7 - - - - 14.1 - - -
35 11.7 - - - - 13.7 - - -
36 11.7 - - - - 13.5 - - -
37 11.7 - - - - 13. 9 - - -
38 11.7 - - - - 13.9 - - -
39 11.7 - - - - 13. 9 - - -
40 11 .7 - - - - 14 .2 - - -
41 11.7 - - - - 14.5 - - -
42 11.7 - - - - 14.8 - - -
43 11 .7 - - - - 15.4 - - -
44 11.7 - - - - 16.0 - - -
45 10.0 - - - - 17.4 - - -
46 10.0 - - - - 17.7 - - -
47 10.0 - - - - 17. 9 - - -
48 10.0 - - - - 18.2 - - -
(W TASR 10.0 - - - - 18.8 - - -
TDPV 5.0 - - - - 21.5 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
BASR 1.0 - - - - 23.7 - - -
Ul -3.0 - - - - 25. 6 - - -
U2 -3.0 - - - - 25. 9 - - -
BFD -3.0 - - - - 29.0 - - -
BFS -3.0 - - - - 34 .0 - - -
MD -3.0 - - - - 34.1 - - -
MS -3.0 - - - - 35.1 - - -
SOURCE 0.0 SOURCE 34 .9 584 .8
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic . 10 2535 100 Hose
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 1 5. 60 16.9 Disch 6.3 2.00 100 1.6
1 11.7 10.8 0.0 1.000 T: 3. 6 3.57 -0. 9
101 13.7 9.2 16.9 1.049 5.57 0.134 0.7
Pipe: 2 5.60 17.1 Disch 6.3 2.00 100 1.6
2 11.7 10. 9 0.0 1.000 T: 3.6 3.57 -0.9
102 13.7 9.3 17.1 1.049 5.57 0. 136 0.8
Pipe: 3 5. 60 17.5 Disch 6.5 2.00 100 1.7
3 11.7 11.4 0.0 1.000 T: 3.6 3.57 -0.9
103 13.7 9.7 17.5 1.049 5.57 0.142 0.8
Pipe: 4 5. 60 18.2 Disch 6.8 2.00 100 1 .7
4 11.7 12.3 0.0 1 .000 T: 3.6 3.57 -0.9
104 13.7 10.6 18.2 1.049 5.57 0.154 0.9
Pipe: 5 5. 60 15.8 Disch 5.9 5.00 100 3.2
5 11.7 11.2 0.0 1.000 T: 3.6 3.57 -2.2
105 16.7 8.0 15.8 1 .049 8.57 0.118 1.0
Pipe: 6 5.60 15. 9 Disch 5.9 5.00 100 3.2
6 11.7 11.3 0.0 1 .000 T: 3.6 3.57 -2.2
4w 106 16.7 8.1 15. 9 1.049 8.57 0.120 1.0
Pipe: 7 5. 60 16.3 Disch 6.0 5.00 100 3.2
7 11.7 11.7 0.0 1.000 T: 3. 6 3.57 -2.2
107 16.7 8.5 16.3 1.049 8.57 0.125 11 .1
Pipe: 8 5.60 17.0 Disch 6.3 5.00 100 3.3
8 11.7 12.5 0.0 1.000 T: 3.6 3.57 -2.2
108 16.7 9.2 17.0 1 .049 8.57 0.135 1.2
Pipe: 9 5. 60 17.0 Disch 6.3 2.00 100 1.6
9 11.7 10.8 0.0 1 .000 T: 3.6 3.57 -0. 9
109 13.7 9.2 17.0 1.049 5.57 0.135 0.8
Pipe: 10 5.60 17 .1 Disch 6.4 2.00 100 1. 6
10 11.7 11.0 0.0 1.000 T: 3.6 3.57 -0.9
110 13.7 9.3 17.1 1.049 5.57 0.137 0.8
Pipe: 11 5.60 17.5 Disch 6.5 2.00 100 1.7
11 11.7 11.4 0.0 1.000 T: 3. 6 3.57 -0.9
ill 13.7 9.8 17.5 1.049 5.57 0.143 0.8
Pipe: 12 5. 60 18.3 Disch 6.8 2.00 100 1.7
12 11.7 12.4 0.0 1.000 T: 3.6 3.57 -0. 9
112 13.7 10.7 18.3 1.049 5.57 0.155 0.9
4w
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 13 5.60 15.8 Disch 5. 9 7.92 100 4.6
13 11.7 12.5 0.0 1.000 T: 3.6 3.57 -3.2
113 19.1 8.0 15.8 1.049 11.49 0.118 1.4
Pipe: 14 5.60 15. 9 Disch 5.9 7 . 92 100 4. 6
14 11.7 12.7 0.0 1.000 T: 3. 6 3.57 -3.2
114 19.1 8.1 15. 9 1.049 11.49 0.119 1.4
Pipe: 15 5. 60 16.3 Disch 6.0 7.92 100 4.6
15 11.7 13.1 0.0 1 .000 T: 3. 6 3.57 -3.2
115 19.1 8.4 16.3 1.049 11 .49 0.124 1.4
Pipe: 16 5.60 16.3 Disch 6.0 7. 92 100 4.6
16 11 .7 13.1 0.0 1 .000 T: 3.6 3.57 -3.2
116 19.1 8.4 16.3 1.049 11.49 0.124 1.4
Pipe: 17 5.60 15. 9 Disch 5.9 7.92 100 4.6
17 11.7 12. 6 0.0 1.000 T: 3.6 3.57 -3.2
117 19.1 8.1 15. 9 1 .049 11.49 0.119 1.4
Pipe: 18 5. 60 15.8 Disch 5. 9 7. 92 100 4.6
18 11.7 12.5 0.0 1.0!,-,0 T: 3. 6 3.57 -3.2
118 19.1 8.0 15 .8 1.049 11.49 0.118 1.4
(W Pipe: 19 5. 60 14.8 Disch 5.5 10.42 100 6.0
19 11.7 13.0 0.0 1.000 T: 3. 6 3.57 -4.5
119 22.1 7.0 14 .8 1.049 13.99 0.105 1.5
Pipe: 20 5. 60 14. 9 Disch 5.5 10.42 100 6.0
20 11.7 13.1 0.0 1.000 T: 3.6 3.57 -4.5
120 22.1 7.1 14.9 1.049 13.99 0.106 1.5
Pipe: 21 5. 60 15.2 Disch 5.7 10.42 100 6.1
21 11.7 13.5 0.0 1.000 T: 3. 6 3.57 -4.5
121 22.1 7.4 15.2 1.049 13. 99 0.110 1.5
Pipe: 22 5. 60 15.2 Disch 5.7 10.42 100 6.1
22 11.7 13.5 0.0 1.000 T: 3. 6 3.57 -4.5
122 22.1 7 .4 15.2 1.049 13.99 0.110 1.5
Pipe: 23 5. 60 14. 9 Disch 5.5 10.42 100 6.0
23 11.7 13.1 0.0 1.000 T: 3.6 3.57 -4.5
123 22.1 7.1 14. 9 1.049 13.99 0.106 1.5
Pipe: 24 5.60 14.8 Disch 5.5 10.42 100 6.0
24 11.7 13.0 0.0 1.000 T: 3. 6 3.57 -4.5
124 22.1 7.0 14.8 1.049 13.99 0.105 1 .5
Pipe: 25 5. 60 15.3 Disch 5.7 9.83 100 5.8
25 11.7 13.2 0.0 1.000 T: 3.6 3.57 -4.3
4w 125 21.5 7.5 15.3 1.049 13.40 0.111 1.5
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
Pipe Tag K-fac Add F1 Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) NC
how To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 26 5. 60 15.4 Disch 5.7 9. 83 100 5.8
26 11.7 13. 3 0.0 1 .000 T: 3. 6 3.57 -4 .3
126 21 .5 7. 6 15.4 1.049 13. 40 0.113 1 .5
Pipe: 27 5. 60 15.8 Disch 5. 8 9.83 100 5.8
27 11.7 13.7 0.0 1 .000 T: 3. 6 3.57 -4.3
127 21.5 7. 9 15. 8 1 . 049 13.40 0. 117 1. 6
Pipe: 28 5. 60 15.7 Disch 5.8 9.83 100 5.8
28 11 .7 13.7 0.0 1 .000 T: 3. 6 3.57 -4 .3
128 21.5 7. 9 15.7 1 .049 13. 40 0.117 1. 6
Pipe: 29 5. 60 15.4 Disch 5.7 9.83 100 5.8
29 11.7 13.3 0.0 1 .000 T: 3. 6 3. 57 -4.3
129 21 .5 7. 6 15.4 1 .049 13.40 0. 113 1 .5
Pipe: 30 5. 60 15.3 Disch 5.7 9.83 100 5.8
30 11.7 13.2 0.0 1.000 T: 3. 6 3.57 -4.3
130 21.5 7.5 15.3 1 .049 13.40 0. 111 1.5
Pipe: 31 5. 60 16.7 Disch 6.2 7.33 100 4.6
31 11.7 13.5 0. 0 1 .000 T: 3. 6 3.57 -3.2
131 19. 1 8. 9 16.7 1 .049 10. 90 0.132 1. 4
Pipe: 32 5. 60 16.8 Disch 6.2 7.33 100 4.7
32 11.7 13.7 0. 0 1 . 000 7: 3. 6 3.57 -3.2
132 19. 1 9.0 16.8 1 .049 10. 90 0.132 1.4
Pipe: 33 5. 60 17.2 Disch 6. 4 7.33 100 4.7
33 11.7 14 . 1 0. 0 1.000 T: 3. 6 3.57 -3.2
133 19. 1 9.4 17 .2 1 .049 10. 90 0. 138 1.5
Pipe: 34 5. 60 17.2 Disch 6.4 7.33 100 4.7
34 11.7 14.1 0.0 1 .000 T: 3. 6 3.57 -3.2
134 19.1 9.4 17.2 1 . 049 10. 90 0.138 1.5
Pipe: 35 5. 60 16.8 Disch 6.2 7.33 100 4 .7
35 11.7 13.7 0.0 1 .000 T: 3. 6 3.57 -3.2
135 19.1 9. 0 16.8 1 .049 10. 90 0.132 1.4
Pipe: 36 5. 60 16.7 Disch 6.2 7.33 100 4. 6
36 11.7 13.5 0.0 1 . 000 T: 3. 6 3.57 -3.2
136 19.1 8. 9 16.7 1 .049 10. 90 0.131 1.4
Pipe: 37 0.0 0. 0 2.7 8.00 100 0.1
2 11.7 10. 9 16. 9 1 .500 ---- 0. 00 0.0
1 11 .7 10.8 16. 9 1 . 610 8.00 0. 017 0.1
Pipe: 38 0.0 16. 9 1 5. 4 8.00 100 0.5
3 11.7 11 .4 17.1 102 1 .500 ---- 0.00 0.0
2 11.7 10. 9 34 .0 1 . 610 8. 00 0.060 0.5
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 39 0.0 34.0 2 8.1 7.25 100 0.9
4 11 .7 12.3 17.5 103 1.500 ---- 0.00 0.0
3 11.7 11.4 51.5 1. 610 7.25 0.130 0.9
Pipe: 40 0.0 51.5 3 11.0 1.04 100 1.5
37 11.7 13. 9 18.2 104 1.500 T: 5.7 5.71 0.0
4 11.7 12.3 69.7 1. 610 6.75 0.228 1.5
Pipe: 41 0.0 0.0 2.5 8.00 100 0.1
6 11.7 11.3 15.8 1.500 ---- 0.00 0.0
5 11.7 11.2 15.8 1. 610 8.00 0.015 0.1
Pipe: 42 0.0 15.8 5 5.0 8.00 100 0.4
7 11.7 11.7 15. 9 106 1.500 ---- 0.00 0.0
6 11.7 11.3 31.7 1. 610 8.00 0.053 0.4
Pipe: 43 0.0 31.7 6 7. 6 7.25 100 0.8
8 11.7 12.5 16.3 107 1.500 ---- 0.00 0.0
7 11.7 11.7 48.0 1. 610 7.25 0.114 0.8
Pipe: 44 0.0 48.0 7 10.2 1.04 100 1.4
38 11.7 13. 9 17.0 108 1.500 T: 5.7 5.71 0.0
8 11.7 12 .5 65.0 1 . 610 6.75 0.200 1.4
Pipe: 45 0.0 0.0 2.7 8.00 100 0.1
10 11.7 11.0 17.0 1.500 ---- 0.00 0.0
9 11.7 10 . 8 17.0 1.610 8.00 0.017 0.1
Pipe: 46 0.0 17.0 9 5.4 8.00 100 0.5
11 11.7 11.4 17.1 110 1 .500 0.00 0.0
10 11.7 11.0 34.1 1.610 8.00 0.061 0.5
Pipe: 47 0.0 34.1 10 8.1 7.25 100 0. 9
12 11.7 12.4 17.5 111 1.500 ---- 0.00 0.0
11 11.7 11.4 51.6 1. 610 7.25 0.131 0.9
Pipe: 48 0.0 51. 6 11 11.0 1.04 100 1.5
39 11.7 13.9 18.3 112 1.500 T: 5.7 5.71 0.0
12 11.7 12.4 69. 9 1. 610 6.75 0.229 1.5
Pipe: 49 0.0 0.0 2.5 8.00 100 0.1
14 11.7 12.7 15.8 1.500 ---- 0.00 0.0
13 11.7 12.5 15.8 1. 610 8.00 0.015 0.1
Pipe: 50 0.0 15.8 13 5.0 8.00 100 0.4
15 11.7 13.1 15. 9 114 1.500 ---- 0.00 0.0
14 11.7 12.7 31.7 1. 610 8.00 0.053 0.4
Pipe: 51 0.0 31.7 14 7. 6 3.92 100 1.1
40 11.7 14 .2 16.3 115 1.500 T: 5.7 5.71 0.0
(W 15 11.7 13.1 48.0 1. 610 9. 63 0.114 1.1
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 52 0.0 31.7 17 7.6 4.15 100 1 .1
40 11 .7 14 .2 16.3 116 1 .500 T: 5.7 5.71 0.0
16 11.7 13.1 47.9 1 . 610 9.86 0.114 1 .1
Pipe: 53 0.0 15.8 18 5.0 8.00 100 0.4
16 11.7 13.1 15. 9 117 1 .500 ---- 0.00 0.0
17 11.7 12. 6 31.7 1 . 610 8.00 0.053 0.4
Pipe: 54 0.0 0.0 2.5 8.00 100 0.1
17 11.7 12.6 15.8 1 .500 ---- 0.00 0.0
18 11.7 12.5 15.8 1.610 8.00 0.015 0.1
Pipe: 55 0.0 0.0 2.3 8.00 100 0.1
20 11.7 13.1 14.8 1.500 ---- 0.00 0.0
19 11.7 13.0 14 .8 1. 610 8.00 0.013 0.1
Pipe: 56 0.0 14.8 19 4.7 8.00 100 0.4
21 11.7 13.5 14. 9 120 1.509 ---- 0.00 0.0
20 11.7 13.1 29.7 1.610 8.00 0.047 0.4
Pipe: 57 0.0 1-9.7 20 7 ,1- 4.08 100 1.0
41 11.7 14.5 1.5.2 121 1 .500 T: 5.7 5.7-1 0.0
21 11.7 13.5 45.0 1. 61�-, 9.79 0.101 1.0
Pipe: 58 0.0 29.7 23 7.1 4.13 100 1.0
41 11.7 14 .5 15.2 122 1.500 T: 5.7 5.71 0.0
22 11.7 13.5 45.0 1 .610 9.83 0.101 1.0
Pipe: 59 0.0 14.8 24 4 .7 8.00 100 0.4
22 11.7 13.5 14.9 123 1.500 ---- 0.00 0.0
23 11.7 13.1 29.7 1.610 8.00 0.047 0.4
Pipe: 60 0.0 0.0 2.3 8.00 100 0.1
23 11.7 13.1 14.8 1.500 ---- 0.00 0.0
24 11.7 13.0 14.8 1 .610 8.00 0.013 0.1
Pipe: 61 0.0 0.0 2.4 8.00 100 0.1
26 11.7 13.3 15.3 1.500 ---- 0.00 0.0
25 11.7 13.2 15.3 1.610 8.00 0.014 0.1
Pipe: 62 0.0 15.3 25 4.8 8.00 100 0.4
27 11.7 13.7 15.4 126 1.500 ---- 0.00 0.0
26 11.7 13.3 30.7 1.610 8.00 0.050 0.4
Pipe: 63 0.0 30.7 26 7.3 4.08 100 1.1
42 11.7 14.8 15.8 127 1.500 T: 5.7 5.71 0.0
27 11.7 13.7 46.5 1.610 9.79 0.108 1.1
Pipe: 64 0.0 30.7 29 7.3 4.13 100 1.1
42 11.7 14 .8 15.7 128 1 .500 T: 5.7 5.71 0.0
(W 28 11.7 13.7 46.5 1.610 9.83 0.108 1.1
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
Pipe Tag K-fac Add Fl F1 To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
sw Pipe: 65 0.0 15.3 30 4.8 8.00 100 0.4
28 11.7 13.7 15.4 129 1.500 ---- 0.00 0.0
29 11.7 13.3 30.7 1.610 8.00 0.050 0.4
Pipe: 66 0.0 0.0 2.4 8.00 100 0.1
29 11.7 13.3 15.3 1 .500 ---- 0.00 0.0
30 11.7 13.2 15.3 1. 610 8.00 0.014 0.1
Pipe: 67 0.0 0.0 2. 6 8.00 100 0.1
32 11.7 13.7 16.7 1.500 ---- 0.00 0.0
31 11.7 13.5 16.7 1.610 8.00 0.016 0.1
Pipe: 68 0.0 16.7 31 5.3 8.00 100 0.5
33 11.7 14 .1 16.8 132 1 .500 ---- 0.00 0.0
32 11.7 13.7 33.5 1.610 8.00 0.059 0.5
Pipe: 69 0.0 33.5 32 8.0 4.13 100 1.2
43 11.7 15.4 17 .2 133 1.500 T: 5.7 5.71 0.0
33 11.7 14.1 50.7 1.610 9.83 0.126 1.2
Pipe: 70 0.0 33.5 35 8.0 4.12 100 1.2
43 11.7 15.4 17.2 134 1 .500 T: 5.7 5.71 0.0
34 11.7 14 .1 50.7 1. 610 9.83 0.126 1.2
Pipe: 71 0.0 16.7 36 5.3 8.00 100 0.5
34 11.7 14 .1 16.8 135 1 .500 ---- 0.00 0.0
35 11.7 13.7 33.5 1. 610 8.00 0.059 0.5
Pipe: 72 0.0 0.0 2. 6 8.00 100 0.1
35 11.7 13.7 16.7 1.500 ---- 0.00 0.0
36 11.7 13.5 16.7 1. 610 8.00 0.016 0.1
Pipe: 73 0.0 0.0 1. 6 9.08 100 0.0
38 11.7 13.9 69.7 4 4 .000 ---- 0.00 0.0
37 11.7 13.9 69.7 4.260 9.08 0.002 0.0
Pipe: 74 0.0 69.7 37 3.0 9.08 100 0.1
39 11.7 13.9 65.0 8 4 .000 ---- 0.00 0.0
38 11.7 13.9 134.7 4.260 9.08 0.007 0.1
Pipe: 75 0.0 134.7 38 4 .6 7.29 100 0.2
40 11.7 14.2 69.9 12 4.000 E: 9.3 9.28 0.0
39 11.7 13. 9 204.7 4.260 16.57 0.015 0.2
Pipe: 76 0.0 204 .7 39 6.8 9.00 100 0.3
41 11.7 14.5 48.0 15 4.000 ---- 0.00 0.0
40 11.7 14.2 300.6 4.260 9.00 0.030 0.3
Pipe: 77 0.0 300.6 40 8.8 7.17 100 0.3
42 11.7 14.8 45.0 21 4 .000 ---- 0.00 0.0
4w 41 11.7 14.5 390.5 4 .260 7.17 0.048 0.3
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 12
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
(W To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf)
Pipe: 78 0.0 390.5 41 10. 9 8.00 100 0.6
43 11.7 15.4 46.5 27 4 .000 ---- 0.00 0.0
42 11.7 14 .8 483.5 4.260 8.00 0.072 0. 6
Pipe: 79 0.0 483.5 42 5. 9 13.04 100 0.6
44 11.7 16.0 50.7 33 6.000 T:27 .1 27.12 0.0
43 11.7 15.4 584 .9 6.357 40.16 0.015 0.6
Pipe: 80 0.0 0.0 5. 9 26.29 100 1.5
45 10.0 17.4 584.9 43 6.000 2E:25.7 25. 69 -0.7
44 11.7 16.0 584.9 6.357 51.98 0.015 0.8
Pipe: 81 0.0 0.0 5.9 7.04 100 0.3
46 10.0 17.7 584.9 44 6.000 E:12.8 12.85 0.0
45 10.0 17.4 584 . 9 6.357 19.89 0.015 0.3
Pipe: 82 0.0 0.0 5. 9 11.00 100 0.2
47 10.0 17.9 584 . 9 45 6.000 ---- 0.00 0.0
46 10.0 17.7 584 .9 6.357 11.00 0.015 0.2
Pipe: 83 0.0 0.0 5. 9 21.33 100 0.3
48 10.0 18.2 584 .9 46 6.000 ---- 0.00 0.0
47 10.0 17.9 584.9 6.357 21.33 0.015 0.3
Pipe: 84 0.0 0.0 5. 9 14.33 100 0. 6
TASR 10.0 18.8 584 . 9 47 6.000 2E:25.7 25.69 0.0
48 10.0 18.2 584 .9 6.357 40.02 0.015 0.6
Pipe: 85 0.0 0.0 5.9 5.00 100 2.7
TDPV 5.0 21.5 584. 9 48 6.000 B: 9.3 34.26 -2.2
TASR 10.0 18.8 584 .9 6.357 D:25.0 39.26 0.015 0.6
Pipe: 86 0.0 0.0 5.9 4.00 120 2.2
BASR 1.0 23.7 584. 9 TASR 6.000 C:40.0 40.00 -1.7
TDPV 5.0 21.5 584.9 6.357 44.00 0.010 0.5
Pipe: 87 0.0 0.0 5.9 4.00 150 1.9
Ul -3.0 25. 6 584 .9 TDPV 6.000 E:27.2 27.20 -1.7
BASR 1.0 23.7 584.9 6.357 31.20 0.007 0.2
Pipe: 88 0.0 0.0 5.9 10.00 150 0.3
U2 -3.0 25.9 584 .9 BASR 6.000 E:27.2 27.20 0.0
Ul -3.0 25. 6 584.9 6.357 37.20 0.007 0.3
Pipe: 89 0.0 0.0 5.9 400.00 150 3.1
BFD -3.0 29.0 584.9 Ul 6.000 2E:S4 .4 54.40 0.0
U2 -3.0 25.9 584. 9 6.357 454 .40 0.007 3.1
Pipe: 90 0.0 Fixed Pressure Loss Device
BFS -3.0 34.0 584.9 U2 5.0 psi, 584.9 gpm
taw BFD -3.0 29.0 584 .9
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 13
DATE: 11/26/2013LEET LANDING AREA CALC 100 ATTIC 10-2535 100 HOSE SDF
JOB TITLE: Fleet Landing Attic .10 2535 100 Hose
Pipe Tag K-fac Add Fl Fl To Vel Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nc
To Node El (ft) PT Tot. (Q) Disch Act TD (ft. ) T Pf/ft. (Pf)
Pipe: 91 0.0 0.0 5.9 8.00 150 0.1
MD -3.0 34.1 584.9 BFD 6.000 ---- 0.00 0.0
BFS -3.0 34 .0 584.9 6.357 8.00 0.007 0.1
Pipe: 92 0.0 Fixed Pressure Loss Device
MS -3.0 35.1 584.9 BFS 1.0 psi, 584.9 gpm
MD -3.0 34 .1 584 .9
Pipe: 93 Source 0.0 5.9 2E:54.4 40.00 150 0.2
SOURCE 0.0 34.9 584.8 MD 6.000 T:57 .4 117.86 1.3
MS -3.0 35.1 584.8 6.357 G: 6.0 157.86 0.007 1.1
NOTES (HASS) :
(1) Calculations were performed by the HASS 8.4 computer program
under license no. 50071123 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
(2) The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
04W imbalance at any node of 0.103 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 11.0 ft/sec at pipe 48.
(4) Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
(5) Available pressure at source node SOURCE under full flow conditions is
40.19 psi compared to the minimum required pressure of 0.00 Psi.
(6) PIPE FITTINGS TABLE
Pipe Table Name: CUSTOM.PIP
�W