1849 Ocean GRove 2014 HVAC CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 14-00000781 Date 5/13/14
Property Address . . . . . . 1849 OCEAN GROVE DR
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . RES GEN 2F DISTRICT
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
2 cu 2 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
LINING, JOHN H DONOVAN HEATING & AIR
890 SEMINOLE RD. 315 SIXTH AVENUE SOUTH
ATLANTIC BEACH FL 32233 JACKSONVILLE BEACH FL 32250
(904) 241-3785
----------------------------------------------------------------------------
Permit MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 127 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 11/09/14
----------------------------------------------------------------------------
Special Notes and Comments
STICKER FOR OVERCURRENT PROTECTION MUST
BE ON A/C EQUIPMENT PRIOR TO
INSPECTION. FAILURE TO COMPLY WILL
RESULT IN A FAILED INSPECTION AND
REINSPECT FEES . NO EXCEPTIONS .
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 127 . 00 127 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 131 . 00 131 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247-5826 Fax (904) 247-5845
1011 ADDRESS: Oceav-\ Oxrayn- PERMIT#
PROJECTVALUE $ 156VV' ARI# 46 s 5 m /5 02- REQ UIRED
I
Air Handling Equipment Only _�LAir Handling Unit & Condenser Condenser Only
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity 2— TonsPerUnit 2-SI 14 Seer RatinR 1!5
Heat: Unit Quantity BTU's Per Unit soowl 10,000
Duct Systems: Total CFM REQ61RED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers MU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
iis application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
ot. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name NPJ'D9J2vJ _)) etl Phone Number N1 - 1�612-74S
Mechanical Company —bon(SVOY\ -Office Phone Z Y1 3_4�_ Fax 20
it
Co. Address: S6 (n city �,P( �C�, State EL Zip 32260
License Holder(Print): t1l, /17a'n, 2/,�Ov O.."n State Certification/Registration# CA610
Notarized Signature of License Holder !::�_z
ARD TOMPKI7 Before -met Is /,;�7 day 20
4 -
RICH
commission#FF 040399
Signature of Notary Publi
44 Expires July 29,2017
-,zF c
4, wr,-M
S.WW Th.Ty FW� 0 19
Job:
+ wrightsoft Project Summary Date: 5/5/14
Entire House By: Brandon Zaharie
Donovan Heat & Air
315 6th ave south,Jacksonville Beach,FL 32250 Phone:241-3785 Email:brariclon6dormanac.com
Project Information
For: Dehart
1849 Ocean Grove DR,Atlantic Beach, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 oF Outside db 95 'F
Inside db 68 oF Inside db 75 'F
Design TD 29 'F Design TD 20 'F
Daily range L
Relative humidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 13919 Btuh Structure 11729 Btuh
Ducts 2799 Btuh Ducts 5690 Btuh
Central vent (12 cfm) 370 Btuh Central vent (12 cfm) 255 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 17088 Btuh Use manufacturer's data n
Rate/swing mult iT lier 1.00
Infiltration Equipment sens le load 17674 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 1 (Average) Structure 1638 Btuh
Ducts 973 Btuh
Heatin Coolin� Central vent (12 cfm) 420 Btuh
Area (ft' 115Y 115 Equipment latent load 3031 Btuh
Volume�ft-) 10368 10368
Air changes/hour 0.57 0.23 Equipment total load 20706 Btuh
Equiv.AVF (cfm) 98 40 Req. total capacity at 0.70 SHR 2.1 ton
Heating Equipment Summary Cooling Equipment Summary
Make Ameican Standard r Make Ameican Standard r
Trade Trade
Model 4A6H5030 Cond 4A6H5030
ARI ref no. 5021983 Coil *AM7AOA24
ARI ref no. 5021983
Eff iciency 8.5 HSPF Eff iciency 14.5 SEER
Heating input Sensible cooling 15747 Btuh
Heating output 22384 Btuh @ 47'F Latent cooling 6749 Btuh
Temperature rise 27 'F Total cooling 22496 Btuh
Actual air flow 750 cfm Actual air flow 750 cfm
Air flow factor 0.045 cfm/Btuh Air flow factor 0.043 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
Space thermostat Load sensible heat ratio 0.85
Printout certified by ACCA to meet all requirements of Manual J 8th Ed.
Right-Suitee Universal 7.1.01 RSU05996 2014-May-05 16:20:53
C�\Users\Sales\Documents\Wrightsoft HVAC\2Ton.rup Calc=MJ8 Orientation=N Page I
Job:
wrightsoft Project Summary Date: 5/5/14
Entire House By: Brandon Zaharie
Donovan Heat & Air
315 6th ave south,Jacksonville Beach, FL 32250 Phone.241-3785 Email:brandon@donovanac.com
Project Information
For: Dehart
1849 Ocean Grove Dr, Atlantic Beach, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 'F Outside db 95 'F
Inside db 68 'F Inside db 75 'F
Design TID 29 'F Design TD 20 'F
Daily range L
Relative hurnidity 50 %
Moisture difference 53 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 14414 Btuh Structure 14371 Btuh
Ducts 3195 Btuh Ducts 4674 Btuh
Central vent (13 cfm) 409 Btuh Central vent (13 cfm) 282 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 18019 Btuh Use manufacturer's data n
Rate/swing multiglier 1.00
Infiltration Equipment sensi le load 19327 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 1 (Average) Structure 1921 Btuh
Ducts 1006 Btuh
Heating Cooling Central vent (13 cfm) 465 Btuh
Area (ft2 121 121 Equipment latent load 3392 Btuh
Volume k 10962 10962
Air changes/hour 0.56 0.23 Equipment total load 22718 Btuh
Equiv.AVF (cfm) 102 42 Req. total capacity at 0.70 SHR 2.3 ton
Heating Equipment Summary Cooling Equipment Summary
Make American Standard Make American Standard
Trade Trade
Model 4A6H5018 Cond 4A6H5018
ARI ref no. 4655316 Coil *AM7AOA24
ARI ref no. 4655316
Efficiency 8.4 HSPF Eff iciency 15 EER
Heating input Sensible cooling 20906 Btuh
Heating output 29717 Btuh @ 47'F Latent cooling 8960 Btuh
Temperature rise 34 'F Total cooling 29866 Btuh
Actual air flow 801 cfm Actual air flow 801 cfm
Air flow factor 0.045 cfm/Btuh Air flow factor 0.042 cfm/Btuh
Static pressure 0 in H20 Static pressure 0 in H20
I Load sensible heat ratio 0.85
Space thermostat
Printout certified by ACCA to meet all requirements of Manual J 8th Ed.
Right-Sulteg Universal 7.1.01 RSU05996 2014-May-05 16:16:51
ACCK C:\Users\Sales\Documents\Wrightsoft HVAC\2.5 TON Caic=MJ8 orientation=N Page 1