920 Mayport BLDG DENIAL CITY OF ATLANTIC BEA CH J N� 800 SEMINOLE ROAD , ATLANTIC BEACH, FL 32233 (904) 247-5800 PLAN REVIEW 920 Mayport Rd. 15-COTH-990 6/03/2015 Permit Application was denied for the following: 1. Please submit original signed/sealed/dated engineering for metal building, including foundation. Copies cannot be accepted. 2. Please submit Energy Sheets and calculations. 3. Please submit Florida Product Approval Numbers, on Product Approval Form. 4. Code Summary, on Page A0.1, states Occupancy as S-1. Building appears to be mixed occupancy, Groups B and S-2 (electric motors and batteries). Please clarify/verify. 5. Groups B and S-2 require 2-hour fire separation, per Table 508.4. Some 1-hour and 2-hour rated walls are shown; floor details are not provided. Please submit details for occupancy separation and all fire protection/rating. 6. Please provide UL or other listing/label numbers for fire-rated assemblies. 6/23/15 Second submittal denied for the following: (Numbers from above) 1. On first submittal, "Not for construction" was checked. On second submittal, None of 6 boxes were checked. "Final drawings for construction" must be checked. 2. Energy sheets, calculations, and related mechanical details: a. Owner/agent must sign page 3 of both energy packages. b. Lighting sensors required, per FBC-EC, 505.2.2. Please indicate on Electrical Pages. c. Please indicate all fire dampers and duct smoke detectors, where required by FBC-M, Chapter 6. 3. Florida product Approval. 1