2321 MAYPORT RD - HVAC TEST REPORT HTB
NEBB CERTIFIED TEST, ADJUST AND
BALANCE REPORT
DATE: 7/15/2015
PROJECT Dollar Tree
ADDRESS 2031 Mayport Road
Atlantic Beach, Florida 32233
ARCHITECT Not Specified
ENGINEER Not Specified
HVAC CONTRACTOR Progressive Air
HOLISTIC TEST & BALANCE
3614 LENOX AVE.
JACKSONVILLE, FL 32254
(904) 900-1484
om
1 r
-�1 - LOYD E.UFFELDAAN
L CERTIFICATION
2701
Exp.3/31/17
9'�� �0`°g l4 - � rl � .-� - .5 6,
n°'M(iron\c
7
Zszt
Table of Contents
Abbreviation Sheet 1
RTU-1 2
RTU-1 Grille Sheet 3
RTU-2 4
RTU-2 Grille Sheet 5
RTU-3 6
RTU-3 Grille Sheet 7
RTU-4 8
RTU-4 Grille Sheet 9
RTU-5 10
RTU-5 Grille Sheet 11
Duct-Traverse Totals 12
EF-1 13
EF-1 Grille Sheet 14
Instrument Calibration Report 15
HOLISTIC TEST & BALANCE
3614 Lenox Avenue
Jacksonville, Florida 32254
(904) 900-1484
Abbreviations and Terms
A/C or ACU Air Conditioner Unit Max Maximum
AHU Air Handling Unit MBH BTU's per hour
Amp(s) Amperage Min. Minimum
BHP Brake Horse Power NA Not Applicable
BTU British Thermal Unit NI Not Installed
CFM Cubic Feet per Minute NS Not Specified
CFLA Corrected Full Load Amperage # Number
Comp. Compressor OA Outside Air
DB Dry Bulb Ph. Phase
Diff. Differential P.D. Pressure Drop
EF Exhaust Fan PSI Pounds Per Square Inch
Elev. Elevator Qty Quantity
Ent. Entering Req Required
Equip. Equipment RPM Rotations Per Minute
FLA Full Load Amps SF Safety Factor
FTU Fan Terminal Unit S.P. Static Pressure
Ft. Feet Sq Square
G.C. General Contractor Svc Service
GPM Gallons Per Minute TAB Test and Balance
HP Horse Power Temp Temperature
Hz Hertz VAV Variable Air Volume
Inches VEL Velocity
KW Kilowatt WB Wet Bulb
lb(s) Pound(s) WG Water Gauge
Lvg. Leaving
Page 1
HOLISTIC TEST & BALANCE
PROJECT: Dollar Tree DATE: 7/14/2015 BY: NLU
LOCATION: Atlantic Beach, Florida SYSTEM: RTU-1
SPECIFICATIONS:
FAN CFM: 2850 TSP/ESP: /1 .0 BHP/HP: /NS
RPM: NS OA CFM: 700
COOLING: MBH: 93.3 TYPE: DX EAT DB/WB: 80.0/67.0 LAT DB/WB: NS
HEATING: KW: 12.0
TEST DATA:
UNIT: Carrier SIZE: 50HC-DO8A2P5AF10 SER#: 0415P78778
MOTOR: Marathon HP: NS RPM: 1725 VOLT: 208-230/3v FLA: 6.9
TEST VOLT: 210/3v CORR. FLA: 6.9 MISC:
HTR SIZE: RATING: RUN. AMPS: 4.2, 4.2, 4.6 BHP: NA
FAN CFM: 3045 TSP/ESP: /0.98 RPM: 733 OA CFM: 750
COIL: EAT DB LAT DB DIFF TYPE MBH
COOLING: 75.8/65.2 56.2/55.7 6.56 DX 86.9
HEATING:
COMP. FLA: 2 @ 13.6A @ 208-230/3v TEST: 12.9A + 13.2A @ 210/3v
COND. FLA: 2 @ 1.5A @ 208-230/1v TEST: 1 .2A + 1 .2A @ 210/1v
LRA: 83.0 (2)
ELECT HT. 31.8A @ 210/3v= 11 .6 KW
REMARKS: Supply Air - Return Air = Outside Air Per Design
Page 2
HOLISTIC TEST & BALANCE
DIFFUSER AND GRILLE TEST REPORT
PROJECT: Dollar Tree LOCATION: Atlantic Beach, Florida
SYSTEM: RTU-1 AREA SERVED: Retail
DESIGN FINAL
LOCATION # TYPE SIZE AK TEST 1 MEN Percent Variance
VEL CFM
Supply
Retail 1 A 12" Hood 450 490 109%
Office 2 B 8" Hood 150 160 107%
Retail 3 A 12" Hood 450 480 107%
Retail 4 A 12" Hood 450 485 108%
Retail 5 A 12" Hood 450 480 107%
Retail 6 A 12" Hood 450 470 104%
Retail 7 A 12" Hood 450 480 107%
2850 3045 107%
Return
Retail 1 D 36"x14" Hood 2850 2300 81%
DATE: 7/14/2015 BY: NLU
Page 3
HOLISTIC TEST & BALANCE
PROJECT: Dollar Tree DATE: 7/14/2015 BY: NLU
LOCATION: Atlantic Beach, Florida SYSTEM: RTU-2
SPECIFICATIONS:
FAN CFM: 2800 TSP/ESP: /1.0 BHP/HP: /NS
RPM: NS OA CFM: 700
COOLING: MBH: 93.3 TYPE: DX EAT DB/WB: 80.0/67.0 LAT DB/WB: NS
HEATING: KW: 12.0
TEST DATA:
UNIT: Carrier SIZE: 50HC-DO8A2P5A0F10 SER#: 5014P76782
MOTOR: Marathon HP: NS RPM: 1725 VOLT: 208-230/3v FLA: 6.9
TEST VOLT: 210/3v CORR. FLA: 6.9 MISC:
HTR SIZE: RATING: RUN. AMPS: 4.1, 4.4, 4.0 BHP: NA
FAN CFM: 2910 TSP/ESP: /0.94 RPM: 715 OA CFM: 740
COIL: EAT DB LAT DB DIFF TYPE MBH
COOLING: 74.8/65.0 56.2/55.3 6.65 DX 87.1
HEATING:
COMP. FLA: 2 @ 13.6A @ 208-230/3v TEST: 13.0A + 12.5A @ 210/3v
COND. FLA: 2 @ 1.5A @ 208-230/1v TEST: 1.1A + 1.3A @ 210/1v
LRA: 83.0 (2)
ELECT HT. 32.0A @ 210/3v= 11 .6 KW
REMARKS:
Page 4
HOLISTIC TEST & BALANCE
DIFFUSER AND GRILLE TEST REPORT
PROJECT: Dollar Tree LOCATION: Atlantic Beach, Florida
SYSTEM: RTU-2 AREA SERVED: Retail
DESIGN FINAL
LOCATION # TYPE SIZE AK TEST 1 Percent Variance
VEL CFM VEL 1 CFM ,
Supply
Retail 1 A 12" Hood 500 470 94%
Office 2 A 12" Hood 500 510 102%
Retail 3 A 12" Hood 450 490 109%
Retail 4 A 12" Hood 450 470 104%
Retail 5 A 12" Hood 450 490 109%
Retail 6 A 12" Hood 450 480 107%
2800 2910 104%
Return
Retail 1 D 36"x14" Hood 2800 2150 77%
DATE: 7/14/2015 BY: NLU
Page 5
HOLISTIC TEST & BALANCE
PROJECT: Dollar Tree DATE: 7/14/2015 BY: NLU
LOCATION: Atlantic Beach, Florida SYSTEM: RTU-3
SPECIFICATIONS:
FAN CFM: 2400 TSP/ESP: /1.0 BHP/HP: /NS
RPM: NS OA CFM: 500
COOLING: MBH: 75.2 TYPE: DX EAT DB/WB: 80.0/67.0 LAT DB/WB: NS
HEATING: KW: 12.0
TEST DATA:
UNIT: Carrier SIZE: 50HC-A07A2P5A0F1 F0 SER#: 0915P61536
MOTOR: Marathon HP: NS RPM: 1725 VOLT: 208-230/3v FLA: 6.9
TEST VOLT: 210/3v CORR. FLA: 6.9 MISC:
HTR SIZE: RATING: RUN. AMPS: 4.5, 4.3, 4.6 BHP: NA
FAN CFM: 2610 TSP/ESP: /0.98 RPM: 735 OA CFM: 525
COIL: EAT DB LAT DB DIFF TYPE MBH
COOLING: 74.4/65.5 56.1/55.3 7.04 DX 82.7
HEATING:
COMP. FLA: 1 @ 19.0A @ 208-230/3v TEST: 18.3A @ 210/3v
COND. FLA: 2 @ 1.5A @ 208-230/1v TEST: 1 .1A + 1 .3A @ 210/1v
LRA: 123.0
ELECT HT. 32.0A @ 210/3v= 11 .6 KW
REMARKS:
Page 6
HOLISTIC TEST & BALANCE
DIFFUSER AND GRILLE TEST REPORT
PROJECT: Dollar Tree LOCATION: Atlantic Beach, Florida
SYSTEM: RTU-3 AREA SERVED: Retail
DESIGN FINAL
LOCATION # TYPE SIZE AK TEST 1 Percent Variance
VEL CFM VEL CFM
Supply
Retail 1 A 12" Hood 400 440 110%
Retail 2 A 12" Hood 400 430 108%
Retail 3 A 12" Hood 400 490 123%
Retail 4 A 12" Hood 400 430 108%
Retail 5 A 12" Hood 400 420 105%
Retail 6 A 12" Hood 400 400 100%
0 2400 2610 109%
Return
Retail 1 G 26"x14" Hood 1400 1250 89%
Retail 2 G 22"x22" Hood 500 440 88%
Retail 3 G 22"x22" Hood 500 440 88%
2400 2130 89%
DATE: 7/14/2015 BY: NLU
Page 7
HOLISTIC TEST & BALANCE
PROJECT: Dollar Tree DATE: 7/14/2015 BY: NLU
LOCATION: Atlantic Beach, Florida SYSTEM: RTU-4
SPECIFICATIONS:
FAN CFM: 2400 TSP/ESP: /1.0 BHP/HP: /NS
RPM: NS OA CFM: 500
COOLING: MBH: 75.2 TYPE: DX EAT DB/WB: 80.0/67.0 LAT DB/WB: NS
HEATING: KW: 12.0
TEST DATA:
UNIT: Carrier SIZE: 50HC-A07A2P50F1 F0 SER#: 5114P77025
MOTOR: Marathon HP: NS RPM: 1725 VOLT: 208-230/3v FLA: 6.9
TEST VOLT: 210/3v CORR. FLA: 6.9 MISC:
HTR SIZE: RATING: RUN. AMPS: 4.6, 4.9, 4.5 BHP: NA
FAN CFM: 2490 TSP/ESP: /0.95 RPM: 918 OA CFM: 540
COIL: EAT DB LAT DB DIFF TYPE MBH
COOLING: 75.2/65.5 56.3/55.5 6.92 DX 77.5
HEATING:
COMP. FLA: 1 @ 19.0A @ 208-230/3v TEST: 18.0A @ 210/3v
COND. FLA: 2 @ 1.5A @ 208-230/1v TEST: 1.4A+ 1.2A @ 210/1v
LRA: 123.0
ELECT HT. 31.7A @ 210/3v= 11.5 KW
REMARKS:
Page 8
HOLISTIC TEST & BALANCE
DIFFUSER AND GRILLE TEST REPORT
PROJECT: Dollar Tree LOCATION: Atlantic Beach, Florida
SYSTEM: RTU-4 AREA SERVED: Retail
DESIGN FINAL
LOCATION # TYPE SIZE AK TEST 1 Percent Variance
VEL CFM VEL CFM
Supply
Retail 1 A 12" Hood 400 390 98%
Retail 2 A 12" Hood 400 410 103%
Retail 3 A 12" Hood 400 430 108%
Retail 4 A 12" Hood 400 410 103%
Retail 5 A 12" Hood 400 430 108%
Retail 6 A 12" Hood 400 420 105%
2400 2490 104%
Return
Retail 1 G 26"x14" Hood 2400 1925 80%
DATE: 7/14/2015 BY: NLU
Page 9
HOLISTIC TEST & BALANCE
PROJECT: Dollar Tree DATE: 7/14/2015 BY: NLU
LOCATION: Atlantic Beach, Florida SYSTEM: RTU-5
SPECIFICATIONS:
FAN CFM: 2000 TSP/ESP: /1.0 BHP/HP: /NS
RPM: NS OA CFM: 300
COOLING: MBH: 60.4 TYPE: DX EAT DB/WB: 80.0/67.0 LAT DB/WB: NS
HEATING: KW: 12.0
TEST DATA:
UNIT: Carrier SIZE: 50HC-A06A2P5A0F1 F0 SER#: 0913C85098
MOTOR: Marathon HP: NS RPM: 1725 VOLT: 208-230/3v FLA: 6.9
TEST VOLT: 210/3v CORR. FLA: 6.9 MISC:
HTR SIZE: RATING: RUN. AMPS: 3.7, 4.0, 3.6 BHP: NA
FAN CFM: 2091 TSP/ESP: /0.93 RPM: 1090 OA CFM: 325
COIL: EAT DB LAT DB DIFF TYPE MBH
COOLING: 75.5/65.0 56.1/55.5 6.53 DX 61.4
HEATING:
COMP. FLA: 1 @ 15.9A @ 208-230/3v TEST: 15.0A @ 210/3v
COND. FLA: 1 @ 1.4A @ 208-230/1v TEST: 1.1A @ 210/1v
LRA: 110.0
ELECT HT. 31.9A @ 210/3v= 11.6 KW
REMARKS:
Page 10
HOLISTIC TEST & BALANCE
DIFFUSER AND GRILLE TEST REPORT
PROJECT: Dollar Tree LOCATION: Atlantic Beach, Florida
Restrooms, Hallway, Stockroom,
SYSTEM: RTU-5 AREA SERVED: and Employee Area
DESIGN FINAL
LOCATION # TYPE SIZE AK TEST 1 Percent Variance
VEL CFM VEL I CFM
Supply
Toilet 1 F 6" Hood 50 50 100%
Hallway 2 F 6" Hood 100 95 95%
Toilet 3 F 6" Hood 50 50 100%
Stockroom 4 C 14"x10" 0.97 371 360 405 393 109%
Stockroom 5 C 14"x10" 0.97 371 360 390 378 105%
Stockroom 6 C 14"x10" 0.97 371 360 390 378 105%
Stockroom 7 C 14"x10" 0.97 371 360 380 369 103%
Employee Area 8 C 14"x10" 0.97 371 360 390 378 105%
2000 2091 105%
DATE: 7/14/2015 BY:
Page 1
r----- HOLISTIC TEST & BALANCE
DUCT TRAVERSE SHEET ZONE TOTALS
DATE: 7/14/2015
PROJECT: Dollar Tree
LOCATION Atlantic Beach, Florida
TRAVERSE DUCT REQUIRED FINAL
SIZE AREA
SYSTEM LOCATION VEL CFM VEL PRES. VEL CFM
RTU-1 OA 36"x20" 5.0 140 700 150 750
RTU-2 OA 36"x20" 5.0 140 700 148 740
RTU-3 OA 36"x20" 5.0 100 500 105 525
RTU-4 OA 36"x20" 5.0 100 500 108 540
RTU-5 OA 30"x16" 5.0 60 300 65 325
REMARKS:
Page 12
HOLISTIC TEST & BALANCE
PROJECT: Dollar Tree DATE: 7/14/2015
LOCATION: Atlantic Beach, Florida
FAN TEST SHEET
SPECIFIED
EF-1
LOCATION Restrooms
TOTAL CFM 200
FAN RPM 1360
TOTAL SP 0.25
MOTOR BHP 71.3 KW
TEST
MANUFACTURER Greenheck
MODEL # CSP-A200
SERIAL # 1418683
MOTOR MFG Fasco
MOTOR HP NS
MOTOR RPM 900
MOTOR VOLTS 115/1v
MOTOR F.L.A. 0.54A
RUN AMPS 0.49A
LINE VOLTAGE 120/1v
TOTAL CFM 190
FAM RPM 620
TOTAL S.P. 0.20
NOTES:
Page 13
HOLISTIC TEST & BALANCE
DIFFUSER AND GRILLE TEST REPORT
PROJECT: Dollar Tree LOCATION: Atlantic Beach, Florida
SYSTEM: EF-1 AREA SERVED: Toilets
DESIGN FINAL
LOCATION # TYPE SIZE AK TEST 1 Percent Variance
VEL CFM VEL CFM
Men's Restroom 1 E 10"x10" Hood 100 90 90%
Women's Restroom 2 E 10"x10" Hood 100 100 100%
200 190 95%
DATE: 7/14/2015 BY: NLU
Page 14
NEBB
INSTRUMENT CALIBRATION REPORT
INSTRUMENT SERIAL # APPLICATION CALIBRATION
TEST DATE
Shortridge Hood 860C/M11557 Direct Reading 10/1/2014
Tachometer 634-513-044 Direct Reading 10/1/2014
Thermometer Cooper/ SRH77A Temp. Contact 10/2/2014
Thermometer Extech/GA10 Temp. Immersion 10/2/2014
Humidity Cooper/SRH77A Humidity 10/2/2014
Amprobe Field Piece/1201103231 Volts + Amps 10/1/2014
Thermo-Anonometer Extech/ AN100 Air Velocity 10/20/2014
Manometer Extech/ HD755 Pressure 9/30/2014
Differential Pressure Orange 0 to 100" GPM 9/30/2014
Differential Pressure Orange 0 to 100' GPM 9/30/2014
Gauges -30 to 60 PSI 9/26/2014
Gauges 0 to 100 PSI 9/26/2014
Gauges 0 to 200 PSI 9/26/2014
Magnehelic Diff. Pressure 0 to 50 -#2000 In. of H2O 10/2/2014
Tachometer Extect/1113665 RPM's 10/1/2014
Hot Wire Anemometer Alnor/9870 Air Velocity 10/20/2014
Pilot Tubes 0 to 18" & 0 to 24 Pilot Traverse NA
REMARKS:
NEBB TAB FIRM: HOLISTIC TEST & BALANCE
TAB SUPERVISOR: LOYD E. UFFELMAN REG. NO. 2701
Page 15
LT,41110 NEBB Certification Board
NEBB Certified Professional
_Loyd T. ffeCman
HAS MET ALL THE NEBB REQUIREMENTS FOR
NEBB CERTIFIED PROFESSIONAL STATUS IN
[esting, Adjusting and_Balancing of environmental Systems
This Certificate,as well as individual affiliation with a NEBB Certified Firm and associated NEBB Certification stamp
are REQUIRED to provide a NEBB Certified Report. Participation in the NEBB Quality Assurance Program
requires that the holder of this certification also be affiliated with a NEBB Certified Firm.
►-larch 31, 2017
Expiration Date NEBB Certification Board Chairman
21703 `1,Ct,GCt; ��
NEBB Certificant Number NEBB Certification Director
The NEBB Certification Board retains sole ownership of all certificates.Use of this certificate is governed by the NEBB Certification Board Policy Manual.
I
I rill ai
` Y
NEBB Certification Board
NEBB Certified Technician
Nicholas C. rUffe(man
HAS MET ALL THE NEBB REQUIREMENTS FOR
NEBB CERTIFIED TECHNICIAN STATUS IN
-Cesting, Adjusting and_Balancing of&ivitori rental Systems
4 This Certificate,as well as individual affiliation with a NEBB Certified Firm and associated NEBB Certification stamp
are REQUIRED to provide a NEBB Certified Report. Participation in the NEBB Quality Assurance Program
requires that the holder of this certification also be affiliated with a NEBB Certified Firm.
.March 31, 2017 G �4t
Expiration Date NEBB Certification Board Chairman
21357
NEBB Certificant Number NEBB Certificatf.n Director
The NEBB Certification Board retains sole ownership of all certificates.Use of this certificate is governed by the NEBB Certification Board Policy Manual.
I
•
II
- —
y
Tuff—tuition
THIS IS TO CERTIFY THAT
3-Lolistic Test & Balance Inc.
HAS MET ALL REQUIREMENTS FOR NEBB CERTIFICATION
IN THE FOLLOWING DISCIPLINE
£[eslirig Adjusting anc L a`ancing of envilionmerltal Systems
FOR THE NEBB BOARD OF DIRECTORS
.March 31, 2017 -
Expiration Date NEBB P esident
2701
NEBB Certification Number NEBB President-Elect