1765 MARITIME OAK DR - HVAC DUCT LEAKAGE TEST
Jacksonville Building Science, LLC
450 -106 State Rd 13 N
Suite 132
Jacksonville, FI 32259
Phone: 904 - 807 -3540 OFFICE COPY
Fax: 886 - 678 -6204
Date of Test: December 30, 2015 Technician: M O'Donoughue
Test File: Riverside ABCC 103 Outside
Customer: Riverside Homes Building Address: Riverside ABCC 103
414 Old Hard Road 1765 Maritime Oak Dr.
Suite 502 Atlantic Beach, Fl
Fleming Island, FI
Phone: (904) 264 -6553
Fax:
Test Results
1. Measured Duct Leakage: 12.7 CFM / 2.4 sq. in. ( +/_ 62265530476846642000000000000000
2. Duct Leakage as a Percent of System Airflow: 0.8 %
3. Duct Leakage as a Percent of Building Floor Area: 0.5 %
4. Leakage Split: Supply Side:
Return Side:
5. Duct Leakage Curve: Flow Coefficient (C): 1.8
Exponent (n): 0.600 (Assumed)
6 Test Settings: Test Mode: Depressurization
Test Pressure: 25.0 Pa
Equipment: Series B Minneapolis Duct Blaster, S/N 001
Test Type: Outside Leakage
(Combined Duct Blaster
and Blower Door Test)
Building and System Parameters:
Floor Area: 2709 sq. ft. Average Supply Operating Pressure: Pa
System Airflow: 1600 CFM Average Return Operating Pressure: Pa
Supply Leakage Split: % Supply Leakage Penalty:
Return Leakage Split: % Return Leakage Penalty:
Percentage of Measured Leakage Connected to Outside: 100% (12.7 CFM)
DUCT LEAKAGE TEST Page 2
Date of Test: December 30, 2015 Test File: Riverside ABCC 103 Outside
Data Points - Data Entered Manually:
Duct Fan Fan Flow Fan
Pressure (Pa) Pressure (Pa) (CFM) % Error Configuration
-25.0 -4.5 13 0.0 Ring 3
Comments